U-Series

Air Circuit Breaker

LV &
MV
Circ
uit B
reak
ers
Leader of Technology
Hyundai Heavy Industries' state-of-the-art technologies
have created circuit breakers and contactors
for electrical systems that are genuine masterpieces.

CONTENTS
04 Features 11 Structure 13 Ratings 14 Protection Trip Relay (OCR) 30 Accessories 72 Circuit Diagrams
74 Dimensions 92 Ordering Codes 96 Technical Data 105 Operating Conditions 106 Ordering Sheet
U-Series
Air Circuit Breaker
HYUNDAI ACB meets your demands for high
breaking capacity, full line-up, and optimized
panel size. Various accessories and connection
methods realize user-friendly handling.
U-Series / Air Circuit Breaker

Features

| Full line-up |
U-Series ACB maximize your choice and satisfaction with compact size and dual (UAN/UAS) model.
460mm

766mm

624mm
D frame1)
399mm [150kA]
36

C frame
8m

328mm
m

[100kA] 4,000-6,300A(UAN)
B frame
A frame [100kA] 4,000-5,000A(UAN)
[85kA] 2,000-4,000A(UAN)
2,000-3,200A(UAS)
630-2,000A(UAN)
630-1,600A(UAS)

- Breaking capacity is at AC500V.


1) D frame will be available from October 2013.

| Applications |
U-Series ACB offering high breaking capacity and advanced protection trip relay is suitable to cover various applications
including buildings, data centers, industrials and so on. U-Series ACB protects these facilities from harmonic frequency by
100% capacity of N phase.

Buildings Data centers & Networks Industrials Electric power facilities


Multipurpose buildings Broadcasting stations Steel/Metal Electric power stations
Hospitals IT/Telecommunications Gas/Chemical Electric power substations
Commercial buildings Pulp/Paper Dispersed power generators
Hotels Renewable energy facilities

4
ACB

| Compliance with standards |


Standard
IEC 60947-1,2 International Electrotechnical Commission
EN 60947-2 European Standard
GB China National Standard (Guojia Biaozhun)
GOST R 50030.2-99 9 Government Standard of Russia
GOST R 50030.1-2000 Government Standard of Russia
KS C 4620 Korean Standards Association

Approval
ISO 18001, 14001, 9001
KS/KOREA Korea Quality Certificate Standard Association
CE Community European
GOST-R/RUSSIA Government Standard of Russia
CCC/CHINA China Compulsory Certification
KR/KOREA Korean Register of Shipping
GL/GERMANY Germanischer Lloyd
LR/U.K Lloyd's Register of Shipping
ABS/U.S.A American Bureau of Shipping
BV/FRANCE Bureau Veritas
NK/JAPAN Nippon Kaiji Kyokai

CB type test
DEKRA Formerly KEMA Quality Registered
KERI Korea Electrotechnology Research Institute

U-Series Air Circuit Breaker_ 5


U-Series / Air Circuit Breaker

Features

| Various accessories |

[ Body side ]

Motor Auxiliary switch OCR portable checker Test jumper


Closing coil Condenser trip device Key lock device Draw-in/out handle
Trip coil Lifting lug Wrong insertion preventer Draw-in/out and
Double trip coil Mechanical interlock kit Fixing block position lock device
Trip supervision coil Phase insulation barrier Counter Door flange
Under voltage trip coil ON/OFF button cover O CR & Alarm switch reset device Dust cover

6
ACB

[ Cradle side ]

UVT time delay controller Mechanical interlock kit Safety shutter


Remote operation module Phase insulation barrier Arc shield
Temperature detection module Mechanical operated cell (MOC) switch Control terminal protection cover
Short bcontact Dummy ACB
Position switch Wrong insertion preventer

U-Series Air Circuit Breaker_ 7


U-Series / Air Circuit Breaker

Features

| High performance protection trip relay (OCR) |


The protection trip relay (OCR) of U-Series ACB supports stable power supply with temperature alarm, fault recording, and
others in addition to main protection functions.

Type UPR-1L-GL UPR-2L-GS UPR-1D-GT UPR-2L-GM

Ordering 50Hz 33 35 36 37
code 60Hz 43 45 46 47

Externals

Main function L/S/I/G L/S/I/G L/S/I/G L/S/I/G


Self-power Self-power Self-power Self-power
Failsafe AC, DC100-250V AC, DC100-250V AC, DC100-250V
Pre-trip alarm Failsafe Failsafe Failsafe
Integrated Pre-trip alarm Pre-trip alarm Pre-trip alarm
instantaneous output Individual continuous Individual output Individual output
contact output contact contact contact
Fault event Fault event Fault event
Temperature alarm Temperature alarm Temperature alarm
Earth leakage trip
Communication
(Modbus)

8
ACB

| Multiple terminal busbar connections |


Increases the user's convenience by diversified terminal connection methods according to busbar's type.
Simply turn a horizontal connector 90 to make it a vertical connector (The opposite case is same).

Standard connection

Vertical Horizontal Front

Mixed connection (Top/Bottom)

Vertical/Horizontal Horizontal/Vertical Vertical/Front

Horizontal/Front Front/Vertical Front/Horizontal

- Changing connector is available only for UAN/UAS A frame 630-1,600A, UAN/UAS B frame 2,000-3,200A.
- Front connection type is suitable the panel requirement for limited installation space.
- Changing connection above 4,000A needs additional component, please contact us.

U-Series Air Circuit Breaker_ 9


U-Series / Air Circuit Breaker

Features

| Easy-to-install |
Fixed type
Installed in a switchboard directly.

Draw-out type
Consists of ACB and cradle.
Cradle is fixed to a switchboard.
ACB may be in the position of CONNECTED, TEST, ISOLATED,
and REMOVED.
Switchboard door may be closed in ISOLATED position. [ Draw-in/out guide rail ]

(Connected Position)

Connected position Test position

- Main and control circuit are all connected. - Main circuit is isolated, control circuit is connected.
- Normal condition of use - Control test is possible when switchboards door is closed.

Isolated position Removed position

- Main and control circuit are all isolated. - ACB is totally drawn out from the cradle.
- Switchboard door may be closed in isolated position.

10
ACB

Structure

| Externals |

[ Front ]

[ Fixed type ] [ Draw-out type ]

[ Cradle ]

[ Inside ] [ Rear ]

Control terminal Position lock device Manual charging handle


Front cover Position lock release button Name plate
Close/Open indicator Draw-in/out handle insertion hole Arc shield
Close button Position indicator Terminal busbar
Protection trip relay (OCR) Counter OCR & Alarm switch reset button
Open button Charged/Discharged indicator Draw-in/out guide rail

U-Series Air Circuit Breaker_ 11


U-Series / Air Circuit Breaker

Structure

| Internals |

Arc chamber MHT device Control terminal Current transformer


Frame Protection trip telay (OCR) Manual charging handle Terminal clip
Counter Mechanism Closing spring Cradle
Auxiliary switch Draw-in/out device Moving contact
Motor Front cover Fixed contact
Closing/Trip/UVT coil Control terminal protection cover T erminal busbar

12
ACB

Ratings

Frame A frame B frame C frame A frame B frame


Model UAN UAS
06 : 630 06 : 630 32 : 3,200 06 : 630 20 : 2,000
08 : 800 08 : 800 40 : 4,000 08 : 800 25 : 2,500
10 : 1,000 10 : 1,000 50 : 5,000 10 : 1,000 32 : 3,200
12 : 1,250 12 : 1,250 12 : 1,250
Recognition order code:
16 : 1,600 16 : 1,600 16 : 1,600
Rated current (In max at 40C) (A)
20 : 2,000 20 : 2,000
25 : 2,500
32 : 3,200
40 : 4,000
Rated operating voltage (Ue) (V) AC 690 AC 690
Rated insulation voltage (Ui) (V) AC 1,000 AC 1,000
Frequency (Hz) 50/60 50/60
Number of poles 3, 4 3, 4
Current setting range (.. x In max) 0.4-1.0 0.4-1.0
Rated current of neutral pole (..% x In) 100% 100%
Rated breaking capacity IEC 60947-2 AC 690/600/550V 65 85 85 55 70
(Icu) category B AC 500/480/460V 85 100 100 65 85
(kA sym) KS C 4620 AC 415/380/230/220V 85 100 100 65 85
Rated service breaking capacity (..% x Icu) 100% 100%
Rated making capacity IEC 60947-2 AC 690/600/550V 143 187 187 121 154
(Icm) category B AC 500/480/460V 187 220 220 143 187
(kA peak) KS C 4620 AC 415/380/230/220V 187 220 220 143 187
Rated short-time capacity 1 sec 65 85 85 55 70
(Icw) 2 sec 60 75 75 45 65
(kA, without Inst.) 3 sec 50 65 65 36 55
Rated impulse withstand voltage (Uimp) (kV) 12 12
Maximum total breaking time (ms) 40 40
Motor charging time (sec) max. 10 10
Closing operating time
Closing time (ms) max. 40 40
Without maintenance 20,000 15,000 10,000 20,000 15,000
Mechanical
With maintenance 30,000 2,000 2,000 30,000 20,000
Life cycle (times) 06-20 : 10,000
Without maintenance 5,000 25-40 : 5,000
2,000 5,000 5,000
Electrical
06-20 : 15,000
With maintenance 10,000 25-40 : 10,000
5,000 10,000 10,000
06-32 : 87
Draw-out type 63 40 : 107
145 63 87
3 pole
06-32 : 44
Fixed type 34 40 : 61
76 34 44
Weight (kg)
06-32 : 130
Draw-out type 280 40 : 61
173 74 103
4 pole
06-32 : 55
Fixed type 44 40 : 81
81 44 55
Draw-out type 328 x 460 x 368 399 x 460 x 368 624 x 460 x 368 328 x 460 x 368 399 x 460 x 368
3 pole
External dimension (mm) Fixed type 337 x 404 x 296 408 x 404 x 296 633 x 404 x 296 337 x 404 x 296 408 x 404 x 296
(WxHxD, except busbar) Draw-out type 413 x 460 x 368 514 x 460 x 368 794 x 460 x 368 413 x 460 x 368 514 x 460 x 368
4 pole
Fixed type 422 x 404 x 296 523 x 404 x 296 803 x 404 x 296 422 x 404 x 296 523 x 404 x 296

Fixed type Draw-out type


H

W D
W D

U-Series Air Circuit Breaker_ 13


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Overview |

LCD display window


Fault indication LED


PTA: Pre-trip alarm
LTD: Long time delay
STD/INST: Short time or instantaneous tripping
GFT/ELT: Ground fault trip or earth-leakage trip
TAL: Temperature alarm

Overload indication LED


Function key

Reset: Fault reset


Hi/Low: Field test function
(Hi: STD/INST, Low: LTD)
Move
List: Secondary menu
Enter: Setting input


Phase indication Iine
Ir: Long time current setting knob
Tr: Long time tripping delay setting knob
Isd: Short time current setting knob
Tsd: Short time tripping delay setting knob
Ii: Instantaneous current setting knob
GFT/STD, MCR setting knob
Ip: Pre-trip alarm current setting knob
Tp: Pre-trip alarm delay setting knob
Ig: Ground fault current setting knob
Tg: Ground fault tripping delay setting knob
Rated current setting knob
Test jack
Earth leakage pick-up and
tripping delay setting knob

14
ACB

General feeder Generator


Application
UPR-1L-GL UPR-2L-GS UPR-1D-GT UPR-2L-GM UPR-1S-AL UPR-2S-AS

Externals

Control power - -
Power supply
Self power
Long time delay (LTD)
Short time delay (STD)
Instantaneous trip (INST)
Protection Pre trip alarm - -
Ground fault trip - -
Field test - -
Failsafe
True RMS detection
Fault indication LED - -
Indication
Overload indication LED - -
Display window - -

Integrated instantaneous - - PTA: 1a -
contact (1a)
L/S/I/G: 2a
Output contact

Individual continuous LTD: 1a
- PTA: 1a -
contact (4a) S/I: 1a
L/S/I/G: 2a PTA:1a
MCR
Temperature detection - - - -
Optional
Event/Fault recording - -
function
Earth leakage trip (ELT) - - - - -
Communication - - - - -
: Standard : Option

O
 rdering codes

Ordering codes Application


Model Frequency Complete parts Specifications Mounting position
Spare part UAN UAS
of ACB/Cradle
UPR-1L-GL 33 UANS OCR33A/33J for auto connection/manual connection type
UPR-2L-GS 35 UANS OCR35A/35J for auto connection/manual connection type
UPR-1D-GT 36 UANS OCR36A/36J for auto connection/manual connection type
50Hz
UPR-2L-GM 37 UANS OCR37A/37J for auto connection/manual connection type
UPR-1S-AL 38 UANS OCR38A/38J for auto connection/manual connection type
UPR-2S-AS 39 UANS OCR39A/39J for auto connection/manual connection type
Inside of ACB body
UPR-1L-GL 43 UANS OCR43A/43J for auto connection/manual connection type
UPR-2L-GS 45 UANS OCR45A/45J for auto connection/manual connection type
UPR-1D-GT 46 UANS OCR46A/46J for auto connection/manual connection type
60Hz
UPR-2L-GM 47 UANS OCR47A/47J for auto connection/manual connection type
UPR-1S-AL 48 UANS OCR48A/48J for auto connection/manual connection type
UPR-2S-AS 49 UANS OCR49A/49J for auto connection/manual connection type

U-Series Air Circuit Breaker_ 15


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| UPR-1L-GL |

Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional
Self power
1a DO (Digital output)

Characteristic

Ir: Long time current setting

Ir tr: Long time tripping delay setting


Isd: Short time current setting
tr tsd: Short time tripping delay setting
Ii: Instantaneous current setting
tg: Ground fault tripping delay setting
I2t on
Isd Ig: Ground fault current setting
Ig I2t on
tsd
tg

I2t off Ii
I2t off

Protection

In = Ict (A) 0.5 0.63 0.7 0.8 0.9 1


Current setting (Ir)
Ir = In (A) 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
Long time Time delay (tr) tr at (1.5Ir) (sec) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy: 15% tr at (6.0Ir) (sec) 0.5 1.25 2 2.5 5 10 15 20 25 30
or below 100ms tr at (7.2Ir) (sec) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 4 6 8 10 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 20% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Pick-up (Ig)
Accuracy: 15% (Ig0.4In) Ig = Ict (A) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
20% (Ig0.4In)
Ground fault I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tg) tg
I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 1In
Min. trip time (msec) 20 80 160 260 360 460
Accuracy: 20% (I2t off)
Max. trip time (msec) 80 140 240 340 440 540

16
ACB

| UPR-2L-GS, UPR-2L-GM |

Overload protection Event recording


- Long time delay - Short time delay, instantaneous trip
Short circuit protection - I2t on/off optional (for STD)
- Short time delay, instantaneous trip Pre-trip alarm
- I2t on/off optional (for STD) - Prevent unnecessary over load trip
Ground fault protection according to rated current (In)
- I2t on/off optional Field test
Realization of protective - Simulation of long time, short time,
coordination by ZSI (Zone selective instantaneous delay
interlocking) 4a(3a) DO (Digital output)
Fault recording - 4a (UPR-2L-GS)
- Records max. up to 10 fault information - 3a (UPR-2L-GM)
about fault type, fault phase, fault
valve, occurrence time of fault

Characteristic

Ir: Long time current setting

Ir tr: Long time tripping delay setting


Isd: Short time current setting
IP
tr tsd: Short time tripping delay setting

Tp Ii: Instantaneous current setting


tg: Ground fault tripping delay setting
I2t on
Isd Ig: Ground fault current setting
Ig I2t on
tsd tp: Pre-trip alarm delay setting
tg
Ip: Pre-trip alarm current setting
I2t off Ii
I2t off

Protection

In = Ict (A) 0.5 0.63 0.7 0.8 0.9 1


Current setting (Ir)
Ir = In (A) 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
Long time Time delay (tr) tr at (1.5Ir) (sec) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy: 15% tr at (6.0Ir) (sec) 0.5 1.25 2 2.5 5 10 15 20 25 30
or below 100ms tr at (7.2Ir) (sec) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 4 6 8 10 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 15% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Pick-up (Ig) In = Ict 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
Time delay (tg) I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
tg
Ground fault at 1In I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Accuracy: 15% (Ig0.4In) Min. trip time (msec) 20 80 160 260 360 460
20% (Ig0.4In) (I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ip)
Ip = In (A) 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre trip alarm Accuracy: 15%
Time delay (tp) tp (sec) 5 10 15 20 40 60 80 120 160

U-Series Air Circuit Breaker_ 17


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| UPR-1D-GT |

Overload protection Event recording


- Long time delay - Records events of device related to
Short circuit protection setting change, operation and state
- Short time delay, instantaneous trip change (Max. up to 10)
- I2t on/off optional (for STD) Pre trip alarm
Ground fault protection - Prevent unnecessary over load trip
- I t on/off optional
2 according to rated current (In)

Realization of protective Field test


coordination by ZSI (Zone selective - Simulation of long time, short time,
interlocking) instantaneous delay

Fault recording 4a DO (Digital output)


-R
 ecords max. up to 10 fault information Communication: Modbus-RTU/RS-485
about fault type, fault phase, fault Earth leakage trip (Optional)
valve, occurrence time of fault

Characteristic

Ir: Long time current setting


Ir tr: Long time tripping delay setting
IP Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Tp Ii: Instantaneous current setting
I2t on tg: Ground fault tripping delay setting
Isd
Ig I2t on Ig: Ground fault current setting
tsd
tg tp: Pre-trip alarm delay setting
Ip: Pre-trip alarm current setting
I2t off Ii
I2t off

Protection

In = Ict (A) 0.5 0.63 0.7 0.8 0.9 1


Current setting (Ir)
Ir = In (A) 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
Long time Time delay (tr) tr at (1.5Ir) (sec) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy: 15% tr at (6.0Ir) (sec) 0.5 1.25 2 2.5 5 10 15 20 25 30
or below 100ms tr at (7.2Ir) (sec) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 4 6 8 10 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Min. trip time (msec) 20 80 160 260 360 460
Accuracy: 15% (I t off)
2
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Pick-up (Ig) Ig = Ict 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
Time delay (tg) I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
tg
Ground fault at 1In I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Accuracy: 15%(Ig0.4In) Min. trip time (msec) 20 80 160 260 360 460
20%(Ig0.4In) (I t off)
2
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ip) Ip = In (A) 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre trip alarm Time delay (Tp)
tp (sec) 5 10 15 20 40 60 80 120 160
Accuracy: 15%
Current setting (In) In (A) 0.5 1 2 3 5 10 20 30 Non
Earth leakage 140 230 350 800 950 80 120 160
Time delay (t) Alarm time (msec)
(optional) t
Accuracy: 15% or below 40ms Trip time (msec) 60 140 230 350 800

18
ACB

| UPR-1S-AL |

Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional (for STD)
Self power
1a DO (Digital output)

Characteristic

Ir: Long time current setting


Ir tr: Long time tripping delay setting
Isd: Short time current setting
tr tsd: Short time tripping delay setting
Ii: Instantaneous current setting

