You are on page 1of 114

DRAWINGS AND DOCUMENTS

CUSTOMER UMI ENGINEERING CO., LTD.

FINAL USER SIAM SEMPERMED

1 DISTRIBUTOR: EBARA THERMAL SYSTEMS(THAILAND)CO.,LTD

Serial No. B15V015701


Model REW045
Set 1

CONTENTS

TITLE DRAWING NUMBER REV


2 1 SPECIFICATION DATA SHEET ERS155Y-Q15714R 1
2 OUTLINE DIMENSIONS RB15V015701-901 0
3 FOUNDATION DETAIL REW045-E2001A 0
4 ANCHOR BOLT DETAIL RCD028-E2101XB 0
5 PIPING FLOW SHEET RCW015-E4001XA 0
6 INSTALLATION GUIDE CRA139E-K001F 1
7
2 8 STEAM CONTROL VALVE ASSEMBLY CRA475E-K001 0
2 9
10 CONTROL PANEL WIRING DRAWING UNFIXED 0
11 LIFTING DRAWING REW015-E1906X 0
12 TYPICAL RELIEF PIPING FROM FUSHIBLE PLUG CRA434E/K001A 0
13 TYPICAL INSULATION WORK REW028-E5001A 0
14 INSTRUCTION MANUAL CRA605E-H001 0
15
16
17
18
19
20

TO SET
ERS091 1C APPROVED by CHECKED by DOCUMENT NAME
Naka REW ABS. CHILLER
Z.Z
ERS076 1C 4

Jul,16th,'15 DRAWING AND DOCUMENTS

3 APPROVED by PREPARED by
23 Jul,23th,'15 z.z L.Q DOCUMENT NO. REV
1
1 Jul,22th,'15 z.z L.Q T.SH L .Q ERS155Y-Q15714Q 2
YEA Ori. REV PAGE DATE APP'D BY Jul,20th,'15 Jul,14th,'15

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


Page.1/7

Serial No. B15V015701 Model REW045 Set 1


ABSORPTION CHILLER SPECIFICATION DATA SHEET
APPLIED STANDARD JIS B 8622
ITEM UNIT
REFRIGERANT CAPACITY kW(USRt) 1336 (380
CHILLED WATER MEDIUM : CHILLED WATER
INLET TEMP. 12 7
FLOW RATE L/ 3830
PASS NUMBER 3
PRESSURE DROP kPa 50
MAX. WORKING PRESSURE MPa (gage) 0.78
COOLING WATER MEDIUM : COOLING TOWER WATER
INLET TEMP. 32 37.3
FLOW RATE L/ 6330
PASS NUMBER Abs. 2 Cond. 1
PRESSURE DROP kPa 53
MAX. WORKING PRESSURE MPa (gage) 0.78
HEATING MEDIUM : STEAM
SUPPLY PRESSURE MPa (gage) 0.588
SUPPLY TEMP. SATURATED
CONSUMPTION kg/h 1482
DRAIN TEMP. UNDER 90
DRAIN PRESSURE MPa (gage) 0.05 ABOVE
MAX. WORKING PRESSURE MPa (gage) 0.98
VALVE CONTROL TYPE ELECTRIC TYPE
FLANGE CONNECTION
1 CHILLED WATER/SPEC. inch 200 (8) /JIS 10K F.F
1 COOLING WATER/SPEC. inch 250 (10) /JIS 10K F.F
1 STEAM/DRAIN/SPEC. inch 80 (3) / 25 (1) /JIS 10K F.F
1 STEAM CONTROL VALVE/SPEC. inch 40 (1.1/2) /JIS 10K F.F
1
ELECTRIC POWER SOURCE V x Hz 380 50
CONTROL CIRCUIT 200
ELECTRIC POWER CAPACITY kVA 14.5
SOL.PUMP kW 3.7
SOL.SPRAY PUMP kW 3.0
REF.PUMP kW 0.4
PURGE PUMP kW 0.2
VACUUM PUMP kW 0.75
LOCATION / ATMOSPHERE INDOOR NON-HAZARDOUS AREA
SHIPMENT (PER UNIT) ONE PIECE

NOTE.

1The permissible range of variable steam pressure is within 0.02MPa.


2Fouling factorm2K/W) Chilled Water 0.000086 Cooling Water 0.000086
3Capacity control range10020%. Out of range(under 20%)ON-OFF operation.
4Solution pump and solution spray pump are controled by inverter.
TO SET
ERS091 1C APPROVED by CHECKED by DOCUMENT NAME
Naka REW ABSORPTION CHILLER
ERS175 1C Z.Z
(R-Insp')
4

Jul,16th,'15 SPECIFICATION DATA SHEET

ERS076 1C 3 APPROVED by PREPARED by
ERS171 1C 2 DOCUMENT NO. REV
1
6
P1P2 Jul,22th,'15 Z.Z L.Q T.SH L .Q ERS155Y-Q15714R 1
YEA Ori' REV PAGE DATE APP'D BY Jul,20th,'15 Jul,14th,'15

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


P.2

2. EQUIPMENTS LIST (REW)

No. EQUIPMENTS QUANT. VENDER PURCHASER DESCRIPTION


/UNIT
1 ABSORBER, 1 SHELL AND TUBE
EVAPORATOR, TUBE SET : EXPANDING
CONDENSER AND
LOW TEMP. GEN. SHELL
2 HIGH TEMPERATURE 1 SHELL AND TUBE
GENERATOR SHELL TUBE SET : EXPANDING
3 LOW TEMP. SOLUTION 1 PLATE TYPE
HEAT EXCHANGER
4 MIDDLE TEMP. SOLUTION 2 PLATE TYPE
HEAT EXCHANGER
5 HIGH TEMP. SOLUTION 1 PLATE TYPE
HEAT EXCHANGER
6 REFRIGERANT COOLER 1 PLATE TYPE

7 DRAIN HEAT EXCHANGER 1 PLATE TYPE

8 SOLUTION PUMP 1 HERMETIC TYPE


3.7 kW
9 SOLUTION SPRAY PUMP 1 HERMETIC TYPE
3.0 kW
10 REFRIGERANT PUMP 1 HERMETIC TYPE
0.4 kW
11 INVERTER FOR 1 APROPER STRING WAVE PWM CONTROL
SOLUTION PUMP FORM(DCL ACCESSORY)
12 INVERTER FOR 1 APROPER STRING WAVE PWM CONTROL
SOLUTION SPRAY PUMP FORM(DCL ACCESSORY)
13 LOCAL CONTROL PANEL 1SET WALL CABINET TYPE

14 SAFETY CONTROL 1SET REFER TO SAFETY INSTRUMENT LIST


DEVICES
15 PURGE PUMP 1 AUTOMATIC PURGE UNIT 0.2 kW

16 CAPACITY 1
CONTROL VALVE
17 LITHIUM BROMIDE 1SET
SOLUTION
18 REFRIGERANT 1SET
(PURE WATER)
19 STANDARD ACCESSORIES 1SET LINER FOR SETTING
OIL FOR PURGE PUMP etc.
20 FACTORY TEST 1SET HYDRAULIC PRESS. TEST
AND INSPECTION (WATER BOX)
AIR TIGHTNESS TEST (MACHINE)
APPEARANCE INSPECTION etc.
21 SOLUTION FILTER UNIT 1SET

1 22

23 VACUUM PUMP 1SET 0.75kW

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


P.3

3. MATERIALS (REW)

COMPONENT PART MATERIALS DESCRIPTION


(ACCORDING TO JIS OR EQUIVALENT CODE )

EVAPORATOR/ABSORBER SHELL SS400(JIS G 3101) / Q235B(GB/T700)


