You are on page 1of 7

A

Comparative
Guide to
Inlet Air
Cooling
Technologies
Under High
Temperature/Humidity
Conditions

An Overview

MEE INDUSTRIES, INC.


During hot weather, combustion There is, however, a limitation on Gas turbines typically
turbine (CT) operators are posed a the amount of inlet air cooling that can operate at as little as
significant problem by the degradation safely be accomplished. If the tempera- 80% of their rated
of turbine generation capacity. The ture is allowed to go too low, ice can capacity on hot days
typical CT on a hot summer day, for form on the bell-mouth or inlet guide due to the lower air
instance, produces up to 20% less vanes, with the risk of this ice flaking density and higher
power than on a cold winter day. As a off and doing mechanical damage to temperatures. Inlet air
result, a number of cooling techniques the compressor blades. This phenome- cooling helps to make
have evolved over the years to non can occur even when the inlet air up the difference by
maximize turbine output. temperature is above freezing, because increasing the air mass
suction at the turbine inlet creates a low flow through the turbine
1.25
pressure ‘cool zone’ at the bell-mouth. and by cooling the air,
1.20 TURBINE
1.15 PERFORMANCE To avoid this problem, most turbine which reduces the work
CHART manufacturers recommend that inlet air of compression.

Correction Factor
1.10
1.05 be kept at or above 45ºF.
1.00 Traditionally, either mechanical
0.95 chillers or media-type evaporative cool-
0.90 ers have been used to cool combustion
0.85 turbine inlet air.
0.80
0.75
0 10 20 30 40 50 60 70 80 90 100 110 120
Compressor Inlet Temperature - º F
INLET AIR CHILLERS Inlet Air
Various refrigerant-type air chilling Chillers
The basic theory of inlet air cooling systems have been successfully
for gas turbines is simple enough. employed for combustion turbine inlet The most powerful
Combustion turbines are constant vol- air cooling. These range from method of inlet air cooling,
ume machines – at a given shaft speed compressor-type chillers to absorption chillers are capable of
they always move the same volume of chillers, which utilize “waste” heat as an keeping inlet air at 45°F
air – but the power output of a turbine energy source for the chilling process. throughout the year,
depends on the flow of mass through Thermal storage systems have also though costs can be
it. That’s why on hot days, when air is been successfully applied to CTs. higher than with other
less dense, power output falls off. By These use relatively small chiller plants, approaches.
feeding cooler air into the CT, mass running off-peak, to make ice or cold-
flow is increased, resulting in higher brine solutions which are stored in an
output. Another factor is the power insulated tank and used to cool the
consumed by the CT’s compressor. inlet air during peak-power demand.
The work required to compress air is Such systems have proven to be a cost-
directly proportional to the temperature effective way to overcome power loss
of the air, so reducing the inlet air tem- during peak-demand periods, while
perature reduces the work of compres- reducing the high costs normally
sion and there is more work available associated with chiller plants.
at the turbine output shaft.

Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364
Overall, chillers are capable of wetted honeycomb-like pad of cellulose HIGH PRESSURE FOGGING Fog systems have been installed on High Pressure
achieving a greater drop in inlet air fiber material (the medium). When air High pressure fogging is a more both base-loaded and peaking gas tur- Fogging
temperature than other methods of is pulled through, it evaporates water recent addition to the roster of tech- bines and are used in both simple-cycle
inlet air cooling. The most powerful off the convoluted surfaces of the wet- nologies employed for inlet air cooling. and combined-cycle plants. In most In high humidity
chillers, for example, are capable of ted media, thereby cooling the inlet air. Fogging systems are similar to media- cases, turbine operators opt to install conditions, high pressure
keeping the inlet air at 45°F through- Evaporative coolers are limited by type evaporative cooling systems in that the fog nozzle manifolds downstream fogging usually can
out the year, if desired. This compares the amount of moisture present in the they cool by evaporating water, but of the air filters and just upstream of the provide more cooling than
well to its competing technologies air. Once saturation (i.e., 100% relative instead of using an evaporative medi- silencers. This form of installation usu- media-type evaporative
which can manage temperature drops humidity) is reached, evaporative cool- um, the water is atomized into billions ally requires one to two outage days coolers. Chillers take the
of anywhere from 15 to 25°F in ing systems are unable to evaporate of super-small fog droplets. and calls for minor modifications to the temperature lower yet,
temperate climates and as much as more water into the air stream. For this Fog systems use high pressure turbine inlet structures. Fog systems but with much higher
40°F of cooling in arid, desert climates. reason, in hot, humid regions, it often water pumps to pressurize demineral- can also be positioned upstream of air installation and operating
There are drawbacks to chillers, isn’t possible to accomplish more than ized water to between 1000 and 3000 filters, resulting in no outage time. This costs.
however, including high first costs, and about 10 to 15ºF of cooling. Chillers psi. The water then flows through a type of installation, however, requires
high operating and maintenance costs. don’t have this problem. They are not network of stainless steel tubes to fog the use of fog droplet eliminators to
These factors may explain why few restricted by high ambient humidity nozzle manifolds that are installed in prevent wetting of the air filters. When
turbine operators have taken advantage and are therefore capable of giving a the air stream. These nozzles atomize fog nozzles are installed inside the air
of inlet air chillers. larger power boost than evaporative the water into micro-fine fog droplets ducts, special attention must be given
coolers. which evaporate quickly. to the nozzle manifolds. They must be
Another factor to be considered Other factors being equal, the correctly designed to avoid the possibil-
with evaporative coolers is the cost of speed of evaporation of water depends ity of small parts breaking off and
Evaporative EVAPORATIVE COOLERS retrofitting and installing them. Although on the surface area of water exposed to being ingested by the turbine.
Coolers Evaporation is a natural process that the units themselves are generally fairly the air. This is why media-type evapo- One advantage of high pressure
results in the conversion of water from inexpensive, installation usually calls for rative coolers use convoluted honey- fogging is its efficiency level in hot,
The most widely used CT a liquid to a vapor. This conversion is duct enlargement, as evaporative coolers comb type media – to maximize the humid areas. As a comparison, take
inlet air cooling system, called a phase change. When water require relatively low air velocities. If the surface area of water exposed to the Houston, TX at 96°F in high humidity.
media-type evaporative changes phase, it either absorbs or air velocity across the wetted media is air. In high pressure fogging, however, In this climate, a fog system can
cooling is less effective in releases heat. For instance, when a too high, it can strip water from the the evaporative surfaces are the fog achieve as much as 19 to 20°F of cool-
hot, humid conditions. In pound of water changes from the liquid media, cause excessive wetting of the droplets themselves. For this reason, ing, while a media-type evaporative
low humidity environ- phase to vapor phase it consumes 1160 ducts and even fouling of the compres- the size of droplet generated by the cooler can get only about 15 to 17°F of
ments, though, it can BTUs of heat. A good example of sor blades. For these reasons, evapora- fog system is a critical factor. For cooling. A chiller takes the temperature
boost power output by evaporation is the cooling effect of a tive coolers are sometimes ruled out as instance, because of the geometry of far lower, but energy demands and
10% or more, depending breeze on a summer day. Even if the a retrofit option. Overall though, if spheres, a given amount of water installation costs are much higher.
on ambient conditions. air is hotter than body temperature, retrofitting or installation costs are not atomized into 10-micron droplets yields
the breeze feels cooler because it prohibitive, evaporative coolers work ten times more surface area than the
evaporates perspiration off the skin. well. In low-humidity environments they same amount of water atomized into
Media-type evaporative coolers are capable of increasing power output 100-micron droplets.
make use of this principle and are the by as much as 15%, while in high-
most common cooling system humidity areas, the power boost tends
employed in combustion turbine inlet to be 10% or less.
air cooling. They generally consist of a

Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364 Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364
Fog
Intercooling
FOG INTERCOOLING
An innovative application of high
rates and the cooling effect outweighs
the addition of the inherently less CaseChiller
Study: remove the heat of compression and
liquefy the ammonia vapors. Liquid
pressure fogging, known as fog dense water vapor. Installation ammonia then returns to the recircula-
While the limits of this intercooling, is showing great promise The limits of fog intercooling have tion tank, and from there it is pumped
technology have not been as a means of increasing the power not been fully investigated. Several Ripon Cogeneration, near Modesto, to the coils (situated in the air inlet
fully studied, fog intercool- boost gained from traditional inlet air turbine manufacturers are looking into CA, is a good example of how duct, after the filters). Hot inlet air is
ing shows tremendous cooling fog systems. The basic concept the idea as the benefits are substantial. compressor-type chilling is used for fed past the coils, resulting in thermal
promise in providing large is to inject more fog into an air stream Theoretically, it’s possible to inject inlet air cooling. The company runs a energy absorption and vaporized
power boosts – even in than will evaporate with the given enough fog to cause a power boost GE LM 5000 gas turbine for power ammonia. These vapors and a small
very humid environments climate conditions. Unevaporated fog that is as high as that obtained by inlet generation and supplies steam to the percentage of liquid return to the
droplets are carried by the air stream air chilling, and at a tiny fraction of the nearby Fox River paper mill. Producing recirculation tank.
into the compressor where they cost. 22,000 tons of paper annually, the “Power consumption is higher with
evaporate when the air is heated by If the water droplets are too large, 200-acre mill demands over 45,000 lbs this type of system,” says Bates. “It
compression. Since the compressor is one possible drawback of intercooling is of steam/hr when operating at full varies from 1 to 1.4 MW per hour
consuming as much as half of the out- the potential for erosion of the com- capacity. Power is also distributed to depending on the load.” To keep
put of the turbine, and the work pressor section. ‘Liquid impaction ero- the public utility grid in California’s consumption to a minimum, the screw
required to compress the air is directly sion’ is a term applied to this phenome- Central Valley. compressors have slide valves, which
proportional to the temperature of the non. The bombardment of a metal Ripon chose a Kohlenberger- regulate the amount of compression
air, the evaporation of fog inside the surface with water droplets can lead to patented 2000-ton, multi-temperature performed according to system needs.
compressor results in a substantial the development of micro-fractures in chilling system. It features Frick Ripon bought the chiller unit to
increase in the net output of the turbine. the crystalline surface of the metal and ammonia screw compressors, 3 Imeco increase peaking capacity, improve fuel
It’s interesting to note that the high- can eventually cause surface pitting. evaporative condensers and Frigid Coil efficiency and generate additional
er output associated with intercooling is But experience has shown, and most cooling coils. Two coils are set at differ- steam power. The result: power output
not due to the mass of the injected fog. experts agree, that compressor blades ent temperatures to provide stages, rose from 42 to 48 MW on hot days.
In fact, water vapor is less dense than would not be subjected to damage enabling the system providing higher
air at the same temperature. So unless the average droplet size exceeds thermodynamic efficiency.
increasing the water vapor content of
the air, without also cooling the air,
would decrease the density of the mix.
about 20 to 30 microns. (The mean
diameter of fog droplets is less than 5
microns.) To date, over 60 fog systems
“Because California’s temperatures
rarely dip below 60 degrees F, the Case Study:
Evaporative Cooling
chillers are capable of making the
However, with a fogging system, the with fog intercooling capacity have system believe it’s a cool 44 degrees
water is added to the air in the liquid been installed on turbines in the USA. outside,” says Plant Manager Steve Nevada Power’s Clark Generating
phase, so it cools the air when it evapo- Bates. “On a really hot day, though, Station in Las Vegas operates 4
the chillers don’t get the temperature Westinghouse 501B6 gas turbines, each
below 50 degrees.” producing 80 to 82 MW per hour. It is
The system works using ammonia a combined cycle plant, with the heat
compression, similar to a home air from the gas turbines being utilized to
conditioner. A compressor draws drive an additional steam turbine. This
ammonia vapor from a recirculation provides another 90 MW of power.
tank, compresses it and discharges it to Three of the utilities’ gas turbines
the evaporative condensers. These have been retrofitted with Premier

Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364 Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364
CaseHigh
Study:
Industries’ evaporative coolers. “The
fourth cooling system is due to be in-
Pressure
Fogging Installation CaseChiller
Study: fatigue. Calpine Gilroy now uses stain-
less steel supply pipes and has installed
pulsation dampeners to cure pump
stalled in the last turbine later this year,” & High
says control room operator Ron Moore. In 1997, Portland General Electric Pressure Fogging #1 vibration – both standard features on
“The capital has been allocated and Co. (PGE) built a new combined cycle today’s fog systems.
work should begin after the summer.” plant at Boardman, Oregon, using a Calpine Gilroy Cogen, LP of Gilroy, The company currently operates its
These units consist of a stainless GE Frame 7-FA gas turbine (159 MW). CA, operates a GE Frame 7-EA cogen- thermal energy chillers during periods
steel, grade 304 housing, a sump After investigating several cooling eration plant which supplies 120 MW of peak power demand and otherwise
section and the cooling media. The options, the utility found that most to PG & E and provides steam to a relies on the fogging system. Result: a
sump section includes a recirculating were expensive to implement and nearby garlic plant. The plant uses significant reduction in cooling costs
water distribution system with pump, required structural modifications to chillers to cool turbine air regardless of since switching to high pressure fog
flow adjustment controls and flow buildings and air inlet housing. “Media- ambient temperature. But running and an additional 3 to 6 MW power
meters to pump water from the sump type evaporative cooling, for instance, increase.
costs make it desirable at certain times
to header pipes over each level of the worked out to be 250 percent more
to add a cheaper supplemental system.
costly to install than inlet fogging,” says
cooling media. The cooling media is a
rigid media manufactured by Glacier- Cheryl Bryant, the mechanical engineer
in charge of specifying and implement-
At first, Calpine Gilroy tried media-
type evaporative cooling. But water CaseChiller
Study:
Cor. It is made of a cellulose fiber con-
ing the cooling system. After factoring
entered the air stream and fouled the & High
struction with 45/15 degree transverse
in maintenance and running costs, PG&E compressor. As a result, turbines had Pressure Fogging #2
flutes. Media thickness is 16 inches, to be washed regularly. Also, water
decided to install a Mee Industries high
provided in two eight-inch sections to pumps required additional maintenance Las Vegas Cogen operates a peak-
pressure fogging system.
reduce replacement costs without loss and media needed frequent replace- ing plant, which starts up 560 times
At this facility, 1120 fog nozzles are
of cooling efficiency. Moisture drift ment. In 1994, the company decided per year using a GE LM 6000 turbine.
installed downstream of air filters/
eliminators are also included to trap to drop evaporative coolers, retain The electricity is sold to Nevada Power
upstream of silencers and trash screens,
raw moisture entrained in the air flow by far the most common location. chillers and supplement them with high and thermal energy is used to heat a
and return it to the sump. Demineralized Operating pressure is 2,000 psi and pressure fogging. 12-acre hydroponic greenhouse owned
water is used. After Premier Industries pressure drop is virtually nil. Gilroy was one of the first to install by the company.
installed the units, Nevada Power mea- Demineralized water is used. inlet fogging and the system was not Because it takes time for the
sured MW output for the entirety of Two pump skids are required, each without its problems. Water would chillers to get online, the cogeneration
1998 and compared it to 1997 figures containing four FM-630-B1057 pumps. sometimes stagnate in the supply lines facility uses high pressure inlet fogging
when no evaporative cooling system These pumps manage eight stages of to the fog pump units, causing bacteria to provide maximum power right away.
existed. July provided the highest cooling, which can be controlled by to grow, which plugged the fog nozzles The Mee Industries fog system is used
monthly increase of 12.32 percent. ambient temperature and humidity and water filters. The lesson learned exclusively when it’s below 70°F out-
The average power boost per month is sensors, as well as manually. here is that a fog system which is left side. If temperatures rise above 70°, a
7 percent. The only reported problem at shutdown for extended periods of time steam absorption chiller is added.
Coyote Springs was water collecting in must be drained, even when deminer- Although the fog system was
the inlet duct. A drain line, installed alized water is used. Other initial installed upstream of air filters, the final
downstream of the fog nozzles, problems involved the design and barrier filters remain dry and the filters
eliminated this situation. installation of the system, such as the stay cleaner due to the scrubbing
The result: 30°F of inlet air cooling, use of PVC pipes to supply the water effects of the mist. The facility achieves
a 16 MW output and a significant to the fogging pumps, and vibrations in around 15°F of cooling, which repre-
improvement in heat rate. the discharge pipes causing mechanical sents a 500 kW power increase.

Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364 Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364
Case Evaporative
Study: CHOOSING THE RIGHT SYSTEM
When considering which cooling
system to implement, it’s important to
Coolers & High study the existing situation at the plant,
Pressure Fogging climatic conditions, budget limitations,
power output expectations and project
The UtiliCorp United plant in economics. There are no simple answers,
Greenwood, MO has standard media- correct in all cases, and sometimes a
type evaporative coolers installed on combination of systems may be best.
four of its Frame 7001B units. However,
the company’s GE MS-7001E gas tur-
bine (85.4 MW at ISO conditions) uses a
Mee Industries fog system to provide
evaporative cooling and intercooling.
Eight fog-cooling stages – a total of
1,196 nozzles – deliver a temperature
drop of 20 to 32°F, depending on
ambient conditions.
After two summers, company
officials have found that the fog system
is easier to clean and maintain than the
evaporative coolers. The evaporative
coolers carry-over untreated water,
resulting in compressor fouling, while
the fog, which is demineralized water,
helps to clean the compressor. In
addition, the fog system takes about
three minutes from startup to full
power boost, compared to 30 minutes
with the media-type systems. The
company plant manager said that even
on a 100°F day with humidity in the
range of 45-50%, the fog system
provides a power boost of approxi-
mately 4 MW or nearly 7%.

Mee Industries Inc. ■ 204 West Pomona Avenue ■ Monrovia, California 91016 ■ 626.359.4550 ■ Fax 626.359.4660 ■ 800.732.5364
MEE INDUSTRIES, INC.

Are you talking to Mee?

Corporate Headquarters
204 West Pomona Avenue
Monrovia, California 91016
626.359.4550
Fax: 626.359.4660
E-mail: meefog@aol.com

www.meefog.com
800.732.5364

You might also like