You are on page 1of 10

SR NO TCE.

5259A-712-CW-3401E
X-59 1 X-63
11kV STATION SWGR-2 [PNL X-60 2 X-64
1 2-712-5705 4C X 4 NO: 1] [DRG NO : PEI-
7602PN058-3-AEI-373] X-61 3 X-65
X-62 4 X-66

X-85 -

X-86 -

X-196 1 *

2 *

11kV STATION SWGR-2 [PNL


2 2-712-5706 2C X 2.5 NO: 1] [DRG NO : PEI-
7602PN063-3-AEI-373] X-197
X-200 *

X-201
X-134 -

X-135 -

X-85 1 TB63-1
11kV STATION SWGR-2 [PNL
3 2-712-5707 3C X 2.5 NO: 1] [DRG NO : PEI- X-86 2 TB63-2
7602PN063-3-AEI-373]
3 SPARE

X-85(X-95) -

X-87 (X-96) -

1 *
X-198

2 *

X-199
11kV STATION SWGR-2 [PNL
4 2-712-5708 2C X 2.5 NO: 1] [DRG NO : PEI-
7602PN063-3-AEI-373]
11kV STATION SWGR-2 [PNL X-202 *
4 2-712-5708 2C X 2.5 NO: 1] [DRG NO : PEI-
7602PN063-3-AEI-373]

X-203
X-136 -

X-137
X-85(X-95) 1 TB63-9
11kV STATION SWGR-2 [PNL
5 2-712-5709 3C X 2.5 NO: 1] [DRG NO : PEI- X-87 (X-96) 2 TB63-10
7602PN063-3-AEI-373]
3 SPARE

TB5-25 1 TB5-25

TB5-26 TB5-26

TB6-25 TB6-25
400 kV GT-2 MAIN BREAKER
6 2-712-5710 3C X 2.5 MARSHALLING BOX [DRG NO : TB6-26 TB6-26
PEI-7602PN063-4-EMI-016]
TB7-25 TB7-25

TB7-26 2 TB7-26
3 SPARE

X-17 1 TB5-5
11kV STATION SWGR-2 [PNL
7 2-712-5711 3C X 2.5 NO: 1] [DRG NO : PEI- 2
7602PN063-3-AEI-373] X-18 TB7-6
SPARE 3 SPARE
X-5 1 X-11

11kV STATION SWGR-1 [PNL


8 2-712-5712 3C X 2.5 NO: 01] [DRG NO : PEI- X-6 2 X-12
7602PN063-3-AEI-373]

3 SPARE
X-11 1 *
11kV STATION SWGR-2 [PNL
9 2-712-5713 3C X 2.5 NO: 1] [DRG NO : PEI- X-12 2 *
7602PN063-3-AEI-373]
SPARE 3 SPARE

X-120 1 TB-15
11kV STATION SWGR-2 [PNL X-121 2 TB-16
10 2-712-5714 4C X 2.5 NO: 01] [DRG NO : PEI-
7602PN063-3-AEI-373] X-122 3 TB-17

X-123 4 TB-18

X-124 1 TB1-21

X-125 2 TB1-22

X-126 3 TB1-23
11kV STATION SWGR-2 [PNL
11 2-712-5715 4C X 2.5 NO: 01] [DRG NO : PEI-
7602PN063-3-AEI-373]
11kV STATION SWGR-2 [PNL 4 TB1-24
X-127
11 2-712-5715 4C X 2.5 NO: 01] [DRG NO : PEI-
7602PN063-3-AEI-373] TB1-1
TB1-2
TB1-3
TB1-4

TB5-25 1 X17
400 kV GT-1 MAIN BREAKER
12 1-712-4710A 3C X 2.5 MARSHALLING BOX [DRG NO : TB7-26 2 x18
PEI-7602PN063-4-EMI-016]
3 SPARE
SR NO
TCE.5259A-545-CW-3401B
CTJB5-8 1 TB-35