I2t on
Isd
tsd

I2t off Ii

Protection

In = Ict (A) (0.5-1.0) x1% unit, or 1A unit


Current setting (Ir)
Ir = In (A) 0.7 0.8 0.9 1 1.05 1.1 1.15 1.2 1.25 Non
Long time Time delay (tr) tr at (1.05Ir) (sec) 20 30 40 50 60 70 80 100 120
Accuracy: 15% tr at (1.2Ir) (sec) 10 15 20 25 30 35 40 50 60
or below 100ms tr at (3Ir) (sec) 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 3.5 4 4.5 5 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 15% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms

U-Series Air Circuit Breaker_ 19


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| UPR-2S-AS |

Overload protection Event recording


- Long time delay - Records events of device related to
Short circuit protection setting change, operation and state
- Short time delay, instantaneous trip change (Max. up to 10)
- I2t on/off optional (for STD) Pre trip alarm
Realization of protective - Prevent unnecessary over load trip
coordination by ZSI (Zone selective according to rated current (In)
interlocking) Field test
Fault recording - Simulation of long time, short time,
-R
 ecords max. up to 10 fault information instantaneous delay
about fault type, fault phase, fault 3a DO (Digital output)
valve, occurrence time of fault

Characteristic

Ir: Long time current setting


Ir tr: Long time tripping delay setting
IP Isd: Short time current setting
tr tsd: Short time tripping delay setting
Tp Ii: Instantaneous current setting
I2t on tp: Pre-trip alarm delay setting
Isd
Ip: Pre-trip alarm current setting
tsd

I2t off Ii

Protection

In = Ict (A) (0.5-1.0) x1% unit, or 1A unit


Current setting (Ir)
Ir = In (A) 0.7 0.8 0.9 1 1.05 1.1 1.15 1.2 1.25 Non
Long time Time delay (tr) tr at (1.05Ir) (sec) 20 30 40 50 60 70 80 100 120
Accuracy: 15% tr at (1.2Ir) (sec) 10 15 20 25 30 35 40 50 60
or below 100ms tr at (3Ir) (sec) 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 3.5 4 4.5 5 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 20% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Current setting (Ip) Ip = In (A) 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1 Non
Ground fault Time delay (Tp)
tp (sec) 1 5 10 15 20 25 30 35 40
Accuracy: 15%

20
ACB

| Operation characteristics |

Long time delay (LTD)


Standard current setting
L type
- The scale is marked as magnification of [In].
- Setting range: (Non, 0.8, 0.83, 0.85, 0.88, 0.9, 0.93, 0.95, 0.98, 1.0)In (10 modes)
- No protection in case of non setting of [Ir].
- The breaker is not tripped below 105% of [Ir], and tripped at 120%.
t S type
t
- Setting range: (Non, 0.7, 0.8, 0.9, 1.0, 1.05, 1.1, 1.15, 1.2, 1.25 )In (8 modes)
Ir
- The breaker is tripped above 100% of [Ir].
tr
Time delay setting
L type Ig2t on
- Standard operating time (sec) is based Ig2on the time of 600%[Ir] with inverse time operation.
t off
- Setting range: 0.5, 1.25,Ig2, 2.5, 5, 10, 15, 20, 25, 30sec (10 modes)
t - The breaker is tripped
t at 15% of setting time.
S type Tg
Ir I I
- Standard operating time (sec) is based on the time of 120%[Ir] with inverse time operation.
tr
- Setting range: 10, 15, 20, 25, 30, 35, 40, 50, 60sec (9 modes)
- The breaker is tripped at 15% of setting
Ig2t ontime.
t t t t Ig2t off
Ig
Ir Standard current setting
Short time delay (STD)
tr L type Tg
I - The scale is marked as magnification of [In]. I
I2t on Ig2t on
- Setting range: (Non, 1, 1.5, 2, 2.5, 3, 4, 6, 8, 10)In (10 modes)
S type Ig2t off
I2t off Ig I n
Isd - The scale is marked as magnification of [In].
Tsd
t - Setting range: (Non,
t 1, 1.5,T2,g 2.5, 3, 3.5, 4, 4.5, 5)In (10 modes)
T
I I Time delay setting I I
L type
- Standard operating time (msec) is based on the time of 120%[Isd] with definite time operation.
I2t on
- Setting range: 50, 100, 200, 300, 400, 500msec (6 modes)
t I2t off t curveIapplied
- 1000% of inverse time n in case of inverse time (I2t on) setting.
Isd S type
t Tsd t
- Standard operating time (msec) is based on the time of 120%[Isd] with definite time operation.
T
- The range of set time is 50, 100, 200, 300, 400, 500msec (6 step).
I I
I2t on - 500% of inverse time curve applied in case of inverse time (I2t on) setting.

I2t off I n
Isd Tp(S type)
Tsd
Ip
Instantaneous trip (INST)
Standard current setting T
t Ii I - The scale is markedt as magnification of [In]. I
Tp
I - Setting range: (Non, 2, 3, 4, 6, 8, 10, 12, 15)In (9I modes)
- No protection in case of non setting of [Ii].

Time delay setting


Tp(S type)
- Total breaking time is below 50ms.
t t
Ip

Ii
Tp
I I
Tp(S type)
Ip

Ii
Tp
I I

U-Series Air Circuit Breaker_ 21


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Operation characteristics |

Ground fault trip (GFT)


Standard current setting
L type
- The scale is marked as magnification of OCR rated primary current [ICT].
- Setting range: (Non, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 1.0)[ICT] (10 modes)

Time delay setting


L type
t
- Standard operating time (msec) is based on the time of 120%[Ig] with definite time operation.
- Setting range: 50, 100, 200, 300, 400, 500msec (6 modes)
- Inverse time operated with 100% of [Ict] standard in case of [I2t on] setting.
- The breaker is tripped at 15% of setting time.
Ig2t on

Ig2t off
Ig
t
Tg
I

Ig2t on

tt Ig Ig2t off

Earth leakage trip (ELT)


Standard current setting
Tg L type
I - The scale is marked as magnification of OCR rated primary current [ZCT].
Ig2t on - Setting range: (Non, 0.5, 1, 2, 3, 5, 10, 20, 30[A]) (9 modes)

Ig I n Ig2t off Time delay setting


L type
t
TT
g
- Settings within its alarm range will prevent its breaker from tripping but activating its alarm.
II - Trip time: 60, 140, 230, 350, 800msec (5 modes)
- Alarm time: 140, 230, 350, 800, 950msec (5 modes)

t I n

t
T
I

I n Tp(S type)

Ip
T Standard current setting
tPre-trip alarm (PTA)
Tp I L type
I - The scale is marked as magnification of [In] with definite time operation.
- Setting range: (Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0)In (10 modes)
S type
Tp(S type) - The scale is marked as magnification of [In] with inverse time operation.
t Ip - Setting range: (Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1.1)In (10 modes)

Time delay setting


Tp L type
I - Standard operating time (sec) is based on the time of 100%[Ip].
- Setting range: 5, 10, 15, 20, 40, 60, 80, 120, 160, 200sec (10 modes)
Tp(S type)
S Type
Ip - Standard operating time (sec) is based on the time of 120%[Ip].
- Setting range: 1, 5, 10, 15, 20, 25, 30, 35, 40sec (9 modes)
Tp
I

22
ACB

| Circuit diagrams |

UPR-1L-GL

NCT
k

R S T 21 29 30

R S T N L/S
I/G
NCT NCT
1 2

UPR-1L-GL

Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22

UPR-2L-GS
AC,DC100-250V S0 - S2
Source
NCT + -
k

R S T 21 23 29 30 19

R S T N L PT NCT NCT S2
1 2

UPR-2L-GS

ZO ZO
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2 1 2
A C TN TP S 0
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 26 31 32 33 34 20

+ - + -
In Out
ZSI

U-Series Air Circuit Breaker_ 23


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Circuit diagrams |

UPR-1D-GT
AC,DC100-250V S0 - S2
Source
ZCT NCT + -
k k

R S T 21 23 27 28 29 30 19

R S T N L P/T ELT ELT NCT NCT S2


1 2 1 2

UPR-1D-GT

Rn Sn Tn Nn Ac S/I G/E ZI ZI ZO ZO COM COM A C TN TP S 0


1 2 1 2
CT3
TP
CT2
MHT
CT1
TN

1a for
MCR
Rn Sn Tn 22 24 26 31 32 33 34 35 36 20

+ - + - + -
In Out Communication
ZSI

UPR-2L-GM
AC,DC100-250V S0 - S2
Source
NCT + -
k

R S T 21 23 29 30 19

R S T N L/S PT NCT NCT S2


I/G 1 2

UPR-2L-GM

Rn Sn Tn Nn Ac1 Ac2 L/S ZI


I/G 1
ZI
2
ZO ZO
1 2 A C TN TP S 0
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 26 31 32 33 34 20

+ - + -
In Out
ZSI

24
ACB

UPR-1S-AL

R S T 21

R S T L/
N SI

UPR-1S-AL

Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22

UPR-2S-AS
AC,DC100-250V S 0 - S2

Source

+ -

R S T 21 23 19

R S T N L PT S2

UPR-2S-AS

Rn Sn Tn Nn Ac S/I ZI ZI ZO ZO A C TN TP S 0
CT3 1 2 1 2

TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 31 32 33 34 20

+ - + -
In Out
ZSI

U-Series Air Circuit Breaker_ 25


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Characteristic curves |

General feeder

4
3
Hour

2
1
50
40
30
20
10
8
Minute

6
5
4
3

2

1
50
40
30
Operating time

20

10
8
6
5
4
3
2

1
0.8
0.6
0.5 500ms 500ms
0.4
Second

0.3
0.2

0.1
0.08
0.06 50ms 50ms
0.0
0.05
0.04
0.03
0.02

0.01
0.008
0.006
0.005
1000

1500

2000
2500
3000
100

100
125
150

200
250
300

400
500
600
700
800
900
10

15

20

30

40
50
60
70
80
90

60
70
80
90
7
8
9

Percent for rated primary current of OCR [ICT] Percent for base current of OCR [Io]

Long time delay current setting range Instantaneous tripping current setting range Pre-trip alarm current setting range
Short time delay current setting range Ground fault trip current setting range

26
ACB

Generator

4
3
Hour

1
50
40
30
20

10
8
Minute

6
5
4
3
2

1
50
40
30
Operating time

20

10
8
6
5
4
3
2

1
0.8
0.6
0.5 500ms
0.4
Second

0.3
0.2

0.1
0.08
0.06
0.05
0.0
50ms
0.04
0.03
0.02

0.01
0.008
0.006
0.005
1000

1500

2000
2500
3000
100
125
150

200
250
300

400
500
600
700
800
900
10

15

20

30

40
50
60
70
80
90
7
8
9

Percent for base current of OCR [Io]

Long time delay current setting range Instantaneous tripping current setting range
Short time delay current setting range Pre-trip alarm current setting range

U-Series Air Circuit Breaker_ 27


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Zone selective interlock function |


Zone selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machinery get under fault conditions.

Example

In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site
sends ZSI signal to halt upstream breakers operation.
To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay.

The
 upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time delay for
protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously.
For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will
react before upstream ones under overcurrent/short time delay/ground fault situations.
ZSI connecting line needs to be maximum 3m.

ACB 1
Out
Zone 1 In

ACB 2-1 ACB 2-2


Out
Zone 2 Fault A
In

ACB 3-1 ACB 3-2 ACB 3-N


Zone 3 Out Out
Fault B
Out

In In In

ZSI connecting

28
ACB

| System diagram |

R S T N

ACB trip
ACB

Display
(LCD, LED)
MHT
Trip
Rogowski Relay operation
CT Measurement
part selection

PTA contact
MCU
processing
LTD contact

External
contact STD/INST contact

GFT contact
Power
CT Self power COMMON contact

Trip relay
ZSI output +
ZSI output -
ZSI
ZSI input +
ZSI input -

ZCT Earth RS-485 +


leakage COMM.
RS-485 -

SMPS Test
110V - 220V power terminal

| Communication function |
Modbus-RTU / RS-485
SCADA system
Operation mode: Differential
Distance: Max.1.2km
Modbus/RS-485
Cable: RS-485 shielded twist 2-pair cable
Baud rate: 9,600, 19,200, 38,400 bps
Transmission method: Half-duplex
Termination: 150

U-Series Air Circuit Breaker_ 29


U-Series / Air Circuit Breaker

Accessories

| Overview |

Ordering codes Application


Item Complete Specifications Mounting position Page
parts of Spare part UAN UAS
ACB/Cradle
M1 UANS M1 AC/DC110V
M2 UANS M2 AC/DC220V
M3 UANS M3 AC380V
Motor M4 UANS M4 AC440V Inside of ACB body 36
M7 UANS M7 DC24V
M8 UANS M8 DC48V
M9 UANS M9 DC125V
Spring charge switch B6 UANS B6 Inside of ACB body 36
C1 UANS C1 AC/DC110V
C2 UANS C2 AC/DC220V
C3 UANS C3 AC380V
Closing coil C4 UANS C4 AC440V Inside of ACB body 37
C7 UANS C7 DC24V
C8 UANS C8 DC48V
C9 UANS C9 DC125V
S1 UANS S1 AC/DC110V
S2 UANS S2 AC/DC220V
S3 UANS S3 AC380V
Trip coil S4 UANS S4 AC440V Inside of ACB body 38
S7 UANS S7 DC24V
S8 UANS S8 DC48V
S9 UANS S9 DC125V
S1 UANS SS1 AC/DC110V
S2 UANS SS2 AC/DC220V
S3 UANS SS3 AC380V
Double trip coil S4 UANS SS4 AC440V Inside of ACB body 39
S7 UANS SS7 DC24V
S8 UANS SS8 DC48V
S9 UANS SS9 DC125V
T1 UANS T1 AC/DC110V
T2 UANS T2 AC/DC220V
T3 UANS T3 AC380V
Trip supervision
T4 UANS T4 AC440V Inside of ACB body 40
coil
T7 UANS T7 DC24V
T8 UANS T8 DC48V
T9 UANS T9 DC125V
U1 UANS U1 AC/DC110V
U2 UANS U2 AC/DC220V
U3 UANS U3 AC380V
UVT coil
U4 UANS U4 AC440V Inside of ACB body 41
(Instantaneous type)
U7 UANS U7 DC24V
U8 UANS U8 DC48V
U9 UANS U9 DC125V

30
ACB

Ordering codes Application


Item Complete Specifications Mounting position Page
parts of Spare part UAN UAS
ACB/Cradle
- UANS UT1 AC/DC110V
- UANS UT2 AC/DC220V
- UANS UT3 AC380V
UVT time delay Outside of ACB body
- UANS UT4 AC440V 42
controller & cradle
- UANS UT7 DC24V
- UANS UT8 DC48V
- UANS UT9 DC125V
V1 UANS V1 AC/DC110V
V2 UANS V2 AC/DC220V
UVT time delay Controller: outside of
controller V3 UANS V3 AC380V ACB body & cradle
& V4 UANS V4 AC440V 42
UVT coil V7 UANS V7 DC24V UVT coil: inside of
(Instantaneous type) ACB body
V8 UANS V8 DC48V
V9 UANS V9 DC125V
- UANS A3A Auto connection type, 3a+3b
- UANS A3J Manual connection type, 3a+3b
Auxiliary switch A5 UANS A5A Auto connection type, 5a+5b Inside of ACB body 43
A5 UANS A5J Manual connection type, 5a+5b
AA UANS AA Additional 1a1b (Max. 6a6b)
Test jumper - UANS AJ for auto connection type 43
AQ UANS AQ Test 1C, Connected 1C
AR UANS AR Connected 2C
AS UANS AS Test 2C
AT UANS AT Isolated 1C, Inserted 1C
AU UANS AU Inserted 2C
Position switch AV UANS AV Isolated 2C Right side of cradle 44
P4 UANS P4 Test 2C, Connected 2C
PS UANS PS Isolated 1C, Test 1C, Connected 2C
PQ UANS PQ Inserted 1C, Isolated 1C, Test 1C, Connected 1C
PR UANS PR Inserted 1C, Isolated 1C, Test 3C, Connected 3C
P8 UANS P8 Inserted 2C, Isolated 2C, Test 2C, Connected 2C
Condenser trip - UANS CTD1 AC/DC110V
45
device (CTD) - UANS CTD2 AC/DC220V
Lifting lug - UANS AL 2EA/SET (supplied as standard only for C frame) Outside of ACB body & cradle 46
- UANS DUA3 A frame, 630-2,000A, 3P
- UANS DUA4 A frame, 630-2,000A, 4P
- UANS DUB3 B frame, 630-4,000A, 3P Outside of ACB body
Dummy ACB 46
- UANS DUB4 B frame, 630-4,000A, 4P & cradle
- UANS DUC3 C frame, 3,200-5,000A, 3P
- UANS DUC4 C frame, 3,200-5,000A, 4P

U-Series Air Circuit Breaker_ 31


U-Series / Air Circuit Breaker

Accessories

| Overview |

Ordering codes Application


Item Complete Specifications Mounting position Page
parts of Spare part UAN UAS
ACB/Cradle
- UANS DWB1 for Draw-out type, 2way interlock
- UANS DWB2 for Draw-out type, 3way interlock
Mechanical - UANS FAWB1 for A/C frame, Fixed type, 2way interlock Outside of ACB body
47
interlock kit - UANS FAWB2 for A/C frame, Fixed type, 3way interlock & cradle
- UANS FBWB1 for B frame, Fixed type, 2way interlock
- UANS FBWB2 for B frame, Fixed type, 3way interlock
- UANS DWB1A for A frame, Draw-out type, 2way interlock
- UANS DWB2A for A frame, Draw-out type, 3way interlock
- UANS DWB1B for B frame, Draw-out type, 2way interlock
- UANS DWB2B for B frame, Draw-out type, 3way interlock
- UANS DWB1C for C frame, Draw-out type, 2way interlock Interlock kit: outside
Mechanical of ACB body or cradle
interlock kit - UANS DWB2C for C frame, Draw-out type, 3way interlock
47
& ACB internal - UANS FWB1A for A frame, Fixed type, 2way interlock
interlock part Interlock part: inside
- UANS FWB2A for A frame, Fixed type, 3way interlock of ACB body
- UANS FWB1B for B frame, Fixed type, 2way interlock
- UANS FWB2B for B frame, Fixed type, Wire type, 3way interlock
- UANS FWB1C for C frame, Fixed type, Wire type, 2way interlock
- UANS FWB2C for C frame, Fixed type, Wire type, 3way interlock
- UANS HVA3 Horizontal/Vertical type 6EA for A frame, 630-1,600A, 3P
- UANS HVA4 Horizontal/Vertical type 8EA for A frame, 630-1,600A, 4P
Terminal busbar 48
- UANS HVB3 Horizontal/Vertical type 6EA for B frame, 630-3,200A, 3P
- UANS HVB4 Horizontal/Vertical type 8EA for B frame, 630-3,200A, 4P
- UANS FRA3F Front type 6EA for A frame, 630-1,600A, 3P
- UANS FRA4F Front type 8EA for A frame, 630-16,00A, 4P
- UANS FRB3F Front type 6EA for B frame, 2,000-3,200A, 3P
- UANS FRB4F Front type 8EA for B frame, 2,000-3,200A, 4P
Front type 3EA & horizontal/Vertical type 3EA
- UANS FHVA3F
Termanal busbar for A frame, 630-1,600A, 3P Outside of ACB body
48
for fixed type Front type 4EA & horizontal/Vertical type 4EA & cradle
- UANS FHVA4F
for A frame, 630-1,600A, 4P
Front type 3EA & horizontal/Vertical type 3EA
- UANS FHVB3F
for B frame, 630-3,200A, 3P
Front type 4EA & horizontal/Vertical type 4EA
- UANS FHVB4F
for B frame, 630-3,200A, 4P
- UANS FRA3 Front type 6EA for A frame, 630-1,600A, 3P
- UANS FRA4 Front type 8EA for A frame, 630-1,600A, 4P
- UANS FRB3 Front type 6EA for B frame, 2,000-3,200A, 3P
- UANS FRB4 Front type 8EA for B frame, 2,000-3,200A, 4P
Front type 3EA & horizontal/Vertical type 3EA
- UANS FHVA3
Termanal busbar for A frame, 630-1,600A, 3P Outside of ACB body
48
for draw-out type Front type 4EA & horizontal/Vertical type 4EA & cradle
- UANS FHVA4
for A frame, 630-1,600A, 4P
Front type 3EA & horizontal/Vertical type 3EA
- UANS FHVB3
for B frame, 630-3,200A, 3P
Front type 4EA & horizontal/Vertical type 4EA
- UANS FHVB4
for B frame, 630-3,200A, 4P