TUBE PLATE SS400(JIS G 3101) / Q235B(GB/T700)
TUBE SUPPORT SS400(JIS G 3101) / Q235B(GB/T700)
EVATUBE C1201(JIS H 3300) / TP1(GB/T17791) ACCORDING TO JIS
ABSTUBE C1201(JIS H 3300) / TP1(GB/T17791) ACCORDING TO JIS
WATER BOX & COVER SS400(JIS G 3101) / Q235B(GB/T700) NON TAR-EPOXY PAINT
LOW TEMPGEN SHELL SS400(JIS G 3101) / Q235B(GB/T700)
/CONDENSER TUBE PLATE SS400(JIS G 3101) / Q235B(GB/T700)
TUBE SUPPORT SS400(JIS G 3101) / Q235B(GB/T700)
GENTUBE C1201(JIS H 3300) / TP1(GB/T17791) ACCORDING TO JIS
CONDTUBE C1201(JIS H 3300) / TP1(GB/T17791) ACCORDING TO JIS
WATER BOX & COVER SS400(JIS G 3101) / Q235B(GB/T700) NON TAR-EPOXY PAINT
HIGH TEMP SHELL SS400(JIS G 3101) / Q235B(GB/T700)
GENERATOR TUBE PLATE SS400(JIS G 3101) / Q235B(GB/T700)
TUBE SUPPORT SS400(JIS G 3101) / Q235B(GB/T700)
TUBE SUS430TB(JIS G 3463) / ASTM A268 ACCORDING TO JIS
STEAM BOX & COVER SS400(JIS G 3101) / Q235B(GB/T700)
HEAT EXCHANGER FRAME SUS304(JIS G 4303)
(HIGH, MIDDLE, LOW TEMP.) PLATE SUS316(JIS G 4303) /ASTM A240-316L
NOZZLE SUS304(JIS G 4303)
DRAIN HEAT EX FRAME SUS304(JIS G 4303)
PLATE SUS316(JIS G 4303) /ASTM A240-316L
NOZZLE SUS304(JIS G 4303)
PIPES SOL./REF. PIPES SGP(JIS G 3452)/20#(GB8163-87)
DILUTION VALVE PIPES SUS304TP(JIS G 3459)/1Cr18Ni9Ti(GB2270-80)
WATER PIPES SGP(JIS G 3452)/20#(GB8163-87)
STEAM/DRAIN PIPES SGP(JIS G 3452)/20#(GB8163-87)

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


P.4

4. SAFETY AND CONTROL DEVICE (REW)

NO. ITEM QUANT. SYMBOL DESCRIPTION


/UNIT
1 CHILLED WATER LOW 1 Er0033 ABSORPTION CHILLER AUTOMATICALLY
FLOW CUTOUT STOP (WITHOUT DILUTION CYCLE)
2 CHILLED WATER 1 Er0034 ABSORPTION CHILLER AUTOMATICALLY
LOW TEMP. CUTOUT STOP (WITH DILUTION CYCLE)
3 REFRIGERANT WATER 1 Er0037 DITTO
LOW TEMP.
4 SOLUTION PUMP MOTOR 1 Er0021 ABSORPTION CHILLER AUTOMATICALLY
OVERLOAD CUTOUT STOP (WITHOUT DILUTION CYCLE)
5 REFRIGERANT PUMP MOTOR 1 Er0020 ABSORPTION CHILLER AUTOMATICALLY
OVERLOAD CUTOUT STOP (WITH DILUTION CYCLE)
6 SOLUTION SPRAY PUMP 1 Er0026 DITTO
MOTOR OVERLOAD CUTOUT
7 HIGH TEMP. GEN. OUTLET 1 Er0047 DITTO
SOL. HIGH TEMP.
8 HIGH TEMP. GEN. 1 Er0056 DITTO
HIGH PRESS. CUTOUT
9 COOLING WATER HIGH TEMP. 1 Er0044 DITTO

10 COOLING WATER LOW TEMP. 1 Er0045 DITTO

11 ABSORBER SOLUTION 1 Er0046 DITTO


TEMPERATURE HIGH
12 COOLING CAPACTY DROP 1 Er0035 DITTO

13 TEMPERATURE REGULATION 1
STOPPAGE
14 CYCLE GUARD VALVE 1 CYCLE-GUARD VALVE OPEN

15 J-LOOP 1 PREVENT PROGRESS OF SOL.


CRYSTALLIZATION
16 REF.OVERFLOW PIPE 1

17 TEMPERATURE CONTROLLER 1

5. LOCAL CONTROL PANEL ( Refer to CONTROL PANEL WIRING DRAWING ) (REW)

NAME DESCRIPTION

MODEL ENCLOSED WALL CABINET TYPE

LOCATION INDOOR, NON-HAZARDOUS AREA

APPLIED STANDARD JIS, JEM, JEC, Ebaras Standard

POWER SOURCE 380 V 50

CONTROL POWER SOURCE 200 V 50

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


P.5

6.SETTING LIST (REW)

NO ITEM QUANT VENDER PURCHASER DESCRIPTION


/UNIT

1 EXPORT PACKING 1SET


AND FREIGHT
2 CARRYING AND ROUGH 1SET
SETTING
3 SETTING 1SET

4 TEST OPERATION 1SET

5 LECTURE OPERATION 1SET

6 FOUNDATION 1SET

7 INSULATION 1SET

8 WATER PIPING 1SET

9 STEAM PIPING 1SET

10 PAINTING 1SET ANTICORROSIVE PAINT ONLY


(AT SHOP)
11 WIRING 1SET WIRING BETWEEN POWER SOURCE
AND LOCAL CONTROL PANEL
WIRING BETWEEN LOCAL CONTROL
PANEL AND MACHINE
WIRING BETWEEN LOCAL CONTROL
PANEL AND STEAM CONTROL VALVE
OTHER WIRING IF REQUIRED

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


P.6

7.NOTES (REW)

(1) PERIODICALLY INSPECT THE CHILLER ONCE A YEAR. IT IS RECOMMENDED THAT THE REFRIGERANT PUMP

AND THE SOLUTION PUMP BE OVERHAULED EVERY 20,000 HOURS OF OPERATION OR 5 YEARS, WHICHEVER COMES FIRST.

IF THE CHILLER IS USED FOR CRITICAL PURPOSES, SHORTER OVERHAUL INTERVALS ARE RECOMMENDED.

(2) THE SPECIFICATION OF THE CAPACITY CONTROL RANGE ASSUMES THAT TEMPERATURE CONTROL IS

CARRIED OUT UNDER RATED CONDITIONS (THE CHILLED WATER OUTLET TEMPERATURE AND THE COOLING

WATER INLET TEMPERATURE ARE CONSTANT).

(3) TO PREVENT CORROSION OF THE HEAT TRANSMISSION TUBES, INSTALL STRAINERS OF APPROXIMATELY 10 MESH IN

INLET PIPING FOR CHILLED WATER AND COOLING WATER.

(4) THE CHILLER IS DESIGNED TO MAINTAIN A CONSTANT FLOW OF CHILLED WATER/COOLING WATER REGARDLESS OF

LOAD FLUCTUATIONS. IF VARIABLE FLOW CONTROL IS DESIRED, CONSULT US SEPARATELY.

(5) PROPERLY CONTROL THE QUALITY OF CHILLED WATER AND COOLING WATER. ENSURE THAT THE WATER QUALITY

GUIDELINE OF THE JAPAN REFRIGERATION AND AIR CONDITIONING INDUSTRY ASSOCIATION (JRA-GL-02E-1994) IS MET.

(6) OUR STANDARD TUBE MATERIAL FOR THE HIGH TEMPERATURE GENERATOR IS JIS G3463 SUS430TB.

FOR THE QUALITY OF STEAM DRAIN WATER, ENSURE THAT THE WATER QUALITY GUIDELINE OF THE JAPAN

REFRIGERATION AND AIR CONDITIONING INDUSTRY ASSOCIATION (JRA-GL-02E-1994) IS MET.

(7) THE STARTUP TIME OF THE ABSORPTION CHILLER IS TYPICALLY 20 TO 30 MINUTES, BUT IT MAY VARY DEPENDING

ON THE MODEL, CHILLED WATER/COOLING WATER CONDITIONS, THE TYPE OF THE STEAM DRAIN RECOVERY SYSTEM,

AND THE LEVEL OF APPLIED LOAD. THE STARTUP PROCESS CONSUMES A LARGER AMOUNT OF STEAM THAN THE RATED

LEVEL (130 TO 140 % OF THE RATED VALUE) AND MAY CAUSE DROP OF STEAM SUPPLY PRESSURE AND FAILURE OF

DISCHARGING THE STEAM DRAIN. IT IS ADVISABLE TO DESIGN THE SYSTEM WITH CONSIDERATION GIVEN TO THESE POINTS.

(8) CONTROL THE COOLING WATER INLET TEMPERATURE BETWEEN 15 AND 32 C. EQUIPMENT/PIPING REQUIRED FOR

CONTROLLING THE COOLING WATER TEMPERATURE ARE NOT IN OUR SCOPE OF SUPPLY. IN TRANSITIONAL SEASONS

OR DURING COOLING OPERATION IN WINTERTIME, THE COOLING WATER TEMPERATURE AND LOAD MAY BE LOW,

AND THE CHILLER MAY FREQUENTLY START/STOP. IN SUCH CASES, IT IS RECOMMENDED TO CONTROL THE COOLING WATER

TEMPERATURE WITH ITS LOWER LIMIT SET TO THE RATED VALUE - 5 C FOR THE STABLE SUPPLY OF CHILLED WATER.

(9) THE DESIGN DRAIN TEMPERATURE AND OUTLET PRESSURE OF THE CHILLER IS 90 C AND 0.2 TO 0.39 MPa (gage).
NOTE THAT THE PRESSURE FALLS TO APPROXIMATELY 0.05 MPa (gage) WITH LOAD REDUCTION.

