USER GUIDE

NMC-PRO
TABLE OF CONTENTS

GENERAL 1
KEYBOARD 1
HOT SCREENS 1
MAIN MENU ICONS 2
INTRODUCTION 3
OPERATION MODE 4

1. PROGRAM 6
1.1 RUN TIME PROGRAM 6
1.2 DOSING PROGRAM 7
1.3 IRRIGATION BASED ON TIME 13
1.4 IRRIGATION BASED ON EXTERNAL CONDITION (FIELD) 17
1.5 IRRIGATION BASED ON RADIATION SUM (GREENHOUSES) 19
1.6 IRRIGATION BASED ON VPD SUM (FIELD) 20
1.7 AGITATOR 21
1.8 SELECTOR 21
1.9 FILTER FLUSHING 22
1.10 COOLING 24
1.11 MISTING 25
1.12 WATER HEATING 25

2. MANUAL 26
2.1 SYSTEM PAUSE 26
2.2 START/STOP PROGRAM 26
2.3 START/STOP VALVE 27
2.4 MANUAL FILTER FLUSH 28

3. ALARM 29
3.1 RESET 29
3.2 ALARM HISTORY 29
3.3 ALARM DEFINITION 30
3.4 ALARM SETTING 32
3.5 EC/PH ALARM DEFINITION 32
3.6 EC/PH ALARM SETTING 32
3.7 RADIO SYSTEM ALARM DEFINITION 33
3.8 RADIO SYSTEM ALARM VIEW 33
3.9 SMS SUBSCRIPTION 34

4. HISTORY 35
4.1 SYSTEM HISTORY 35
USER GUIDE
NMC-PRO
GENERAL
Keyboard
Numeric- To enter values, quantities. Act as
shortcuts to selections.

+/- Key- Toggles between positive and negative


values and marks check boxes option selection.
In a History screen, use to toggle between
quantities and time format.

Arrows- Scroll up, down, left, and right to select


menus.

MENU- To main menu, also acts as "ESC" and


"Back" keys.

ENTER- Enter menu, submenu, value, open


window, confirm a value or change.

ZONE LOG IN- Access Mode


DELETE- Erases typing mistake.

Hot Screens

Press MENU from Main Menu to see Read-Only overview running


processes. Press MENU again to return to Main Menu.

9 Hot Screens/Keys:
0- Hot Key- Icon of active actions/processes
1- Main Screen/System Status
2- Irrigation Process
3- Irrigation Program Status
4- Water, EC/pH, Dosing
5- Filter Flushing Status
6- Temperature & Humidity measurement
7- Weather Station measurement
8- System Pressure

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 1

Crop Management technologies


USER GUIDE
NMC-PRO

Main Menu Icons

Conduct manual
irrigation process, Set alarm
filter flush, system threshold, and
pause reset

Programs: Data log-


irrigation irrigation log,
regimen, water meter,
dosing recipe, and system
filter flushing, event log
entire program

1.Program 2.Manual 3.Alarm 4.History

5.Test 6.Setup 7.Config 8.Install

Manually test
field devices
(valves,
pumps), For
sensor values professional
(EC, pH, temp, technical use
hum) only

System set-up, For


time/date, professional
sensors technical use
calibration, unit only
measurements

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 2

Crop Management technologies


USER GUIDE
NMC-PRO

Introduction
To set an irrigation program-regiment/strategy- the grower must select
necessary valves and set Run Time and Dosing program. May define 1 or
more programs for 1 or more valves.

Irrigation
Programs
(15)

Valve Dosing Irrigation


Run time Programs Triggers
Programs (10) (15)
(60)

Run Time Programs-


Based on Time or Quantity
Set water before and after dosing process (fertilizer injection)
Dosing Programs (fertilization)
Up to 8 dosing channels per program
Dosing method per channel (Time, Quantity, EC/pH)
Irrigation Timing based on External Conditions
Start/ Stop up to 2 Dry Contacts
Start/End time for irrigation period
Trigger Type

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 3

Crop Management technologies


USER GUIDE
NMC-PRO

Operation Mode
There are three levels of operation:
Read Only (restricted)
All the parameters and menus are visible, but cannot be modified
User (partially restricted): Menus 1-6 are fully accessible and can
be modified. Menus 7 and 8 can be viewed but not modified
Technician (unrestricted): All menus are fully accessible (no
restrictions)

To change the operation mode, press the LOG IN key

OPERATION MODE USER


1
2
3 ?
Mode Help Graph

Enter the MODE icon and insert the password

OPERATION MODE
Please Enter Password

The controller recognizes the operation mode according to the password


that is entered:
MODE PASSWORD
Read Only 0000
User 9785 or 0101

If an incorrect password is entered, then this screen will appear:

OPERATION MODE

WRONG PASSWORD
Please Try Again.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 4

Crop Management technologies


USER GUIDE
NMC-PRO
The Operation mode can be configured to automatically return to the
Read-Only mode after a certain amount of time.

NOTE: Refer to the SYSTEM SETUP section in the Installation Manual.

SYSTEM SETUP
HISTORY
History Resolution 1 HOUR
WEATHER STATION
Controller Function LOCAL
OPERATION MODE
Automatic return to RO mode NO
Return period to RO mode 00:10
COMMUNICATION
Controller Number 1
Lower Port Protocol NMC NET
Lower Port BaudRate 9600
Upper Port Protocol NONE
Upper Port BaudRate 9600

In order to perform a cold start or firmware upgrade, the controller


must be in the Technician mode (refer to Operation Mode, page 4).

If there is a power failure, the controller will power up with the last
mode that used.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 5

Crop Management technologies


USER GUIDE
NMC-PRO
1. PROGRAM
1.1 Run Time Program
For every irrigation program, define a Run Time recipe

2. Water Run Time

1. Program

Based on Time/Qty: WATER RUN TIME PROGRAM


# Method Water Before After
1 QTY. 10.000 0.000 0.000
2 QTY. 25.000 0.000 0.000
3 QTY. 0.000
QTY. 0.000 0.000
4 QTY. 0.000
TIME 0.000 0.000
5 QTY. 0.000 0.000 0.000
Qty. 6 QTY. 0.000 0.000 0.000
7 QTY. 0.000 0.000 0.000
8 QTY. 0.000 0.000 0.000
9 QTY. 0.000 0.000 0.000
10 QTY. 0.000 0.000 0.000
11 QTY. 0.000 0.000 0.000

WATER RUN TIME PROGRAM


# Method Water Before After
1 TIME 00:15:00 00:00:00 00:00:00
2 QTY. 25.000 0.000 0.000
3 QTY. 0.000 0.000 0.000
Define Time 4 QTY. 0.000 0.000 0.000
5 QTY. 0.000 0.000 0.000
6 QTY. 0.000 0.000 0.000
7 QTY. 0.000 0.000 0.000
8 QTY. 0.000 0.000 0.000
9 QTY. 0.000 0.000 0.000
10 QTY. 0.000 0.000 0.000
11 QTY. 0.000 0.000 0.000

Define value for "before"


and "after" time program

Water Before and After Dosing process:


WATER RUN TIME PROGRAM
# Method Water Before After
1 TIME 00:15:00 00:02:00 00:01:00 Water Water + dosing Water
2 QTY. 25.000 5.000 5.000
3 QTY. 0.000 0.000 0.000
4 QTY. 0.000 0.000 0.000
5 QTY. 0.000 0.000 0.000
6 QTY. 0.000 0.000 0.000 2 min 12 min 1 min
7 QTY. 0.000 0.000 0.000
8 QTY. 0.000 0.000 0.000
9 QTY. 0.000 0.000 0.000
10 QTY. 0.000 0.000 0.000
11 QTY. 0.000 0.000 0.000
Time

NOTE: Define total Time/Qty. Before and after


deducted from total Time/Qty.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 6

Crop Management technologies


USER GUIDE
NMC-PRO
1.2 Dosing Program
For every irrigation program, define a Dosing recipe

3. Dosing
1. Program
Dosing Channel Definition (Channel mode pre-configured by
technician):

Channel Define dosing method


for specific channels
(USA: Qty. = gallon)

Proportional Qty. (1/1000, Litre/m, gallon/1000gallons):


DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL


1 2 3 ---
EC EC ACID ---
5.00 5.00 5.00 ---
EC Dosing Method P.QTY
PH Dosing Method P.QTY

5 liters (gallon) of
fertilizer for every M
(1000 gallon) of water

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 7

Crop Management technologies


USER GUIDE
NMC-PRO
Proportional Time:

DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL


1 2 3 ---
P. Time EC
00:00
EC
00:00
ACID
0.00
---
---
Define minimum dose
EC Dosing Method
P. QTY
P.TIME for each channel
PH Dosing Method P.QTY
P. TIME
TIME
QTY.

DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL


Irrigation
1 2 3 ---
EC EC ACID ---
00:10 00:10 00:05 ---
EC Dosing Method P.TIME
PH Dosing Method P.TIME
P1 P2 P3 P4 P5 P6

Ex: Ch 1= P1+P2+P3+Pn= 10 min. Time in pulses for


Channel 1 or 2
NOTE: Proportional Time= Take desired dosing time and spread out
dose over irrigation program in open/close pulses per channel.