32
ACB

Ordering codes Application


Item Complete Specifications Mounting position Page
parts of Spare part UAN UAS
ACB/Cradle
Phase insulation - UANS 3PBAR for 3P Terminal side of ACB
49
barrier - UANS 4PBAR for 4P body & cradle
ON/OFF button lock AM UANS AM ON/OFF button cover with padlock hole Outside of ACB body & cradle 49
OCR portable checker - UANS OC 50
Key lock device AB UANS AB Key lock device Inside of ACB body 51
Wrong insertion Outside of ACB body
AW UANS AW 52
preventer & cradle

OCR & BR UANS BR for OCR manual reset only


Alarm switch reset BA UANS BA for OCR manual reset & alarm switch reset Inside of ACB body 53
device BM UANS BM for OCR auto reset & alarm switch reset
UANS AEA3 for A frame, 630-2,000A, 3P
UANS AEA4 for A frame, 630-2,000A, 4P
UANS AEB3 for B frame, 630-4,000A, 3P
Safety shutter lock AE Inside of cradle 54
UANS AEB4 for B frame, 630-4,000A, 4P
UANS AEC3 for C frame, 3,200-5,000A, 3P
UANS AEC4 for C frame, 3,200-5,000A, 4P
Control terminal
BC UANS BC for auto connection control terminal Control terminal of cradle 55
protection cover
UANS AXA3 for A frame, 630-2,000A, 3P
UANS AXA4 for A frame, 630-2,000A, 3P
UANS AXB3 for B frame, 630-4,000A, 3P
Arc shield AX Upper side of cradle 55
UANS AXB4 for B frame, 620-4,000A, 4P
UANS AXC3 for C frame, 3,200-5,000A, 3P
UANS AXC4 for C frame, 3,200-5,000A, 4P
A UANS CJ Auto connection terminal Inside of ACB body
Control terminal 56
J UANS MJ Manual connection terminal & cradle
Short "b" contact AK UANS AK Control terminal of cradle 56
Counter - UANS AD Counter Inside of ACB body 57
UANS AF for ACB body and cradle
Outside of ACB body &
Fixing block AF UANS AFB for ACB body 57
cradle
UANS AFC for cradle
- UANS RTU Temperature detection module
Temperature detection module with
- UANS RTUN
temperature sensor Module: outside of
Remote operation ACB body or cradle
- UANS RCU Remote operation module
& temparature 58
detection module Remote operation & temperature detection Sensor: inside of
- UANS RCTU
module cradle
Remote operation & temperature detection
- UANS RCTUN
module with temparature sensor
Temperature sensor - UANS TSN Temperature sensor Inside of cradle 59
Draw-in/out &
- UANS DR Inside of ACB body 60
position lock device
- UANS HANDLE Standard type
Draw-in/out
- UANS LHANDLE Long type 60
handle
- UANS UHANDLE Universal joint type

U-Series Air Circuit Breaker_ 33


U-Series / Air Circuit Breaker

Accessories

| Overview |

Ordering codes Application


Item Complete Specifications Mounting position Page
parts of Spare part UAN UAS
ACB/Cradle
- UANS NCTAT for A frame, 630A
- UANS NCTAH for A frame, 800A
- UANS NCTAJ for A frame, 1,000A
- UANS NCTAK for A frame, 1,250A
- UANS NCTAL for A frame, 1,600A
Neutral CT - UANS NCTBM for B frame, 2,000A 61
- UANS NCTBN for B frame, 2,500A
- UANS NCTBP for B frame, 3,200A
- UANS NCTBQ for B frame, 4,000A
- UANS NCTCQ for C frame, 4,000A
- UANS NCTCS for C frame, 5,000A
Door flange - UANS AG for IP30 Panel door 62
Dust cover - UANS DC for IP52 62
ATS controller - UANS ATS Automatic transfer switch & controller 63
OCR MCR wire B8 UANS MCR Inside of ACB body -
Motor controller - UANS MCU Inside of ACB body -
- UANS M1U AC/DC110V
- UANS M2U AC/DC220V
- UANS M3U AC380V
Motor unit - UANS M4U AC440V Inside of ACB body -
- UANS M7U DC24V
- UANS M8U DC48V
- UANS M9U DC125V
I UANS CTAI for A frame, 80A
B UANS CTAB for A frame, 160A
O UANS CTAO for A frame, 200A
V UANS CTAV for A frame, 320A
E UANS CTAE for A frame, 400A
T UANS CTAT for A frame, 630A
H UANS CTAH for A frame, 800A
J UANS CTAJ for A frame, 1,000A
K UANS CTAK for A frame, 1,250A
L UANS CTAL for A frame, 1,600A
M UANS CTAM for A frame, 2,000A
Current
E UANS CTBE for B frame, 400A Inside of ACB body -
transformer (CT)
T UANS CTBT for B frame, 630A
H UANS CTBH for B frame, 800A
J UANS CTBJ for B frame, 1,000A
K UANS CTBK for B frame, 1,250A
L UANS CTBL for B frame, 1,600A
M UANS CTBM for A frame, 2,000A
N UANS CTBN for B frame, 2,500A
P UANS CTBP for B frame, 3,200A
Q UANS CTCQ for C frame, 4,000A
S UANS CTCS for C frame, 5,000A
Q UANS CTDQ for D frame, 4,000A

34
ACB

Ordering codes Application


Item Complete Specifications Mounting position Page
parts of Spare part UAN UAS
ACB/Cradle
Current S UANS CTDS for D frame, 5,000A
Inside of ACB body -
transformer (CT) X UANS CTDX for D frame, 6,300A
- UANS DIA for A frame, C frame
Arc chamber Inside of ACB body -
- UANS DIB for B frame
- UANS MHTU MHT (Magnetic holding trigger) unit
MHT device Inside of ACB body -
- UANS MHT MHT (Magnetic holding trigger) coil only
- UANS CLA16 for A frame, 630-1,600A

Draw-in/out - UANS CLA20 for A frame, 2,000A / C frame, 3,200-5,000A


connection - UANS CLAB20 for B frame, 630-2,500A Inside of ACB body -
terminal - UANS CLAB32 for B frame, 3,200A
- UANS CLAB40 for B frame, 4,000A
- UANS ISOL 5 clip Terminal side of ACB
Terminal clip -
- UANS ISOL4 4 clip body & cradle
MOC switch MC UANS MOC Mechanical operated cell switch 10a10b Outside of ACB body & cradle -
UANS 50Hz, UPR-1L-GL, for auto connection
33
OCR33A/33J /manual connection type
UANS 50Hz, UPR-2L-GS, for auto connection
35
OCR35A/35J /manual connection type
UANS 50Hz, UPR-1D-GT, for auto connection
36
OCR36A/36J /manual connection type
UANS 50Hz, UPR-2L-GM, for auto connection
37
OCR37A/37J /manual connection type
UANS 50Hz, UPR-1S-AL, for auto connection
38
OCR38A/38J /manual connection type
UANS 50Hz, UPR-2S-AS, for auto connection
39
Protection trip OCR39A/39J /manual connection type
Inside of ACB body -
relay (OCR) UANS 60Hz, UPR-1L-GL, for auto connection
43
OCR43A/43J /manual connection type
UANS 60Hz, UPR-2L-GS, for auto connection
45
OCR45A/45J /manual connection type
UANS 60Hz, UPR-1D-GT, for auto connection
46
OCR46A/46J /manual connection type
UANS 60Hz, UPR-2L-GM, for auto connection
47
OCR47A/47J /manual connection type
UANS 60Hz, UPR-1S-AL, for auto connection
48
OCR48A/48J /manual connection type
UANS 60Hz, UPR-2S-AS, for auto connection
49
OCR49A/49J /manual connection type

U-Series Air Circuit Breaker_ 35


U-Series / Air Circuit Breaker

Accessories

| Motor |
Manual charging method and geared motor charging
by external power source.
Operating voltage range: 85-110%

R
 atings Wire ratings C
 onnection diagram

Rated voltage Rated voltage Source

DC110V DC220V DC24/48V DC110/220V


Rated current (A) 1.2 0.5 Insulation Insulation 1 15
AWG AWG
Starting pick-up (A) 5-6 times of rated current level (V) level (V)
Source
Revolutions per minute (RPM) 163 18 600 18 600 Spring
charge
off sw.
Charging time (sec) within 5sec1)
1 15
Torque (kgf) 300kgf x cm
Source

Rated watt (W) 100 100Spring


M
charge
Insulation voltage (V/min) 1 2,00015 off sw.

Insulation resistance (M) 100


Spring

Ambient temperature (C) charge


off sw. -15-60
1) Charging time is within 10sec of rated, in case of DC24/48V. M
2 16

O
 rdering code
Ordering code 2 16
Application
Item Complete parts Specification Mounting position
2 Spare
16 part UAN UAS
of ACB/Cradle
M1 UANS M1 AC/DC110V
M2 UANS M2 AC/DC220V
M3 UANS M3 AC380V
Motor M4 UANS M4 AC440V Inside of ACB body
M7 UANS M7 DC24V
M8 UANS M8 DC48V
M9 UANS M9 DC125V

| Spring charge switch |


These contacts (No.15,16) are for delivering spring charge status to outside.
Optional device mounted on the body.
Ordering code: B6, UANS B6 (Spare part)

36
ACB

| Closing coil |
A control device which closes a circuit breaker
remotely, when applying 85-110% of rated control
voltage over 150ms to coil terminals (3,4).

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
C1 UANS C1 AC/DC110V
C2 UANS C2 AC/DC220V
C3 UANS C3 AC380V
Closing coil C4 UANS C4 AC440V Inside of ACB body
C7 UANS C7 DC24V
C8 UANS C8 DC48V
C9 UANS C9 DC125V
Source
PB
(Close)

R
 atings C
 onnection diagram
3
Power supply (Vn) Power consumption (VA) OpeningSource
time
Operating limits Source
DC (V) AC (V) Inrush Steady-state (ms) PB
PB
(Close)
(Close)
24 - 0.85-1.1Vn
3
100-130 100-130 0.85-1.1Vn 300 10 60 3

200-250 200-250 0.85-1.1Vn

CC

W
 ire ratings

Rated voltage (Vn)


DC24 ADC110/220 CC
CC

AWG Insulation level (V) AWG Insulation


4 level (V)
18 600 18 600

4
4

U-Series Air Circuit Breaker_ 37


U-Series / Air Circuit Breaker

Accessories

| Trip coil |
A control device which trips a circuit breaker
remotely, when applying 70-110% of rated control
voltage over 150ms to coil terminals (7,8).

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
S1 UANS S1 AC/DC110V
S2 UANS S2 AC/DC220V
S3 UANS S3 AC380V
Trip coil S4 UANS S4 AC440V Inside of ACB body
S7 UANS S7 DC24V
S8 UANS S8 DC48V
S9 UANS S9 DC125V

R
 atings C
 onnection diagram

Power supply (Vn) Power consumption (VA) Opening time Source


Operating limits
DC (V) AC (V) Source
Inrush Steady-state (ms)
PB(Open)

24 - 0.7-1.1Vn
PB(Open)

7
100-130 100-130 0.7-1.1Vn 300 10 40
7
200-250 200-250 0.7-1.1Vn

Source
W
 ire ratings
PB(Open)

Rated voltage (Vn)


7
DC24 ADC110/220 TC
TC
AWG Insulation level (V) AWG Insulation level (V)
20 300 20 300

8
8
TC

38

8
ACB

| Double trip coil |


A control device which trips a circuit breaker doubly
from the outside.
Not available with UVT (Under-voltage trip) coil when
installing double trip coil.
Rated control voltage range 70-110%, applying
voltage over 150ms to coil terminals (9,10).

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
S1 UANS SS1 AC/DC110V
S2 UANS SS2 AC/DC220V
S3 UANS SS3 AC380V
Double trip coil S4 UANS SS4 AC440V Inside of ACB body
S7 UANS SS7 DC24V
S8 UANS SS8 DC48V
S9 UANS SS9 DC125V

R
 atings C
 onnection diagram

Power supply (Vn) Power consumption (VA) Opening time


Operating limits
DC (V) AC (V) Inrush Steady-state (ms) Source Source
PB(Open)

PB(Open)

24 - 0.7-1.1Vn
100-130 100-130 0.7-1.1Vn
Source Source 300 10 40 7 9

200-250 200-250 0.7-1.1Vn


PB(Open)

PB(Open)

7 9

W
 ire ratings
Source Source

Rated voltage (Vn)


PB(Open)

PB(Open)

DC24 ADC110/220 TC TC
7 9
AWG Insulation level (V) AWG Insulation level (V)
20 300 20 300
TC TC

8 10

TC TC
8 10

U-Series Air Circuit Breaker_ 39

8 10
U-Series / Air Circuit Breaker

Accessories

| Trip supervision coil |


To trip the circuit breaker, 70-110% of rated control
voltage should be applied to both terminals (7,8) over
150ms.
Add your selection (S1-S9) to main body's ordering
code and mark T1-T9 in option list.
When using trip coil supervision, aux. contact is 3a3b
(Not available aux. switch 43/44, 53/54).
Output contact is No.59.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
T1 UANS T1 AC/DC110V
T2 UANS T2 AC/DC220V
T3 UANS T3 AC380V
Trip supervision
T4 UANS T4 AC440V Inside of ACB body
coil
T7 UANS T7 DC24V
T8 UANS T8 DC48V
T9 UANS T9 DC125V

Source
R
 atings C
 onnection diagram
PB(Open)

Power supply (Vn) Power consumption (VA)


Supervision Opening time
Operating limits7 59
DC (V) AC (V) Inrush Steady-state (ms) Source
Source
PB(Open)

24 - 0.7-1.1Vn
PB(Open)

Supervision
100-130 100-130 0.7-1.1Vn 300 10
Supervision 40 7 59
7 59
200-250 200-250 0.7-1.1Vn

W
 ire ratings
TC

Rated voltage (Vn)


DC24 ADC110/220
TC
AWG Insulation level (V) AWG Insulation
8
level (V) TC

20 300 20 300

8
8

40
ACB

| UVT coil |
If the voltage of the main or the control power is
under 70% of the standard, UVT breaks the circuit
automatically.
Connect instantaneous type with both terminals
(9,10) and connect with time delay type in order to
present time delay controller.
- The circuit breaker is opened with trip unit power
supply voltages below 70%.
- The circuit breaker is closed with unit power supply
voltage above 85%.
Instantaneous type can not be used with double trip
coil.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
U1 UANS U1 AC/DC110V
U2 UANS U2 AC/DC220V
U3 UANS U3 AC380V
UVT Coil
U4 UANS U4 AC440V Inside of ACB body
(Instantaneous type)
U7 UANS U7 DC24V U1
Source

COM
a
U8 UANS U8 DC48V b
U2

Controller

U9 UANS U9 DC125VT2 C1

PB(Open)

UVT

C2
T1

R
 atings C
 onnection diagram

Power supply (Vn) Power consumption (VA) Opening time


Pickup Drop U1
Source

DC (V) AC (V) Inrush Steady-state (ms)


COM U1
Source

a COM
U2
b a U2
b
24 -
Controller

C1
Controller
PB(Open)

UVT

T2 C1
PB(Open)

UVT

T2
C2
110 (100-130) 110 (100-130) UVT T1
T1
C2
9
9
220 (200-250) 220 (200-250) Above 0.85Vn Below 0.35Vn 300 10 60
- 380
- 440
10

W
 ire ratings
UVT
UVT

Rated voltage (Vn)


DC24 ADC110/220 AC380/440
AWG Insulation level (V) AWG Insulation level (V) AWG Insulation level (V)
20 300 20 300 20 600 10
10

U-Series Air Circuit Breaker_ 41


U-Series / Air Circuit Breaker

Accessories

| UVT time delay controller |


Use of UVT time delay controller is recommended to
prevent tripping when the power supply network for
the trip unit is subject to brief voltage drops or power
supply failures.
This device is possible to delay as (0.5, 1.0, 1.5, 3 sec).
It can be mounted at the left side of cradle or the DIN
rail.
Controller is mounted at cradle (Draw-out type) or
outside of main body (Fixed type).

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
- UANS UT1 AC/DC110V
- UANS UT2 AC/DC220V
- UANS UT3 AC380V
UVT time delay Outside of ACB body
- UANS UT4 AC440V
controller & cradle
- UANS UT7 DC24V
- UANS UT8 DC48V
- UANS UT9 U1 DC125V
Source

COM
a
V1 UANS V1 b
U2
AC/DC110V
V2 UANS V2 C1 AC/DC220V Controller: outside
Controller

UVT time delay


PB(Open)

T2
UVT

controller V3 UANS V3 T1
C2
AC380V of ACB body &
& V4 UANS V4 AC440V
9
cradle
UVT coil V7 UANS V7 DC24V UVT coil: inside of
(Instantaneous type) V8 UANS V8 DC48V ACB body
V9 UANS V9 DC125V

C
 onnection & Operating time C
 onnection diagram
UVT
C
 onnection diagram

120 U1
Source

COM
102 a U2
b
Controller

C1
V Source
PB(Open)

ACB UVT T2
UVT

V Source 10
ACB UVT U1 C2
Source

CONTROLLER COM T1
CONTROLLER 0
a U2 9
b
0
Controller

128
142

TYPE : UANS UT RATED VOLTAGE : V C1


PB(Open)

T2
UVT

TYPE : UANS UT RATED VOLTAGE : V


UVT Trip T1
C2
Remote
trip Rated
Pick up
Output-Contact
Rated
Voltage
UVT Trip 0.5 1.0 1.5 3.0
Remote Pick up CAUTION

trip Output-Contact
DELAY Voltage
UVT
Coil 0.5 1.0 1.5 3.0 9
0
CAUTION

DELAY TIME(S) UVT


Coil
9 10 Sec
TIME(S) 0 9
0.5 10 0 Sec
1.0
0
0.5 T1 T2 a b COM C1 C2 U1 U2
1.5
1.0
T1 T2 a b COM 3.0C1 C2
1 2U1 3U2 4 5 6 7 8 9
1.5
3.0 1 2 3 4 5 6 7 8 9
UVT

[ 0.5 - 1.0 - 1.5 - 3 (sec) ] 2-4.2, M4*25L

UVT

10

42
10
ACB

| Auxiliary switch |
A contact to monitor On/Off position of ACB remotely.
3a3b is provided as standard for UAS type and 5a5b is
standard for UAN type.
Applicable AUX switch is up to 6a6b. Add AA on your order.
When working with monitoring contact for trip coil the
AUX switch will be 3a3b. When working with OCRs MCR
function it will be 4a5b. When both monitoring contact and
MCR function working together it will be 3a4b.
When ordering short badditionally it will be attached to
bcontacts 51, 52 when the product is out. The additional
short b which enclosed in the product is applicable as the
number of the b contact.
5a5b is separate product and available. Add UANS AS on
extra order.