WHEN SPECIAL SPECIFICATIONS FOR THE HOT WELL TANK POSITION OR THE DRAIN TEMPERATURE ARE

REQUIRED, THE QUOTATION IS RECALCULATED BASED ON YOUR SPECIFICATIONS.

(10) AFTER ON-SITE INSTALLATION, AN AIR-TIGHTNESS TEST AND OPERATION CHECK ARE PERFORMED FOR THE CHILLER.
IF PERFORMANCE CONFIRMATION IS ADDITIONALLY REQUIRED, MAKE SURE THAT SUFFICIENT LOAD IS AVAILABLE.

YOU ARE ASKED TO PREPARE PERFORMANCE MEASUREMENT INSTRUMENTS AND DATA COLLECTION PERSONNEL,

AS WELL AS WATER, ELECTRICITY, AND OTHER UTILITIES NECESSITY FOR THE TEST RUN.

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


P.7

(11) UPON DELIVERY OF THE ABSORPTION CHILLER FROM US, THE UNIT IS TEST RUN AND ADJUSTED FREE OF CHARGE.
AN INSPECTION IS PERFORMED ONCE FREE OF CHARGE BY VISITING THE SITE WITHIN ONE YEAR AFTER
THE START OF OPERATION. IF THE PRODUCT FAILS DUE TO ANY DEFECT ATTRIBUTABLE TO US WITHIN
THE WARRANTY PERIOD, PART REPLACEMENT OR REPAIR IS CARRIED OUT WITHOUT CHARGE. OTHER SERVICES
ARE ALSO AVAILABLE AT YOUR COST. CONSULT US, IF REQUIRED. ESPECIALLY, NOTE THAT TUBE CLEANING
SERVICE IS OFFERED AT YOUR COST. THIS PROVISION IS SUBJECT TO FURTHER NEGOTIATION IN THE CASE OF
USING THE CHILLER FOR INDUSTRIAL PURPOSES.

(12) THE SELECTION OF CHILLER PARTS AND EQUIPMENT SHOULD BE LEFT TO US.

(13) AVOID ABRUPT LOAD FLUCTUATIONS.


ENSURE THAT THE AMPLITUDE OF LOAD FLUCTUATIONS OVER 10 MINUTES IS WITHIN 20 %.

(14) THE STEAM REGULATING VALVE IS DELIVERED SEPARATELY.


YOU ARE ASKED TO PERFORM PIPING AND WIRING WORK FOR THE VALVE.

(15) INSTALL A VALVE ON THE STEAM SUPPLY LINE AND CLOSE IT WHEN STOPPING THE CHILLER.
IN THE CASE OF PROLONGED STOPPAGE OF THE CHILLER WITH THE STEAM SUPPLY VALVE OPEN FOR REMOTE
START/STOP CONTROL, IT IS RECOMMENDED TO INSTALL AN OPTIONAL STEAM SHUTOFF VALVE.

EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.



AC
TITLE INSTALLATION GUIDE DOC. No. CRA139E-K001F REV. 1

CUSTOMER COMPLETE IN 10 SHEETS


WITH COVER

FINAL USER

PROJECT SERVICE

JOB No. EBARA SER. No.

ITEM No. MODEL/ EQUIP. 16JSE/RAW/RCW/REW SET

TO SET

Refrigeration Products
ISSUED BY & System Division

S.Tanaka Feb.28.07

M. Agatsuma Feb.22.07
APPROVED BY

CHECKED BY M. Agatsuma Feb.22.07

7 May,26,09 M.A. T.K.


REV. PAGE DATE APPD BY PREPARED BY T. Kanai Feb.22.07

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.1

CONTENTS

1. FOUNDATION P.2

2. INSTALLATION P.2

3. WATER PIPING P.3

4. STEAM PIPING P.6

5. HANDLING OF THE RUPTURE DISK P.9

6. TYPICAL RELIEF PIPING FROM FUSIBLE PLUG P.9

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.2

1. FOUNDATION

1) The running weight of the Absorption chiller (described in the attached OUTLINE
DIMENSIONS ) is distributed equally on the foundation contact surface
(shown by in the attached FOUNDATION DETAIL ).

2) Fixing to the foundation is conducted by the Anchor Bolt Method.

3) Finished horizontal surface of the foundation should be within the accuracies noted in
the attached FOUNDATION DETAIL.

4) The foundation floor should have carry out waterproofing finish for machine of
maintenance making it easy.

5) Install drainage channels around the machine foundation.

2. INSTALLATION

1) Select location of machine installation to be where good ventilation is available. It is


recommended that a ventilator should be furnished.

2) Avoid a location liable to excessive moisture and dust to prevent future electrical
problems.

3) When the temperature around a Absorption chiller is to be below 0 deg C during


operation, special treatment is required. Consult Ebara in advance.

4) Machine room temperature should not exceed 40 deg C.

5) Pay attention to good lighting for convenient routine monitoring, maintenance and
inspection.

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.3

6) Install the machine on a well drained place.

+20
7) Consider manufacturing allowances as -10
mm to the dimensions of OUTLINE
DIMENSIONS .

8) Prepare sufficient maintenance space (1m min. around the machine. 0.2m min. above
the machine) and a space for withdrawing the tubes referring to attached OUTLINE
DIMENSIONS , and FOUNDATION DETAIL.

9) Regarding the level of the machine, never exceed 1/1000 in both length and width
directions of the shell as below.

10) When installing machine, carry out machine leveling as above using shim liners and then
set anchor bolts and fill anchor holes firmly with mortar. Shim liners are standard
accessories.

3. WATER PIPING

1) Specify the chilled water inlet nozzle at the right side or the left side on the OUTLINE
DIMENSIONS. The inlet nozzle for cooling water is always to the left side of the
machine as shown in the OUTLINE DIMENSIONS. Refer to the OUTLINE
DIMENSIONS and the specification data sheet regarding the nozzle positions, nozzle
side and water pressure drop.

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.4

2) The specifications of nozzle flanges of chilled water and cooling water of the Absorption
chiller is stated in SPECIFICATION DATA SHEET. Companion flanges and bolts
shall be provided by vendor.

3) The maximum allowable working pressure of chilled water lines and cooling water lines
is stated in SPECIFICATION DATA SHEET. Regarding the installed positions of the
chilled water pump, the cooling water pump and the expansion tank or pressurization
unit, design their installed positions so that pressure does not exceed the above
maximum pressure on the Absorption chiller water box when considering both static
water head and pump head.

4) Install stainers of 10 meshes or more at the inlet lines of chilled water and cooling water
to prevent foreign objects entering tubes.

5) Keep the chilled water and the cooling water flow rate always at the specified flow rate.
Install thermometers and pressure gauges immediately adjacent to inlet and outlet of
chilled and cooling water connections to allow easy maintenance. It is recommended
that a flow meter should be provided on the chilled water lines in order to measure the
refrigerating capacity by comparing chilled water flowrate with inlet and outlet
temperatures.

6) Chilled water pump and cooling water pump should be designed specifically for use on
each Absorption chiller.

7) Install an expansion tank or pressurization unit on the chilled water line. ( Refer to the
attached PIPING FLOW SHEET ).

8) 3/4 sockets or Rc3/4 female screws are provided to fit an air vent and a drain valve on
each water box. Mount the respective stop valves to them and run piping into the drain
pit. Install air vent valves at suitable locations on the chilled water piping or the cooling
water piping to eliminate water hammer and air locks.

9) Allow sufficient access for cleaning or replacing tubes.

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.5

10) Provide an adequate water source for tube cleaning.

11) In hydraulic pressure tests of chilled water lines or cooling water lines, always confirm
the test pressure marked on water box flange section of each line and under no
circumstances exceed the marked test pressure. Further, never execute the pressure
test using gas. pressure tests using gas can be very dangerous due to the risk of broken
pieces scattering under failure.

12) Control the water quality according to the standard of the Japan Refrigeration and Air
Conditioning Industry Association (JRA-GL 02-94). Install bleed-off devices on the
cooling water lines. (Refer to an attached PIPING FLOW SHEET ).