Time:
DOSING PROGRAM
Program: 1
Define in 1 bulk: Open
INJECTION PER DOSING CHANNEL
1 2 3 --- for a set time straight
Time EC
00:10
EC
00:10
ACID
00:05
---
--- through, i.e. not spread
EC Dosing Method
PH Dosing Method
P. QTY
P.TIME
P.TIME
out over a defined
P. TIME
TIME program.
QTY.

DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL


Irrigation
1 2 3 ---
EC EC ACID ---
00:15 00:10 00:05 ---
EC Dosing Method TIME
PH Dosing Method TIME
5 min

Time in bulk
Ex: Ch 3= P1= 5 min. (1 pulse)
Channel 3
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 8

Crop Management technologies


USER GUIDE
NMC-PRO
Quantity: (Example shows liters, in USA use gallons.)
DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL


Qty. 1
EC
2
EC
3
ACID
---
---
4.00 5.00 2.00 ---
EC Dosing Method QTY.
PH Dosing Method QTY.

Option A- In Bulk (similar to Time above).


Irrigation
Ex: Ch 1= P1= 4liters.
4 liters (1 pulse)
Quantity in bulk Channel 1

Option B- Spread Out (According to dosing configuration done


by technician).
Irrigation

Ex: Ch 1= P1+P2+P3
P1 P2 P3 P4 P5 P6
+Pn= 4 litres.

Quantity in pulses

Main Menu 7. Dosing Configuration

DOSING CONFIGURATION
EC Alarms NO
pH Alarms
Minimum On Time (sec)
NO
1.0
Define according to
Minimum Off Time (sec)
EC Coarse Tuning (0-10)
1.0
5
Bulk or Spread
EC Fine Tuning (0-10) 5
pH Coarse Tuning (0-10) BULK 5 DOSING PROGRAM
pH Fine Tuning (0-10) 5
SPREAD Program: 1
Control Cycle (sec) 6
EC/pH Averaging (0-Low, 20-High) 3 INJECTION PER DOSING CHANNEL
Dosing Boost. Off Delay (mm:ss) 00:10
1 2 3 ---
Dosing by QTY. Method BULK
EC EC ACID ---
4.00 5.00 2.00 ---
EC Dosing Method QTY.
Back in Dosing Program menu, PH Dosing Method QTY.

define Injection per Dosing


Channel.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 9

Crop Management technologies


USER GUIDE
NMC-PRO
Common Dosing Program for Open Fields (example):
DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL Fertilization (EC) amounts are fixed, no matter
1 2 3 ---
PASSIV PASSIV ACID --- how much water goes through (channels 1 &2-
2.00 5.00 3.00 ---
Target PH 5.50 Passive)
Passive Dosing Method
PH Dosing Method
QTY.
P.QTY pH is controlled at 5.50

Irrigation

Ch.2 P1 P2 P3 P4

Ch.1
P1 P2 P3 P4 P5 P6

Ch. 1 Spread Qty. = 2 liters


Ch. 2 Spread Qty. = 5 liters

**Channel 3 (Acid channel) - Pulse width fluctuates according to


controller calculations depending on pH levels to keep it on target.

Irrigation
pH Dosing P1 P2 P3
by P. Qty.

3 liter 1m
pH Target = 5.5

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 10

Crop Management technologies


USER GUIDE
NMC-PRO
Controlled EC/pH based on P.Qty. (example):
DOSING PROGRAM
Example A- Program: 1

INJECTION PER DOSING CHANNEL


1 2 3 ---
EC EC ACID ---
5.00 5.00 5.00 ---
Target EC 1.50
Target PH 5.50
EC Dosing Method P.QTY
PH Dosing Method P.QTY

Define dosing program:


Nutrient amount and
DOSING PROGRAM
desired EC/pH levels
Example B- Program: 1

INJECTION PER DOSING CHANNEL


1 2 3 ---
EC EC ACID ---
2.00 5.00 3.00 ---
Target EC 1.50
Target PH 5.50
EC Dosing Method P.QTY
PH Dosing Method P.QTY

Controlled EC/pH Target


1.5 EC
5.5 pH

Ex. A Ex. B
5 liters 3 liters
(gallons) (gallons)

5 liters 5 liters
(gallons) (gallons)
5 liters 2 liters
(gallons) (gallons)

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 11

Crop Management technologies


USER GUIDE
NMC-PRO

EC Pre-Control (example if previously defined by technician):

For hydraulic pre-control systems in greenhouses: When collecting excess


water from drains, grower can set EC target before water goes through
irrigation system. Discrepancies
DOSING PROGRAM
Program: 1 EC Pre-Control: OFF

INJECTION PER DOSING CHANNEL


1 2 3 OFF
---
EC Pre-Control ON EC
2.00
EC
5.00
ACID
3.00
ON
---
---
*Only if this was pre-defined Target EC 1.50
by technician during Target PH
EC Dosing Method
5.50
P.QTY
installation. PH Dosing Method P.QTY

DOSING PROGRAM
Program: 1 EC Pre-Control: ON

INJECTION PER DOSING CHANNEL


1 2 3 ---
EC EC ACID ---
2.00 5.00 3.00 ---
Target EC 1.50
Target PH
Target EC Pre-Control
5.50
----- Define pre-controlled EC target
EC Dosing Method P.QTY
PH Dosing Method P.QTY

DOSING PROGRAM
Program: 1 EC Pre-Control: ON

INJECTION PER DOSING CHANNEL


1 2 3 ---
EC EC ACID ---
2.00 5.00 3.00 ---
Target EC 1.50
Target PH 5.50
Target EC Pre-Control 0.80
EC Dosing Method P.QTY
PH Dosing Method P.QTY

Fresh Water
EC Sensor-
Target 0.8
3-Way
Valve
NetaJet
NetaJet NetaJet
Inlet Outlet

Drain Water

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 12

Crop Management technologies


USER GUIDE
NMC-PRO

1.3 Irrigation Based on Time

1. Irrigation Select program

1. Program

Example 1 Valve

DATE : 19-Apr-07 TIME : 16:12:32 V2


IRRIGATION PROGRAM

Program: 4 Priority: -- Const. 0%


Start Time 08:00
Clock Start 2 V1
Min. Time 01:00
Valve # 001 Cycle 1 Cycle 2
Run Time # 1
Dosing Prog 1
Day: 01/01 1
Dose/Water D 8:00 9:00 10:00

Irrigation program for 1 valve

NOTE: Min. Time= Delay between cycles from start time to start time
Clock Start= Number of cycles

Valve 1- runs 2 cycles, 1 hour between start


times on Run Time & Dosing Prog. 1

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 13

Crop Management technologies


USER GUIDE
NMC-PRO
Example 2
DATE : 19-Apr-07 TIME : 16:12:32
IRRIGATION PROGRAM

Program: 4 Priority: -- Const. 0% Irrigation program for a


Start Time
Clock Start
08:00
2
group of 2 valves
Min. Time 01:00
Valve # 001+002
Run Time #
Dosing Prog
1
1
1
1
+
Day: 01/01 1
Dose/Water D

Valve

V2

V1 Cycle 1 Cycle 2

8:00 9:00 10:00

Valve 1 & 2- run 2 cycles, 1 hour between


start times on Run Time & Dosing Prog. 1

NOTE: Min. Time= Delay between cycles from start to start


Clock Start= Number of cycles

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 14

Crop Management technologies


USER GUIDE
NMC-PRO
Example 3
DATE : 19-Apr-07 TIME : 16:12:32
IRRIGATION PROGRAM
Irrigation program for a
Program: 4 Priority: -- Const. 0%
Start Time 08:00 10:30 12:30 group and individual valve
Clock Start 2 2 2
Min. Time 01:00 00:30 01:00
Valve #
Run Time #
001+002 003
1 1 2
+
Dosing Prog 1 1 2
Day: 01/01 1 2 3
Dose/Water D W D

Valve C1= cycle 1


C2= cycle 2
V3
C1 C2 C1 C2 C1 C2
V2

V1 C1 C2 C1 C2 C1 C2

8:00 9:00 10:30 11:00 12:30 1:30 Time


Valve 1 & 2- runs 6 cycles simultaneously on Run Time & Dosing
Program 1, valve 3 runs after valves 1& 2 on Run time & Dosing
Program 2, different/interchangeable start times.