R
 atings W
 ire ratings C
 onnection diagram

Load Resistance Lamp Inductor Motor Wire ratings


AC125V 5A 0.7A 4A 1.3A AWG Insulation level (V)
41 43 45 47 49 51 53 55 57 59
AC250V 5A 0.5A 4A 0.8A 20 300

O
 rdering code

Used for short b contact (Option)


Used for SHT supervision (Option)

Used for SHT supervision (Option)


Used for MCR(Option)

Ordering code Application


Mounting
Item Complete parts Specification
Spare part UAN UAS position
of ACB/Cradle
- UANS A3A Auto connection type, 3a+3b
- UANS A3J Manual connection type, 3a+3b
Auxiliary 41 43 45 47 49 51 53 55 57 59 Inside of ACB
A5 UANS A5A Auto connection type, 5a+5b 42 44 46 48 50 52 54 56 58 60
switch body
A5 UANS A5J Manual connection type, 5a+5b
AA UANS AA Additional 1a1b (Max. 6a6b)
Used for short b contact (Option)
Used for SHT supervision (Option)

Used for SHT supervision (Option)


Used for MCR(Option)

41 43 45 47 49 51 53 55 57 59

| Test jumper |
A connecting device to make the body of auto connection
Used for short b contact (Option)
Used for SHT supervision (Option)

Used for SHT supervision (Option)

type operate separately.


Used for MCR(Option)

42 44 46 48 50 52 54 56 58 60
Ordering code: UANS AJ (Spare part)

42 44 46 48 50 52 54 56 58 60

U-Series Air Circuit Breaker_ 43


U-Series / Air Circuit Breaker

Accessories

| Position switch |
This switch is for indicating the position of ACB in the
cradle. It is mounted on the side of cradle.
Indicating position Connected/Test/Isol/Insert.
Only one switch is applicable.

R
 atings

Load Resistance Lamp Inductor Motor


AC125V 10A 1.5A 6A 2A
DC30V 6A 3A 6A 3A
DC125V 0.6A 0.1A 0.6A 0.1A
DC250V 0.3A 0.05A 0.3A 0.05A

Composition

Ordering code Application


Mounting
Item Complete parts Specification Inserted Isolated Test Connected
Spare part UAN UAS position
of ACB/Cradle
AQ UANS AQ Test 1C, Connected 1C - - (1C) (1C)
AR UANS AR Connected 2C - - - (2C)
AS UANS AS Test 2C - - (2C) -
AT UANS AT Isolated 1C, Inserted 1C
61

64
(1C)
71 74
(1C)
81 84
- -
AU UANS
Insert AU Inserted 2C (2C) - - -
Position IsolUANSTest Connect Right side
AV AV Isolated 2C - (2C) - -
switch of cradle
P4 UANS P4 Test 2C, Connected 2C - - (2C) (2C)
PS UANS PS Isolated 1C, Test 1C, Connected 2C - (1C) (1C) (2C)
PQ
Connect UANS PQ Inserted 1C, Isolated 1C, Test 1C, Connected 1C (1C) (1C) (1C) (1C)
PR UANS PR Inserted 1C, Isolated 1C, Test 3C, Connected 3C (2C) (2C) (2C) (2C)
P8 Test UANS P8 Inserted 2C, Isolated 2C, Test 2C, Connected 2C
62 63 6566 (1C)
72 73 75 76 (1C)
82 83 85 86(3C) (3C)
61 64 71 74 81 84
Isol Test Connection Isolation
Insert Position Position Position
Isol Test Connect 61-62 a 71-72 a 81-82 a
Position switch
Insert operating sequence C
 onnection diagram 61-63 b
64-65 a E
71-73 b
74-75 a xterior 81-83 b
Insert
64-66 b 74-76 b Position
67-68 a 77-78 a 91-92 a
67-69 b 77-79 b 91-93 b
61 64 71 74 63.5
Connect 61 6481 84
71 74 81 84
Insert Insert
Isol Test Isol Connect
Test Connect
Test
62 63 65 66 72 73 75 76 82 83 85 86

Isol Test Connection Isolation


Position Position Position
61-62 a 71-72 a 81-82 a
Connect 61-63 b 71-73 b 81-83 b
Connect Insert 64-65 a 74-75 a Insert
64-66 b 74-76 b Position
67-68 a 77-78 a 91-92 a
Test Test 67-69 b 77-79 b 91-93 b
62 63 65 66 72 73 75 62 76
63 65826683 8572 86
73 75 76 82 83 85 86
Isol Test ConnectionTest Isolation
Connection Isolation
Isol Position Position Position PositionPosition Position
61-62 a 71-72 a 61-62 a 81-82 a71-72 a 81-82 a
61-63 b 71-73 b 61-63 b 81-83 b71-73 b 81-83 b
Insert Insert 64-65 a 74-75 a 64-65 a Insert 74-75 a Insert
64-66 b 74-76 b 64-66 b Position74-76 b Position
67-68 a 77-78 a 67-68 a 91-92 a77-78 a 91-92 a
67-69 b 77-79 b 67-69 b 91-93 b77-79 b 91-93 b

44
ACB

| Condenser trip device |


In case of using AC/DC power for trip control, it gets a
circuit breaker tripped once electrically when power
supply is broken down.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
Condenser trip - UANS CTD1 AC/DC110V
device (CTD) - UANS CTD2 AC/DC220V

C
 TD operating sequence C
 onnection diagram

Source
72 130 1 6
CONDENSER TRIP DEVICE
6 7 U V
WITH RECTIFIER
2- R1
CDT
SA R2 R3 P N
72
22

PB(Open)

SW C1 NL
2 7
80 5
90 3 4

AC Input power NO. 1, 2 DC Normal power NO. 6(+), 5(-)


CTD Trip power NO. 7(+), 5(-) Delay contact NO. 3, 4

YC

R
 atings

Rated input voltage AC110V AC220V


Normal charging voltage DC145V DC290V
8
Normal current capacity DC2A
Rated frequency 50/60Hz
Delay circuit time within 1.5sec
Applicable standards IEC 60694 / KSC 4611

U-Series Air Circuit Breaker_ 45


U-Series / Air Circuit Breaker

Accessories

| Lifting lug |
A device to make an ACB easy to shift.
Hang it to both handles of the arc shield, cradle, and ACB.
When handling products, please be sure to use crane. In
case of products under 3,200A and handling cradle only,
please comply with safety regulation.
Offered 2ea of 1set as a standard in 5,000AF "C" frame.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
Lifting lug - UANS AL 2EA/SET (Supplied as standard only for C frame) Outside of ACB body & cradle

| Dummy ACB |
The dummy ACB which is a frame to apply electric current can conduct
ACBs function temporarily when the maintenance work takes long due to
malfunction.
When connecting the dummy ACB please check the primary power is out
since the CB is close.
The early stage of each frame is maximum rated current.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
- UANS DUA3 A frame, 630-2,000A, 3P
- UANS DUA4 A frame, 630-2,000A, 4P
- UANS DUB3 B frame, 630-4,000A, 3P Outside of ACB body
Dummy ACB
- UANS DUB4 B frame, 630-4,000A, 4P & cradle
- UANS DUC3 C frame, 3,200-5,000A, 3P
- UANS DUC4 C frame, 3,200-5,000A, 4P

46
ACB

| Mechanical interlock kit |


It is used to interlock closing and trip between two or
three breakers mechanically so as to prevent unintended
operation at the same time.
The MI is a safety gear installed in ACB for distribution line
and it creates a mechanical interlock between two or three
circuit-breakers through each CBs open/close work.
To operate the MI every component linked to the MI unit
and the MI must be combined before use.
MI unit is separate product. After installing ACB it is
additionally attached.
When ordering B0 all components linked to the MI unit
are provided.
Order other separate kits when having purchased only
ACB without B0.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
- UANS DWB1 for draw-out type, 2way interlock
- UANS DWB2 for draw-out type, 3way interlock
Mechanical - UANS FAWB1 for A/C frame, fixed type, 2way interlock Outside of ACB body
interlock kit - UANS FAWB2 for A/C frame, fixed type, 3way interlock & cradle
- UANS FBWB1 for B frame, fixed type, 2way interlock
- UANS FBWB2 for B frame, fixed type, 3way interlock
- UANS DWB1A for A frame, draw-out type, 2way interlock
- UANS DWB2A for A frame, draw-out type, 3way interlock
- UANS DWB1B for B frame, draw-out type, 2way interlock
- UANS DWB2B for B frame, draw-out type, 3way interlock
Interlock kit:
- UANS DWB1C for C frame, draw-out type, 2way interlock
Mechanical outside of ACB body
interlock kit - UANS DWB2C for C frame, draw-out type, 3way interlock or cradle
& ACB internal - UANS FWB1A for A frame, fixed type, 2way interlock
interlock part Interlock part:
- UANS FWB2A for A frame, fixed type, 3way interlock
inside of ACB body
- UANS FWB1B for B frame, fixed type, 2way interlock
- UANS FWB2B for B frame, fixed type, wire type, 3way interlock
- UANS FWB1C for C frame, fixed type, wire type, 2way interlock
- UANS FWB2C for C frame, fixed type, wire type, 3way interlock

U-Series Air Circuit Breaker_ 47


U-Series / Air Circuit Breaker

Accessories

| Terminal busbar |
Standard connection U-Series ACB have the following front types:
Vertical Horizontal Front Vertical, horizontal, top vertical-bottom
horizontal and top horizontal-bottom vertical
type. There are also P-types which have no
terminal cradle and fixed body type. For these
models (P and fixed body type) separate
terminal is additionally supplied.
Separate terminal is applicable for only
A-frame 630-1,600[A] and B-frame
Mixed connection (Top/Bottom) 2,000- 3,200[A].
Vertical/Horizontal Horizontal/Vertical Vertical/Front

Horizontal/Front Front/Vertical Front/Horizontal

Ordering code

Ordering code Application


Mounting
Item Complete parts Specification
Spare part UAN UAS position
of ACB/Cradle
- UANS HVA3 Horizontal/Vertical type 6EA for A frame, 630-1,600A, 3P
- UANS HVA4 Horizontal/Vertical type 8EA for A frame, 630-1,600A, 4P Outside of
Terminal
ACB body &
busbar - UANS HVB3 Horizontal/Vertical type 6EA for B frame, 630-3,200A, 3P
cradle
- UANS HVB4 Horizontal/Vertical type 8EA for B frame, 630-3,200A, 4P
- UANS FRA3F Front type 6EA for A frame, 630-1,600A, 3P
- UANS FRA4F Front type 8EA for A frame, 630-1,600A, 4P
- UANS FRB3F Front type 6EA for B frame, 2,000-3,200A, 3P
Terminal - UANS FRB4F Front type 8EA for B frame, 2,000-3,200A, 4P Outside of
busbar ACB body &
for fixed type - UANS FHVA3F Front type 3EA & Horizontal/Vertical type 3EA for A frame, 630-1,600A, 3P
cradle
- UANS FHVA4F Front type 4EA & Horizontal/Vertical type 4EA for A frame, 630-1,600A, 4P
- UANS FHVB3F Front type 3EA & Horizontal/Vertical type 3EA for B frame, 630-3,200A, 3P
- UANS FHVB4F Front type 4EA & Horizontal/Vertical type 4EA for B frame, 630-3,200A, 4P
- UANS FRA3 Front type 6EA for A frame, 630-1,600A, 3P
- UANS FRA4 Front type 8EA for A frame, 630-1,600A, 4P
Terminal - UANS FRB3 Front type 6EA for B frame, 2,000-3,200A, 3P
Outside of
busbar - UANS FRB4 Front type 8EA for B frame, 2,000-3,200A, 4P
ACB body &
for draw-out - UANS FHVA3 Front type 3EA & Horizontal/Vertical type 3EA for A frame, 630-1,600A, 3P
cradle
type - UANS FHVA4 Front type 4EA & Horizontal/Vertical type 4EA for A frame, 630-1,600A, 4P
- UANS FHVB3 Front type 3EA & Horizontal/Vertical type 3EA for B frame, 630-3,200A, 3P
- UANS FHVB4 Front type 4EA & Horizontal/Vertical type 4EA for B frame, 630-3,200A, 4P

48
ACB

| Phase insulation barrier |


Phase insulation barrier prevents the
arc which may arise and result in
short-circuit between phase in
advance.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
Phase insulation - UANS 3PBAR for 3P Terminal side of ACB body &
barrier - UANS 4PBAR for 4P cradle

| ON/OFF button lock |


Prevents manual operation of ACB's
closing/tripping button due to user's
wrong handling.
It is not possible to handle on/off
operation under the "Button lock"
status.
Padlock is in not included, key lock
size: 5-8

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
ON/OFF button lock AM UANS AM ON/OFF button cover with padlock hole Outside of ACB body & cradle

U-Series Air Circuit Breaker_ 49


U-Series / Air Circuit Breaker

Accessories

| OCR portable checker |


UAN portable checker tests for the operation of UAN OCR
(Long time/Short time delay/Instantaneous/Ground fault).
It is possible to set current level, phases, and frequency for
OCRs test.
All testing factors are adjustable through front monitor and
you can check operating time.
Battery equipped inside (Available without external power
source).
Ordering code: UANS OC (Spare part)

C
 onnection diagram

Item Specifications

Input: AC/DC100-200V, 50/60Hz


External power
Output: DC24V, 2.5A

Battery Alkaline 9V: 3EA


Trip time measurement 0-999,999sec
Test output 03Ict - 17Ict
Output precision 20% (1Ict - 17Ict)
Size (H x W x D) 193mm x 111mm x 45mm

K
 ey Pad E
 xternals

OCRTEST POWER S/W

110.60


HIPDS-D



193.40

UP DOWN FUNC. ENTER

START STOP




DC24V
44.60

Number Button Function Number Button Function


1 UP Move menu and increasing setpoint 1 LCD Menu, setting current, trip time
2 DOWN Move menu and decrease setpoint 2 Key pad Move menu and setting
3 FUNC Move to the previous menu and return to the setup screen 3 Signal output terminal OCR connection terminals
4 ENTER Save the settings and move the number of digits of setting current 4 Power switch On/Off
5 START Waveform occurrence 5 Terminal Control terminal of checker
6 STOP Waveform stop

50
ACB

| Key lock device |


The key lock prevents the circuit breaker closing, it
maintains interlock condition (Mechanical prevention).
When the key has been unlocked you can operate spring
changing/manual on or off, when the key is removed from
circuit breaker it becomes interlock. The key doesnt turn
to lock position until user push the off button, when the
key is locked.
Ordering code: AB, UANS AB (Spare part)

| Key interlock |
Configure the system with three breaker mounted key lock device. Only two breakers are possible to input with 2EA key, and
the other breaker can supply stable load with interlocking.

ACB 3 is interlocked ACB 2 is interlocked ACB 1 is interlocked


Power 1 Power 2 Power 1 Power 2 Power 1 Power 2
ACB 1 ACB 2 ACB 1 ACB 2 ACB 1 ACB 2

Bus-tie Bus-tie Bus-tie


ACB 3 ACB 3 ACB 3

Load 1 Load 2 Load 1 Load 2 Load 1 Load 2

U-Series Air Circuit Breaker_ 51


U-Series / Air Circuit Breaker

Accessories

| Wrong insertion preventer |


When the main body of ACB is inserted to the
cradle if the ratings of ACB do not match with
cradle it mechanically prevents ACB from
being inserted into cradle of ACB.
Each part will have been installed on body or
cradle.
This device is set by CT rated current.
Ordering code: AW (Attachment)
UANS AW (Accessory only)
Add each ordering cade to both body and
cradle code.

M
 ounting position according to rated current

Mounting position Mounting position


CT CT
Cradle ACB Cradle ACB
0 = Without OCR ADEG 236 K = 1,250A ABCF 457
I = 80A AEFG 234 L = 1,600A ABCE 467
B = 160A ADFG 235 M = 2,000A ABCD 567
O = 200A ADEF 237 N = 2,500A BCDE 167
V = 320A ABEF 347 P = 3,200A BCDF 157
E = 400A ABDG 356 Q = 4,000A BCDG 156
T = 630A ABDF 357 S = 5,000A BCEF 147
H = 800A ABDE 367 X = 6,300A ABEG 346
J =1,000A ABCG 456
1 A
2 B
3 C
4 D
1 A
5 E
M
 ounting position according to rated current
2 B
3
4
C 6 F
5 E
D
7 G
6 F
7 G

1 A
1 2 A B
3 2 C B
4 D 1 A
3 C 2 B
1 A
5 4 E D
2 B
6 F 3 C
1 3
2 4
A C
5 E 4 D
3 5 C E
B D
7 6 G F
4 6 D F
1 A
5 E
5 7 E G 3
2
C
B
7 G 6 F
6 F 4
7 G 5 E
D
7 G
6 F
7 G

52
ACB

| OCR & Alarm switch reset |


When a circuit breaker tripped by fault current or over load
and only if the circuit breaker has been tripped by OCR, the
MRB operates interlock and resets the interlock to restore
electric lines after fault factors have been removed. -(BR)
When the CB is tripped by OCR it provides functions of
interlocking above mechanism -(BR) and output contacts
(2a) which check operation of CB by OCR as well. The
output contact displays OCR operation by long time, short
time delay, instantaneous and ground fault. And resetting
above mechanism occurs. -(BA)
Except above functions when emergent restoration of
electric load is needed it automatically reset itself to get
ready to open immediately after trip and reset only output
contacts. (BM)
It will have been installed when the product is out. Add BR/
BA/BM on your order.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
OCR & BR UANS BR for OCR manual reset only
Alarm switch reset BA UANS BA for OCR manual reset & alarm switch reset Inside of ACB body
device BM UANS BM for OCR auto reset & alarm switch reset

U-Series Air Circuit Breaker_ 53


U-Series / Air Circuit Breaker

Accessories

| Safety shutter lock |


An automatic safety device to protect the connectors of
main circuit by cutting off dangerous contact from outside
while the breaker is drawn out.
Shutter lock is a locking device which prevents safety
shutter from being opened when it is closed. (Key lock is
not included. Size is 5-8)

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
UANS AEA3 for A frame, 630-2,000A, 3P
UANS AEA4 for A frame, 630-2,000A, 4P
UANS AEB3 for B frame, 630-4,000A, 3P
Safety shutter lock AE Inside of cradle
UANS AEB4 for B frame, 630-4,000A, 4P
UANS AEC3 for C frame, 3,200-5,000A, 3P
UANS AEC4 for C frame, 3,200-5,000A, 4P

54
ACB

| Arc shield |
Arc which may arise while breaking fault current is
extinguished first by arc chute in main body of circuit
breaker and then completely extinguished by arc cover.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
UANS AXA3 for A frame, 630-2,000A, 3P
UANS AXA4 for A frame, 630-2,000A, 3P
UANS AXB3 for B frame, 630-4,000A, 3P Upper side of
Arc shield AX
UANS AXB4 for B frame, 620-4,000A, 4P cradle
UANS AXC3 for C frame, 3,200-5,000A, 3P
UANS AXC4 for C frame, 3,200-5,000A, 4P

| Control terminal protection cover |


Protects control terminals which are exposed to the
outside, and prevent damage from foreign substances.
Ordering code: BC (In case of auto-connection mode)

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
Control terminal protection cover BC UANS BC for auto connection control terminal Control terminal of cradle

U-Series Air Circuit Breaker_ 55


U-Series / Air Circuit Breaker

Accessories

| Control terminal |
Two types of connecting control power. Auto connection
type which the body connected or isolated from control
power automatically and manual connection type which
the connector is inserted to the body manually.
Fixed type is provided with manual control plug type as
standard.
Draw-out type's ordering code: "A" for auto connection,
"J" for manual control plug type.

