You are on page 1of 34

ZXDU58 B900

DC Power System
Product Description

Version: V4.5R04M02

ZTE CORPORATION
NO. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://ensupport.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright 2012 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided as is, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit ZTE technical support website http://ensupport.zte.com.cn to inquire related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History

Revision No. Revision Date Revision Reason

R1.0 2011-04-13 First edition

Serial Number: SJ-20110329120059-003

Publishing Date: 2011-04-13(R1.0)

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Safety Precautions
The table below describes the safety signs in this manual.

Safety Signs Meaning

Indicates an imminently hazardous situation, which if not avoided, will


Danger result in death or serious injury. This signal word should be limited to only
extreme situations.

Indicates a potentially hazardous situation, which if not avoided, could


Warning result in death or serious injury.

Indicates a potentially hazardous situation, which if not avoided, could


Caution result in minor or moderate injury. It may also be used to alert against
unsafe practices.

There is a risk of electric shock.


Electric shock

The device may be sensitive to static electricity.


Electrostatic

Read the safety instructions before any operation of the equipment. The safety precautions
mentioned in this manual only serve as a supplement to the local safety codes.
Only trained professionals are allowed to install, operate and maintain the equipment. ZTE
bears no liability to the consequences incurred by violation of the general safety operation
requirements, or violation of the safety standards for designing, manufacturing and using
the equipment.
Take the following precautions when installing and operating the equipment.

High Voltage
Direct contact or indirect contact with high voltage and mains through damp object will
endanger the operators life.
l Observe the local safety codes during the equipment installation. The installation
personnel must be qualified for high voltage and AC power operations.
l Never wear any conductive object, such as watch, bracelet or ring during the operation
on the equipment.
l Prevent any moisture from entering the equipment during operations.

No Object With Harmful Effects


Protect the equipment against ingress of objects with harmful effects, such as conductive
object and water. Otherwise, short circuit may occur and damage the equipment!
I

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


High Leakage Current
Earth connection is essential before connecting supply.

DC Short Circuit
Avoid short circuit during operation. ZXDU58 B900 system is a power supply product of
constant DC voltage.

Connecting or Disconnecting Power Cable


Power cable operation with power ON will cause fatal danger to operation personnel and
damage to the equipment.
l Set all the breakers and switches to Off prior to connecting or disconnecting a power
cable.

Setting all the breakers and switches to Off will cause power supply interruption to the
loads connected. Do not shut down the system without permission. Or, switch the
loads to another power supply system.
l Prior to connecting a cable, make sure that the cable and its label are in accordance
with the requirement.

Tools Safety
When operating high-voltage equipment, tools safety must be considered. Use Insulated
Tools.

Electrostatic Damage
Electrostatic discharges generated by human body may damage components. Use wrist
straps when handling the equipment. Insulate the uncovered metals to prevent short
circuit.

Operation on Battery
l Before performing any operation on battery, read the safety precautions in the battery
manual.
l Connect the battery cables according to the instructions. Avoid short circuit and
electrolyte leakage.

II

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Documentation Guide
Applicable Product
This guide and related documents apply to the ZXDU58 B900 (V4.5R04M02) DC power
system.

Manual Suite
The table below lists the manual suite of the ZXDU58 B900 system.

S.N. Document Description and Intended Audience

1 ZXDU58 B900 (V4.5R04M02) This document is intended for the use of all the users.
DC Power System Product In this document, you will learn about:
Description l System structure and components
l System configuration
l System features and technical specifications
l Electrical connection diagram
l Term list

2 ZXDU58 B900 (V4.5R04M02) This guide is intended for the use of engineers that
DC Power System Quick are authorized to install the equipment.
Installation & Commissioning In this document, you will learn about:
Guide l Equipment installation
l Cable connection
l System commissioning

3 ZXDU58 B900 (V4.5R04M02) This document is intended for the use of all the users.
DC Power System User Guide In this document, you will learn about:
l System structure
l Monitoring software
l Symptoms and Troubleshooting
l Status Indication of Rectifier and Monitoring Unit
l Relays and Corresponding Alarms
l Shutdown and Startup

4 ZXDU28/ZXDU58 B900-CSU This document is intended for the use of all the users.
(V1.20C) In this document, you will learn about the alarms of
Monitoring Unit Alarm List the system