NOTE: Different/interchangeable delays (multiple start time) dividing the day into periods

NOTE: Min. Time= Delay between cycles from start to start


Clock Start= Number of cycles in every period (start time)

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 15

Crop Management technologies


USER GUIDE
NMC-PRO
Depending on weather conditions, increase/decrease amount of water
emitted from valves without changing the program.
Example 4
DATE : 19-Apr-07 TIME : 16:12:32
IRRIGATION PROGRAM
Program: 4
Start Time
Priority:
08:00 10:30
-- Daily 20%
If a lot of radiation, want to
Clock Start
Min. Time
2
01:00 00:30
2
irrigate more, +20%
Valve # 001+002 003 (Regular 10min. runtime12 min.)
Run Time # 1 1 2
Dosing Prog 1 1 2
Day: 01/01 1 2 3 NOTE: Daily = Current day only.
Dose/Water D W - Regular program will resume the
following day.
Example 5
DATE : 19-Apr-07 TIME : 16:12:32
IRRIGATION PROGRAM
If there is bad weather,
Program: 4 Priority: -- Const. -10% want to irrigate less, -10%
Start Time 08:00 10:30 (Regular 10min. runtime9 min.)
Clock Start 2 2
Min. Time 01:00 00:30
Valve # 001+002 003
Run Time # 1 1 2
Dosing Prog 1 1 2 NOTE: Const.= Constant running of program on
Day: 01/01 1
Dose/Water D daily basis. May increase/decrease amount of
water in this mode according to weather conditions.

Select water/dosing program by days of week


Example 6
DATE : 19-Apr-07 TIME : 16:12:32
IRRIGATION PROGRAM
Select program
Program: 4 Priority: -- Daily 20% by days of week
Start Time 08:00 10:30
Clock Start
Min. Time
2
01:00 00:30
2
S M T W TH F ST
Valve # 001+002 003 X X X X
Run Time # 1 1 2
Dosing Prog 1 1 2
Day: 01/01 1 2 3 4 5 6 7
Dose/Water D D D D D D D

OR
Choose cycle of days
DATE : 19-Apr-07 TIME : 16:12:32 DATE : 19-Apr-07 TIME : 16:12:32
IRRIGATION PROGRAM IRRIGATION PROGRAM
Program: 4 Priority: -- Daily 20% Program: 4 Priority: -- Daily 20%
Start Time 08:00 10:30 Start Time 08:00 10:30 12:30 --:--
Clock Start 2 2 Clock Start 2 2 2 --
Min. Time 01:00 00:30 Min. Time 01:00 00:30 01:00
Valve # 001+002 003 Valve # 001+002 003
Dose
Run Time # 1 Water1 2 Run Time # 1 1 2
Dosing Prog 1 1 2 Dosing Prog 1 1 2
None
Day: 01/01 1 2\ Day: 01/01 1 2 3
Dose/Water D W - Dose/Water D W -

S M T W TH F ST
D W - D W - D
D = Dosing + Water
W = Just Water
- = Nothing

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 16

Crop Management technologies


USER GUIDE
NMC-PRO

1.4 Irrigation Based on External Condition (Field)


To operate irrigation by peripheral equipment (i.e., filling a water tank
according to level float switch) EXTERNAL CONDITION PROGRAM
From To Start
#
hh:mm hh:mm Dry Cont.

4. Ext. Set 1
2
07:00
--:--
18:00
--:--
Dry Con 1
<NONE>
Condition start/end 3
4
--:--
--:--
--:--
--:--
<NONE>
<NONE>
1. Program time 5
6
--:--
--:--
--:--
--:--
<NONE>
<NONE>
7 --:-- --:-- <NONE>
Select trigger type 8 --:-- --:-- <NONE>
9 --:-- --:-- <NONE>
EXTERNAL CONDITION PROGRAM 10 --:-- --:-- <NONE>

Start Trigger Stop


#
Dry Cont. Type Dry Cont.
1 Dry Con 1 One Shot Dry Con 2
2 <NONE> One Shot <NONE>
One Shot
3 <NONE> One Shot <NONE>
Multi Shot
4 <NONE> One Shot <NONE>
Only If On
5 <NONE> One Shot <NONE>
6 <NONE> One Shot <NONE>
7 <NONE> One Shot <NONE>
8 <NONE> One Shot <NONE>
9 <NONE> One Shot <NONE>
10 <NONE> One Shot <NONE>

Trigger Type: One Shot = 6 sec


Condition On
Input
Off

Irrigation On
Program Run Time Run Time
Off

Trigger Type: Multi Shot


Condition On
Input
Off

Irrigation On
Program Run Time Run Time Run Time Run Time
Off
Trigger Type: Only if ON
Condition On
Input
Off

Irrigation On
Program Run Time Run Time
Off
Start On Trigger Type: Stop Dry Con.
Condition
Input Off
Stop On
Condition
Input Off
Irrigation On
Program Off Run Time Run Time
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 17

Crop Management technologies


USER GUIDE
NMC-PRO
EXTERNAL CONDITION PROGRAM
Start Trigger Stop
#
Dry Cont. Type Dry Cont.
1 Dry Con 1 One Shot Dry Con 2
Select dry contact (pre-defined by 2
3
<NONE>
<NONE>
One Shot
One Shot
<NONE>
<NONE>
technician) to start/stop condition and 4
5
<NONE>
<NONE>
One Shot
One Shot
<NONE>
<NONE>
set limit 6
7
<NONE>
<NONE>
One Shot
One Shot
<NONE>
<NONE>
8 <NONE> One Shot <NONE>
9 <NONE> One Shot <NONE>
10 <NONE> One Shot <NONE>

DATE : 1-May-07 TIME : 10:12:09


IRRIGATION PROGRAM

Program: 2 Priority: -- Cond. 1


1. Irrigation Start Time
Clock Start
08:00
--
Con. Starts ON
Min. Time --:--
1. Program Max. Time --:--
Valve # 004
Run Time # 2
Dosing Prog 2
Reaching the bottom line

Start On Start/Stop Irrigation by Dry Contact


Condition
Input Off
Stop On
Condition
Input Off
Irrigation On
Program Off Run Time Run Time
8:00

Example of tank filling:

Dry contact 2

Dry contact 1
Water Tank with Floats

Start On Trigger Type: Stop Dry Con.


Condition
Input Off
Stop On
Condition
Input Off
Irrigation On
Program Off

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 18

Crop Management technologies


USER GUIDE
NMC-PRO

1.5 Irrigation Based on Radiation Sum (Greenhouses)


Set trigger based radiation sum limit Joul/cm=Energy
DATE : 1-May-07 TIME : 10:12:09
IRRIGATION PROGRAM

1. Irrigation Program: 1 Priority: -- Const.


Rad Sum
Daily
Start Time 07:00 08:00 10:00 16:00
Cond.
Clock Start 1 -- -- Rad Sum1
1. Program Rad Sum Li.
Min. Time
----
--:--
300
00:30
150
00:20
----
--:--
Max. Time --:-- --:-- --:-- --:--
Valve # 001
Run Time # 1
Dosing Prog 1
For Next Screen Press The DOWN Arrow

DATE : 1-May-07 TIME : 10:12:09


IRRIGATION PROGRAM

Program: 1 Priority: -- Rad Sum


Set start/end time Start Time 07:00 08:00 10:00 16:00
Rad. Sum limit Clock Start
Rad Sum Li.
1
----
--
300
--
150
--
----
Set min./max. resting time Min. Time
Max. Time
--:--
--:--
00:30
01:00
00:20
01:00
--:--
--:--
Select program Valve #
Run Time #
001
1
Dosing Prog 1
For Next Screen Press The DOWN Arrow

NOTE: Start Time= When to begin measuring radiation levels to implement irrigation program.
Min. rest time most important so as to not irrigate too often when radiation levels fluctuate. In
this example, 8:00-10:00 irrigation should occur at most every 30 min. when radiation hits
300joules/cm.Max. rest time here indicates that irrigation must occur at least every hour if there
is less radiation.

Rad. Sum Rad. Sum


limit 300 limit 150

Irrigation

300
Joules/cm
150

7:00 8:00 10:00 16:00

Irrigation by clock start at 7:00


Irrigation by radiation sum

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 19

Crop Management technologies


USER GUIDE
NMC-PRO

1.6 Irrigation Based on VPD Sum (Field)


Set trigger based VPD sum limit kPamin. The VPD behavior
throughout the daytime is similar to the behavior of ET, therefore
using the VPD Sum will allow for irrigation as if ET calculations were
being used.
DATE : 1-May-07 TIME : 10:12:09
IRRIGATION PROGRAM

1. Irrigation Program: 1 Priority: -- VPD Sum


Daily
Cond.
Start Time 07:00 08:00 10:00 16:00
Rad Sum
Clock Start 1 -- --VPD Sum1
Rad Sum Li. ---- 300 150 ----
1. Program DATE : 1-May-07 Min. Time TIME--:--
: 10:12:09
00:30 00:20 --:--
IRRIGATION PROGRAM --:--
Max. Time --:-- --:-- --:--
Valve # 001
Program: 1 Priority:
Run--Time # VPD
1 Sum
Set period Start time Start Time 07:00 Dosing Prog
08:00 1
10:00 16:00
VPD Sum limit Clock Start
VPD Sum Li.
1
----
For Next
--
300
Screen
-- Press--
150
The DOWN Arrow
----
Set min./max. resting time Min. Time
Max. Time
--:--
--:--
00:30
01:00
00:20
01:00
--:--
--:--
Select program Valve #
Run Time #
001
1
Dosing Prog 1
For Next Screen Press The DOWN Arrow
Irrigation based on VPD Sum is available for operation only during the VPD time frame. Refer to
the 6.1 SETUP TIME & DATE for defining the start and end time for VPD Sum.