JRA-GL 02-94

Cooling Water Chilled Hot Water


Water Tendency
Item Circulating
Circulat- MakeupW Circulating
ing water ater (<20 deg C) (60 deg C Corrosive Scaling
90 deg C)

Standard Item
PH 25 deg C 6.58.2 6.08.0 6.88.0 7.08.0

ELECTRIC CONDUCTIVITY (mS/m) < 80 < 30 < 40 < 30

(S/cm) < 800 < 300 < 400 < 300


-
CHLORIDE ION (mgC1 /l) < 200 < 50 < 50 < 30
2-
SULFURIC ACID ION (mgSO /l)
4 < 200 < 50 < 50 < 30

ACID CONSUMPTION (mgCaCO3/l) < 100 < 50 < 50 < 50

TOTAL HARDNESS (mgCaCO3/l) < 200 < 70 < 70 < 70

CALCIUM HARDNESS (mgCaCO3/l) < 150 < 50 < 50 < 50

IRONIES SILICA (mgSiO2/l) < 50 < 30 < 30 < 30

referent Item
FERROUS (mgFe/l) < 1.0 < 0.3 < 1.0 < 1.0

COPPER (mgCu/l) < 0.3 < 0.1 < 1.0 < 1.0
2-
SULFIDE ION (mgS /l) traceless traceless traceless Traceless

AMMONIUM ION (mgNE4+/l) < 1.0 < 0.1 < 1.0 < 0.1

CHIORINE RESIDUE (mgCl/l) < 0.3 < 0.3 < 0.3 < 0.1

CARBONATION ISOLATED (mgCO2/l) < 4.0 < 4.0 < 4.0 < 0.4

STABILITY INDEX 6.07.0

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.6

13) If the cooling water inlet temperature can fall below 15 deg C at a steady load operation,
provide a by-pass valve for the cooling tower or contriol the cooling water temperature
by scheduling operation of the cooling tower fan(s) so that water does not fall below
15deg C.

14) Connect piping between the absorber and the condenser water box nozzle.
(16JSE032-080, RAW)

15) Install short bent pipes as shown in the drawing below, in the nozzle section of
each water box in order to enable opening of the water box cover.

16) Install a stop valve for chemical tube cleaning on the cooling water pump delivery line.
(Refer to an attached PIPING FLOW SHEET ).

17) Apply adequate supports and flexible piping etc, so that piping weight and vibration have
no direct effect on the Absorption chiller.

4. STEAM PIPING

1) If there is any possibility of the steam supply pressure exceeding 0.78MPaG, a pressure
reducing valve and a safety valve(blow off pressure : 0.88MPaG) should be furnished on
the steam pipe line. The exhaust pipe from the safety valve should be run to a safe
location external to the building.

2) If supply steam temperature to be used is to exceed 175 deg C, a proper


countermeasure such as a desuperheater etc. is to be provided. Contact Ebara for
further information.

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.7

3) Strainers having 80-100 meshes should be located on the up- stream side of the
capacity control valve together with a reducer valve (if provided ).

4) Steam traps should be installed in steam supply line up-stream of steam valve.

5) Allow a length of straight pipe of 1 metre or 10 pipe diameters, whichever is the longer,
before and after the control valve. Piping between the capacity control valve and
generator inlet should slope downwards least 0.2m to prevent flow - back of drain.

6) The capacity control valve (=the steam control valve) is sized by calculating rated supply
pressure ( inlet side of the capacity control valve) and the rated steam consumption. If
the valve size is smaller than the piping diameter, inlet and outlet piping diameter is to
be reduced gradually with pipe reducing fittings.

7) A pressure gauge (range : 0-1.5MPaG) are to be installed respectively before and after
the capacity control valve. It is recommended that by - pass piping around the capacity
control valve be provided for convenient maintenance and inspection of the control valve.

8) Installation of the nozzle flange of the generator should be detachable so that bolts can
be easily tightened after initial steam application.

9) Install short bent pipes as shown in the drawing below, in the nozzle section of the
steam box on the high temperature generator in order to enable opening of the steam
box cover.

1 10) Connect the generator nozzle using a flexible pipe or equivalent to prevent the nozzle
flange of the generator from excess force due to thermal expansion.

11) A check valve and a stop valve should be installed at the outlet of steam drain.

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.8

12) In applications employing electrical capacity control, install wiring between the capacity
control valve motor and the junction box mounted on Absorption chiller at job site. If
pneumatic capacity control is used, install air piping between the actuator of the capacity
control valve and the temperature controller mounted on the Absorption chiller.

13) Allowable back pressure on the steam condensate outlet of the chiller is 0.05MPaG
when the steam supply pressure is 0.78MPaG. Steam condensate piping shall be
designed suitable for those pressure.

14) In case of installation of any Absorption chiller, each Absorption chiller should be
installed the separate steam drain piping. If that piping should be used in common, it will
be possible to make troubles.

15) Control the water quality for steam according to the following table.

Steam Condensate Quality Standard


Item Standard

pH (25 deg C) 7.5 8.5

ELECTRIC CONDUCTIVITY (S/cm) (25 deg C) <10

ACID CONSUMPTION (pH4.8) (mgCaCO3/l) <10

TOTAL HARDNESS (mgCaCO3/l) <1

+
AMMONIUM ION (mgNH 4/l) <0.1

-
CHLORIDE ION (mgCl /l) <20

2
SULFURIC ACID ION (mgSO4 -/l) <10

HYDROGEN SULFIDE (mgH2S/l) traceless

DISSOLVED OXYGEN (mgO/l) <0.2

CARBONIC ACID (mgH2CO3/l) <20

FERROUS (gFe/l) <300

COPPER (gCu/l) <300

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


DOC.No. CRA139E-K001F REV.1 P.9

5. HANDLING OF THE RUPTURE DISK

Rapture disk should be handled carefully to prevent external damage during transportation
or setting-up of Absorption chiller.

Install appropriate piping from the rupture disk to safety place where nobody is damaged
with spouted solution or refrigerant vapor from the rupture disk at the burst of the rupture
disk.

Accumulating tank to keep those liquids from the rupture disk is recommended to install at
the intermediate of exhaust piping line to prevent discharging to the surroundings.

6. TYPICAL RELIEF PIPING FROM FUSIBLE PLUG

1) Be sure not to loose the machine side thread of the fusible plug when the exhaust piping
work behind the fusible plug is performed. The loosen connection may cause air
tightness trouble .

2) Perform the exhaust piping work in order to assemble or disassemble itself easily. It
makes easy to do air tightness test around the fusible plug at periodical maintenance.

3) Apply adequate supports so that the fusible plug exhaust piping weight have no direct
effect on the fusible plug.

PM32U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


CRA605E-H001

INSTRUCTION MANUAL

STEAM DOUBLE-EFFECT
ABSORPTION CHILLER
MODEL REW SERIES

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Introduction

Introduction
Thank you for purchasing a REW Series Absorption Chiller from the Ebara
Refrigeration Equipment Systems
This Instruction Manual provides the information that is necessary for the operation,
maintenance of the absorption chiller, and describes its construction.
Prior to operate this absorption chiller, be sure to read and understand thoroughly
this manual and specified documents such as Specifications, Installation
Instructions, etc. The instructions in these documents are prepared to ensure correct
and safe operation of the absorption refrigerator, and to prolong its service life.

CAUTION
For safety:

Before using the machine, thoroughly read Chapter 1 Safety Instructions, so that
you will use the machine safely and correctly.

The safety instructions in Chapter 1 are divided into WARNINGS and


CAUTIONS.

WARNINGS contain the most important instructions, failure to


follow these instructions could result or serious injury.
The instructions given in CAUTIONS are less important, but failure to follow
them could have serious consequences in certain circumstances.
Both types of instruction are important for safety and must always be followed-up.

After reading this manual, keep it at the place where operators can
consult it at any time.

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Introduction

Environmental Considerations
(Instructions for Operation)
Absorption chiller (models using a Molybdenum based absorbent
Considerations for environmental conservation
To pursue the purposes of the PRTR Law and the MSDS Law enacted/enforced to promote improvements
in the voluntary control of chemical substances by businesses and to prevent any impediment in
environmental protection, considerations for environmental conservation are given below.
Mishandling absorption chillers (generally referring to absorption chillers and chiller-heaters) and their
accessories may impose extra burden on the environment. To operate them or perform work/maintenance
for them, pay close attention to the following considerations.
Reference) PRTR Law: Law Concerning Reporting, etc. of Release of Specific Chemical
Substances to the Environment and Promotion of the Improvement of Their
Management (PRTR stands for Pollutant Release and Transfer Register.)
MSDS Law: Ministerial Ordinance to Define the Method of Offering
Information on the Properties and Handling of Specific Chemical Substances
(MSDS stands for Material Safety Data Sheet.)

1. Chemical substances
The following chemical substances are generally used for newly installed absorption chillers.
They are not specific chemical substances subject to the PRTR Law.

Absorbent (Molybdenum based): Lithium bromide solution (containing less than 0.1 % of inhibitor):
approx. 1000 kg/100 USRt
Performance enhancement agent:Octyl alcohol:approx. 3.8 L x 1 bottle/100USRT
Lubricant: Mineral oil (attached to models with a purge (vacuum) pump): 500 mL x 3 bottles/unit
Sealant: Anaerobic sealant: 50 mL x 1 to 2 bottles/unit
(attached for on-site welding if a split unit is carried in)

Pure water (ion-exchanged water) of 50 to 500 kg (per unit) may be attached as a refrigerant.
The quantities above are for reference only. For actual quantities required for specific chillers, contact
us or your service agent after checking the serial number written on the nameplate.

