Tabel FMEA

Sistem : mechanical system


Part name : HVAC system
Mission : Provide temperature control to room

Efek kegagalan
Mode Menkanisme
No. Fungsi
kegagalan kegagalan Next higher Detection
Local effect End effect Klasifikasi
level method
Lower
Reservoir/contain Crack in wall Water will condenser
No immediate
1. 6000 gallons of Leak drain pipe not be efficiency, Inspection
effect
water broke contained chiller uses
more energy
Pump can Lower
Transport Impeller
not produce condenser
water at a degraded, No immediate
required efficiency, Flow sensor
rate below gasket leak, effect
rate of chiller uses
1000 gpm motor degraded
Pump/transport water more energy
industrial water No
2.
supply at 1000 Broken condender Room temp
GPM Produce coupling, leak Pump will function, above max,
no water on suction line, not be able chiller will allowed Flow sensor
flow motor to pump lose ability mission
inoperable to remove failure
heat
Fan will
Lower
operate Room
Coolong Scaling condenser
Untreated longer temperature Inspection/water
3. tower/maintain a (deposit efficiency,
water period of will raise analysis
water of 75oF on media) chiller uses
time. Poor slightly
more energy
cooling
Room
Water will Condenser
Clogged Untreated/unfil- temperature Inspection/water
not be will not be
sprayer tered water will raise analysis
cooled efficient
slightly
Motor winding Lower Slight rise in
Low
open, condenser air temp. no
Fan evaporative
No supply efficiency. severe effect. Flow sensor
Failure cooling will
voltage to Chiller uses Mission
take place
motor more energy compromised.
Degraded
Pump Chiller
operating-
Pump #5/ Impeller cannot needs to
produce
Transport chilled degraded, produce decrease
4. water at No effect Flow sensor
water supply at gasket leak, required water temp
rate less
960 gpm motor degraded rate of to satisfy air
than 960
water handler
gpm
Broken Chiller will No air
Produce coupling, leak Damage to not be able cooling room
no water on suction line, motor or to remove temp above Flow sensor
flow motor pump shafts heat from max. Mission
inoperable water failure
Compressor Air handling
Degraded Refrigerant leak Air temp will
Chiller/ remove will cycle on unit will run
operation- degraded rise but not
heat (10oF) from frequently/ continuously Temperature
5. remove compressor, above
chilled water chiller will trying to sensor
less than tube leak, dirty maximum
supply be less meet
10oF coil allowed
efficient demand
Compressor Chiller will Air handling Minimal air
Remove no Temperature
seizure, motor be unable to unit will run cooling-temp
heat sensor
failure function continuously rise above

Keterangan :
1 = Very low
2 = Low
3 = Medium
4 = High
5 = Very high