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


S.N. Document Description and Intended Audience

5 ZXDU28/ZXDU58 B900-CSU This manual is intended for the use of maintenance


(V1.20C) engineers.
Monitoring Unit Operation Manual In this document, you will learn about:
l Querying real-time running status
l Querying real-time alarms
l Query history alarms
l Energy-saving management
l Battery management
l System management, including parameter
setting, rectifier power-on and power-off by the
software

6 ZXDU28/ZXDU58 Series(V4.5) This manual is intended for the use of maintenance


DC Power System Maintenance engineers.
Manual In this document, you will learn about:
l System startup and shutdown
l Indicators description
l Routine maintenance
l Components replacement
l Alarm handling

How to Get in Touch


ZTE welcomes your comments and suggestions on the quality and usefulness of this
document.
The following sections provide information on how to obtain support for the documentation.
If you have problems, questions, comments, or suggestions regarding your product,
contact us by e-mail at 800@zte.com.cn. You can also call our customer support center
at (86) 755 26771900.

For further questions, comments, or suggestions on the documentation, you can fax your
comments and suggestions to (86) 755 26770801. You can also browse our website at htt
p://ensupport.zte.com.cn, which contains various interesting subjects like documentation,
knowledge base, forum and service request.

II

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Contents
Safety Precautions ......................................................................................... I
Documentation Guide .................................................................................... I
Chapter 1 System Overview ...................................................................... 1-1
1.1 System Introduction............................................................................................ 1-1
1.2 System Features ................................................................................................ 1-1
1.3 Working Scenario ............................................................................................... 1-2

Chapter 2 System Structure ...................................................................... 2-1


2.1 System Components .......................................................................................... 2-1
2.2 Slots Configuration ............................................................................................. 2-2

Chapter 3 Terminals and Interfaces.......................................................... 3-1


3.1 Electrical Interfaces ............................................................................................ 3-1
3.2 Signal Interface of SIB ........................................................................................ 3-2

Chapter 4 ZXD030 S480 Rectifier .............................................................. 4-1


4.1 Rectifier Parts .................................................................................................... 4-1
4.2 Rectifier Indicators.............................................................................................. 4-1
4.3 Rectifier Specifications ....................................................................................... 4-2

Chapter 5 Monitoring Unit ......................................................................... 5-1


5.1 CSU Parts ......................................................................................................... 5-1
5.2 CSU Indicators................................................................................................... 5-1
5.3 Operation of the Monitoring Unit .......................................................................... 5-2
5.4 CSU Specifications............................................................................................. 5-2

Chapter 6 Characteristics and Specifications ......................................... 6-1


6.1 Configuration List ............................................................................................... 6-1
6.2 Automatic BLVD Control ..................................................................................... 6-2
6.3 Technical Specifications...................................................................................... 6-2
6.3.1 Environment Specifications ....................................................................... 6-2
6.3.2 Electrical Specifications ............................................................................ 6-3
6.3.3 Other Specifications ................................................................................. 6-4
6.4 Compliance Standards ....................................................................................... 6-5

Appendix A Dimensions and Weight....................................................... A-1


Appendix B Electrical Connection Diagram ........................................... B-1
Appendix C Term List................................................................................ C-1
I

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


II

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 1
System Overview
Table of Contents
System Introduction....................................................................................................1-1
System Features ........................................................................................................1-1
Working Scenario .......................................................................................................1-2

1.1 System Introduction


The ZXDU58 B900 is an embedded power supply equipment. It can provide 53.5 V power
for mobile base stations, access network equipment, remote switch offices, transmission
equipment, ground satellite transceiver stations, and microwave communication devices.
l AC input mode: single-phase, three-wire (L/N/PE).
l In full configuration, the ZXDU58 B900 system is equipped with three ZXD030 S480
rectifiers, which form a power system with a maximum of 90 A output.
Figure 1-1 shows its appearance.

Figure 1-1 ZXDU58 B900 Appearance

1.2 System Features


The ZXDU58 B900 system has the following features:
l A wide range of input phase voltage (85 VAC to 300 VAC) makes the system suitable
for areas with unstable voltage.
l Compact structure design.
The ZXDU58 B900 chassis is 6U in height and 19 inches in width. It can be
embedded into a main equipment rack or cabinet.