2. Packaging materials
For unnecessary packaging materials after carry-in/installation, have them disposed of by a specialist
company.
2-1 For cardboard boxes, wooden crates, and plastics, have them disposed of by a specialist company.

2-2 Steel materials, such as frames used for carry-in, can be disposed of by us at your cost.

3. Absorbent
An absorption chiller is filled with an absorbent (lithium bromide solution), a refrigerant (pure water), and a
small amount of performance enhancement agent (Octyl alcohol). The absorbent (lithium bromide
solution) contains a trace of inhibitor.
If the chiller is damaged or if its valves are mishandled, the undiluted absorbent may leak through the drain
to the outside of the building. To prevent it, pay attention to the following.

3-1 Facility considerations


The following measures should be implemented to protect against possible leakage.
To prevent the absorbent from leaking into the foundation, the surface of the chiller installation floor
should be waterproof/water-repellent.
Also, a measure to prevent the absorbent from flowing directly into the drain should be provided.
For example, a temporary shut-off mechanism for the drain port with liquid absorbing materials
around it or a flood prevention ditch/weir around the chiller may be provided on.

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Introduction
3-2 Considerations upon carry-in/installation
When carrying in and installing the chiller filled with the absorbent, pay close attention not to damage
it. Particularly, small tubing and valves should be protected from being stepped on.

3-3 Considerations upon storage


Do not touch the valves in the chiller.
If the chiller is under vacuum, never perform welding for vacuum sections, such as the shell.
During storage, monitor changes in the internal pressure by the vacuum gauge on the chiller.
To store the absorbent in plastic containers, keep them out of reach and handle them carefully. Put
plastic sheets on the floor, and make sure that the containers are stacked in 2 layers or less.
Protection measures (fall prevention, sunshade sheet to protect from solar radiation through
windows,etc.) should be provided.
In the vicinity of the storage area, avoid performing any work that may damage plastic containers,
such as welding.

3-4 Filling/adjusting the absorbent


Your service agent will fill the chiller with the absorbent at the time of commissioning. Please inform
us of the date of commissioning as soon as fixed.
The absorbent will be adjusted by your service agent based on the analysis of absorbent samples
taken periodically. Please request us for the work. More frequent absorbent adjustments (every 2 to
3 months) are required for chillers that are operated for a longer time per day.
If the absorbent must be replenished, contact us so that your service agent refills the chiller with the
specified absorbent.

3-5 Considerations during operation


Be careful not to touch the valves in the chiller and not to step on small tubing and valves to avoid
damaging them.
Perform a regular check around the chiller at least once a day.
If a leak is found, immediately stop the chiller and inform your service agent of the leak location,
condition, and amount.
The absorbent itself is odorless, but the inhibitor mixed in it is volatile and has an alcohol odor. The
absorbent may cause metal corrosion, leather/fiber shrinkage, or skin irritation. Wear rubber gloves,
protective goggles, etc. to avoid directly contacting it. If the absorbent contacts your body, wash off
with plenty of water. Also, thoroughly clean or wash fixtures, tools, clothes, etc. with water, and
provide rust prevention measures (e.g. greasing) for metal parts.
Upon leakage, close it by securing a plastic sheet, etc. to the leak location.
When an auxiliary vacuum pump for maintenance is available on the chiller side, perform vacuum
extraction from the shell of the chiller.
Wipe the spilled absorbent using highly absorbable materials, such as sand, sawdust, waste paper,
and waste cloth. Seal the used absorbing materials in plastic bags/containers and have them
disposed of by a specialist company. Use water to thoroughly clean or wash the floor surface that
the absorbent contacted. Then, clean or wash the floor surface with water again after drying for
about one day. Do not discharge the absorbent directly to the drain. If the absorbent is discharged
from the drain, perform emergency measures, such as temporarily shutting off the flow.
If there is a possibility of discharging the absorbent to the drain, flush the drain with sufficient water
to dilute the absorbent (65 times in weight or 100 times in volume of the discharged absorbent) for
odor or metal corrosion prevention.

3-6 Considerations upon absorbent disposal


For a used absorbent/refrigerant extracted from the chiller upon maintenance, etc., have it disposed
of by your service agent. Do not discharge it directly to the drain.

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Introduction

3-7 Considerations upon chiller disposal/scrapping


Request us to handle the absorbent in the chiller in advance.
Special knowledge and techniques, such as treating the absorbent accumulated in the chiller, are
required to address possible absorbent leakage during scrapping. Your service agent will extract and
collect all the remaining absorbent.
The collected absorbent will be treated by a specialist company for reusing it as a resource.

4. Oil
To manage a lubricant for the purge pump (if provided with absorption chillers/chiller-heaters) or a fuel oil
for oil-fired chiller-heaters, pay attention to the following.
4-1 Lubricant
Add an appropriate amount of the lubricant to the purge pump while checking the oil gauge after
stopping the pump. If the proper level is exceeded, discharge the excessive lubricant from the drain
valve. Overfilling may cause the blowout of the lubricant from the pump discharge during pump
operation. If the accumulation of condensed water in the lubricant exceeds the proper level, the
lubricant may also blow out from the pump discharge during pump operation. Check the oil gauge
periodically and discharge the excessive lubricant from the drain valve, if required.
The lubricant should be replaced periodically. Use the specified lubricant only. Waste lubricant may
contain the absorbent, water, and performance inhibitor. Have it disposed of by a specialist company.
Do not discharge waste lubricant directly to the drain.

4-2 Fuel
Oil fired absorption chiller/heater damages the fuel oil piping etc. or mistakes the handling such as
valves and does the oil leakage etc. The fuel oil might flow out directly from the drain ditch outside
the building. Please note each item.
Asking in equipment
It must not flow directly into the drain ditch when the fuel oil leaks.
For Example, the outlet stopping lid is prepared. Or, the fuel equipment and piping are made a
coating that prevents oil. There is a method of setting up the side ditch and the oil retaining wall.
Asking under use
The fuel oil must use specified oil. Oil outside specification might interfere to pakkin used for the
oil piping and other parts. Please note it.
Please do not touch mistaking it to valves of the fuel oil piping. Please do not damage it by putting
the foot on the small piping and valves.
Please open a fuel oil supply former valve after confirming oil doesn't leak when
it starts every day first time. Please check the machine surroundings once or more a day going.
Please promptly stop the machine, intercept the fire, and close a former valve of the fuel oil
service tank when the fuel oil begins to leak from the fuel piping (The equipment side is laid, and
include it in equipment). Please contact the leakage location, the leakage condition, and the leak
rate, etc. our service technology member of charge.
Please close the upstream side valve in the vicinity of the leakage location.
Please do not throw the fuel oil directly to the drain ditch.
Please give the emergency measure such as damming up temporarily when flowing out
from the drain ditch.
Please spread the material that absorbs oil when leaking to the floor side.
Asking a long time stopping
The fuel oil supply valve is to close without fail and confirm that it is, please when you stop the
machine for a long time.

5. Exhaust gas
Absorption chiller-heaters are not legally defined as boilers. However, they may be deemed as
soot/smoke emitting facilities depending on the firing rate; in such cases, they are subject to the
emission standard of soot/dust, SOx, and NOx set by the Air Pollution Control Law. Consult your local

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Introduction
Bureau of Environmental Protection since the emission of exhaust gas is regulated differently by each
prefecture's ordinances, and related laws/ordinances may be revised. The user may be required to
periodically submit the report of measurements after starting chiller operation.
For EBARAs absorption chiller-heaters, burner combustion has been adjusted to satisfy the emission
standard. Use the specified gas and operate the chiller within the rated firing rate. Using a fuel that
consists of different components or of low quality may cause poor combustion, and the exhaust gas may
impose extra burden on the environment.
If the burner must be adjusted, have it adjusted by your service agent.

6. Energy saving operation


Perform the inspection and maintenance of ancillary facilities so that no energy is wasted during the
operation of absorption chiller-heaters.

6-1 Water quality in the cooling water system


With facilities that are open to air and are highly likely to cause water contamination (cooling water
system, etc.), chiller efficiency may decrease due to scale in the heat transmission tubes that
interrupts heat transmission. Control the water quality properly; if required, remove scale in the heat
transmission tubes in the cooling water system.

6-2 Cooling water pump and cooling tower


A decrease in the cooling capacity of cooling water reduces chiller efficiency. To check if the cooling
water circulation pump is operated under rated conditions or if the cooling tower capacity is sufficient,
monitor that the chiller runs with its cooling water inlet/outlet temperature within the specified range.

6-3 Vapor drain system


For chillers using steam as a heat source, the strainer in the steam drain system may be clogged
due to the effect of steam boiler chemicals. Clean the strainer, if required.