Start Time: define the time of day in which the irrigation based on VPD Sum should begin for
the period (next period overrides the previous)
Clock Start: define the number of cycles per Start Time (period)
VPD Sum Limit: define the VPD Sum trigger for irrigation to begin
NOTE: after irrigation, the VPD Sum counter will reset. In cases where the limit was achieved
but the minimum time between irrigation was not, the counter continues summing until irrigation
and will re-calculate after the irrigation in this manner:
VPD SUM counter = VPD SUM counter VPD SUM LIMIT
Minimum Time: define the minimum amount of time between cycles
Maximum Time: define the maximum amount of time without an irrigation cycle

FOR EXAMPLE ONLY!

IMPORTANT: Each Climate zone has different VPD values. It is critical for the grower to learn the VPD values
of their specific area in order to properly use the Irrigation Program based on the VPD Sum.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 20

Crop Management technologies


USER GUIDE
NMC-PRO

1.7 Agitator
To operate fertilizer tanks with mixing devices
AGITATOR

5. Agitator On
mm:ss
Off
mm:ss
Dosing Active --:-- --:--
Dosing Not Active --:-- --:--

1. Program Operation Mode Parallel

Define On/Off time during dosing and


when system is idle
Select Parallel to operate +1 Agitator
simultaneously AGITATOR

Select Serial if not enough power to On


mm:ss
Off
mm:ss
operate +1 agitator at a time Dosing Active
Dosing Not Active
01:00
05:00
05:00
60:00
Operation Mode Parallel
AGITATOR
On Off
mm:ss mm:ss
Dosing Active
Dosing Not Active
01:00
05:00
05:00
60:00
OR
Operation Mode Parallel
AGITATOR
Parallel
Serial On Off
mm:ss mm:ss
Dosing Active 01:00 05:00
Dosing Not Active 05:00 60:00
Operation Mode Serial

1.8 Selector
+1 fertilizer tank (with different fertilizers) attached to a single dosing
channel SELECTOR
Dosing
S1 S2
Prog.
1
6. Selector 2




3
4
1. Program 5
6




7
S1 S2 S1 S2 8
9
10

Dos. Chan. 1 / Dos. Chan. 2

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 21

Crop Management technologies


USER GUIDE
NMC-PRO

1.9 Filter Flushing


Program filter flushing during irrigation process
7. Filter FILTER FLUSHING PROGRAM
Time Between Flushing (hh:mm) 02:00
Flushing Flushing Time (mm:ss) 00:10
Delay Between Filters (mm:ss) 00:05
Delta Pressure (Digital) YES
Delta Pressure Valve (bar) 0.5
1. Program Delay Delta Pressure (mm:ss)
Delta Pressure Reiteration
00:06
3
Dwell Time Main (mm:ss) 00:10

NOTE: Filter flush process can start only after main


water line is full. Default set at 1 min., see menu 3.3.

ALARM DEFINITION
Water Fill Up (min) 1
Water Leak (m3) 1.000
Water Leak Period (hh:mm) 00:30
Identify Leak-Subtr. Meter? NO
Dosing Channel Leak Delay(s) 3
Dosing Channel Leak (Pulse) 10
Dosing Flow Difference (%) 25
Missing Pulses For No Flow 10
Stop System Cons.Flow Alarms --
# of Irrig. Without Drainage 3
Low Pressure Alarm (bar) 2.5
No. Of Short Circ. To Pause 3

NOTE: See graph on next page for further information.

Item Description
Time Between Time between flushes accumulated during set
Flushing irrigation time (one filter flush a time).
Flush Time Flush time per filter.
Delay Between
Set delay between flushes to build up pressure.
Filters
Set flush by pressure sensor. Pressure at filter
Delta Pressure inlet/outlet, if there is a significant difference, a filter
may be blocked.
Delta Pressure If there is a differential, (DP signal or Analog DP
Value (sensor) value), a flush is needed.
Delta Pressure
Set delay to verify if there is a definite blockage.
Delay
Delta Pressure Set to give signal after XX flushes. If Delta Pressure
Reiteration still indicates a blockage, an alarm will be raised.
Open main filter valve before flush to balance
Dwell Time Main
pressure for a reliable flushing process.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 22

Crop Management technologies


USER GUIDE
NMC-PRO
FILTER FLUSHING PROGRAM
Time Between Flushing (hh:mm) 02:00
Flushing Time (mm:ss) 00:10
Delay Between Filters (mm:ss) 00:05
Delta Pressure (Digital) YES
Delta Pressure Valve (bar) 0.5
Delay Delta Pressure (mm:ss) 00:06
Delta Pressure Reiteration 3
Dwell Time Main (mm:ss) 00:10

Start Time

1 hr 1 hr
Irrigation Delay Irrigation

8:00 9:00 10:00 11:00 3:00


After 2 hours of water flowing through
Trigger filters, flush every filter for 10 seconds.

Trigger Flush Process

Flush Time/Delay Between Filters

Flush 1 Flush 2 Flush 3

5 sec. 10 sec. 5 sec. 10 sec.


Delay Delay
10 seconds of flushing with 5 second
delay between flushes/filters.
Dwell Time Main

10 sec.
Dwell Flush 1
Time

Delta Pressure Reiteration


DP DP DP
Signal Signal Signal Alarm/Stop Flushing

Flush 1 Flush 2 Flush 3

After 3 flushes, if Delta Pressure shows


a blockage, system will raise an alarm.
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 23

Crop Management technologies


USER GUIDE
NMC-PRO
1.10 Cooling
Set cooling program for cooling/humidification process in greenhouses.
This program will operate according to temperature, humidity or time (to
reduce temp, increase hum.)

8. Cooling Set On/Off time and


select sensors
1. Program
Temp. Sens. 1 +1 of each sensor:
Hum. Sens. 1 uses average of both
COOLING/HUMIDIFICATION PROGRAM COOLING/HUMIDIFICATION PROGRAM

Program: 1 Status: Cooling Program: 1 Status: Cooling

Below RH On Off Below RH On Off


1 80 00:00:10 00:00:10 1 80 00:00:10 00:00:10
2 --- --:--:-- --:--:-- 2 --- --:--:-- --:--:--

Cool# 1 2 - - - - - - - - Cool# 1 2 - - - - - - - -
OR
Temp. Sens.: 1 -- Hum. Sens.: 1 -- Temp. Sens.: 1 2 Hum. Sens.: 1 2

Dynamic cooling: 2 temp.


threshold, same Hum.
COOLING/HUMIDIFICATION PROGRAM COOLING/HUMIDIFICATION PROGRAM

Program: 1 Status: Cooling Program: 1 Status: Cooling

From To Above t To Above t Below RH


1 08:00 16:00 25.0 1 16:00 25.0 80
2 08:00 16:00 35.0 2 16:00 35.0 80

Cool# 1 2 - - - - - - - - Cool# 1 2 - - - - - - - -

Temp. Sens.: 1 2 Hum. Sens.: 1 2 Temp. Sens.: 1 2 Hum. Sens.: 1 2

COOLING/HUMIDIFICATION PROGRAM

Program: 1 Status: Cooling On time is set.


Below RH On Off Off time can be controlled according
1
2
80
80
00:00:10
00:00:10
00:00:10
00:00:05
to temp.
Cool# 1 2 - - - - - - - -
High temp.= less off time
Low temp.= more off time
Temp. Sens.: 1 -- Hum. Sens.: 1 --
Temp.

35C
V1 V2 80%- Stop the
30C process

25C

Off Time

2.5 5 7.5 10 12.5


Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 24

Crop Management technologies


USER GUIDE
NMC-PRO

1.11 Misting
MISTING PROGRAM
General program using a timer # No. Start End On Off
hh:mm hh:mm hh:mm:ss hh:mm:ss
1 1 08:00 16:00 00:00:10 00:00:05
2 -- --:-- --:-- --:--:-- --:--:--
3 -- --:-- --:-- --:--:-- --:--:--
4 -- --:-- --:-- --:--:-- --:--:--
9. Misting 5 -- --:-- --:-- --:--:-- --:--:--
6 -- --:-- --:-- --:--:-- --:--:--
7 -- --:-- --:-- --:--:-- --:--:--
1. Program 8
9
--
--
--:--
--:--
--:--
--:--
--:--:--
--:--:--
--:--:--
--:--:--
10 -- --:-- --:-- --:--:-- --:--:--

Define Start/End time


Define misting On/Off time

1.12 Water Heating


Heat water in cold areas/seasons

WATER HEATING
From Time 08:00
To Time 16:00
10. Water Water Temperature
Difference
20.0
2.0
Heating Temp. Sensor #1
Temp. Sensor #2
1
2

1. Program

Define Start/End time


Define Water Temp. Difference (dead band) to stop
Define sensors

ON /OFF

Cold

Hot
16 18 20 22 24
C
Temperature
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 25

Crop Management technologies


USER GUIDE
NMC-PRO
2. MANUAL
2.1 System Pause
Manually pause system during an irrigation program (EC/pH calibration,
fix pipes)