1-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

The ZXDU58 B900 chassis contains the AC distribution unit, DC distribution unit,
rectifiers and monitoring unit.
Cable connection and system maintenance in front.
l Hot-pluggable rectifiers.
l Intelligent monitoring unit.
l Support multiple networking modes, such as RS232, RS485 and IP/SNMP (optional).
l High reliability with MTBF 2.2 105 h.

1.3 Working Scenario


Figure 1-2 shows the working scenario of ZXDU58 B900 which can be embedded into a
19inch rack or cabinet.

Figure 1-2 Working Scenario

Caution!
Protect the equipment against ingress of objects with harmful effects, such as conductive
object and water. Otherwise, short circuit may occur and damage the equipment!

The requirements of the AC input power system of ZXDU58 B900 are as follows:
l The AC input mode of the ZXDU58 B900 system is single-phase three-wire (L/N/PE).
l The AC input voltage is 85 V - 300 V (phase voltage). The capacity of the AC input
switch that powers ZXDU58 B900 should be larger than 40 A.
l It is suggested to install a leakage current protection device in the AC power
distribution system that powers ZXDU58 B900.

1-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 2
System Structure
Table of Contents
System Components ..................................................................................................2-1
Slots Configuration .....................................................................................................2-2

2.1 System Components


The components of the ZXDU58 B900 system are shown in Figure 2-1 and Figure 2-2.

Figure 2-1 ZXDU58 B900 Overall Structure

1. ZXD030 S480 rectifiers 3. Signal Interface Board


(13) (SIB)
2. Monitoring unit 4. Power distribution unit

Figure 2-2 ZXDU58 B900 Power Distribution Unit

1. AC input breaker 4. Battery breakers (12, 5. DC output breakers (16,


2. AC SPD BATT-) 48 V)
3. Rectifier breakers (13)

2-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

6. Battery input terminals 7. DC output terminals (16,


(12, BATT+) +/GND)

Note: Battery input terminals and DC output terminals hide behind the panel.

2.2 Slots Configuration


The slots configuration of the rectifier, monitoring unit and signal interface board is shown
in Figure 2-3.

Figure 2-3 Slots Configuration

SMR: rectifier CSU: monitoring unit SIB: signal interface board

2-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 3
Terminals and Interfaces
Table of Contents
Electrical Interfaces ....................................................................................................3-1
Signal Interface of SIB................................................................................................3-2

3.1 Electrical Interfaces


The electrical interfaces of the ZXDU58 B900 are shown in Figure 3-1.
Table 3-1 describes the terminal types.

Please note that the customized product might be different from this terminal diagram.

Figure 3-1 Electrical Interfaces

1. PE 4. Battery input (BATT-) 7. DC output (+/GND)


2. Neutral wire input (N) 5. DC output (-48 V)
3. Live wire input (L) 6. Battery input (BATT+)

Table 3-1 Electrical Connection Terminals

Item Description

AC input L 40 A MCB

N UK10

PE UK10

Battery input BATT- 2*40 A MCBs

BATT+ 2*UIK35

DC output -48 V 6 output braches:


l 12: 2*16 A MCBs
l 34: 2*10 A MCBs
l 56: reserved for expansion

+/GND 6*UK10

3-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

3.2 Signal Interface of SIB


The Signal Interface Board (SIB) provides external communication interfaces and
monitoring unit signals interfaces. The SIB board is shown in Figure 3-2.
Table 3-2 describes the interfaces.

Figure 3-2 SIB Interface

Table 3-2 Signal Interfaces Description

Interface Interface Name Description

X1 Battery 1 Temperature Connected to the temperature sensor of battery pack 1

X2 Battery 2 Temperature Connected to the temperature sensor of battery pack 2

X3 Environment Temperature Connected to the temperature sensor of environment

X4 Door Magnet Alarm Connected to the door magnet switch

X5 Flood Alarm Connected to the flood sensor

X6 Smoke Alarm Connected to the smoke sensor

X7 Input Relays 1, 2 Support attribute customization

X8 Input Relays 3, 4 Support attribute customization

X9 Output Relays 1, 2 Correspond to alarm codes A1 and A2, support alarm


customization

X10 RS485/422 Interface Communication interface, cannot be used with RS232 si-
multaneously

X11 RS232 Interface Communication interface, cannot be used with RS232 si-
multaneously