6-4 Cooling load


If cooling (heating) load is low, and the temperature regulation based on the chilled (hot) water
temperature frequently starts/stops, energy can be saved by setting a larger differential between the
thresholds for automatic stop and automatic restart to reduce the start/stop frequency, or if possible,
by stopping the temperature regulation.
Absorption chillers maximize the performance of cooling operation in the absorber by concentrating
the absorbent in the generator. When not in use, the absorbent is normally diluted to a uniform
internal concentration to prevent crystallization. If cooling load is too low, the absorbent is
concentrated by the heat source in the generator after startup. However, the temperature regulation
stops soon, and dilution operation for uniform concentration starts. Such frequent start/stop
operations waste energy.

7. Maintenance and inspection


To minimize aging, maintain optimal conditions, and provide efficient operation, perform periodic
maintenance/inspection, as well as overhaul and parts replacement as required. Maintenance support
and maintenance contracts, is provided by us. Please make a request, if required.

7-1 Maintenance management


The following items are important for the maintenance management of absorption chillers.
Vacuum management (air-tightness, purge equipment, etc.)
Absorbent management (corrosion suppressant, alkalinity, products, etc.)
Water quality management (chilled water, cooling water, and hot water systems)
Heat source facility management (combustion, steam, and heat source hot water facilities)

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Introduction
7-2 Periodic inspection
For the details of periodic inspection and periodic replacement of consumable parts, see the
appropriate section of this Instruction Manual. Use the specified parts for replacement. Have repair
and replacement performed by your service agent.

7-3 Prolonged shutdown


To stop using the chiller for a long period, make sure that the heat source or fuel gas supply valve is
closed. During prolonged shutdown, keep power supplied to the chiller control panel (required for
preserving microcomputer memory). To stop using the chiller for six months or longer, it is
recommended to fill the unit with nitrogen gas for preventing air from entering the unit and to provide
protection measures for electric instruments (e.g. rust prevention with desiccant agents). Have such
preparations made by your service agent. It is also recommended to drain the cooling water system
after tube cleaning for antifreeze and to refill it with nitrogen gas for rust prevention.

7-4 Unnecessary parts


For unnecessary parts after replacement, have them disposed of by a specialist company. For
absorbent disposal, see Section 3-6. For lubricant disposal, see Section 4-1.

8. Relocation/disposal of equipment
To relocate, dispose of, or scrap an absorption chiller, special knowledge and techniques, such as handling
the absorbent in the unit, are required. Never discharge the absorbent in the chiller directly to
the drain.

8-1 Relocation
To relocate the chiller to another site, consult your service agent on absorbent handling, vacuum
maintenance, equipment protection, etc.

8-2 Before disposal/scrapping


Have the absorbent in the chiller handled by your service agent in advance (see Section 3-7).

8-3 Disposal/scrapping
Have the chiller disposed of/scrapped by a specialist company that separates materials, such as
copper and steel, for reusing them as resources.

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

CONTENTS

CONTENTS

Introduction
Environmental Considerations
Chapter1 Safety Instructions
Chapter2 Functions and Appearance
Chapter3 Control Panel
Chapter4 Operation
Chapter5 Maintenance and Treatment
Chapter6 Troubleshooting
Chapter7 Maintenance Contract
Chapter8 Others

PM15U EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.


INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001

Chapter1 Safety Instructions P 1-1

Chapter 1 Safety Instructions


Instructions relating to operation.
Instruction relating to repair, shifting and scrap
Instructions for safe working.

Instructions relating to operation

WARNING
Instructions
Before cleaning or inspecting the cooling tower fan, or chilled water
pump, etc., (whose operation is coupled with that of the
absorption chiller) be sure to turn off the power to such
equipment.
Otherwise, you could be injured by electric shock or by the equipment
operating.
Stop the absorption chiller immediately if fire, earthquake or
lightning occurs.
Continuing operation in such situations could result in fire or electric
shock.
Do not touch the components or wiring inside the operation
panel, especially of your hands are wet.
You could receive an electric shock if you touch these items.
Carry out the periodic inspection on the high temperature
generator once a year.
The unit is defined as a second class pressure vessel in Industrial Safety
and Health Law.
Do not place inflammable hazardous substances (gasoline,
thinner, etc.) or easily combustible materials in the vicinity of the
absorption chiller.
Doing so could result in fire.
Do not put fingers or bars into the rotating parts of the fans or
pumps.
Such rotating parts will injure you.
Do not place materials in the operation panel or Ventilating hole
of outdoor cover.
Doing so could result in fire or breakdown.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001

Chapter1 Safety Instructions P 1-2

CAUTION
Instructions
When a safety device or protective device is actuated, do not
restart operation until the cause of the actuation has been
eliminated.
Restarting operation without eliminating the cause of the fault could result
in fire.
Do not place heavy objects on the machine body or the operation
panel, and do not get on top of the equipment.
Falls could result in injury.
Have inspection and maintenance of the machine and equipment
performed by your service agent.
Erroneous or poor inspection/maintenance could result in electric shock,
fire or burn injury.
Put up signs forbidding unauthorized persons to touch the machine.
If there is danger that persons may touch the machine in spite of warning signs,
fence off the machine.
Misuse of the machine could result in injury.
Do not allow water to get onto or into the machine body or the
operation panel.
Presence of water could result in electric damage or electrical leakage.
Use only fuses of the correct capacity.
Incorrect capacity fuses will cause breakdown of the equipment, or fire.
Use only the power supply stipulated on the equipments
nameplate.
Use of an incorrect power supply will result in fire or electric damage.
Keep the chilled water, cooling water and steam at the prescribed
pressures at all times.
Other pressures could result in spouting or leaks, which could cause
injury.
During storage of the machine, do not touch the absorbent, or leaked
absorbent, with bare hands.
The absorbent will inflame skin, and will corrode metals that it comes into
contact with.
Do not alter the value settings of the safety devices and
protective devices.
Operation with incorrect value settings could lead to breakdown or fire.
Do not touch those parts where a Caution! High temperature!
sticker is affixed.
Touching such parts will result in burn injury.
Stop the operation of the purge pump before changing the oil
The oil will spout and may result in burn injury.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001

Chapter1 Safety Instructions P 1-3

Where outer casings are installed: Some outdoor covers are very heavy; take
special care when installing or removing such covers in moderate gale. Securely
install fixtures so that they will not fall off.
Careless handling of such covers could result in injury.
Where outer casings are used: Do not run the machine with the covers
opened.
Exposure to wind and rain could cause breakdown or electrical leakage in
electrical components.

Instruction relating to repair, shifting and scrap


WARNING

Instructions
Disassembly, repair and remodeling of the absorption chiller

should be performed by a specialist company only.
Errors in repair could result in electric shock or fire.

CAUTION

Instructions
Have shifting or transportation of the absorption chiller

performed by a specialist company.
Errors in shifting or transportation work could result in damage, water
leaks, electric shock or fire.
Have disposal of the absorption chiller performed by a

specialist company.
Incorrect disposal could lead to leaks of the absorbent from the
machines interior, which could cause skin inflammation and corrosion of
metals.

Instructions for safe working


1. Please have room and do the absorption driving of the Absorption chiller.
It takes 30 minutes from 20 minutes to the state of the ratings driving in the
method of popular use.
2. For scavenging or pressurizing of the absorption chillers interior, always use

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001

Chapter1 Safety Instructions P 1-4

nitrogen. Never use oxygen or air at any cases.


3. When pressurizing the absorption chiller body, NEVER exceed a reading of 7.8
10-2 MPa(gage) (0.8kgf/cm2(gage)) on the pressure gauge.
Have pressurization of the absorption chiller body performed by your service agent.
4. Never perform welding work on the absorption chillers vessels when its
interior is under a vacuum.
5. When performing pressure tests using water on the chilled water and cooling water
systems, never exceed the test pressure stamped on the water chamber flange
parts in each system.
Never use gas to perform pressure tests. Use of gas for pressure tests could
result in bursting, producing hazardous flying splinters.
6. For replacement parts, use only items specified by our company.
Consult your service agent before performing repair or replacement.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 2 Functions and Appearance P 2-1

Chapter 2 Functions and Appearance


Functions .
Appearance .