IRRIGATION PAUSE

1. Irrigation pause Pause Irrigation?


NO
YES

YES

2. Manual
IRRIGATION PAUSE
Pause Irrigation? YES

Menu

ACTIVE IRRIGATION
SET ACTUAL LEFT
CYCLE 0 0 0
WATER 00:15:00 00:01:00 00:14:01
FLOW 100.000 0.000
EC 1.5 4.5 To resume, reverse steps
Ph 5.5 3.3
STATUS ACTIVE
above and select NO
PROGRAM: PAUSE 15:38:16 IRRIGATION
VALVE: 1 25-Apr-07 DOSING
FILTER
3 MESSAGES COOLING
(2) EC Low Valve #1
ALARM

2.2 Start/Stop program


Manually start/stop a program

2. Start/Stop Select program


Program
2. Manual
START/STOP PROGRAM To resume, reverse
Program: 1
Yes Menu steps above and
select NO
DATE : 1-May-07 TIME : 10:12:09
IRRIGATION PROGRAM

Program: 1 Priority: -- Rad Sum


Start Time 07:00 08:00 10:00 13:00
NOTE: Start 1 cycle only from Clock Start 1 -- -- --
Rad Sum Li. ---- 300 150 300
program 1 Min. Time --:-- 00:30 00:20 00:30
Max. Time --:-- 01:00 01:00 01:00
Valve # 001
Run Time # 1
Dosing Prog 1
For Next Screen Press The DOWN Arrow

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 26

Crop Management technologies


USER GUIDE
NMC-PRO

2.3 Start/Stop Valve


Manually start/stop a valve

3. Start/Stop Select Valve and


Valve corresponding Run
2. Manual Time/Dosing program

START/STOP VALVE To resume, reverse


Valve
Run Time #
2
1 Menu Yes steps above and
Dosing Program 1 select NO

WATER RUN TIME PROGRAM


# Method Water Before After
1 TIME 00:10:00 00:00:00 00:00:00
2 QTY. 0.000 0.000 0.000
3 QTY. 0.000 0.000 0.000
4 QTY. 0.000 0.000 0.000
5
6
QTY.
QTY.
0.000
0.000
0.000
0.000
0.000
0.000 Run Time
7
8
QTY.
QTY.
0.000
0.000
0.000
0.000
0.000
0.000
Program (1)
9 QTY. 0.000 0.000 0.000
START/STOP VALVE 10 QTY. 0.000 0.000 0.000
Valve 1 11 QTY. 0.000 0.000 0.000
Run Time # 1
Dosing Program 1
DOSING PROGRAM
Program: 1

INJECTION PER DOSING CHANNEL


1
EC
2
EC
3
EC
4
EC
5
ACID Dosing
5.00
Target EC
5.00 5.00 5.00
1.60
3.00
Program (1)
Target PH 5.50
EC Dosing Method P.QTY
PH Dosing Method P.QTY

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 27

Crop Management technologies


USER GUIDE
NMC-PRO

2.4 Manual Filter Flush


Manual filter flush only when system is irrigating

4. Filter Flush Select filters (usually all)

2. Manual

MANUAL FILTER FLUSHING MANUAL FILTER FLUSHING


Which Filter <None> Which Filter to Flush? All Filters
<None>
All Filters
Filter 01
Filter 02

FILTER FLUSHING STATUS


Item
Hot Screen 5 to Flush Status ON
Yes Menu
view flushing Time To Nest Flush
Delta Pressure (Digital)
--:--:--
OFF
status Flushing Filter No.
Remaining Filters Qty.
1
1
Flush Time 00:07
Current Delta Pressure ----
Main Filter Delay 00:00:00

NOTE: "All Filters" means all filter's but 1 at a time.


No more than 1 filter may be flushed at a time.

NOTE: Filter flush process can start only after main water
line is full. Default is 1min. as shown in picture below (See
menu 3.3
ALARM DEFINITION
Water Fill Up (min) 1
Water Leak (m3) 1.000
Water Leak Period (hh:mm) 00:30
Identify Leak-Subtr. Meter? NO
Dosing Channel Leak Delay(s) 3
Dosing Channel Leak (Pulse) 10
Dosing Flow Difference (%) 25
Missing Pulses For No Flow 10
Stop System Cons.Flow Alarms --
# of Irrig. Without Drainage 3
Low Pressure Alarm (bar) 2.5
No. Of Short Circ. To Pause 3

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 28

Crop Management technologies


USER GUIDE
NMC-PRO
3. ALARM
3.1 Reset
Reset alarm (in case of high flow, low flow, water leak, fertilizer leak)

1. Alarm Reset Option A: Reset manually

3. Alarm
ALARM RESET ALARM RESET
Reset Now? No Reset Now? No
Period Of Automatic Reset 24 h Period Of Automatic Reset NO 24 h
Complete Irrig. On Reset? YES Complete Irrig. On Reset? YES YES

ACTIVE ALARMS ACTIVE ALARMS


No. Message Date Time No. Message Date Time Yes
1 High Flow Valve #1 25/Apr 15:49 1 High Flow Valve #1 25/Apr 15:49

Option B: Automatic reset to check ALARM RESET


Reset Now? No
itself every so often as desired: Period Of Automatic Reset 24 h
Complete Irrig. On Reset? 24 h YES
Select how often system should ACTIVE ALARMS
12 h
6h
reset itself No. Message Date 4 h Time
3h
2h
1h
None

ALARM RESET
Reset Now? No
Period Of Automatic Reset 24 h
"Complete Irrig. On Reset?" Complete Irrig. On Reset?

NO YES
YES
Select Yes or No ACTIVE ALARMS
No. Message Date Time

3.2 Alarm History


View alarm history (Read-Only)
ALARM HISTORY

No. Message Date Time


112 EC Low Valve # 1 25/Apr 13:43
113 EC Low Valve # 1 25/Apr 13:44
114 High Flow Valve # 4 25/Apr 14:26
2. History 115
116
Emergency pH Low
Emergency EC High
25/Apr
25/Apr
14:44
15:46
117 High Flow Valve # 1 25/Apr 15:49
3. Alarm 118
119
High Flow Valve # 1
High Flow Valve # 4
25/Apr
25/Apr
15:52
15:53
120 High Flow Valve # 1 25/Apr 15:54
121 High Flow Valve # 1 25/Apr 15:55
NOTE: Logs up to 250 alarms
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 29

Crop Management technologies


USER GUIDE
NMC-PRO

3.3 Alarm Definition


Define system threshold

3. Alarm Definition

3. Alarm
Define trigger: deviation from
target pressure, flow
ALARM DEFINITION ALARM DEFINITION
Water Fill Up (min) 1 Dosing Channel Leak Delay(s) 3
Water Leak (m3) 1.000 Dosing Channel Leak (Pulse) 10
Water Leak Period (hh:mm) 00:30 Dosing Flow Difference (%) 25
Identify Leak-Subtr. Meter? NO Missing Pulses For No Flow 10
Dosing Channel Leak Delay(s) 3 Stop System Cons. Flow Alarms 3
Dosing Channel Leak (Pulse) 10 # of Irrig. Without Drainage 3
Dosing Flow Difference (%) 25 Low Pressure Alarm (bar) 2.5
Missing Pulses For No Flow 10 No. Of Shor Cir. To Pause 3
Stop System Cons.Flow Alarms -- Short Output Level (60-350) 300
# of Irrig. Without Drainage 3 Short O. Level EXP1 (60-350) 300
Low Pressure Alarm (bar) 2.5 Short O. Level EXP2 (60-350) 300
No. Of Short Circ. To Pause 3 Short O. Level EXP3 (60-350) 300

Item Description
Time of filling the main irrigation line. In that time, the
Water Fill Up
system will ignore high flow alarm and won't
(min)
implement a filter flushing process.
Water Leak (m3
Quantity of water leaking while the system is in idle.
or Gal)
Water Leak Time frame to measure the water leak quantity
3
Period (hh:mm) Example; 1m was leaking in less than 30min.
This setting relevant only when working in "Water
Identify Leak-
source" method. User can ignore or identify a water
Subtr. Meter?
leak.
Dosing Channel Delay between switching off a dosing channel and
Leak Delay (s) generating dosing leak alarm.
Number of pulses (by dosing meter) during the delay
Dosing Channel
above to generate an alarm. Example; 10 pulses in 3
Leak (Pulse)
seconds will generate alarm.
Difference between calculated and measured dosing
channel flow. Example; Dosing Channel 1 defined by
Dosing Flow
technician as 100liter/hour, but if the system
Difference (%)
measured less than 75liter/hour or more than
125liter/hour, an alarm will be generated.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 30