Manual connection Auto connection


terminal terminal

O
 rdering code

Ordering code Application


Item Complete parts of Specification Mounting position
Spare part UAN UAS
ACB/Cradle
A UANS CJ Auto connection terminal Inside of ACB body
Control terminal
J UANS MJ Manual connection terminal & cradle

| Short b contact |
A contact which keeps the external control circuit in
normal by auxiliary contact which disconnects AUX "b"
when ACB is moved from connected position to test
position.
The number of "Shorting "b" contact" corresponds to the
number of AUX "b" (5b).
Ordering code: AK, UANS AK (Spare part)

ACB operating
ACB close ACB open
ACB position (AUX b off) (AUX b on)
Off On
Connected position
(Short b off) AUX "b" Short "b" AUX "b" Short "b"

Off On
Test position
(Short b on) AUX "b" Short "b" AUX "b" Short "b"

56
ACB

| Fixing block |
The fixing block can reinforce safety gear to prevent
malfunction from vibration.
Able to strengthen bodies, cradles, and panel supporter
together.
It will have been installed when the product is out.
Add AF on main body of ACB and cradles order
respectively.

O
 rdering code

Ordering code Application


Item Complete parts of Specification Mounting position
Spare part UAN UAS
ACB/Cradle
UANS AF for ACB body and cradle
Outside of ACB body
Fixing block AF UANS AFB for ACB body
& cradle
UANS AFC for cradle

| Counter |
Displays the total number of on/off operation of ACB
The counter displays the total number of on/off operation
of ACB.
Extra order is unnecessary (It is a primary component of
UAN/UAS).
Ordering code: UANS AD (Spare part)

U-Series Air Circuit Breaker_ 57


U-Series / Air Circuit Breaker

Accessories

| Remote operation & Temparature detection module |


Installed on the cradle or inside of panel, and
communicates with Modbus/RS-485 basically.
Needs to be purchased separately and can be operated
with temperature alarm unit at the same time.
Please refer to page 59 for temperature sensor.
Temperature alarm unit is a device to show the busbar's
temperature through a sensor inside of ACB.
Temperature sensor can be installed up to 3 and alarm
can occur when it reaches the specified temperature.
Display the maximum temperature on the segment LED
and transmits through a network.
Communicates with modbus/RS-485 basically, and needs
to be purchased separately.
Installed on the cradle or inside of panel, and can be
operated with remote closing & trip unit at the same time.

C
 ontact specification

Division Range of application


Contact ratings 10A 240VAC, 30VDC
ACB control
Max switching power 2,400VA, 300W

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
- UANS RTU Temperature detection module
- UANS RTUN Temperature detection module with temperature sensor Module: outside of
Remote operation - UANS RCU Remote operation module ACB body or cradle
& temperature
detection module - UANS RCTU Remote operation & temperature detection module Sensor: inside of
Remote operation & temperature detection cradle
- UANS RCTUN
module with temperature sensor

58
ACB

| Temperature sensor |
The RCTU is used with temperature sensor installed
inside of the ACB.
The temperature sensor is installed in designated
position. However user can change the position to
applicable extra site.

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
Temperature sensor - UANS TSN Temperature sensor Inside of cradle

U-Series Air Circuit Breaker_ 59


U-Series / Air Circuit Breaker

Accessories

| Draw-in/out device unit & Position lock device |


Draw-in/out device unit is mounted on the body of draw
type ACB as standard.
Draw-in/out device unit consists of draw-in/out handle
storage space, push button, position indicator, pad lock.
Position pad lock is a safety device as locking draw-in/out
function in connected/test/sol position.
This device is offered as standard except key lock.
Available key lock size: 5-8
Ordering code: UANS DR (Spare part)

| Draw-in/out handle |
Draw-in/out handle is attached on the side of cradle as
standard.
Ordering code: UANS L handle or UANS U handle

UANS L handle

UANS U handle

O
 rdering code

Ordering code Application


Item Complete parts of Specification Mounting position
Spare part UAN UAS
ACB/Cradle
- UANS HANDLE Standard type
Draw-in/out
- UANS LHANDLE Long type -
handle
- UANS UHANDLE Universal joint type

60
ACB

| Neutral CT |
The NCT is additionally applied for 3-pole circuit breaker
when it is connected to distribution line (3 phases 4 lines).
For distribution line (3 phases 4 lines) 3pole circuit
breaker can protect the ground fault however, we can not
classify unbalanced load and ground fault. To complement
this when only a ground fault occurs the NCT senses the
N phase load and operates the GFT.
When connecting a relay or electric instrument checking
phase is mandatory. Please connect the designated
terminal.
It is a separate product. Refer to the table below (Rated
current level) and check the item on your order.

O
 rdering code

Ordering code Application


Item Complete parts of Specification Mounting position
Spare part UAN UAS
ACB/Cradle
- UANS NCTAT for A frame, 630A
- UANS NCTAH for A frame, 800A
- UANS NCTAJ for A frame, 1,000A
- UANS NCTAK for A frame, 1,250A
- UANS NCTAL for A frame, 1,600A
Neutral CT - UANS NCTBM for B frame, 2,000A -
- UANS NCTBN for B frame, 2,500A
- UANS NCTBP for B frame, 3,200A
- UANS NCTBQ for B frame, 4,000A
- UANS NCTCQ for C frame, 4,000A
- UANS NCTCS for C frame, 5,000A

630-2,000A 2,500-4,000A 4,000-5,000A


150 W

K 4- 4-
1 1
0 4 4
8
175

Sec. M5 5 0
13 20
300
240

300
300
240

300
97


25

80
107 100
75 SUS 2T
30
30

30 240 40 30 240 40
17.5

300 300
10

U-Series Air Circuit Breaker_ 61


U-Series / Air Circuit Breaker

Accessories

| Door flange |
Protects the protruding front of ACB and the cutting
side of panel door by attaching it to the panel door.
Both fixed/draw-out type are the same size of the
panel cutting, even if the dust cover is installed.
Refer to dimension for panel cutting size.
Protection rating of IP30.

Panel door cutting dimensions

292
103.5 100 103.5 R5
4-

122.5
Door flange

345
115
Panel door

4
-

122.5
12

7.5
Bottom
7.5

25.6
O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
Door flange - UANS AG for IP30 Panel door

| Dust cover |
A protective cover which completely protects the
292
103.5 100
front
103.5
panelR5 of ACB from dust and moisture, with a
4-
protection rating of IP54.
Locks the cover in the test or connected position.
122.5

Refer to dimension for panel cutting size.


345
115
4
-

122.5
12

7.5

292
Bottom 103.5 100 103.5 R5
4-
7.5
25.6

122.5
345
115

O
 rdering code
4
-

122.5
12

7.5

Ordering code Application


Item Complete parts Specification
Bottom Mounting position
Spare part 7.5 UAN UAS
25.6

of ACB/Cradle
Dust cover - UANS DC for IP52 -

62
ACB

| Automatic transfer switch & Controller |

Features

Stable transfer system


Provides definite protection for electric power system by
using Hyudai ACB which has the highest breaking capacity.
4
An unmanned woking system
An unmanned automatically transfering system is realized
by installing auto power control device to the ACB with
mechanic interlock device.
Various mode
Offers four selection modes for user's convenience.
Multi protection device
ACB1 Multi protection device installed in ACB has various
3
protecting functions such as self-monitoring, simple set
up. Unlike existing ATS, it has overload protection to offer
stable use.
Compact size Light weight
ACB is more compact and lighter. It is easily installed in
switchgear and occupies less space.
ATS configuration and interlock
- ACB1: "Normal" power (First order side, UN)
3 ACB2 - ACB2: "Stand-by" power (Power generator side, UR)
- 3 : Mechanical interlock device unit
- 4 : ATS unit
Each ACB should meet the following specifications.
- Mechanism of geared motor
- SHT
- LRC
- Overload or short protection device
Interlock conditions
ACB1 ACB2
Open Open
Close Open
Open Close

ACB1 ACB2

O
 rdering code

Ordering code Application


Item Complete parts Specification Mounting position
Spare part UAN UAS
of ACB/Cradle
ATS controller - UANS ATS Automatic transfer switch & controller -

U-Series Air Circuit Breaker_ 63


U-Series / Air Circuit Breaker

Accessories

| Automatic transfer switch & Controller |

Description of mode

Stop mode
Time delay State display of controller
This mode is for compulsory trip of ACB1 (Electric power
t1: 0.1-30sec
company) or ACB2 (Power station) when UN (Power supply of On, Off, Fault
t2: 0.1-240sec
electric power company) or UR (Power supply of power
station) is available.
220/240V 50/60Hz 2 4 t1
Auto mode N UN R UR N UN=0
1
0.5
8
15
0.1 30
This mode is for transferring a circuit breaker automatically
On/I On/I
to available power supply of UN or UR. 0.5s 0.5s
Off/0 Off/0
N mode t2 15 30
8 60
This mode is for compulsory closing of ACB1 when UN is 4 120
Fault Fault 0.1 240 UN=I R
available.
Reset
R mode Stop Auto
Manu
This mode is for compulsory closing of ACB2 during the use
of UR regardless of that UN is available or not.
N R

Operation characteristic

UN or KT

UR

KR

QN

QR

0.1 - 30s 500 250 0.1 - 240s 500 250

T1(ms) T2(ms)

UN: Normal KR: Re-checking : On/Off


UR: Stand-by QN: Normal
KT: Stand-by QR: Stand-by

64
ACB

System operation

Stop mode Auto mode N mode


(Normal power ON compulsory)

N R
4-position switch
ACB1 / ACB2 Normal
Off (N, UN supplied)
Trip manually On
I O
ACB2 Trip
Auto mode UN loss above +1 or received
auto-switching command

t0.5s
ACB1 Trip
Reset 1sec

ACB1 Input
t0.5s
Reset end
Stand- ACB1 closed
ACB2 Input
by ON
NR
Operation stop
ACB2 Input
N R I O
4-position switch

I O
UN exist during t t2 or stop
auto-switching command R mode
("Stand-by" ON compulsory)
ACB2 Trip

4-position switch
t0.5s
(N, UN supplied)

ACB1 Input ACB1 Trip

ACB1 Input t0.5s

ACB2 Input

ACB2 Input
N R

ACB1 : UAN(S) ACB1


Normal(UN)
ACB2 : UAN(S) ACB2 I O
Stand-by(UR)
UN : Normal 4-position switch
UR : Stand-by

U-Series Air Circuit Breaker_ 65


U-Series / Air Circuit Breaker

Accessories

| Automatic transfer switch & Controller |

Description of mode [ UAN, UAS type ]

Circuit diagram of ATS auxilliary device


ACB1, Normal UN
1
1
Stop
2 1
Control circuit terminal block

Control circuit terminal block


UN on 1
3 2
UR on 2
4 3
Auto 7
5 4
Common 3
6 5
54 5343 26 7 1 3
7 6
26
Communi- 8 7
cation 53
9 8 Spring
43 charge
10

B1
A1

A1
offSW.

Aux. SW.
1
Control circuit terminal block

1
1 2 TC M CC
Control circuit terminal block

Common 2
2 3
Stop 7

OCR Alarm SW.


3 4
UN on Mode Aux. Switch 3
4 5
UR on 54 Aux. SW.
5 6
Auto 26
7
53
8
43
5444 24 8 2 4

1 Standard model is equipped switch on the controller (Control terminal type is not standard model).

Wiring diagram of ATS with applied two ACBs

UN UR 20
1
19
3
18
7
17
19
T 16
20
15
ATS Terminal block

26
14
24
13
R S T R S T 45
12
UN UR 46
11
MCCB MCCB 47
10
48
9
55
Controller IVE 56
8
7
N R 57
6
58
5
4
3
2
1

1 20
3 19
18
7
17
19
16
20
15
ATS Terminal block

26
14
24
13
45
12
46
11
47
10
48
9
55
UN ACB 56
8
7
57
6
58
5
4
3
2
UR ACB 1

66
ACB

ACB2, Stand-by UR

26 24 OCR DO
43 44 Aux. switch a
53 43 26 7 1 3
53 54 Aux. switch b

Spring TC Voltage trip


Charge
B1
A1

A1

7 8 Shunt trip power terminals


Aux. SW.

OFFSW.

1 2 Spring charge power terminals


3 4 Close power terminals
TC M CC
M Charging motor
OCR Alarm SW.

CC Latch release (Close)


Aux. SW.

54 44 24 8 2 4

Wiring diagram of ATS panel remote

1
PB(Close) Do not supply power, ATS
3
ATS controller UN Normal 7
PB(Open) controller is power ON.1)
control voltage (AC220V) ACB 19 OCR control ACDC100-250 S0-S2
ATS Terminal block

20 terminal
N R 26
24 OCR+OCGR 1acontact
45
46
47
48 Aux. SW. 2a-2b
55
56
57
58

1
PB(Close)
Do not supply power, ATS
Stand-by 3
PB(Open) controller is power ON.1)
7
ACB 19 OCR control
ATS Terminal block

20 terminal ACDC100-250 S0-S2


26
OCR+OCGR 1acontact
24
45
46
47
ATS controller UR 48 Aux. SW. 2a-2b
control voltage (AC220V) 55
56
57
58

1) Do not supply additional control power in case of operating remote, open/close power is supplied from ATS controller (Terminal No. 1, 7, 16).

U-Series Air Circuit Breaker_ 67


U-Series / Air Circuit Breaker

Accessories

| Automatic transfer switch & Controller |

Dimensions
(unit: mm)

UAN(S)06-16 A frame
[ UAN(S)06-16 A, Front ] [ UAN(S)06-16 A, Vertical type ] [ UAN(S)06-16 A, Horizontal type]
40 470
89 220 89
27.5

20.5 128 36 154


245

46.3
46.3
39.9 79 39.9 79

50 94.1 50

15

159.1
343
20.1

15
1810

420.9

455.9
1440
615

50 94.1 50

15

159.1
343
20.1

15
357.05

374.55
250

107 296 50 235 50 235


560 335 335
600 435 435

UAN20 A frame
[ UAN20 A, Front ] [ UAN20 A, Vertical type ]
40 89
27.5

128 36 154
20.5
245

46.3
39.9 79
75 69.1 75
343
20.1
1810

395.9
1440

615

75 69.1 75
343
20.1

344.6
250

107 296 50 235


560 335
600 435

68
ACB

(unit: mm)

UAN(S)20-25 B frame
[ UAN(S)20-25 B, Front ] [ UAN(S)20-25 B, Vertical type ] [ UAN(S)20-25 B, Horizontal type ]
140
40 89 89
27.5

128 36 154
20.5
245

39.9 79 48.3 39.9 79 48.3

75 68.1 75

20 20
163.1
343
20.1
1810

396.9

451.9
1440
615

75 68.1 75

163.1
20 20
343
20.1

345.05

372.55
250

154.7 296 50 235 50 235


660 335 335
700 435 435

UAN32 B frame
[ UAN32 B, Front ] [ UAN32 B, Vertical type ] [ UAN32 B, Horizontal type ]
140
40 89 89
27.5

128 36 154
20.5
245

39.9 79 48.3 39.9 79 48.3


20
90 53.1 90

123.1
343

20
20.1
1810

615
381.9
1440
615

20
90 53.1 90

163.1
343

20
20.1

372.55
337.55
250

154.7 296 50 235 50 235


660 335 335
700 435 435

U-Series Air Circuit Breaker_ 69


U-Series / Air Circuit Breaker

Accessories

| Automatic transfer switch & Controller |

Dimensions
(unit: mm)

UAN40 B frame
[ UAN40 B, Front ] [ UAN40 B, Vertical type ] [ UAN40 B, Horizontal type ]
140
40
27.5

128 36 154 89 89
20.5
245

39.9 79 90.3 39.9 64.3


79

15
125

40 128 40
15
343

68

15
125
20.1

15
1810

407
297
1440

15
615

68 125

128 40
15
343

15

40
125
20.1

15

362.55
295.05
250

154.7 296 50 235 50 235


660 335 335
700 435 435

70
ACB

(unit: mm)

UAN40-50 C frame, 3P
[ UAN40-50 C, 3P, Front ] [ UAN40-50 C, 3P, Vertical type ] [ UAN40-50 C, 3P, Horizontal type ]
240
40 89 89
128 36 154
27.5

20.5
245

39.9 79 39.9 79 66.3


66.3

20
110 86.1 110
125 69.1 125

20
343

20
20
20.1
1810

295.9

308.9
1440

615

20
110 86.1 110
125 69.1 125

20
343

20
20
20.1

301.1
294.5
250

415.2 296 50 235 50 235


760 335 335
800 435 435

UAN40-50 C frame, 4P
[ UAN40-50 C, 4P, Front ] [ UAN40-50 C, 4P, Vertical type ] [ UAN40-50 C, 4P, Horizontal type ]
440
40 128 36 154 89 89
27.5

20.5
245

39.9 79 66.3 39.9 79 66.3


125 69.1 125

110 86.1 110


20
20
343

20
20
20.1
1810

295.9

308.9
1440
615

125 69.1 125

110 86.1 110


20
20
343

20
20
20.1

301.1
294.5
250

500.2 296 50 235 50 235


960 335 335
1000 435 435

U-Series Air Circuit Breaker_ 71


U-Series / Air Circuit Breaker

Circuit Diagrams

Main circuit Protection trip relay Spring charge Closing


Motor switch coil

ZSI
NCT In Out PB
(Close)

Spring
charge
off SW.