1-3CTF CORE-3 (DRG NO. CTJB5-9 2 TB-36


6 1-545-4064 4C x 4
3369283)
CTJB5-10 3 TB-37
CTJB5-11 4 TB-38
CTJB5-15 1 TB-120

1-3CTF CORE-2 (DRG NO. CTJB5-16 2 TB-121


7 1-545-4065 4C x 4
3369283)
CTJB5-17 3 TB-122
CTJB5-18 4 TB-123
CTJB5-1 1 TB-63

1-3CTF CORE-4 (DRG NO. CTJB5-2 2 TB-64


8 1-545-4066 4C x4
3369283)
CTJB5-3 3 TB-65
CTJB5-4 4 TB-66
TB-63 1 TB-59

33KV CICO PANEL(DRG NO. PEI- TB-64 2 TB-60


9 1-545-4067 4C x 4
7602PN063-3-AEI-371 PG 4 OF 7)
TB-65 3 TB-61
TB-66 4 TB-62
TB-3 TB-1
NGR CT FOR 64REF(11KV SIDE TB-4 TB-2
10 1-545-4068 2C x 2.5 OF ST)(DRG NO: PEI-7602PN063-
4-RSI-101)

2N1S1 TB-81

CT FOR 64REF(33KV SIDE OF 2N1S2 TB-82


11 1-545-4069 2C x 2.5
ST,FROM CT JB)

TB-5 TB-83
NGR CT FOR 51G(11KV SIDE OF TB-6 TB-84
12 1-545-4070 2C x 2.5 ST)(DRG NO: PEI-7602PN063-4-
RSI-101)

PEI-7602PN063-4-CAL-084
29 1C
30 2C
13 C4-03-040A 5CX2.5 11KV UT 1B 31 3C
32 4C
5C
29 1C
30 2C
14 C4-03-040B 5CX2.5 11KV ST 31 3C
32 4C
5C
TB5-49 1C TB-33
15 C4-03-055 3C*2.5 403RA TB5-50 2C TB-34
3C
TB5-39 1C TB-33
16 C4-03-058 3C*2.5 403RB
16 C4-03-058 3C*2.5 403RB TB5-40 2C TB-34
3C

TCE.5259A-580-LS-ICS-06
T-46 1 X49
T-47 2 X50
T-48 3 X55
T-49 4 X56
T-50 5 X45
T-51 6 X46
T-31 7 X41
17 2-545-5045 19C x 2.5 ST-1 MARSHALLING BOX
T-32 8 X42
T-56 11 X57
T-57 12 X58
T-58 13 X43
T-59 14 X44
T-60 15 X25
T-61 16 X26
T-62 T-66 1 X39
T-63 T-67 2 X40
T-64 T-68 3 X51
T-65 T-69 4 X52
18 12-545-5046 19C x2.5 ST-1 MARSHALLING BOX
T-70 9 X47
T-71 10 X48
T-72 11 X53
T-73 12 X54

NOTE: The Instrumental cable are not considered in this list.


-3401E

33kV STATION SWGR-1 [PNL NO: 1] CT INPUT FOR ST DIFFERENTAIL


[DRG NO : PEI-7602PN058-3-AEI- PROTECTION FROM 33 KV SIDE
371] TO 11KV SIDE
ST-2 11KV SIDE & ST-2 33KV SIDE
DIFFERENTIAL, REF AND
TRANSFORMER FAULTS FOR
CLASS A2 TRIP (TERMINAL NO.85
& 86 SHALL BE PROGRAMMED
FOR ALL THE ABOVE MENTIONED
FAULTS)
ST-2 STANDBY E/F OPERATED &
HV WTI TRIP (RL6 USED FOR
OVER VOALTGE TRIP SHALL BE
REMOVED AND PROGRAMMED
FOR 51N & WTI TRIP OUTPUT
FROM MICOM P127) FOR CLASS
A2 TRIP. (CONTACT
MULTIPLICATION RELAY 4NO+4NC
SHALL BE USED ACROSS THE
CONTACTS OF 5 &7 OF RL6). THE
OUTPUT CONTACTS OF CONTACT
MULTIPLICATION RELAY SHALL BE
33kV STATION SWGR-2 [PNL NO: 1] USED.
[DRG NO : PEI-7602PN058-3-MVI-
031]