Crop Management technologies


USER GUIDE
NMC-PRO
ALARM DEFINITION ALARM DEFINITION
Water Fill Up (min) 1 Dosing Channel Leak Delay(s) 3
Water Leak (m3) 1.000 Dosing Channel Leak (Pulse) 10
Water Leak Period (hh:mm) 00:30 Dosing Flow Difference (%) 25
Identify Leak-Subtr. Meter? NO Missing Pulses For No Flow 10
Dosing Channel Leak Delay(s) 3 Stop System Cons. Flow Alarms 3
Dosing Channel Leak (Pulse) 10 # of Irrig. Without Drainage 3
Dosing Flow Difference (%) 25 Low Pressure Alarm (bar) 2.5
Missing Pulses For No Flow 10 No. Of Shor Cir. To Pause 3
Stop System Cons.Flow Alarms -- Short Output Level (60-350) 300
# of Irrig. Without Drainage 3 Short O. Level EXP1 (60-350) 300
Low Pressure Alarm (bar) 2.5 Short O. Level EXP2 (60-350) 300
No. Of Short Circ. To Pause 3 Short O. Level EXP3 (60-350) 300

Table continued
Item Description
Number of missing pulses before the system will
generate a No Flow alarm. The system calculates the
Missing Pulses
expected time between pulses of water meter and if a
For No Flow
certain time elapsed without receiving the desired
number of pulses, then generate an alarm.
Number of consecutive flow alarms of the same type
Stop System (high flow, low flow etc) but different valves before the
Consecutive Flow system is stopped. Example; High flow at valve 1 -
Alarms >High flow at valve 2->High flow at valve 3 = 3
consecutive High flow, then system stops.
Number of irrigations given without measuring
drainage, above which an alarm will be generated.
# of Irrigations
Common reasons: Irrigation quantity is too small so
Without Drainage
there is not enough drain, or drain measurement
malfunction because of technical problem.
Low Pressure
Minimum system pressure before generate an alarm.
Alarm (bar/psi)
Num. Of Short Number of short circuit (in field device) alarms
Circ. To Pause measured before the system is paused.
Short Output Define the A/D threshold value to be considered as a
Level (60-350) short circuit (For technician use only).
Define the A/D threshold value to be considered as a
Short O. Level
short circuit for Extension box no. 1 (For technician
EXT1 (60 350)
use only)
Define the A/D threshold value to be considered as a
Short O. Level
short circuit for Extension box no. 2 (For technician
EXT2 (60 350)
use only)
Define the A/D threshold value to be considered as a
Short O. Level
short circuit for Extension box no. 3 (For technician
EXT3 (60 350)
use only)

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 31

Crop Management technologies


USER GUIDE
NMC-PRO
3.4 Alarm Setting
Set alarms and define action in event of an alarm
ALARM SETTING
Irr. Dose Delay Alarm
Description
4. Alarm Setting High Flow CONT. STOP
mm:ss
01:00
Active
NO
Low Flow STOP STOP 01:00 YES
No Flow STOP STOP ---- YES
3. Alarm D. Ch. Leak STOP STOP 30:00 YES
D. Ch. Fault STOP STOP 01:00 YES
Ext. Pause PAUSE IRRIG. 00:30 YES
Define alarm action: automatically D. Boos.Prot.
Low Pressure
CONT.
STOP
STOP
STOP
01:00
01:00
YES
YES
stop or continue. R.U. Error STOP STOP 01:00 YES
Host Error STOP STOP 01:00 YES
Delay before generating alarm.
Alarm output activation: YES/NO (siren, light).

3.5 EC/pH Alarm Definition


Define EC/pH threshold EC/pH ALARM DEFINITION
Delta EC Low 0.5
Delta EC High 0.5
Delta pH Low 0.5
Delta pH High 0.5
5. EC/pH Alarm Delta EC-Pre Control Low 0.5
Delta EC-Pre Control High 0.5
Definition Emergency EC High (1 Min.Dly) 5.0
3. Alarm Emergency pH Low (1 Min.Dly) 2.0

Delta Low: Maximum differences


bellow EC, pH and EC Pre-Control targets.
Delta High: Maximum difference above EC, pH and
EC Pre-Control targets.
Emergency: Critical values of High EC and Low pH
that stop the system after 1min.
3.6 EC/pH Alarm Setting
Set EC/pH alarm and define action in event of an EC/pH alarm
EC/pH ALARM SETTING
Irr. Dose Delay Alarm
Description
mm:ss Active
EC High/Fail STOP STOP 01:00 YES
EC Low STOP STOP 01:00 YES
6. EC/pH Alarm pH High
pH Low/Fail
STOP
STOP
STOP
STOP
01:00
01:00
YES
YES
Setting EC-P. Hi/Fail
EC-Pre. Low
STOP
STOP
STOP
STOP
01:00
01:00
YES
YES
3. Alarm E. Tank Fresh STOP STOP 01:00 YES
E. Tank Drain STOP STOP 01:00 YES
EC Sen. Dif. STOP STOP 01:00 YES
pH Sen Dif. STOP STOP 01:00 YES

Define EC/pH alarm action: automatically stop or continue.


Delay before generating alarm.
Alarm output activation: YES/NO (siren, light).
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 32

Crop Management technologies


USER GUIDE
NMC-PRO
3.7 Radio System Alarm Definition
IMPORTANT: For Radio System to work properly, MUST define in the
6.2 SYSTEM SETUP menu Remote Unit type parameter SN/RF Net.
Define Radio Systems alarm activity and notification.

RADIO SYS. ALARM DEFINITION


Delay Active Inform
Alarm Type mm:ss

7. Radio Sys RTU


Vbatt failure 00:00 YES YES
Alarm Definition Vbatt low
Vbatt warn
00:00
00:00
NO
NO
YES
YES
3. Alarm Cap failure 00:00 NO YES
Card failure 00:00 NO YES
I/O Open 00:00 NO YES
I/O Shor 00:00 NO YES
HOST
Over current 00:00 NO YES

The ACTIVE column defines whether the alarm is used in making decision
regarding the irrigation program (YES / NO)

The INFORM column defines whether the system will notify the user of the
alarm occurrence (YES / NO)

3.8 Radio System Alarm View


View the current alarm status of the Radio System.
RADIO SYS. Alarm view

Unit S/N Comm Vin state Card

8. Radio Sys HOST


BASE
0128
0117
OK
FAIL
-
-
-
-
Alarm View RTU
RTU
0236
0115.3.4
OK
-
-
OK
3.1

3. Alarm RTU 0513.4.1 - FAIL


RTU 0198 - WARN
RTU 0555.3.1 - LOW
RTU ---- - -
RTU ---- - -
RTU ---- - -

The S/N column is the number of the unit. When an Open Circuit or Short
Circuit alarm is detected, the system in addition will also present the card
number and the input/output number that is problematic.

For Example: RTU 0555.3.1

UNIT # CARD # INPUT/OUTPUT #

Exiting and re-entering refreshes the alarm status screen.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 33

Crop Management technologies


USER GUIDE
NMC-PRO
3.9 SMS Subscription
Define which alarms to send for each subscriber. Subscribers need to
be defined in the 6.11 EDIT SMS PHONEBOOK menu.
SMS SUBSCRIPTION
ADAM JAKE
Alarm/Group
*Hardware PRIORITY YES
7. SMS *System VALVE#
*HydraulicVALVE#
PRIORITY
PRIORITY
YES
YES
Subscription *Dosing VALVE# PRIORITY YES
3. Alarm HIGH FLOW VALVE#
LOW FLOW VAVLE#
YES
YES
NO
NO
WATER LEAK YES NO
LOW PRES PRESSOS YES NO
DELTA PRESSURE NO NO
SYS LOW PRESSURE YES YES

Define which subscriber will receive an SMS if there is an active


alarm within the listed alarms or group of alarms according to:

NO Do not send SMS for this alarm

Send SMS for this alarm according to the Send


YES
period parameter defined in the SMS SETUP menu

Send SMS for this alarm as soon as it appears


PRIORITY
(ignores time constraint of the Send Period)

*Refer to the SETUP section (Menus 6.11-6.13) in the Installation manual


for more information on the SMS feature.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 34

Crop Management technologies


USER GUIDE
NMC-PRO
4. HISTORY
4.1 System History
Read-Only screens of system's history (measurements, settings,
processes, events, graphs)
SENSORS LOG
Time Avg. -EC- -pH-
Date
Hum.
25/Apr 16:00 ---- 3.0 4.1

11. Sensor 25/Apr


25/Apr
15:00
14:00
----
----
1.4
1.1
4.8
5.4
Log 22/Apr
22/Apr
16:00
16:00
----
----
1.0
1.0
5.1
5.1
4. History 22/Apr 15:00 ---- 1.0 5.1
22/Apr 15:00 ---- 1.0 5.1
22/Apr 14:00 ---- 1.0 5.1
22/Apr 14:00 ---- 1.0 5.1
22/Apr 13:00 ---- 1.0 5.1
SENSORS LOG
Time Avg. -EC- -pH-
Date
Hum.
25/Apr 16:00 ---- 3.0 4.1
25/Apr
25/Apr
15:00
14:00
----
----
1.4
1.1
4.8
5.4 Select sensors using +/- key
22/Apr
22/Apr
16:00
16:00 ? ----
----
1.0
1.0
5.1
5.1 (no more than 3 per graph)
22/Apr 15:00 Help---- 1.0
Graph 5.1
22/Apr 15:00 ---- 1.0 5.1
22/Apr 14:00 ---- 1.0 5.1
22/Apr 14:00 ---- 1.0 5.1
22/Apr 13:00 ---- 1.0 5.1

GRAPH SELECT
Option Yes/No
Avg. Temp
Avg. Hum.