UPR-2L-GS
Protection trip relay

NCT In Out
ZSI

S
 ymbol description

CT Current transformer 1 2 Charging motor (M) source power


L LTD (Long-time delay) terminal 3 4 Closing coil (CC) source power
PT PTA (Pre-trip alarm) terminal 7 8 Open coil (TC) source power
G Ground fault terminal 9 10 UVT coil terminal
S/I STD (Short-time delay ) / INST (Instantaneous) terminal 15 16 Charge complete contact
Ac Common terminal 19 20 OCR source power
NCT Neutral current transformer 22 21 LTD (Long-time delay) contact
ZI Zone selective input 22 23 PTA (Pre-trip alarm) / TEMP (Temperature) contact
ZO Zone selective output 22 24 STD (Short-time delay) / INST (Instantaneous) contact
A/C MCR input terminal 22 26 GFT (Ground-fault trip) / ELT (Earth-leakage trip) contact
Tp / Tn MHT input source 29 30 NCT input terminal
M Charging motor 31 ~ 34 ZSI (Zone selective input)
CC Close coil (Close) 41 ~ 60 AUX contact
TC Trip coil (Open) 61 ~ 93 Position switch
UVT Under voltage trip coil
MHT Magnetic hold trigger Manufacturers wiring
Users wiring
S0 / S2 UPR protection relay source power Disconnecting device (Draw-out type)

72
ACB

Condensor Under voltage


Trip coil Auxiliary switch Position switch
trip trip
PB (Open)
UVT controller
PB (Open)

PB (Open)

Used for short b contact (Option)

Used for TC supervision (Option)

Used for TC supervision (Option)


Used for supervision (Option)
Used for MCR (Option)

C
 ontrol terminal lay-out

OCR Operating Auxiliary switch

Protection trip relay Operating Auxiliary SW


circuit

OCR
OCR Contact
V input

- Protection trip relay -

Operating Auxiliary switch

- Operating circuit - - Auxiliary SW -

U-Series Air Circuit Breaker_ 73


U-Series / Air Circuit Breaker

Dimensions

| UAN06-20/UAS06-16 fixed type (A frame) |


(unit: mm)

Front

296 381
404.4

404.4

270
270
168.7 253.7
337.4 422.4

[ 3P ] [ 4P ]

Vertical terminal connection

85 85 85 85 85
15 15
5

5
186.8
152.5

186.8
152.5

14 14
20

20
109

109

[ 630-1,600A ] [ 2,000A ]

35 13
35 13 3-
2-
50
75
50
50

25

15 15
144
330
144
330

75
50

132
132

33
33

60 49 186.8 60 49 186.8
295.8 43.6 295.8 43.6

A frame 2,000A of UAN fixed type is applicable horizontal terminal only.

74
ACB

(unit: mm)

Horizontal terminal connection


85 85 85 85 85
50 50

5
5
152.5
186.8

152.5
186.8
14 14

20
20
109

109

35 13
2-
15

50
25

15
129
144
330

15
132
33

60 49 186.8
295.8 43. 6

Front terminal connection


85 85 85 85 85
50 50
5

5
152.5

152.5
186.8

186.8

14 14
20

20
109

109

35 13
2-
526

50
25

15
330
33

60 49 186.8
295.8
118

15
252.4

U-Series Air Circuit Breaker_ 75


U-Series / Air Circuit Breaker

Dimensions

| UAN06-20/UAS06-16 draw-out type (A frame) |


(unit: mm)

Front

440 525
416 501
438 (Manual control plug type)

438 (Manual control plug type)


460 (Auto connection type)

460 (Auto connection type)


1 2

1 2
.1

.1
278.3
270 270
164 164 164 249
328 413

[ 3P ] [ 4P ]

Vertical terminal connection

85 85 85 85 85
15 15
28.8

28.8
250

250
368.4

368.4

1 1
4 4

210 59 210 85

[ 630-1,600A ] [ 2,000A ]
(Test) 26.5 60 Arc shield surface (Test) 26.5 60 Arc shield surface
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)

35 13 35 13
119.3 6 2- 119.3 6 3-
50
50

50
75

75
465.8

465.8
25

Fixing block 15 Fixing block 15


144
330

144

(Option) (Option)
330
50

75
132

15
132

13 13 15

50 250 50 250
33.1

33.1
15

15

328.8 328.8
352.8 352.8
39.6 381.6 39.6 381.6
421.2 421.2

A frame 2,000A of UAN fixed type is applicable horizontal terminal only.

76
ACB

(unit: mm)

Horizontal terminal connection


85 85 85 85 85
50 50
28.8

28.8
250

250
368.4

368.4
1 1
4 4

210 59 210 85

(Test) 26.5 60 Arc shield surface


(Isol) 11.5 20.4 (Option)

119.3 6 35 13
2-
15

50
465.8

Fixing block
25
15
129
144

(Option)
330

15
132

13 15

50 250
33.1

15

328.8
352.8
39.6 381.6
421.2

Front terminal connection


85 85 85 85 85
50 50
28.8

28.8
250

250
368.4

368.4

1 1
4 4

210 59 210 85

(Test) 26.5 60
20.4 Arc shield surface
(Isol) 11.5 (Option)

35 13
119.3 6 2-
50
526

25
465.8

Fixing block 15
330

(Option)

328.8
13 15
33.1

39.6 50 250
15
118

329.6 15
352.8

U-Series Air Circuit Breaker_ 77


U-Series / Air Circuit Breaker

Dimensions

| UAN06-32/UAS20-32 fixed type (B frame) |


(unit: mm)

Front

367 482
404.4

404.4

270
270 204.2 319.2
408.4 523.4

[ 3P ] [ 4P ]

Vertical terminal connection

115 115 115 115 115


20 20
5

5
186.8
152.5

186.8
152.5

14 14
20

20
109
109

[ 630-2,500A ] [ 3,200A ]

35 13 35 13
3- 3-
75

50

90
75

50
90

15
144

144
330

330

15
75

90
132

132
33
33

60 49 186.8 60 49 186.8
295.8 43. 6 295.8 43. 6

78
ACB

(unit: mm)

Horizontal terminal connection


Name Detail A
115 115 115 115 115 UAN06-25 75
A A
UAN32 90
5

5
186.8
152.5

186.8
152.5
14 14
20

20
109

109

[ 630~2,500A ] [ 3,200A ]

35 13 35 13
3- 3-
50
75

90
50
15
330

144
15
330

144

20
20

132
132
33

33

60 49 186.8 60 49 186.8
295.8 43.6 295.8 43. 6

Front terminal connection


115 115 115 115 115
75 75
5

5
152.5

152.5
186.8

186.8

14 14
20

20
109

109

35 13
3-
75
50
644

15
330
33

60 49 186.8
118

295.8

20
257.4

U-Series Air Circuit Breaker_ 79


U-Series / Air Circuit Breaker

Dimensions

| UAN06-32/UAS20-32 draw-out type (B frame) |


(unit: mm)

Front

511 626
487 602

438 (Manual control plug type)


438 (Manual control plug type)

460 (Auto connection type)


460 (Auto connection type)

1 2

1 2
.1

.1
278.3
278.3

270 270
199.5 199.5 199.5 314.5
399 514

[ 3P ] [ 4P ]

Vertical terminal connection

115 115 115 115 115


20 20
28.8
28.8

250
250

368.4
368.4

1 1
4 4

210 94.5 210 115

[ 630-2,500A ] [ 3,200A ]
(Test) 26.5 60 (Test) 26.5 60
Arc shield surface Arc shield surface
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)

35 13
35 13 3-
119.3 6 3- 119.3 6
90

90
50
75

75
50

465.8
465.8

Fixing block Fixing block


143
330

15
330

(Option) (Option)
143

15
90
75

132.5
132.5

13 15 13 15

50 250 50 250
33.1

15

15
33.1

328.8 328.8
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2

80
ACB

(unit: mm)

Horizontal terminal connection


Name Detail A
115 115 115 115 115
A A UAN06-25 75
28.8

28.8
UAN32 90
250

250
368. 4

368. 4
1 1
4 4

210 94.5 210 115

[ 630-2,500A ] [ 3,200A ]
(Test) 26.5 60 (Test) 26.5 60
Arc shield surface Arc shield surface
(Isol) 11.5 20.4 (Option) (Isol) 11.5 20.4 (Option)

35 13 35 13
119.3 6 3- 119.3 6 3-

20
20

50
75

50
90
465.8

465.8
Fixing block Fixing block
15

143
124
330

330

(Option)
143
124

(Option) 15
20

20
132.5
132.5

13 15 13 15

50 250
33.1

33.1

50 250
15

15
328.8 328.8
352.8 352.8
39.6 383.6 39.6 383.6
423.2 423.2

Front terminal connection


115 115 115 115 115
75 75
28.8

28.8
250

250
368.4

368.4

1 1
4 4

210 94.5 210 115

(Test) 26.5 60
20.4 Arc shield surface
(Isol) 11.5 (Option)

35 13
119.3 6 3-
525.5
465.8

50
75

Fixing block
330

(Option) 15

328.8
13 15
33.1

50 250
15

39.6
117.5

329.6 20
352.8

U-Series Air Circuit Breaker_ 81


U-Series / Air Circuit Breaker

Dimensions

| UAN40 fixed type (B frame) |


(unit: mm)

Front

367 482
404.4

404.4

270
270
204.2 319.2
408.4 523.4

[ 3P ] [ 4P ]

Vertical terminal connection

152.5 152.5 140 140 140


15 10 15 15 10 15
5
5

186.8
152.5
186.8
152.5

14 14
20
20

109
109

35 13
5-
25*4=100
125

125
330

169
44

15
125
119.5
57
33

60 49 186.8
295.8 87

82
ACB

(unit: mm)

Horizontal terminal connection

405 520
152.5 152.5 140 140 140
100 100

5
5

186.8
152.5
186.8
152.5

14 14
20

20
109

109

3
35 1
3-
25*3=75
100
40
330

144

15
15
10
15

132
33

60 49 186.8
295.8 58.6

U-Series Air Circuit Breaker_ 83


U-Series / Air Circuit Breaker

Dimensions

| UAN40 draw-out type (B frame) |


(unit: mm)

Front

511 626
487 602

438 (Manual control plug type)


438 (Manual control plug type)

460 (Auto connection type)


460 (Auto connection type)

1 2

1 2
.1

.1
278.3

278.3
270 270
199.5 199.5 199.5 314.5
399 514

[ 3P ] [ 4P ]

Vertical terminal connection

152.5 152.5 140 140 140


15 10 15 15 10 15
28.8

28.8
250

250

368.4
368.4

1 1
4 4

210 94.5 210 115

(Test) 26.5 60
Arc shield surface
(Isol) 11.5 20.4 (Option)

13
35 5-

119.3 6
25*4=100
125
125

465.8

Fixing block 15
330

193
68

(Option)
125
107.5

13 15

50 250
33.1

15

328.8
352.8
39.6 425.6
465.2

84
ACB

(unit: mm)

Horizontal terminal connection


405 520
152. 5 152. 5 140 140 140
100 100

28.8
28.8

250
250

368.4

368.4
1 1
4 4

210 94.5 210 115

(Test) 26.5 60
Arc shield surface
(Isol) 11.5 20.4 (Option)

3
1
35 3-
15

119.3 6
25*3=75
10

100
15

465.8

Fixing block 15
168
330

(Option)
40

132.5

13 15

50
33.1

250
15

328.8
352.8
39.6 399.6
439.2

U-Series Air Circuit Breaker_ 85


U-Series / Air Circuit Breaker

Dimensions

| UAN32-50 fixed type (C frame) |


(unit: mm)

Front

592 762
404.4

404.4

270 270
464.7 168.7 549.7 253.7
633.4 803.4

[ 3P ] [ 4P ]

Vertical terminal connection

190.5 190.5 190.5 190.5 190.5


20 70 20 148 20 70 20 148
5

5
186.8
152.5

152.5
186.8
20

20
109

109

13
35 5-
25*4=100
125
125

15
194
69
330

125
107
33

60 49 186.8
44.5

295.8 63.6

86
ACB

(unit: mm)

Horizontal terminal connection

190.5 190.5 190.5 190.5 190.5

148 125 148


5

5
186.8
152.5

152.5
186.8
20

20
109

109

13
35 5-
20

25*4=100
110

125
70
20

15
330

196
86
110
106
51
33

60 49 186.8
295.8 63.6

U-Series Air Circuit Breaker_ 87


U-Series / Air Circuit Breaker

Dimensions

| UAN32-50 draw-out type (C frame) |


(unit: mm)

Front

736 906
712 882
460 (Auto connection type)

460 (Auto connection type)


438 (Manual control plug type)

438 (Manual control plug type)


12

12
.1

.1
278.3

278.3
270 270
460 164 545 249
624 794

Vertical terminal connection

190.5 190.5 190.5 190.5 190.5


20 70 20 148 20 70 20 148
24

12
6
103.8
103.8

368.4
368.4
175

175

4 4
1 1
50

50

460 164 545 249


260 260 345 345

(Test) 26.5 60 Arc shield surface


20.4 (Option)
(Isol) 11.5

13
35 5-

119.3 6
25*4=100
125

125
465.8

Fixing block
(Option) 15
194
330

69
125
107

13 15
44.5

50 175
33.1

15

328.8
352.8
39.6 401.6
441.2

88
ACB

(unit: mm)

Horizontal terminal connection

190.5 190.5 190.5 190.5 190.5


148 125 148

103.8
103.8

368.4
368.4

175
175

4
1
4
1

50
50

460 164 545 249


260 345 345
260

(Test) 26.5 60 Arc shield surface


(Isol) 11.5 20.4 (Option)

13
35 5-
20

119.3 6
25*4=100
110

125
70

465.8

Fixing block
15
20
196

(Option)
330

86
110
106

13 15
51

50 175
33.1

15

328.8
352.8
39.6 401.6
441.2

U-Series Air Circuit Breaker_ 89


A

122.5
U-Series / Air Circuit Breaker

330
345
115

B
4
Dimensions

122.5
12
Rear panel

7.5
(IP30)

C
31
32
25.6

33.1
7.5 4
Panel door
(25) (323)

| UAN/UAS fixed type, panel cutting size - fixed type |

Front Side Rear (IP30)

Operaing
panel center
ACB center
292
R5 A
103.5 100 103.5 4-
122.5

144
330
345
115

B
75
4
-

122.5
12

132
7.5

33
25.6

C
7.5 (95) (188)
Rear panel
Panel door (IP30)

R
 eal panel cutting size

Model A B C

UAN06-20 / UAS06-16 / A frame, 3P 283 355 25


UAN06-20 / UAS06-16 / A frame, 4P 368 355 25

UAN06-40 / UAS20-32 / B frame, 3P 354 355 25

UAN06-40 / UAS20-32 / B frame, 4P 469 355 25

UAN32-50 / C frame, 3P 579 355 25


UAN32-50 / C frame, 4P 749 355 25

90
ACB

| Panel cutting size - draw-out type |

Front Side Rear (IP30)

(Test)26.5 60
Operaing
panel center (Isol)11.5 20.4
292
R5 ACB center
103.5 100 103.5 4-
A
122.5

330
345
115

B
4
-

122.5
12

Rear panel
7.5

(IP30)

C
31
32
25.6

33.1

7.5 4
Panel door
(25) (323)

Operaing
panel center
ACB center
R
 eal panel cutting
292 size R5 A
103.5 100 103.5 4-

Model A B C
122.5

UAN06-20 / UAS06-16 / A frame, 3P 329 268 70


UAN06-20 / UAS06-16 / A frame, 4P 414 268 70
144
330
345
115

UAN06-40 / UAS20-32 / B frame, 3P 400 298 55 B


75
4
-

122.5

UAN06-40 / UAS20-32 / B frame, 4P 515 298 55


12

132
7.5

UAN32-50 / C frame, 3P 625 338 35


33
25.6

7.5 (95) (188)


UAN32-50 / C frame, 4P 795 Rear panel 338 35
Panel door (IP30)

U-Series Air Circuit Breaker_ 91


U-Series / Air Circuit Breaker

Ordering Codes

| UAN type |

ACB body part

UAN 12 A 3 J M2
Frame size &
Type Rated current Pole Terminal connection Motor
pole arrangement
UAN 06 630A 2,000AF, 630-2,000A 3 3 Pole Draw-out type/ M0 Manual type
A
08 800A 3P: RST, 4P: RSTN 4 4 Pole Control terminal connection M1 AC/DC 110V
10 1,000A 2,000AF, 630-2,000A A Auto connection M2 AC/DC 220V
W
12 1,250A 4P: NRST J Manual connection M3 AC380V
16 1,600A 4,000AF, 630-4,000A Fixed type/ M4 AC440V
B
201) 2,000A 3P: RST, 4P: RSTN Terminal busbar arrangement M5 DC24V
25 2,500A 4,000AF, 630-4,000A H Horizontal type M6 DC48V
X
32 3,200A 4P: NRST V Vertical type M7 DC125V
40 4,000A 5,000AF, 3,200-5,000A Line side: Horizontal
C T
3P: RST, 4P: RSTN Load side: Vertical
50 5,000A
Line side: Vertical
L
5,000AF, 3,200-5,000A Load side: Horizontal
Y
4P: NRST P2) Front type or others

Cradle part for draw-out type ACB

DUN 12 A 3 A H AE
Frame size & Control terminal Terminal busbar
Type Rated current Pole Accessories
pole arrangement connection arrangement
DUN 630-1,600A, 3 3 pole H Horizontal type AE Safe shutter lock
16 A 2,000AF, 630-2,000A A
Auto
A frame 3P: RST, 4P: RSTN/NRST 4 4 pole connection V Vertical type AF Fixing block

2,000A, B 4,000AF, 630-4,000A Manual Line side: Horizontal Short "b" contact for auto
20 J T AK
A frame 3P: RST, 4P: RSTN/NRST connection Load side: Vertical connection terminal

25
630-2,500A, C 5,000AF, 3,200-5,000A L
Line side: Vertical
AW
Wrong insertion
B frame 3P: RST, 4P: RSTN/NRST Load side: Horizontal preventer