ST-2 11KV & 33KV SIDE 50LBB


OPERATED FOR CLASS A2 TRIP
(CONTACT MULTIPLICATION
RELAY 4NO+4NC SHALL BE USED
ACROSS TERMINAL NO. 69 & 70).
THE OUTPUT CONTACTS OF
CONTACT MULTIPLICATION RELAY
SHALL BE USED.

ST-2 20 KV SIDE IDMT


OVERCURRENT, SHORT CIRCUIT
AND SEC WTI TRIP & PRV TRIP
FOR CLASS A2 TRIP (TERMINAL
NO.134, 135 SHALL BE
PROGRAMMED FOR ALL THE
ABOVEA2
CLASS MENTIONED
TRIP FROMFAULTS)
STATION
GT-2 SWITCHYARD RELAY PANEL SWGR-1 TO GT RELAY PANEL
[DRG N0: CPD KA01SC03]
ST-2 11KV SIDE & ST-2 33KV SIDE
DIFFERENTIAL, REF AND
TRANSFORMER FAULTS FOR
CLASS A2 TRIP (TERMINAL NO.85
& 87 SHALL BE PROGRAMMED
FOR ALL THE ABOVE MENTIONED
FAULTS)

ST-2 STANDBY E/F OPERATED &


HV WTI TRIP (RL6 USED FOR
OVER VOALTGE TRIP SHALL BE
REMOVED AND PROGRAMMED
FOR 51N & WTI TRIP OUTPUT
FROM MICOM P127) FOR CLASS
A2 TRIP. (CONTACT
MULTIPLICATION RELAY 4NO+4NC
SHALL BE USED ACROSS THE
CONTACTS OF 5 &7 OF RL6). THE
OUTPUT CONTACTS OF CONTACT
MULTIPLICATION RELAY SHALL BE
USED.

33kV STATION SWGR-2 [PNL NO: 1]


[DRG NO : PEI-7602PN058-3-AEI-
371]
33kV STATION SWGR-2 [PNL NO: 1]
[DRG NO : PEI-7602PN058-3-AEI-
371]
ST-2 11KV & 33KV SIDE 50LBB
OPERATED FOR CLASS A2 TRIP
(CONTACT MULTIPLICATION
RELAY 4NO+4NC SHALL BE USED
ACROSS TERMINAL NO. 69 & 70).
THE OUTPUT CONTACTS OF
CONTACT MULTIPLICATION RELAY
SHALL BE USED.

ST-2 20 KV SIDE IDMT


OVERCURRENT, SHORT CIRCUIT
AND SEC WTI TRIP & PRV TRIP
FOR CLASS A2 TRIP (TERMINAL
NO.136, 137 SHALL BE
PROGRAMMED FOR ALL THE
ABOVE MENTIONED FAULTS)

CLASS A2 TRIP FROM STATION


GT-2 SWITCHYARD RELAY PANEL SWGR-1 TO GT RELAY PANEL
[DRG N0: CPD KA01SC03]

GT-2 MAIN BREAKER & TIE


400 kV GT-2 TIE BREAKER BREAKER (NO CONTACT) FOR ST-
MARSHALLING BOX [DRG NO : PEI- 2 11KV SIDE INCOMER CLOSING
7602PN063-4-EMI-028] INTERLOCK

400 kV GT-2 MAIN BREAKER GT-2 MAIN BREAKER & TIE


MARSHALLING BOX[DRG NO : PEI- BREAKER (NO CONTACT) FOR
7602PN063-4-EMI-016] INCOMER CLOSING INTERLOCK

110V LINE PT SUPPLY FOR


SYNCHRONIZING K25. [TAP FROM
11kV STATION SWGR-2 [PNL NO: 01] E12 AND E32 FROM LPT OF
[DRG NO : PEI-7602PN063-3-AEI- STATION SWGR-1 SHALL BE
373] UTILISED].