Menu
-EC-
-pH-

NOTE: Press the Mode/Zone Key to view


the graphs.

-EC- -pH-

5.0
4.0
3.0
2.0 NOTE: Use arrow keys to zoom in/out.
1.0
Use arrow keys to scroll.
16:00 16:00 14:00 12:00 09:00
25/04 22/04 22/04 22/04 22/04

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 35

Crop Management technologies


USER GUIDE
NMC-PRO
The history menu provides extensive information regarding
measurements and processes performed by the NMC-Pro.
HISTORY HISTORY
1. IRRIGATION LOG 4. UNCOMPLETED PROGRAMS
2. RAD. & VPD SUM & DRAIN LOG 5. DAILY IRRIGATION
3. UNCOMPLETED IRRIGATION 6. IRRIGATION ACCUMULATION
4. UNCOMPLETED PROGRAMS 7. AUX METER ACCUMULATION
5. DAILY IRRIGATION 8. ACCUMULATION RESET
6. IRRIGATION ACCUMULATION 9. FILTERS
4. History 7.
8.
AUX METER ACCUMULATION
ACCUMULATION RESET
10.
11.
COOLING
SENSORS LOG
9. FILTERS 12. EVENT LOG
IRRIGATION LOG 10. COOLING 13. SYSTEM LOG

The Irrigation Log table includes up to 200 rows of the last irrigations' data.
Each row includes information regarding a specific irrigation.
To view additional information, use the left/right arrow keys.
To switch between dosing quantities or time simply press the +/- key.
DATE : 24-Dec-06 TIME : 17:17:20 DATE : 24-Dec-06 TIME : 17:17:20
IRRIGATION LOG IRRIGATION LOG
Date Time V1 Reason Water Date Time V1 Duration Flow
23/Dec 17:21 255 Rad Sum 3.671 23/Dec 17:21 255 00:10:00 22.000
23/Dec 17:32 254 Rad Sum 0.834 23/Dec 17:32 254 00:10:00 5.000
23/Dec 17:42 217 Rad Sum 4.004 23/Dec 17:42 217 00:10:00 24.000
23/Dec 17:52 115 Rad Sum 2.504 23/Dec 17:52 115 00:10:00 15.000
23/Dec 18:02 219 Rad Sum 0.834 23/Dec 18:02 219 00:10:00 5.000
24/Dec 14:50 255 Rad Sum 3.671 24/Dec 14:50 255 00:10:00 22.000
24/Dec 15;00 254 Rad Sum 0.834 24/Dec 15;00 254 00:10:00 5.000
24/Dec 15:10 217 Rad Sum 4.007 24/Dec 15:10 217 00:10:00 24.000
24/Dec 15:20 115 Rad Sum 2.503 24/Dec 15:20 115 00:10:00 15.000
24/Dec 15:30 219 Rad Sum 0.834 24/Dec 15:30 219 00:10:00 5.000
DATE : 24-Dec-06 TIME : 17:17:20
IRRIGATION LOG
Date Time V1 Chan. 1 Chan. 2 NOTE: Water quantity is
17:21 255 3.58 3.60
23/Dec
23/Dec 17:32 254 2.63 2.81
measured in m or gallons;
23/Dec 17:42 217 3.58 3.59 duration is measured by
23/Dec 17:52 115 3.41 3.44
23/Dec 18:02 219 2.64 2.81
time; flow is measured in
24/Dec 14:50 255 3.58 3.59 m/h or gallon/m; dosing
24/Dec 15;00 254 2.63 2.81
24/Dec 15:10 217 3.57 3.60
quantity is measured in liters
24/Dec 15:20 115 3.43 3.44 or gallons.
24/Dec 15:30 219 3.52 2.82

Item Description
Date Date in which the irrigation started.
Time Time in which the irrigation started.
Valve Leading valve; the first valve set for the group of valves
Specification of the irrigation triggers; time, condition, Rad
Reason
Sum, etc.
Water Irrigation quantity (m or gallon) or irrigation time.
Duration Irrigation duration (hh:mm:ss).
Flow Average flow throughout the irrigation cycle.
Chan. # Dosing quantities per channel (liter or gallon) or dosing time.
EC Low Lowest EC value recorded during irrigation.
EC Avg. Average EC value recorded during irrigation.
EC High Highest EC value recorded during irrigation.
pH Low Lowest pH value recorded during irrigation.
pH Avg. Average pH value recorded during irrigation.
pH High Highest pH value recorded during irrigation.
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 36

Crop Management technologies


USER GUIDE
NMC-PRO

RAD. & VPD SUM & DRAIN LOG


DATE : 21-Dec-06 TIME : 14:51:18 DATE : 21-Dec-06 TIME : 14:51:33
RAD. SUM & DRAIN LOG IRRIGATION LOG
Date Time V1 Reason Water Date Time V1 Drain % Drain
20/Dec 17:26 254 Rad Sum 1.400 20/Dec 17:26 254 100.00 1450
20/Dec 17:26 217 Rad Sum 1.400 20/Dec 17:26 217 92.86 1300
20/Dec 17:27 115 Rad Sum 1.400 20/Dec 17:27 115 78.57 1100
20/Dec 17:27 219 Rad Sum 1.400 20/Dec 17:27 219 100.00 1400
20/Dec 17:27 255 Rad Sum 1.400 20/Dec 17:27 255 ----- 0
20/Dec 17:28 254 Rad Sum 0.800 20/Dec 17:28 254 62.50 500
20/Dec 17;28 217 Rad Sum 0.800 20/Dec 17;28 217 100.00 800
20/Dec 17:28 115 Rad Sum 0.800 20/Dec 17:28 115 18.75 150
20/Dec 17:29 219 Rad Sum 0.800 20/Dec 17:29 219 ----- 0
20/Dec 17:29 255 Rad Sum 0.800 20/Dec 17:29 255 100.00 850

DATE : 21-Dec-06 TIME : 14:51:45


IRRIGATION LOG
Date Time V1 Rad Sum Interval
20/Dec 17:26 254 19 ----
20/Dec 17:26 217 19 ----
20/Dec 17:27 115 19 1
20/Dec 17:27 219 19 1
20/Dec 17:27 255 19 2
20/Dec 17:28 254 19 ----
20/Dec 17;28 217 19 ----
20/Dec 17:28 115 19 ----
20/Dec 17:29 219 19 1
20/Dec 17:29 255 15 1

Item Description
Time Time irrigation started.
Valve Leading valve.
Specification of the irrigation triggers; time, condition, Rad
Reason
Sum, etc.
Water Irrigation quantity (m or gallon) or irrigation time.
Drain % Percentage of drain for relevant irrigation cycle.
Drain Drain quantity related to relevant irrigation.
Rad Sum Accumulated radiation sum level when irrigation started.
Time (in minutes) since last irrigation cycle. Refers to the last
Interval
irrigation of a specific valve.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 37

Crop Management technologies


USER GUIDE
NMC-PRO
UNCOMPLETED IRRIGATION
The Uncompleted Irrigation table provides information of irrigations that were
started but could not be completed due to a failure. To understand why
irrigation was not completed, it is advisable to cross-reference between this
table and the Alarm Definition in section 4.3. The Uncompleted Irrigation table
consists of up to 200 lines. Note that if the letter 'C' appears, it refers to a
program that was triggered by condition program.
UNCOMPLETED IRRIGATION

No. Date Time Prog V1. Run Dose


hh:mm No. No. No. Prog
1 20-Dec-06 09:05 1 51+ 1 1
2 20-Dec-06 09:25 2 1 1 --

Each line includes information regarding when the irrigation


was stopped and added to the uncompleted irrigations table.
Item Description
Date in which the current line was added to the
Date
uncompleted irrigation table.
Time in which the current line was added to the
Time
uncompleted irrigation table
92- The program that was added to the table was started
manually.
Prog. No. 93- The relevant irrigation was added to the uncompleted
irrigations table for the second time (or more)
consecutively.
Indicates the associated valve. If a group of valves that is
configured to irrigate together is stopped, only the first
Vl. No.
valve is written but a + sign is added next to it to indicate
that more valves are associated.
The NMC-Pro will attempt to complete the irrigations from the current day
(until end day time) upon manual or automatic alarm reset.
The valve column of irrigations that are to be completed will be highlighted.
The valve column of irrigations that are currently being completed will
blink.
Run No Indicates the associated run time program.
Dose Prog. Indicates the associated dosing program.
Prog. Qty. Planned quantity according to the run time program.
Left Qty. Uncompleted quantity.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 38

Crop Management technologies


USER GUIDE
NMC-PRO
In order to manually stop an uncompleted irrigation you must go to the
START/STOP VALVE in section 3.3 because the activation is according to
single valves.