3-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 3 Terminals and Interfaces

Interface Interface Name Description

X13 Output Relays 3, 4 Correspond to alarm codes A3 and A4, support alarm
customization

X14 Output Relays 5, 6 Correspond to alarm codes A5 and A6, support alarm
customization

X15 Output Relays 7, 8 Relay 7: Correspond to alarm code A7, support alarm
customization
Relay 8: Reserved for monitoring unit fault

X17 RJ11 Interface Telephone interface, used for the communication via MO-
DEM

X18 RJ45 Interface Ethernet interface, used for the communication via
TCP/IP or SNMP

X21 Battery Low Voltage Connected to battery low voltage alarm signal
Alarm

3-3

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

This page intentionally left blank.

3-4

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 4
ZXD030 S480 Rectifier
Table of Contents
Rectifier Parts.............................................................................................................4-1
Rectifier Indicators......................................................................................................4-1
Rectifier Specifications ...............................................................................................4-2

4.1 Rectifier Parts


In the ZXDU58 B900 system, the ZXD030 S480 rectifiers convert AC to DC.
Figure 4-1 shows the appearance and structure of the rectifier.

Figure 4-1 ZXD030 S480 Rectifier

1. Indicators 3. Handle 4. Input/output integrated


2. Air vent socket

4.2 Rectifier Indicators


Figure 4-2 shows the indicators of the ZXD800/ZXD030 S480 rectifier.

Figure 4-2 Rectifier Indicators

The indicators signify the working status of the rectifier. Refer to Table 4-1 for details.

4-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

Table 4-1 Rectifier Indicators

Indicator Normal Abnormal Indication


Status Status

Lit Off No AC input or the AC input voltage is lower

Power (green) than 75 V

Flash Rectifier output current limit

Off Lit l AC input over/under-voltage

Alarm (yellow) l PFC output over/under-voltage


l Over-temperature

Flash The communication between the monitoring unit


and the rectifier is interrupted

Off Lit l DC output over-voltage/current

Fault (red) l DC output fuse blown


l Fan fault
l Other faults

4.3 Rectifier Specifications


Table 4-2 describes the specifications of ZXD030 S480 rectifier.

Table 4-2 Electrical Specifications of the ZXD030 S480 Rectifier

Item Specifications

AC input mode Single-phase, three-wire (L/N/PE)

AC input voltage 85 V to 300 V


Input voltage variation affects the output power of the rectifier. For more
information please refer to the user manual of the rectifier.

DC output voltage Rated output voltage: 53.5 V, range: 42 V to 58 V

Output power Rated output power: 1605 W; maximum output power: 1740 W

4-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 5
Monitoring Unit
Table of Contents
CSU Parts ..................................................................................................................5-1
CSU Indicators ...........................................................................................................5-1
Operation of the Monitoring Unit .................................................................................5-2
CSU Specifications.....................................................................................................5-2

5.1 CSU Parts


The Centralized Supervision Unit (CSU) manages the power distribution unit, rectifiers and
batteries of the ZXDU58 B900 system.
For the appearance and structure of the CSU, see Figure 5-1.

Figure 5-1 Centralized Supervision Unit

1. LED 4. Buttons 7. Interface


2. Indicators 5. Power switch
3. Reset button 6. Handle (Fastening screw)

5.2 CSU Indicators


The indicators signify the working status of the system, for the appearances, see Figure
5-2.

Figure 5-2 CSU Indicators

For a description of the working status they indicated, refer to Table 5-1.

5-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

Table 5-1 CSU Indicators

Indicator Status Indication

PWR Lit (green) The CSU is powered on


Power

RUN Flash (green) The CSU is operating normally


Run

EQU Lit (green) The battery equalized charge is in the process


Equalized charge

COMM1
Flash (green) The CSU is communicating with the rectifiers
Communication 1

COMM2 The CSU is communicating with the background supervision


Flash (green)
Communication 2 center

ALM
Flash (red) A fault occurs to the system
Alarm

5.3 Operation of the Monitoring Unit


Monitoring software version: V1.20C
Operate keys of the monitoring unit, then you can:
l Set parameters
l Query information, alarms and history records
l Manage work modes, alarms, batteries and rectifiers
l Start manual detection for the maintenance purpose
For details about the use of the Monitoring Unit, refer to the ZXDU28/ZXDU58 B900CSU
(V1.20C) Monitoring Unit Operation Manual.