ST-2 FIRE PROTECTION


OPERATED SIGNAL FROM
DELUGE VALVE FOR TRIPPING
FIRE PROTECTION PANEL INTERLOCK [RL1 OF MICOM P122
SHALL BE PROGRAMMED FOR HV
WTI TRIP AND FIRE PROTECTION
TRIP]

IPBD - CT JUNCTION BOX - 5 [DRG


20KV CT INPUT TO MFM METER
NO : PEI-7602PN063-3-IPBD-005,
LOCATED IN STATION SWGR - 2
SH.24]

20KV PT INPUT TO MFM METER


LOCATED IN STATION SWGR - 2

LAVT - [DRG NO : PEI-7602PN063-3-


IPBD-009, SH.5]
20KV PT INPUT TO MFM METER
LOCATED IN STATION SWGR - 2

LAVT - [DRG NO : PEI-7602PN063-3-


IPBD-009, SH.5]

SHORTING BETWEEN TB 1-4 TO TB


21-24 SHALL BE THROUGH MCB

GT-1 MAIN BREAKER & TIE


BREAKER (NO CONTACT) FOR ST-
ST#1 Incomer Panel no 1
1 11KV SIDE INCOMER CLOSING
INTERLOCK
-3401B

MICOM P122 AT 11KV ST-1 INCOMER


CT INPUT FOR 50, 51 PROTECTION
PANEL (DRG NO. PEI-7602PN063-3-
(MICOM P122)
AEI-373 PG 4/8)

MFM P15A AT 11KV ST-1 INCOMER


PANEL (DRG NO. PEI-7602PN063-3- CT INPUT FOR MFM ( P15A)
AEI-373 PG 4/8)

MICOM P633 AT ST-1 INCOMER


CT INPUT FOR ST-1 DIFFERENTIAL
PANEL (DRG NO. PEI-7602PN063-3-
PROTECTION (MICOM P633)
AEI-373 PG 1/8)

MICOM P633 AT 11KV ST-1 INCOMER


CT INPUT FOR ST-1 DIFFERENTIAL
PANEL (DRG NO. PEI-7602PN063-3-
PROTECTION (MICOM P633)
AEI-373 PG 1/8)

MICOM P633 AT 11KV ST-1 INCOMER


PANEL (DRG NO. PEI-7602PN063-3- CT INPUT FOR 64REF (MICOM P633)
AEI-391 PG 1/8)

MICOM P633 AT 11KV ST-1 INCOMER


PANEL (DRG NO. PEI-7602PN063-3- CT INPUT FOR 64REF (MICOM P633)
AEI-391 PG 1/8)

MICOM P127 AT 11kV ST-1 INCOMER


PANEL (DRG NO. PEI-7602PN063-3- CT INPUT FOR 51G (MICOM P127)
AEI-391 PG 1/8)

AL-084

OVERALL DIFFERENTIAL
11KV ST PROTECTION

OVERALL DIFFERENTIAL
Transformer PROTECTION

Down stream brk tripping


ST-1 from Gt& TIE Breaker

Down stream brk tripping


ST-1 from Gt& TIE Breaker
Down stream brk tripping
ST-1 from Gt& TIE Breaker

ICS-06
BUCHHOLZ ALARM

BUCHHOLZ TRIP

MOLG-ALARM

11KV SWITCHYARD SWITCHGEAR COOLER TROUBLE + CONTROL


INCOMER PANEL SUPPLY FAIL

PRD-TRIP

WTI-HV ALARM

WTI-HV TRIP

WTI-SEC-1 & SEC -2 ALARM

WTI-SEC1 & SEC2 TRIP


11KV SWITCHYARD SWITCHGEAR
INCOMER PANEL
OTI ALARM

OTI TRIP