3,200A, Front type or AX Arc shield


32 P
B frame others
Auto connection
BC
control terminal cover
4,000A,
40
B frame SP Cradle only

3,200-5,000A,
50
C frame

92
ACB

C2 S2 45 K AB
Protection trip relay
Closing coil Trip coil CT3) Accessories
(OCR)
C0 N/A S0 N/A 00 N/A 0 N/A Instantaneous type (UVT coil)4) Double trip coil4)
C1 AC/DC 110V S1 AC/DC 110V General feeder, 50Hz I 80A U1 AC/DC 110V S1 AC/DC 110V
C2 AC/DC 220V S2 AC/DC 220V 33 UPR-1L-GL B 160A U2 AC/DC 220V S2 AC/DC 220V
C3 AC380V S3 AC380V 35 UPR-2L-GS O 200A U3 AC380V S3 AC380V
C4 AC440V S4 AC440V 36 UPR-1D-GT V 320A U4 AC440V S4 AC440V
C7 DC24V S7 DC24V 37 UPR-2L-GM E 400A U7 DC24V S7 DC24V
C8 DC48V S8 DC48V General feeder, 60Hz T 630A U8 DC48V S8 DC48V
C9 DC125V S9 DC125V 43 UPR-1L-GL H 800A U9 DC125V S9 DC125V
45 UPR-2L-GS J 1,000A Time delay type4)
46 UPR-1D-GT K 1,250A (UVT coil with UVT controller) Trip supervision coil5)
47 UPR-2L-GM L 1,600A V1 AC/DC 110V T1 AC/DC 110V
M 2,000A V2 AC/DC 220V T2 AC/DC 220V
Generator, 50Hz N 2,500A V3 AC380V T3 AC380V
38 UPR-1S-AL P 3,200A V4 AC440V T4 AC440V
39 UPR-2S-AS Q 4,000A V7 DC24V T7 DC24V
Generator, 60Hz S 5,000A V8 DC48V T8 DC48V
48 UPR-1S-AL X 6,300A V9 DC125V T9 DC125V
49 UPR-2S-AS
AF Fixing block Position switch8)
AW Wrong insertion preventer AQ Test 1C, Connected 1C
AM ON/OFF button cover AR Connected 2C
Additional 1a1b auxiliary
AA 6)
switch AS Test 2C
AB Key lock device AT Isolated 1C, Inserted 1C
1) Vertical type is the only applicable terminal busbar for A frame, 2,000A. B8 5) OCR MCR function AU Inserted 2C
2) Code P is for user installation, and applicable for A frame, 630-1,600A & B frame
630-3,200A. Please refer to page 48. BR OCR manual reset device AV Isolated 2C
3) CT Application OCR manual reset &
Frame A/W: 80-2,000A BA alarm switch reset device P4 Test 2C, Connected 2C
Frame B/X: 400-4,000A OCR auto reset &
BM alarm switch reset device PS Isolated 1C, Test 1C,
Connected 2C
Frame C/Y: 3,200-5,000A
Internal part for
4) UVT coil and double trip coil cannot be installed at the same time. B07) mechanical interlock PQ Inserted 1C, Isolated 1C,
Test 1C, Connected 1C
5) Standard auxiliary switch of UAN type is 5a5b. Trip supervision coil use 1a1b of
standard auxiliary switch, and OCR MCR function use;1a. B6 Spring charge switch P8 Inserted 2C, Isolated 2C,
Test 2C, Connected 2C
6) Additional 1a1b auxiliary switch and mechanical interlock cannot be installed at
the same time. B7 ATS controller PR Inserted 1C, Isolated 1C,
Test 3C, Connected 3C
7) Mechanical interlock kit can be ordered separately, please refer to page 47.
8) Only one type position switch is selectable. SP ACB body only

U-Series Air Circuit Breaker_ 93


U-Series / Air Circuit Breaker

Ordering Codes

| UAS type |

ACB body part

UAS 12 A 3 J M2
Frame size &
Type Rated current Pole Terminal connection Motor
pole arrangement
UAS 06 630A 2,000AF, 630-2,000A 3 3 Pole Draw-out type/ M0 Manual type
A
08 800A 3P: RST, 4P: RSTN 4 4 Pole Control terminal connection M1 AC/DC 110V
10 1,000A 2,000AF, 630-2,000A A Auto connection M2 AC/DC 220V
W
12 1,250A 4P: NRST J Manual connection M3 AC380V
16 1,600A 4,000AF, 630-4,000A Fixed type/ M4 AC440V
B
201) 2,000A 3P: RST, 4P: RSTN Terminal busbar arrangement M5 DC24V
25 2,500A 4,000AF, 630-4,000A H Horizontal type M6 DC48V
X
32 3,200A 4P: NRST V Vertical type M7 DC125V
Line side: Horizontal
T
Load side: Vertical
Line side: Vertical
L
Load side: Horizontal
P2) Front type or others

Cradle part for draw-out type ACB

DUN 12 A 3 A H AE
Frame size & Control terminal Terminal busbar
Type Rated current Pole Accessories
pole arrangement connection arrangement
DUN 630-1,600A, 3 3 pole H Horizontal type AE Safe shutter lock
16 A 2,000AF, 630-2,000A A
Auto
A frame 3P: RST, 4P: RSTN/NRST 4 4 pole connection V Vertical type AF Fixing block

20
2,000A, B 4,000AF, 630-4,000A J
Manual
T
Line side: Horizontal
AK
Short "b" contact for auto
A frame 3P: RST, 4P: RSTN/NRST connection Load side: Vertical connection terminal

630-2,500A, Line side: Vertical Wrong insertion


25 L AW
B frame Load side: Horizontal preventer

3,200A, Front type or AX Arc shield


32 P
B frame others
Auto connection
BC
control terminal cover
4,000A,
40
B frame SP Cradle only

94
ACB

C2 S2 43 K AB
Protection trip relay
Closing coil Trip coil CT3) Accessories
(OCR)
C0 N/A S0 N/A 00 N/A 0 N/A Instantaneous type (UVT coil)4) Double trip coil4)
C1 AC/DC 110V S1 AC/DC 110V General feeder, 50Hz I 80A U1 AC/DC 110V S1 AC/DC 110V
C2 AC/DC 220V S2 AC/DC 220V 33 UPR-1L-GL B 160A U2 AC/DC 220V S2 AC/DC 220V
C3 AC380V S3 AC380V 35 UPR-2L-GS O 200A U3 AC380V S3 AC380V
C4 AC440V S4 AC440V 37 UPR-2L-GM V 320A U4 AC440V S4 AC440V
C7 DC24V S7 DC24V General feeder, 60Hz E 400A U7 DC24V S7 DC24V
C8 DC48V S8 DC48V 43 UPR-1L-GL T 630A U8 DC48V S8 DC48V
C9 DC125V S9 DC125V 45 UPR-2L-GS H 800A U9 DC125V S9 DC125V
47 UPR-2L-GM J 1,000A Time delay type4)
K 1,250A (UVT coil with UVT controller) Position switch8)
Generator, 50Hz L 1,600A V1 AC/DC 110V AQ Test 1C, Connected 1C
38 UPR-1S-AL M 2,000A V2 AC/DC 220V AR Connected 2C
39 UPR-2S-AS N 2,500A V3 AC380V AS Test 2C
Generator, 60Hz P 3,200A V4 AC440V AT Isolated 1C, Inserted 1C
48 UPR-1S-AL Q 4,000A V7 DC24V AU Inserted 2C
49 UPR-2S-AS S 5,000A V8 DC48V AV Isolated 2C
X 6,300A V9 DC125V P4 Test 2C, Connected 2C
PS Isolated 1C, Test 1C,
Connected 2C

AF Fixing block PQ Inserted 1C, Isolated 1C,


Test 1C, Connected 1C
AW Wrong insertion preventer P8 Inserted 2C, Isolated 2C,
Test 2C, Connected 2C
AM ON/OFF button cover PR Inserted 1C, Isolated 1C,
Test 3C, Connected 3C

AA6) Additional
switch
1a1b auxiliary

1) Vertical type is the only applicable terminal busbar for A frame, 2,000A. AB Key lock device
2) Code P is for user installation, and applicable for A frame, 630-1,600A & B frame
630-3,200A. Please refer to page 48.
B8 5) OCR MCR function
3) CT Application
BR OCR manual reset device
Frame A/W: 80-2,000A
Frame B/X: 400-4,000A OCR manual reset &
BA alarm switch reset device
Frame C/Y: 3,200-5,000A
OCR auto reset &
4) UVT coil and double trip coil cannot be installed at the same time. BM alarm switch reset device
5) Standard auxiliary switch of UAN type is 5a5b. Trip supervision coil use 1a1b of
Internal part for
standard auxiliary switch, and OCR MCR function use;1a. B07) mechanical interlock
6) Additional 1a1b auxiliary switch and mechanical interlock cannot be installed at
the same time. B6 Spring charge switch
7) Mechanical interlock kit can be ordered separately, please refer to page 47.
8) Only one type position switch is selectable.
SP ACB body only

U-Series Air Circuit Breaker_ 95


U-Series / Air Circuit Breaker

Technical Data

| Internal resistance and power consumption |

Fixed type Draw-out type


AF Rated current(A)
Internal resistance() Power consumption (W/3Phase) Internal resistance() Power consumption (W/3Phase)
630 20 24 40 48
800 20 38 40 77
UAN/UAS06-16 A frame 1,000 20 60 40 120
1,250 20 94 40 188
1,600 20 154 40 307
630 15 18 30 36
800 15 29 30 58
1,000 15 45 30 90
UAN20 A frame
1,250 15 70 30 141
1,600 15 115 30 230
2,000 13 156 27 324
2,000 10 120 20 240
UAN/UAS20-32 B frame 2,500 10 188 20 375
3,200 10 307 20 614
2,000 10 120 20 240
2,500 10 188 20 375
B frame UAN 40B
3,200 10 307 20 614
4,000 8 384 11 528
4,000 8 384 11 528
C frame UAN 40-50C
5,000 8 600 11 825
4,000 6 288 9 432
D frame UAN 40-63D 5,000 6 450 9 675
6,300 5 595 7 833
1) Power consumption listed is maximum power consumption for each rated current, 50/60Hz, 3/4 pole.
2) This is inner resistance value per pole.
3) Power factor = 1.0

A
| Insulation distance |

I nsulation distance from arc

ACB A B
B B
Fixed type 120mm 50mm
Draw-out Without Arc shield 120mm 50mm
type With Arc shield 0mm 50mm B B

M
 inimum insulation distance at charging side D

Insulating voltage D
[V] 600V 8mm
600V [V] 1,000V 14mm

96
ACB

| Rectification of rated current |

Rated Terminal busbar Applicable


Frame
current of ACB body busbar size

Horizontal type Vertical type


40C 45C 50C 55C 60C 40C 45C 50C 55C 60C
200A 200A 200A 200A 200A 200A 200A 200A 200A 200A 200A
5t50mm1EA
400A 400A 400A 400A 400A 400A 400A 400A 400A 400A 400A
5t50mm2EA
630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
10t60mm1EA
6t50mm2EA
800A 800A 800A 800A 800A 800A 800A 800A 800A 800A 800A
10t60mm1EA
A frame
15t50mm1EA 8t50mm2EA 1,000A 1,000A 1,000A 1,000A 1,000A
UAN/UAS06-16 1,000A 1,000A 1,000A 1,000A 1,000A 1,000A
6t75mm2EA - - - - -
8t60mm2EA
1250A 1250A 1250A 1250A 1250A
1,250A 10t50mm2EA 1,250A 1,250A 1,250A 1,250A 1,250A
6t75mm3EA - - - - -
10t60mm2EA
1,600A 1,600A 1,600A 1520A 1,480A 1,420A 1,600A 1,600A 1,580A 1,550A 1,550A
8t60mm3EA
A frame 8t75mm3EA
2,000A 15t75mm1EA - - - - - 2,000A 2,000A 1,940A 1,860A 1,860A
UAN20 10t100mm2EA
5t50mm2EA
630A 630A 630A 630A 630A 630A 630A 630A 630A 630A 630A
10t60mm1EA
6t50mm2EA
800A 800A 800A 800A 800A 800A 800A 800A 800A 800A 800A
10t60mm1EA
8t50mm2EA 1,000A 1,000A 1,000A 1,000A 1,000A
1,000A 1,000A 1,000A 1,000A 1,000A 1,000A
6t75mm2EA - - - - -
8t60mm2EA
B frame 1,250A 1,250A 1,250A 1,250A 1,250A
1,250A 20t75mm1EA 10t50mm2EA 1,250A 1,250A 1,250A 1,250A 1,250A
UAN/UAS06-16
6t75mm3EA - - - - -
10t60mm2EA
1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A 1,600A
8t60mm3EA
8t75mm3EA 2,000A 2,000A 2,000A 2,000A 2,000A
2,000A 2,000A 2,000A 2,000A 2,000A 2,000A
10t100mm2EA - - - - -
10t75mm3EA
2,500A 2,500A 2,500A 2,500A 2,400A 2,300A 2,500A 2,500A 2,500A 2,500A 2,500A
8t75mm4EA
B frame 10t100mm3EA - - - - -
3,200A 20t90mm1EA 3,200A 3,200A 3,120A 3,050A 3,050A
UAN32 10t75mm4EA 3,200A 3,200A 3,100A 3,000A 2,900A
4,000A 10t100mm4EA
15t100mm2EA 4,000A 4,000A 3,900A 3,800A 3,640A - - - - -
B frame Horizontal 10t125mm3EA
UAN40 4,000A 10t100mm4EA
15t125mm2EA - - - - - 4,000A 4,000A 3,950A 3,800A 3,800A
Vertical 10t125mm3EA
3,200A 10t100mm3EA 3,200A 3,200A 3,100A 3,000A 2,900A 3,200A 3,200A 3,100A 3,000A 3,000A
C frame
4,000A 20t125mm2EA 10t100mm4EA 4,000A 4,000A 3,920A 3,860A 3,800A 4,000A 4,000A 3,960A 3,900A 3,900A
UAN32-50
5,000A 10t125mm4EA 5,000A 5,000A 4,900A 4,800A 4,700A 5,000A 5,000A 4,950A 4,900A 4,900A
4,000A 10t100mm4EA 4,000A 4,000A 4,000A 4,000A 4,000A 4,000A 4,000A 4,000A 4,000A 4,000A
C frame
5,000A 20t125mm2EA 10t125mm4EA 5,000A 5,000A 4,900A 4,820A 4,750A 5,000A 5,000A 4,950A 4,870A 4,870A
UAN40-63
6,300A 10t150mm4EA 6,300A 6,300A 6,170A 6,040A 5,900A 6,300A 6,300A 6,220A 6,160A 6,160A

A
 ltitude Item Altitude 2,000m 3,000m 4,000m 5,000m
U-Series ACB is designed for operation at altitudes Withstand voltage[V] 3,500 3,150 2,500 2,100
under 2,000m. At altitudes higher than 2,000m, Average insulating voltage[V] 1,000 900 700 600
Max. operation voltage [V] 690 590 520 460
change the ratings upon service condition.
Rectificated rated current [A] 1In 0.99In 0.96In 0.94In

U-Series Air Circuit Breaker_ 97


U-Series / Air Circuit Breaker

Technical Data

| Derating table |
A frame Ambient temperature outside of the switchboard: Ta (IEC 60439-1)

4
3
Switchboard composition 2
1
connection type

Applicable ACB UAN/UAS06-08 UAN/UAS10


Busbar dimensions (mm) 2EA x 50 x 6 2EA x 50 x 8
4 800
Ventilated switchboard (IP31) 3 800 800 1,000
Ta=35C
2 800 800 800 1,000 1,000

1 800 800 800 800 800 1,000 1,000 1,000 1,000

H 4 800

H 3 800 800 1,000


Ta=45C
2 800 800 800 1,000 1,000

1 800 800 800 800 800 1,000 1,000 1,000 1,000


D W 4 800
D W 3 800 800 1,000
Ta=55C
Area of inlet vents: 350cm2
2 800 800 800 1,000 1,000
Area of outlet vents: 350cm2
1 800 800 800 800 800 1,000 1,000 1,000 1,000

4 800
Non ventilated switchboard 3 800 800 1,000
(IP41/54) Ta=35C
2 800 800 800 1,000 1,000

1 800 800 800 800 800 1,000 1,000 1,000 1,000

4 800

3 800 800 1,000


H Ta=45C
2 800 800 800 1,000 1,000
H
1 800 800 800 800 800 1,000 1,000 1,000 1,000

4 800

3 800 800 1,000


D W Ta=55C
D
2 800 800 800 1,000 1,000
W
1 800 800 800 800 800 1,000 1,000 1,000 1000

H: 2,300mm, W: 800mm, D: 900mm

98
ACB

Ambient temperature outside of the switchboard: Ta (IEC 60439-1)

4
3
Switchboard composition 2
1
connection type

Applicable ACB UAN/UAS12 UAN/UAS16


Busbar dimensions (mm) 2EA x 75 x 6 2EA x 60 x 10
4
Ventilated switchboard (IP31) 3 1,250 1,000
Ta=35C
2 1,250 1,250 1,600 1,000 1,000

1 1,250 1,250 1,250 1,250 1,600 1,600 1,600 1,000 1,000

H 4

H 3 1,250 1,000
Ta=45C
2 1,250 1,250 1,600 1,000 1,000

1 1,250 1,250 1,250 1,250 1,600 1,600 1,600 1,000 1,000


D W 4
D W 3 1,250 1,000
Ta=55C
Area of inlet vents: 350cm2
2 1,250 1,250 1,470 1,000 1,000
Area of outlet vents: 350cm2
1 1,250 1,250 1,250 1,250 1,500 1,600 1,600 1,000 1,000

4
Non ventilated switchboard 3 1,250 1,000
(IP41/54) Ta=35C
2 1,250 1,250 1,600 1,000 1,000

1 1,250 1,250 1,250 1,250 1,600 1,600 1,600 1,000 1,000

3 1,250 1,000
H Ta=45C
2 1,250 1,250 1,500 1,000 1,000
H
1 1,250 1,250 1,250 1,250 1,480 1,600 1,600 1,000 1,000

3 1,250 1,000
D W Ta=55C
D
2 1,250 1,250 1,400 1,000 1,000
W
1 1,250 1,250 1,250 1,250 1,400 1,520 1,500 1,000 1,000

H: 2,300mm, W: 800mm, D: 900mm

U-Series Air Circuit Breaker_ 99


U-Series / Air Circuit Breaker

Technical Data

| Derating table |
B frame Ambient temperature outside of the switchboard: Ta (IEC 60439-1)

4 4 4 4
3 3 3 3
Switchboard composition 2 2 2 2
1 1 1 1
connection type

Applicable ACB UAN/UAS201) UAN/UAS25 UAN/UAS32 UAN40


Busbar dimensions (mm) 2EA x 75 x 10 3EA x 75 x 10 4EA x 75 x 10 4EA x 75 x 10
4
Ventilated switchboard (IP31) 3 2,000
Ta=35C
2 2,000 2,000 2,000 2,400 2,500 3,100 3,200 3,400 3,750

H 4

H 3 2,000
Ta=45C
2 2,000 2,000 2,000 2,300 2,400 2,900 3,100 3,200 3,550

1
D W 4
D W 3 2,000
Ta=55C
Area of inlet vents: 350cm 2
2 2,000 2,000 2,000 2,200 2,300 2,700 2,900 3,000 3,300
Area of outlet vents: 350cm2
1

4
Non ventilated switchboard 3 2,000
(IP41/54) Ta=35C
2 2,000 2,000 2,000 2,115 2,275 2,650 2,850 3,040 3,320

3 1,900
H Ta=45C
2 1,900 1,960 1,960 2,000 2,150 2,550 2,700 2,880 3,120
H
1

3 1,780
D W Ta=55C
D 2 1,800 1,920 1,920 1,900 2,020 2,370 2,530 2,720 2,960
W
1

- H: 2,300mm, W: 800mm, D: 900mm


1) UAN20 A frame type is also applicable.