5.4 CSU Specifications


For a description of the CSU specifications, refer to Table 5-2.

Table 5-2 CSU Specifications

Item Specifications

Power mode DC power

Operation interface LCD and buttons

Precision of AC voltage 1%

Precision of the battery current and the output current of the system 1%

Precision of the battery voltage and the output voltage of the system 0.5%

Temperature precision 5.4 (3 )

5-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 5 Monitoring Unit

Item Specifications

Humidity precision 5%

Boolean value precision 100%

5-3

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

This page intentionally left blank.

5-4

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 6
Characteristics and
Specifications
Table of Contents
Configuration List .......................................................................................................6-1
Automatic BLVD Control.............................................................................................6-2
Technical Specifications .............................................................................................6-2
Compliance Standards ...............................................................................................6-5

6.1 Configuration List


Table 6-1 describes the system configuration.

Table 6-1 System Configuration

Item Configuration

AC power AC input l Singl-phase, three-wire (L/N/PE)


distribution l AC input breaker: 40 A MCB

AC SPD Class C

DC power Battery input 2*40 A MCBs


distribution
DC output 6 output braches:
l 12: 2*16 A MCBs
l 34: 2*10 A MCBs
l 56: reserved for expansion

Rectifier ZXD030 S480 rectifiers, three sets (maximum)

Monitoring unit One set

Chassis One embedded chassis, 6U in height, 19inch installation interface

Other components l IP board or SNMP (Optional)


l Battery temperature sensors and cables (Optional)

The customized product may be different from this table.

6-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

6.2 Automatic BLVD Control


Introduction to BLVD Control
The ZXDU58 B900 system has Battery Low Voltage Disconnect (BLVD) function.
When the battery voltage falls to LVD1 Volt., the system disconnects the batteries to avoid
battery over-discharge.

Note:
The ZXDU58 B900 system can immediately power the loads with mains recovery after
failure.

Related Parameters
Table 6-2 lists the default and range of the related parameters, LVD1 Volt. and LVD2 Volt.
In the monitoring unit, users can access Ctrl > 1. Setup Para > LVD1 Volt. and LVD2
Volt. to modify the value of the two parameters.

Table 6-2 LLVD Parameters

Parameter Default Range and Constraints

LVD1 Volt. 46.0 V 38.0 V to 51.0 V


LVD2 Volt. LVD1 Volt.
LVD2 Volt. 45.0 V

Note:
LVD2 Volt. does not take any effect here except the above constraint condition.

6.3 Technical Specifications


6.3.1 Environment Specifications
The specifications for the environment of the equipment are described in Table 6-3.

Table 6-3 Environment Specifications

Item Specification

Operating temperature -5 to +45

Storage temperature -40 to +70

6-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 6 Characteristics and Specifications

Item Specification

Relative humidity 10% to 90% (non-condensing); 40% to 60% recommended

Air pressure 70 kPa to 106 kPa

Other requirements l No conductive objective or water falling into the chassis


l No conductive dusts or corrosive gases
l No explosion hazard, no shake or jolt
l Ground slope is no more than 5

6.3.2 Electrical Specifications


The electrical specifications are described in Table 6-4.

Table 6-4 Electrical Specifications

Item Specification

AC input mode Single-phase three-wire (L/N/PE)

AC input voltage 85 V to 300 V

AC input frequency 50/60 Hz

Maximum AC input current 35 A

AC input power factor 0.99 (with full load)

AC SPD Class C, with discharging current 40kA

DC output voltage l Rated output voltage: -53.5 VDC


l Range: -42 VDC to -58 VDC

Rated DC output current 90 A (in full configuration with three rectifiers)

Maximum output power 5220 W

Source effect 0.1%

Load effect 0.5%

Regulated voltage precision 0.6%

Weighted noise voltage < 1 mV

Peak-peak noise voltage 100 mV

Broad frequency noise voltage 30 mV (3.4 kHz~150 kHz)


20 mV (0.15 MHz~30 MHz)

Discrete frequency noise voltage 5 mV (3.4 kHz~150 kHz)


3 mV (150 kHz~200 kHz)
2 mV (200 kHz~500 kHz)
1 mV (0.5 MHz~30 MHz)