Functions
The REW series absorption chiller is a double-effect absorption chiller powered by steam.
It uses water as refrigerant and lithium bromide (LiBr) as absorbent. It uses an evaporator
to produce chilled water for cooling.
As can be seen from the appearance, the absorption chiller integrates an evaporator, an
absorber, a condenser and a low temperature generator inside a shell housing, with the
high- temperature generator deployed alongside the shell. The other components of the
machine are the solution heat exchanger, solution pump, spray pump, refrigerant pump,
steam control valve and control panel.
Major components and their functions
Evaporator
Refrigerant liquid is sprayed onto the evaporator tubes and vaporized under high vacuum;
the refrigerant on the surfaces of the tubes takes evaporation latent heat from the cold
water flowing inside the pipes, thus lowering the temperature of the chilled water.
Absorber
Absorbent is sprayed onto the absorber tubes by solution spray pump, where it absorbs
the refrigerant vaporized from the evaporator. The absorption heat generated by such
absorption is taken up by the cooling water flowing inside the tubes, enabling absorption to
continue on the outsides of the tubes. Absorbent that has absorbed refrigerant vapor and
been diluted thereby (referred to as weak solution below) is sent by the solution pump to
the high- temperature generator and low temperature generator, via the solution heat
exchanger.
High temperature generator
In the high temperature generator, the weak solution sent from the absorber by the solution
pump is heated by steam supplied from the high-temperature generator. When heated, the
weak solution gives off high-temperature refrigerant vapor, and thereby becomes
concentrated once again (referred to as strong solution below). This strong solution is
returned to the absorber via the solution heat exchanger.
Low temperature generator
The high-temperature refrigerant vapor generated by the high temperature generator is
drawn into the low temperature generator tubes, and heats the solution on the outsides of
the tubes, thereby concentrating the solution. The concentrated solution (absorbent) is
then returned to the absorber as strong solution, via the solution heat exchanger.
Condenser
In the condenser, the refrigerant vapor generated by the low temperature generator while
heating the solution is cooled by the cooling water flowing through the condensers heat
transmission tubes, and is thereby condensed into liquid refrigerant. The liquid refrigerant
is returned to the evaporator, where it is once more sprayed onto the evaporators heat
transmission tubes

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 2 Functions and Appearance P 2-2

Solution heat exchangers


The solution heat exchangers effect exchange of heat between the low temperature weak
solution from the high and low temperature generators and the high temperature strong
solution from the high and low temperature generators, so as to enhance the thermal
efficiency of the absorption chiller.
Drain heat exchanger
To weak solution of low temperature sent from absorber to high temperature regenerator
and What condenses steam used to heat high temperature regenerator and became drain
water are heat exchanged. As a result, the efficiency of the absorption freezer rises.
Refrigerant heat exchanger
To Refrigerant sent from condenser to evaporator and a part of cooling water that flows in
absorber are heat exchanged. As a result, the efficiency of the absorption freezer rises.
Steam control valve
This electrically operated steam control valve receives signal from the control panel and
controls the amount of steam flowing to the high-temperature generator in response to
changes in cooling load. Thus, the cooling water inlet temperature is maintained at
specified temperature.
Solution pump, spray pump, and refrigerant pump
Since they must be able to resist vacuum pressure, these pumps are hermetic pumps.
Each pump uses some of its discharge fluid (solution or refrigerant) as the lubricant for its
bearings and as the coolant for its motor.
Control panel
The operation of the absorption chiller is controlled by microcomputer. The control panel
houses functions indispensable for the operation of the absorption chiller, including
detection by safety circuits, operational control of the various equipment and valves and
capacity control. The panel also provides displays giving accurate indications of the
operating conditions.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 2 Functions and Appearance P 2-3

Appearance

z REW Absorption Chiller Front view (Shape may be different depending on model)
(015025)

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 2 Functions and Appearance P 2-4

z REW Absorption Chiller Rear view (Shape may be different depending on model)
(015025)

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 2 Functions and Appearance P 2-5

z REW Absorption Chiller Front view (Shape may be different depending on model)
(028050)

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 2 Functions and Appearance P 2-6

z REW Absorption Chiller Rear view (Shape may be different depending on model)
(028050)

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-1

Chapter 3 Control Panel


Front of control panel P.
Overview of displays and controls P.
Detailed descriptions P.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-2

Front of control panel


For the control panels appearance, see Chapter 2.

Absorption Chiller Control Panel

CONT.VALVE CLOSED
POWER

STOP

RUNNING

DILUTION

FAILURE
SAFETY EQUIP.

PRE-ALARM
STOP RUN STOP RUN STOP RUN

SOL. SOL. REF.


PUMP SPRAY PUMP
PUMP

SELECT. SET
MODE

OPERATG STATUS H. GEN. TEMP. CYCLE TEMP.


CHILLED WATER TEMP. COO L. WATER TEMP CONT. VALVE OPEN ESC JUMP
OPERATG hrs . STEAM HEATING hrs. REF. PUMP hrs.

NO. OF RUN/STOP NO.OF STEAM HEATING SOL. PUMP hrs.


INC . HOME
C/H TEMP. SET. DATE & TIME SET. OPTIONAL SET.
MAINTENANCE SETTING 1 SETTING 2
DEC
SETTING 3 SETTING 4 SETTING 5 SET

SETTING 6 SETTING 7 SETTING 8

REMOTE AUTO RUN


LOCAL MANUAL STOP
CONTROL PURGE
OPERATION
VALVE PUMP

BUZZER BUZZER
STOP START
STOP

Fig. 3.1 Front of control panel

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-3

Overview of displays and controls


Below is an overview of the control panels displays and controls.

Names of displays
and controls
Absorption Chiller Control Panel









Operation displays
POWER

STOP
RUNNING
DILUTION
SAFETY EQUIP.
PRE-ALARM
FAILURE
CONT.VALVECLOSED
STOP RUN STOP RUN STOP RUN
Lamps indicating
SOL. SOL. REF. operating conditions.
PUMP SPRAY PUMP
PUMP

Digital display
Displays various setting
SELECT. SET values and operation
MODE conditions in digital form.

OPERATG STATUS H. GEN. TEMP. CYCLE TEMP Item selector keys


CHILLEDWATERTEMP. COOLING WATERTEMP. CONT. VALVE OPEN Switch among setting
ESC JUMP
and displaying of control
OPERATG hrs. STEAM HEATING hrs. REF. PUMP hrs.
data.
NO. OF RUN/STOP NO.OFSTEAM HEATING SOL. PUMP hrs.
INC. HOME
CHILLER TEMP. SET. DATE & TIME SET. OPTIONAL SET.
MAINTENANCE SETTING 1 SETTING 2
DEC
SETTING 3 SETTING 4 SETTING 5 SET
Selected item displays
SETTING 6 SETTING 7 SETTING 8 Lamps indicating items
selected using the item
selector keys.
REMOTE AUTO RUN
LOCAL MANUAL STOP
OPERATION CONTROL PURGE
VALVE PUMP
Operation switching keys
Switch among local/remote
operation, auto/manual
operation, etc.
STOP START BUZZER
BUZZER
STOP

The push button style (Option) does


Operation keys
operation with push buttons.
For running/stopping the
machine, and resetting the
buzzer.

STOP START BUZZER


STOP

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-4

Detailed descriptions
Operation displays

Lights when the power is turned on.

Indicate whether the absorption chiller is operating or stopped.

Lights to indicate that dilution is being carried out.

Lights to indicate that the safety circuits are normal.


(See note below)

Lights if pre-alarm is issued.

Lights if failure occurs.

Lights to indicate that the steam


control valve is closed.


POWER

STOP

RUNNING

DILUTION

SAFETY EQUIP.

PRE-ALARM

FAILURE

CON T.VALVE CL OSED

STOP RUN STOP RUN STOP RUN

SOL . SOL. REF.


PUMP SPRAY PUMP
PUMP

Indicate whether the solution pump is running or stopped.

Indicate whether the spray pump is running or stopped.

Indicate whether the refrigerant pump is running or stopped.

The term safety circuits refers to the following safety functions: external
emergency stop signal and seismometer.
Note that it is possible that there is abnormality in these items even when this
indicator is lit.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-5

Detailed descriptions (continued)


Digital display and Selected item displays
Digital display
6-digit display. Each
digital place is made up
of 7 segments.

Selected item displays


The item with lit LED lamp
is the item whose value is
OPERATG STATUS H. GEN. TEMP. CYCLE TEMP. displayed.
CH ILL ED WATER TEMP. COOL.WATER TEMP CONT. VALVE OPEN
OPERATG hrs. STEAM HEATING hrs. REF. PUMP hrs.
NO. OF RUN/ STOP NO.OF STEAM HEATING SOL. PUMP hrs.
CHI LLER TEMP. SET. DATE & TIME SET. OPTIONAL SET.
MAINTENANCE SETTING 1 SETTING 2
SETTING 3 SETTING 4 SETTING 5
SETTING 6 SETTING 7 SETTING 8

Sample display: Chilled/hot water temperature

Description
Chilled water temperature is the item
selected
OPERATG STATUS H. GEN. TEMP. CYCLE TEMP b1 indicates chilled water inlet temperature.
CHILLED WATER TEMP. COO L. WATER TEMP. CONT. VALVE OPEN The current chilled water temperature is
OPERATG hrs. STEAM HEATING hrs. REF. PUMP hrs.

NO. OF RUN/STOP NO.OF STEAM HEATING SOL. PUMP hrs. 12.0.