UNCOMPLETED PROGRAMS
The Uncompleted Programs table provides information on programs that could
not be completed. It is important to understand the difference between this
table and the Uncompleted Irrigations table; this table consists only of
irrigation cycles that havent been started and could not be completed during
the current day. This can happen due to wrong system setup (more tasks than
could be completed), or because the system was not active for a long period
of time, for example due to a power failure, and could not complete its tasks.
UNCOMPLETED PROGRAMS
No. Date Time Prog Start Prog Left
hh:mm No. Time Cyc. Cyc.
4 9/Aug 20:00 10 19:00 1 1
5 9/Aug 21:00 10 20:00 1 1
6 10/Aug 04:00 1 13:00 2 2
7 10/Aug 05:00 1 04:00 2 2
The uncompleted program
8 10/Aug 06:00 10 21:00 1 1 table consists of 200 lines.
9 10/Aug 07:00 1 05:00 2 2
10 10/Aug 09:00 1 07:00 2 2
11 10/Aug 11:00 1 09:00 2 2
12 10/Aug 13:00 1 11:00 2 2
13 10/Aug 14:00 10 06:00 1 1

DAILY IRRIGATION
This table allows you to view history of irrigation quantities or time per valve.

Example: 1 day ago means


you would like to view
DAILY IRRIGATION
yesterday's history, and Today
How Many Days Ago? 1 Day Ago

means you would like to view
the accumulated history since
the last End Day. To open the
selection list
Current date viewed at top of screen.
Relevant day DATE : 20-Dec-06
using arrow ENTER DAILY IRRIGATION
keys Valve Water Drain% Dra. Q.
213 0.000 100 0.000
214 0.000 100 0.000
215 70.800 11 8.350
DATE : 20-Dec-06 216 1.400 0 0.000
DAILY IRRIGATION 217 15.900 34 5.500
Valve Chan. 1 Chan. 2 Chan. 3 218 7.200 45 3.300
219 13.600 20 2.850
213 0.00 0.00 0.00
220 0.000 100 0.000
214 0.00 0.00 0.00
221 0.000 100 0.000
215 211.36 211.37 211.37
216 3.93 3.94 3.94 Press +/- to Toggle Quantity/Time
217 30.87 30.82 30.83
218 19.06 19.97 18.12
219 25.25 26.01 24.49 Daily Irrigation table contains all water (m3 or gallon)
220 0.00 0.00 0.00
221 0.00 0.00 0.00
and dosing (liter or gallon). To toggle the view
between quantities and time, press the +/- key.
Press +/- to Toggle Quantity/Time

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 39

Crop Management technologies


USER GUIDE
NMC-PRO
IRRIGATION ACCUMULATION
The Irrigation Accumulation table allows you to accumulate water and dosing
quantities for the required periods. The accumulation of each valve can be
reset separately in the ACCUMULATION RESET table.

DATE : 21-Dec-06 DATE : 21-Dec-06


IRRIGATION ACCUMULATION IRRIGATION ACCUMULATION
Valve Date Water Chan. 1 Valve Chan. 1 Chan. 2 Chan. 3
214 20-Dec-06 0.000 0.00 214 0.00 0.00 0.00
215 20-Dec-06 70.800 211.36 215 211.36 211.37 211.37
216 20-Dec-06 1.400 3.93 216 3.93 3.94 3.94
217 20-Dec-06 19.100 35.28 217 35.28 35.21 35.21
218 20-Dec-06 7.200 19.06 218 19.06 19.97 18.12
219 20-Dec-06 16.800 29.65 219 29.65 30.38 28.86
220 20-Dec-06 0.000 0.00 220 0.00 0.00 0.00
221 20-Dec-06 0.000 0.00 221 0.00 0.00 0.00
222 20-Dec-06 0.000 0.00 222 0.00 0.00 0.00

Press +/- to Toggle Quantity/Time Press +/- to Toggle Quantity/Time

To toggle the view between quantities Water quantity is measured in cubic


and time, press the +/- key meter or gallons; dosing quantity is
measured in liters or gallons.

AUX METER ACCUMULATION


The Auxiliary Meter Accumulation table allows you to accumulate quantities
from meters that do not have designated software, for example, in order to
measure the drain water quantity or to measure the cooling systems
consumption.

AUX METER ACCUMULATION


Meter Quantity Date
1 4.600 20-Dec-06
2 3.500 20-Dec-06 NOTE: Water meters are accumulators only
3 2.200 20-Dec-06
4 2.500 20-Dec-06 and are not a part of the irrigation control.
5 3.450 20-Dec-06
6 3.600 20-Dec-06
7 5.700 20-Dec-06
8 4.200 20-Dec-06 To reset an auxiliary meter refer to the
ACCUMULATION {XE "Reset Total Quantity" }
table below.

The quantities displayed are in liters


(gallons) up to 9999.999.

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 40

Crop Management technologies


USER GUIDE
NMC-PRO
ACCUMULATION RESET

ENTER
ACCUMULATION RESET
Reset Valve Quantity For? <None>
Reset Aux. Meter For? <None>
ENTER to reset Desired option
accumulation of a using arrow keys
specific valve or all
valves
NOTE: When resetting a valve (or all valves), its history will be erased from the following tables:
-Daily Irrigation
-Irrigation Accumulation
ENTER to reset an
individual auxiliary Desired option
ENTER
meter or all auxiliary using arrow keys
meters

NOTE: When resetting an Aux meter (or all Aux meters), its history will be erased from the Aux
Meter Accumulation table.

FILTERS
The filters history table provides daily information of the number and cause of
flushing.

FILTERS
Date Delta P. Time Manual
10/Aug 0 44 0
9/Aug 0 0 0
8/Aug 0 0 0

COOLING
Viewing the history of cooling activities or time per valve is allowed.

COOLING
How Many Days Ago? 1 Day Ago ENTER

ENTER to open Relevant day


selection list using arrow keys

COOLING
Prog. From To Cycles
No. hh:mm hh:mm
1
2
13:10
13:13
18:14
18:14
60
9
For example, 1 day ago means you would like to view
3 --:-- --:-- ----- yesterday's history, and Today means you would like to
4
5
--:--
--:--
--:--
--:--
-----
-----
view the accumulated history since the last End Day.
6 --:-- --:-- -----
7 --:-- --:-- -----
8 --:-- --:-- -----

Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 41

Crop Management technologies


USER GUIDE
NMC-PRO
SENSOR LOG
The sensors Log table includes history of average measurements of logged
sensors. In order to define which sensor to log, the user should access menu
6.8 Sensor Logging, and mark by +/- button the required sensor.
In order to define the measurement interval, the user should go to menu 6.2
and choose the required History resolution.
SENSORS LOG
Date Time Avg. Temp-1 Temp-2
Hum.
10/Aug 16:28 22.7 22.7 ----
10/Aug 16:27 22.7 22.7 ----
10/Aug 16:26 22.7 22.7 ----
10/Aug 16:26 22.7 22.7 ----
10/Aug 16:25 22.7 22.7 ----
10/Aug 16:24 22.7 22.7 ----
10/Aug 16:23 22.7 22.7 ----
10/Aug 16:22 22.7 22.7 ----
10/Aug 16:21 22.7 22.7 ----
10/Aug 16:20 22.7 22.7 ----

The sensors Log table contains up to 10,000 data fields. Date and time are 2
fields per line and every sensor is an additional field.

For example: logging of 2 sensors uses 4 data fields; 2 for time and date and
1 for each sensor. In this case, the table will consist of a maximum of 2,500
lines.
EVENT LOG
The table provides information of all the processes performed by the NMC-Pro
including their time and date.
EVENT LOG
No. Event Date Time
1 Water Leak # 4 20/Dec 09:01
2 Program # 1 Manual On 20/Dec 09:03
3 Valve #51 Manual Off 20/Dec 09:04
4 Program # 1 Man. Off 20/Dec 09:04
5 Program # 1 Manual On 20/Dec 09:04
6 Valve #51 Low Flow 20/Dec 09:04
7 Program # 1 Man. Off 20/Dec 09:05
8 Program # 2 Rad. On 20/Dec 09:21
9 Valve # 1 High Flow 20/Dec 09:23
10 Program # 2 Rad. Off 20/Dec 09:25

The table consists of the last 999 events.


SYSTEM LOG
This table provides information of all the system changes.
SYSTEM LOG
No. Event Date Time
1 PC Irri. Prog #10 Ch. 20/Dec 09:01
2 Reset Alarm 20/Dec 09:03
3 PC Table #1.3 Change 20/Dec 09:04
4 PC Irri. Prog #1 Ch. 20/Dec 09:04
5 PC Irri. Prog #1 Ch. 20/Dec 09:04
6 Irrig. Prog #1 Ch. 20/Dec 09:04
7 Irrig. Prog #2 Ch. 20/Dec 09:05
8 Table #7.7 Change 20/Dec 09:21
9 Table #1.3 Change 20/Dec 09:23
10 Table #1.7 Change 20/Dec 09:25

The table consists of the last 999 events.


Examples of system changes are changes of triggered by the controller, the
PC communication, a power off, etc.
Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 42

Crop Management technologies


Doc. Name: NMC-PRO I User Manual Revision: 02 Page: 43

Crop Management technologies