100
ACB

C/D frame Ambient temperature outside of the switchboard: Ta (IEC 60439-1)

4 4 4 4 4
3 3 3 3 3
Switchboard composition 2 2 2 2 2
1 1 1 1 1
connection type

Applicable ACB UAN40 (C) UAN50 (C) UAN40 (D) UAN50 (D) UAN63 (D)
Busbar dimensions (mm) 4EA x 100 x 10 4EA x 125 x 10 4EA x 100 x 10 4EA x 125 x 10 4EA x 150 x 10
4
Ventilated switchboard (IP31) 3
Ta=35C
2 2,900 4,000 4,750 4,800 4,000 4,000 4,750 5,000 5,850 6,300

H 4

H 3
Ta=45C
2 3,850 3,900 4,350 4,650 4,000 4,000 4,450 4,850 5,670 5,850

1
D W 4
D W 3
Ta=55C
Area of inlet vents: 350cm2
2 3,800 3,850 4,200 4,400 4,000 4,000 4,200 4,600 5,350 5,670
Area of outlet vents: 350cm2
1

4
Non ventilated switchboard 3
(IP41/54) Ta=35C
2 3,800 3,900 4,200 4,550 4,000 4,000 4,400 4,650 5,350 5,000

3
H Ta=45C
2 3,650 3,800 3,950 4,250 4,000 4,000 4,100 4,400 5,040 5,350
H
1

3
D W Ta=55C
D
2 3,550 3,650 3,700 4,050 3,900 3,950 3,850 4,150 4,730 5,040
W
1

H: 2,300mm, W: 800mm, D: 900mm

U-Series Air Circuit Breaker_ 101


U-Series / Air Circuit Breaker

Technical Data

| Discrimination table |
Upstream Breaking capacity: at AC380/415V
Downstream

ACB
UAN/UAS A frame UAN/UAS B frame UAN C frame
Recognition
630 800 1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
category Model Rated
current Breaking
(A) capacity [Icu] 85 85 85 85 85 85 100 100 100 100 100 100
(kA r.m.s)
1 4.5 T T T T T T T T T T T T
2 4.5 T T T T T T T T T T T T
5 4.5 T T T T T T T T T T T T
6 4.5 T T T T T T T T T T T T

HiBD63-NS 10 4.5 T T T T T T T T T T T T
B, C curve 16 4.5 T T T T T T T T T T T T
20 4.5 T T T T T T T T T T T T
25 4.5 T T T T T T T T T T T T
32 4.5 T T T T T T T T T T T T
40 4.5 T T T T T T T T T T T T
1 6 T T T T T T T T T T T T
2 6 T T T T T T T T T T T T
3 6 T T T T T T T T T T T T
4 6 T T T T T T T T T T T T
5 6 T T T T T T T T T T T T
6 6 T T T T T T T T T T T T
10 6 T T T T T T T T T T T T

HiBD63-N 13 6 T T T T T T T T T T T T
MCB B, C, D curve 15 6 T T T T T T T T T T T T
16 6 T T T T T T T T T T T T
20 6 T T T T T T T T T T T T
25 6 T T T T T T T T T T T T
32 6 T T T T T T T T T T T T
40 6 T T T T T T T T T T T T
50 6 T T T T T T T T T T T T
63 6 T T T T T T T T T T T T
1 10 T T T T T T T T T T T T
2 10 T T T T T T T T T T T T
3 10 T T T T T T T T T T T T
4 10 T T T T T T T T T T T T
5 10 T T T T T T T T T T T T
HiBD63H
6 10 T T T T T T T T T T T T
B, C, D curve
10 10 T T T T T T T T T T T T
13 10 T T T T T T T T T T T T
15 10 T T T T T T T T T T T T
16 10 T T T T T T T T T T T T
20 10 T T T T T T T T T T T T
Can be blocked all sectors. Can not be blocked.

102
ACB

Upstream Breaking capacity: at AC380/415V


Downstream

ACB
UAN/UAS A frame UAN/UAS B frame UAN C frame
Recognition
630 800 1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
category Model Rated
current Breaking
(A) capacity [Icu] 85 85 85 85 85 85 100 100 100 100 100 100
(kA r.m.s)
25 10 T T T T T T T T T T T T
32 10 T T T T T T T T T T T T
HiBD63h
40 10 T T T T T T T T T T T T
B, C, D curve
50 10 T T T T T T T T T T T T
MCB 63 10 T T T T T T T T T T T T
63 10 T T T T T T T T T T T T

HiBD125 80 10 T T T T T T T T T T T T
B, C, D curve 100 10 T T T T T T T T T T T T
125 10 T T T T T T T T T T T T
5 30 T T T T T T T T T T T T
10 30 T T T T T T T T T T T T
15 30 T T T T T T T T T T T T
20 30 T T T T T T T T T T T T

UAB100 30 30 T T T T T T T T T T T T
C, R, S 40 30 T T T T T T T T T T T T
50 30 T T T T T T T T T T T T
60 30 T T T T T T T T T T T T
75 30 T T T T T T T T T T T T
100 30 T T T T T T T T T T T T
15 50 T T T T T T T T T T T T
20 50 T T T T T T T T T T T T
30 50 T T T T T T T T T T T T
MCCB
40 50 T T T T T T T T T T T T
UCB100
50 50 T T T T T T T T T T T T
R, S, H, L
60 50 T T T T T T T T T T T T
75 50 T T T T T T T T T T T T
100 50 T T T T T T T T T T T T
125 50 T T T T T T T T T T T T
100 50 T T T T T T T T T T T T
125 50 T T T T T T T T T T T T
150 50 T T T T T T T T T T T T
UCB250
175 50 T T T T T T T T T T T T
R, S, N, H, L
200 50 T T T T T T T T T T T T
225 50 T T T T T T T T T T T T
250 50 T T T T T T T T T T T T
Can be blocked all sectors. Can not be blocked.

U-Series Air Circuit Breaker_ 103


U-Series / Air Circuit Breaker

Technical Data

| Discrimination table |
Upstream Breaking capacity: at AC380/415V
Downstream

ACB
UAN/UAS A frame UAN/UAS B frame UAN C frame
Recognition
630 800 1,000 1,200 1,250 1,600 2,000 2,500 3,200 4,000 4,000 5,000
category Model Rated
current Breaking
(A) capacity [Icu] 85 85 85 85 85 85 100 100 100 100 100 100
(kA r.m.s)
250 100 T T T T T T T T T T T T
300 100 T T T T T T T T T T T T
UCB400
320 100 T T T T T T T T T T T T
R, S, N, H, L
350 100 T T T T T T T T T T T T
400 100 T T T T T T T T T T T T

UCB630 500 100 - T T T T T T T T T T T


R, S, H, L 630 100 - T T T T T T T T T T T

UCB800 700 100 - - T T T T T T T T T T


R, S, H, L 800 100 - - T T T T T T T T T T
15 150 T T T T T T T T T T T T
20 150 T T T T T T T T T T T T
30 150 T T T T T T T T T T T T
40 150 T T T T T T T T T T T T
UPB100
50 150 T T T T T T T T T T T T
S, H, L, X
63 150 T T T T T T T T T T T T
80 150 T T T T T T T T T T T T
100 150 T T T T T T T T T T T T
MCCB
125 150 T T T T T T T T T T T T
125 150 T T T T T T T T T T T T
150 150 T T T T T T T T T T T T

UPB250 175 150 T T T T T T T T T T T T


R, S, N, H, L 200 150 T T T T T T T T T T T T
225 150 T T T T T T T T T T T T
250 150 T T T T T T T T T T T T
250 150 T T T T T T T T T T T T
300 150 T T T T T T T T T T T T
UPB400
320 150 T T T T T T T T T T T T
S, H, L, X
350 150 T T T T T T T T T T T T
400 150 T T T T T T T T T T T T
320 150 T T T T T T T T T T T T
350 150 T T T T T T T T T T T T
UPB630
400 150 T T T T T T T T T T T T
S, H, L, X
500 150 - T T T T T T T T T T T
630 150 - T T T T T T T T T T T
Can be blocked all sectors. Can not be blocked.

104
ACB

Operating Conditions

| Ambient temperature | | Relative humidity |


Operating condition: -5C to 40C is recommended. Relative humidity should be under 85%.
Cradle is fixed to a switchboard.
The average temperature for 24 hours should be within 35C.
Reduce the continuous conducting current when the
temperature is over 45C (Refer to derating table, 98page).

| Load (I/In) | | Storage conditions |


Load Using Effect Installation Device without its control unit: -25C to 85C
I/In 80% 24/24 Hours - Normal condition (Recommend) Device with control unit: -15C to 70C
80 I/In 90% 24/24 Hours - Periodic inspection The product with charging motor should be stored in
I/In = 100% 24/24 Hours Plastic insulator Exhaust added open position.
color changed

| Atmospheric conditions |
Do not apply under corrosive or ammonia gas circumstances (H2S, SO2, NH3).
Use in clean air condition.

| Altitude |
Altitude
Item
2,000m (6,600 feet) 2,600m (8,500 feet) 3,900m (13,000 feet)
Isolation voltage [V] 1,000 950 800
Operating voltage [V] 690 655.5 552
Allowed current [A] 1 x In 0.99 x In 0.96 x In

| Protection degree provided by enclosures (IP code)|


IP
Standard: IP30 First characteristic numeral (Numerals 0 to 6, or letter )
With dust cover: IP52 Second characteristic numeral (Numerals 0 to 8, or letter )
Code letters (International protection)

Degree of protection
First characteristic numeral Second characteristic numeral
0 Non-protected Non-protected (OPEN)
1 Protected against solid foreign objects of 50mm and greater Protected against vertically falling water drops
2 Protected against solid foreign objects of 12.5mm and greater Protected against vertically falling water drops when enclosure tilted up to 15
3 Protected against solid foreign objects of 2.5mm and greater Protected against spraying water (at an angle up to 60)
4 Protected against solid foreign objects of 1.0mm and greater Protected against spraying water (Splash proof)
5 Dust-protected (Ingress of dust is not totally prevented) Protected against spraying jets (Hose proof)
6 Dust-tight (No ingress of dust) Protected against powerful water jets (Deckwater proof)
Protected against the effects of temporary immersion in water
7 -
(Under pressure and time)
Protected against the effects of continuous immersion in water
8 -
(Submersible)

U-Series Air Circuit Breaker_ 105


U-Series / Air Circuit Breaker

Ordering Sheet

To indicate your choice, check the applicable boxes and enter the appropriate information corresponding to your choice.

ACB body Type of ACB UAN UAS1)

Frame size AF
A (630-2,000AF)2) B (630-4,000AF)3) C (3,200-5,000AF) D (4,000-6,300AF)
Phase type Standard type (R, S, T, N) Reverse phase type (N, R, S, T)
Number of poles 3 pole 4 pole
Type of equipment Draw-out type Fixed type
Terminal
connection Manual connection Auto connection
(Draw-out type)
Terminal busbar
arrangement Horizontal Vertical Horizontal/Vertical (Line/Load) Vertical/Horizontal (Line/Load) Front type or others4)
(Fixed type)
Charging Manual closing
Electrical closing
AC/DC110V DC125V DC24V DC48V
Motor operating voltage
AC/DC220V AC380V 5) AC440V 5)
Closing voltage AC/DC110V DC125V AC/DC220V DC24V DC48V AC380V AC440V
Trip voltage AC/DC110V DC125V AC/DC220V DC24V DC48V AC380V AC440V

Protection trip NO
relay YES
Ground
50Hz 60Hz Model LCD/LED Application fault Signal NCT ELT Comm7) MCR Memory Adaptor
detection6)
33 43 UPR-1L-GS - General feeder Integrated instantaneous 1a - - - -
35 45 UPR-2L-GS General feeder Individual continuous 4a - -
36 46 UPR-1D-GT General feeder Individual continuous 4a
37 47 UPR-2L-GM General feeder Integrated continuous 3a8) - -
38 48 UPR-1S-AL - Generator - Integrated instantaneous 1a - - - - -
39 49 UPR-2S-AS Generator - Individual continuous 3a9) - - -

Current transformer 80A 160A

Accessory UVT coil AC/DC110V DC125V DC24V DC48V


(Instantaneous type) AC/DC220V AC380V AC440V

AC/DC110V DC125V DC24V DC48V


Double trip coil10)
AC/DC220V AC380V AC440V

AC/DC110V DC125V DC24V DC48V


Trip supervision coil
AC/DC220V AC380V AC440V

Auxiliary switch 3a3b (Standard for UAS) 5a5b (Standard for UAN) 6a6b (Maximum)
OCR MCR wire Complete parts of ACB/Cradle Spare part

OCR & Alarm switch BR: OCR (Only for manual reset button) BA: OCR manual reset+Alarm switch
reset button BM: OCR (Auto reset)+Alarm switch

Counter (Standard)
Fixing block11) Complete parts of ACB/Cradle Spare part
Wrong insertion preventer11) Complete parts of ACB/Cradle Spare part
Key lock device Complete parts of ACB/Cradle Spare part
ON/OFF button lock Complete parts of ACB/Cradle Spare part
Mechanical interlock12) Complete parts of ACB/Cradle Spare part
Spring charge switch Complete parts of ACB/Cradle Spare part

106
ACB

Cradle Control terminal Manual connection

Terminal busbar
Horizontal Vertical Horizontal/Vertical (Line/Load) Vertical/Horizontal (Line/Load) Front type or others4)
arrangement

Accessory Safety shutter lock13) Complete parts of ACB/Cradle Spare part


Fixing block11) Complete parts of ACB/Cradle Spare part
Wrong insertion preventor11) Complete parts of ACB/Cradle Spare part
Arc shield Complete parts of ACB/Cradle Spare part
Short b contact14) Complete parts of ACB/Cradle Spare part
Control terminal protection cover15) Complete parts of ACB/Cradle Spare part
Mechanical operated cell switch Complete parts of ACB/Cradle Spare part

ACB accessory Purchase Phase insulation barrier


separately
UVT time delay AC/DC 110V DC 125V DC 24V DC 48V
controller16) AC/DC 220V AC 380V AC 440V
AQ=Test1C, Connected1C AR=Connected2C AS=Test2C
AT=Inserted1C, Isolated1C AU=Inserted2C AV=Isolated2C
Position switch16)
PQ=Inserted1C, Isolated1C, P4=Test2C, Connected2C P8=Inserted2C, Isolated2C,
Test1C, Connected1C Test2C, Connected2C
Mechanical interlock Wire type (2 terminals) Wire type (3 terminals)
Condenser trip device AC110V AC220V
Test jumper OCR portable checker
Draw-in/out handle Standard type Long type Universal type
ATS Controller Automatic transfer switch & controller
Lifting lug Dummy ACB
Door flange Dust cover
ZCT (Consultation) NCT (Consultation)
Profibus-DP comm. Remote operation & temperature detection module

1) In case of UAS, A frame size is in the range of 630-1,600AF and B frame size is in the range of 2,000-3,200AF.
2) In case of UAN 20A, only vertical type is available.
3) In case of UAN, B frame size of 630-1,600AF is possible.
4) Front type/User installation need to be ordered separately and attached by the customer. 630-1,600AF is available
for A frame and 2,000-3,200AF is available for B frame.
5) Motor of AC380/440V is available from June. 2013.
6) Standard function for general feeder: Ground fault detection.
7) Communication function is not available under no control voltage.
8) LTD/STD/INST/ELT (except. PTA)
9) LTD/STD/INST/PTA (except. GFT)
10) In case of ordering UVT, double trip coil is not available.
11) In case of ordering fixing block and wrong insertion preventer, mark on both ACB and cradle ordering sheet.
12) MI is separate purchasing item, only assembled parts interacting inside of the body are delivered.
13) In case of ordering safety shutter-attachment type, shutter lock is automatically implemented.
14) Fixing block and wrong insertion preventer have to be marked on both the body and cradle orders.
15) Control terminal protection cover is only available for automatic connection type.
16) UVT controller and position switch can be offered as mounted.

U-Series Air Circuit Breaker_ 107


HHIS-WC-LE-B74-00, 2013.2 Designed by JC Creative
www.hyundai-elec.com

Head Office 1000, Bangeojinsunhwan-doro, Dong-gu, Ulsan, Korea


Tel: 82-52-202-8101~8 Fax: 82-52-202-8100
Seoul 75, Yulgok-ro, Jongno-gu, Seoul, Korea
(Sales & Marketing) Tel: 82-2-746-8519, 7492, 7620 Fax: 82-2-746-7441
Atlanta 6100 Atlantic Boulevard, Norcross, GA 30071, USA
Tel: 1-678-823-7839 Fax: 1-678-823-7553
London 2nd Floor, The Triangle, 5-17 Hammersmith Grove London, W6 0LG, UK
Tel: 44-20-8741-0501 Fax: 44-20-8741-5620
Moscow World Trade Center, Ent. 3# 1902, Krasnopresnenskays Nab. 12, Moscow, 123610, Russia
Tel: 7-495-258-1381 Fax: 7-495-258-1382
Madrid Paseo De La Castellana 216, Planta 0, 28046 Madrid, Spain
Tel: 34-91-732-0454, 733-6069 Fax: 34-91-733-2389
Tokyo 8th Floor, North Tower Yurakucho Denki Bldg., 1-7-1 Yuraku-cho, Chiyoda-ku, Tokyo 100-0006, Japan
Tel: 81-3-3211-4792 Fax: 81-3-3216-0728
Osaka I-Room 5th Floor Nagahori Plaza Bldg. 2-4-8 Minami Senba, Chuo-ku, Osaka, 542-0081, Japan
Tel: 81-6-6261-5766~7 Fax: 81-6-6261-5818
Mumbai 5th Floor, East Quadrant, The IL & FS Financial Centre, Plot No. C-22, G-Block,
Bandra-kurla Complex, Bandra(E), Mumbai 400 051, India
Tel: 91-22-2653-3420~26 Fax: 91-22-2653-3429
Riyadh Office No. 230, 2nd Floor, 4th Akariya Plaza Olaya Street, PO Box 8072, Riyadh 11485, Saudi Arabia
Tel: 966-1-464-4696 Fax: 966-1-462-2352
Dubai Unit 205, Building 4, Emaar Square, Sheikh Zayed Road, Pobox 252458, Dubai, UAE
Tel: 971-4-425-7995 Fax: 971-4-425-7996
Kuwait 15th Floor, Al-Sour Tower, Al Sour Street, Al-Qiblah, Kuwait
Tel: 965-2291-5354 Fax: 965-2291-5355
Sofia 1271, Sofia 41, Rojen Blvd., Bulgaria
Tel: 359-2-803-3200, 3220 Fax: 359-2-803-3203
Montgomery 215 Folmar Parkway, Montgomery, AL 36105, USA
Tel: 1-334-481-2000 Fax: 1-334-481-2098
Vladivostok 15, str. Potemkina, Artem, Primorskiy Krai, 692760, Russia
Tel: 7-423-201-0110 Fax: 7-423-201-0110
Yangzhong No.9 Xiandai Road, Xinba Scientific and Technologic Zone, Yangzhong, Jiangsu, P.R.C. Zip: 212212, China
Tel: 86-511-8842-0666, 0212 Fax: 86-511-8842-0668, 0231

You might also like