DC voltage drop < 500 mV

6-3

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

Item Specification

Load sharing quality of the rectifiers The difference between the maximum current and
minimum current is less than 1.5 A (with 10% of rated load
or above)

AC Vol. Max. Default: (286 5) V

Threshold of recovery from AC Default: (276 5) V


over-voltage alarm

AC Vol.Min. Default: (154 5) V

Threshold of recovery from AC Default: (164 5) V


under-voltage alarm

DC Vol.Max. Default: (58 0.2) V

Threshold of recovery from DC Default: (57.5 0.2) V


over-voltage alarm

DC Vol.Min. Default: (48.0 0.2) V

Threshold of recovery from DC Default: (48.5 0.2) V


under-voltage alarm

BatVol Min. Default: (47.0 0.2) V

The rectifier in this table is the ZXD030 S480 (V1.0) rectifier.

6.3.3 Other Specifications


The other specifications are described in Table 6-5.

Table 6-5 Other Specifications

Item Specification

Chassis dimensions 265.9 mm 482.6 mm 315.7 mm (H W D)

Chassis weight Approximately 15 kg (excluding the rectifiers and


monitoring unit)

Rectifier weight 1.6 kg/set, three sets (maximum)

Monitoring unit weight 1.6 kg

Cable connection Front

Installation mode Embedded

Noise 55 dB(A)

Mean Time Between Failures (MTBF) 2.2 105 h

Safety standard IEC 60950

EMC standard EN55022; IEC61000

6-4

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Chapter 6 Characteristics and Specifications

Item Specification

Conductive disturbance and radioactive EN55022 level A


disturbance

6.4 Compliance Standards


EMC Standards
The ZXDU58 B900 system is in compliance with the following Electromagnetic
Compatibility (EMC) standards:
l EN55022
l IEC61000-3-3; IEC61000-3-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4;
IEC61000-4-6; IEC61000-4-8; and IEC61000-4-11

Safety Standards
The ZXDU58 B900 system is in compliance with the UL/IEC/EN 60950 safety standards.

Other Standards
The ZXDU58 B900 system is also in compliance with the following standards:
l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of the
European Union.
l This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) this device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may
cause undesired operations.

6-5

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

This page intentionally left blank.

6-6

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Appendix A
Dimensions and Weight
Dimensions
The dimensions of the chassis are: 265.9 mm 482.6 mm 315.7 mm (H W D), as
shown in Figure A-1.

Figure A-1 ZXDU58 B900 Dimensions

Unit: mm

Weight
Table A-1 describes the weight of the components.

Table A-1 ZXDU58 B900 Weight

Item Specification

Chassis Weight Approximately 15 kg (excluding monitoring unit and rectifiers)

Monitoring unit 1.6 kg

ZXD030 S480 rectifier 1.6 kg kg/set, three sets (maximum)

A-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

This page intentionally left blank.

A-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


Appendix B
Electrical Connection
Diagram
Figure B-1 shows the electrical connection diagram.

B-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description
Figure B-1 ZXDU58 B900 (V4.5R04M02) Electrical Connection Diagram B-2
SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential
Appendix C
Term List
Refer to Table C-1 for the details of acronyms that are used in this manual.

Table C-1 Term List

Abbreviation Full Name

AC Alternating Current

ACDP AC Distribution Panel

ACDR AC Distribution Rack

ACMU AC Monitoring Unit

ALM Alarm

BLVD Battery Low Voltage Disconnect

CL Current Limit

CSU Centralized Supervision Unit

DC Direct Current

DCDP DC Distribution Panel

DCDR DC Distribution Rack

EMC Electromagnetic Compatibility

LCD Liquid Crystal Display

LED Light Emitting Diode

LLVD Load Low Voltage Disconnect

LVD Low Voltage Disconnect

MCB Miniature Circuit Breaker

MCCB Moulded Case Circuit Breaker

MODEM Modulator-Demodulator

NC Normally Closed

NO Normally Open

PE Protection Earth

PFC Power Factor Correction

PWR Power

RECR Rectifier Rack

C-1

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential


ZXDU58 B900 Product Description

Abbreviation Full Name

RLY Relay

SIB Signal Interface Board

SMR Switching Mode Rectifier

C-2

SJ-20110329120059-003|2011-04-13(R1.0) ZTE Proprietary and Confidential