CHILLER TEMP. SET. DATE & TIME SET OPTIONAL SET
MAINTENANCE SETTING 1 SETTING 2
SETTING 3 SETTING 4 SETTING 5
SETTING 6 SETTING 7 SETTING 8

Pressing SELECT. in the item


selector key. At this point will bring
up a display like that shown below
on the left.

OPERATG STATUS H. GEN. TEMP. CYCLE TEMP Description


CHILLED. WATER TEMP. COOL. WATER TEMP. CONT. VALVE OPEN
Chilled water temperature is the item selected.
OPERATG hrs. STEAM HEATING hrs. REF. PUMP hrs.

NO. OF RUN/STOP NO.OF STEAM HEATING SOL. PUMP hrs. b2 indicates chilled water outlet temperature.
CHILLER TEMP. SET DATE & TIME SET OPTIONAL SET The current chilled water temperature is
MAINTENANCE SETTING 1 SETTING 2
SETTING 3 SETTING 4 SETTING 5 7.0.
SETTING 6 SETTING 7 SETTING 8

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-6

Detailed descriptions (continued): Sample display (condition display)

Cooling tower fan condition


When CONDITION DISPLAY
F: Run command issued
item is selected: O: STOP command issued
Note: This indicates the signal output
from the microcomputer; when the
cooling tower fans operation is not linked
to the control panel, this may not indicate
the fans actual condition.

Cooling water pump condition

Indicates chilled water pump condition

P: Running (interlock and flow switch both ON)


U: Interlock only ON
F: Flow switch only ON
O: Stopped (interlock and flow switch both OFF)
Note: When there is no cooling water flow switch, the

cooling water pump indications are as follows:

P: Running (interlock ON)

O: Stopped (interlock OFF)

Combustion status
H: Heating A: Temperature regulation stopped
O: Stopped J: Checking safety circuits

Steam control valve status


: Automatic control o: Controlling degree of opening
C: Forced closing s: Soft start-up

Operation mode
C: Cooling
U: Automatic restart after power failure

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-7

Detailed descriptions (continued)

Sample display (fault display)

Should a fault occur, an error codes will be displayed. When an error code is
displayed:
Make a note of the error code.
Refer to Chapter 4 for details of what action to take for the error code.
Press the STOP button to reset the error.
Note down this
number.
Quote the number to
your service agent.

OPERATG STATUS H. GEN. TEMP. CYCLE TEMP.

CHILLED WATER TEMP. COOL. WATER TEMP CONT. VALVE OPEN

OPERATG hrs. STEAM HEAT ING hrs. REF. PUMP hrs.

NO. OF RUN/STOP NO.OF STEAM HEATING SOL. PUMP hrs.

CHILLER TEMP. SET. DATE & TIME SET. OPTIONAL SET.

MAINTENANCE SETTING 1 SETTING 2

SETTING 3 SETTING 4 SETTING 5


SETTING 6 SETTING 7 SETTING 8

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-8

Detailed descriptions (continued)

Item selector keys


Selected item display
The item with the lit lamp is the one
selected.
DISPLAY SET
ITEM VALUE
SELECT. CHANGE

OPERATG STATUS H. GEN. TEMP. CYCLE TEMP.


CHILLED WATER TEMP. COOL. WATER TEMP. CONT. VALVE OPEN ESC
Displays sub-items in sequence.
JUMP
OPERATG hrs. STEAM HEATING hrs. REF. PUMP

Each press of the switches to display of


hrs.

NO. OF RUN/STOP NO.OF STEAM HEATING SOL. PUMP hrs.


INC . HOME
CHILLER TEMP. SET DATE & TIME SET OPTIONAL SET
MAINTENANCE SETTING 1 SETTING 2
SETTING 3
SETTING 6
SETTING 4
SETTING 7
SETTING 5
SETTING 8
DEC SET
another item.
If there are no sub-items, pressing the key will
switch to the next item.
Detail
Used for changing the various set
values.
Before changing the settings, be sure to
contact your service company.
SET
SELECT.
MODE Switch among selection items. Press to
move the selection either to right or left
one at a time.

Press to cancel setting change.

ESC JUMP

Press to jump ahead to the


INC. HOME third next item.

DEC SET Press to return to the first item.

Used to set changes to or


registration of set values.

Used to decrease set values during set value change.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-9

Detailed descriptions (continued)

Operation switching keys

REMOTE AUTO RUN


LOCAL MANUAL STOP
OPERATION CONTROL PURGE
VALVE PUMP

Purge pump
Display of purge pumps operation condition.
Pressing the button down for 2 seconds activates
the auto purge circuits. Pressing the button again
stops purging immediately.
Before performing this purging operation, make
sure the machines condition is appropriate for it.

Steam control valve auto/manual selection


Pressing the button toggles between manual and auto
operation of the valve.
The lighting of the lamps indicates whether the valve
is in auto or manual operation.
Remember that when operation is manual, the
steam control valves opening degree is fixed.
The process of changing the opening degree of the
steam control valve is as follows.
Set the selected item display to CONT. VALVE
OPEN.
Using the SELECT. on the item selector key, select
GL.
Change the value with using INC. and DEC. keys.
The selected GL value represents the opening
degree of the steam control valve.

Operation mode selection


Pressing the button toggles between remote and local control
operation modes.
The lighting of the lamps indicates whether the machine is
under remote or local control.
For the remote control mode, monitoring of the
absorption chillers operation is necessary.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 3 Control Panel P 3-10

Detailed descriptions (continued)

Operation keys

STOP START BUZZER


STOP

Turns off the buzzer after it has


sounded.
Resets pre-alarms.

Pressing this when the absorption chiller is


in the local control mode starts operation.

Stops operation.
Pressing this when the absorption chiller is in the
remote control mode switches to the local control
mode.
Also used to reset the controls after a fault has been
cleared.

It is same even in the case of push


button style (Option).

STOP START BUZZER


STOP

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-1

Chapter 4 Operation
Pre- operation checks P
Preparation for operation. P
Starting operation P
Items to monitor during operation. P
Stopping operatio P
Fault stop P
Cautions for operation P

Pre-operation checks
Before running the absorption chiller, carry out the following checks:
1) Make sure that the preparation has been made to supply steam. (Steam supply
valve should be open.)
2) Make sure that the chilled water pump, cooling water pump, cooling tower fan and
other auxiliary equipment are all normal, and that their interlocks with the absorption
chiller are correctly wired. Also check that the chilled water and cooling water
systems have been primed with water and purged of air.
3) Make sure that the air conditioning equipment is ready to operate.
4) Perform the startup of the absorption chiller with sufficient lead time. Under normal
usage, it takes 20 to 30 minutes for the absorption chiller to become normal
operating condition.

Preparation for operation


1) Turn on the control panels main circuit breaker (MCB).
2) The following four operation condition indicators (on the front of the control panel)
will light:

POWER


STOP
POWER

STOP

RUNNING

DILUTION
SAFETY EQUIP.

CONT.VALVE CLOSED
PRE-ALARM
FAILURE

SAFETY EQUIP.
CONT. VALVE CLOSED

3) The 7-segment LED displays will appear :

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-2

Starting operation
Follow the procedure described below to start operation.

Press the START key on


the control panel.

BUZZER
STOP START
STOP

The chilled water pump will start


up.

The functioning of the protective


circuits will be checked.

: Perform this operation.

: Observe the display to


check that this After about 5 seconds, the cooling
happens. water pump will start operation.

It is same even in the case of push


The operation of the cooling water button style (Option).

pump and its protective circuits


will be checked, then heating will
start up.
STOP START BUZZER
STOP

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-3

After a further 5 seconds, the


cooling tower fan will start up.

Useful tips
Observe the operation condition lamps.

The STOP lamp and CONT. VALVE ClOSED lamp


should go out, and the RUNNING lamp should light.

Refregirant pump will run after about 5


minutes has elapsed.


POWER

STOP

RUNNING

DILUTION

SAFETY EQUIP.

PRE-ALARM

FAILURE

CONT.VALVE CLOSED

STOP RUN STOP RUN STOP RUN

SOL. SOL. REF.


PUMP SPRAY PUMP
PUMP

The RUN lamp should light to


indicate that the solution pump
and spray pump are running.
NOTE:
When the chilled water pump and cooling water pump interlock conditions are met,
the solution pump starts operating and pumps solution into the high temperature
generator.
The steam control valve opens gradually, then continuous operation is carried out
with the command from control panel that is proportional to the chilled water outlet
temperature.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-4

Items to monitor during operation


1) Observe the 7-segment display
Periodically observe the 7-segment display on the front of the control panel, to see if
any fault displays (error codes) appear.
Number displayed
depends on the type of
protective equipment.

2) Check the solution, spray, and refrigerant pumps.


Are these pumps operating normally?
If any of these pumps makes a continuous rattling or chattering noise, it is
consiered abnormal.
The refrigerant pump should start running about 5 minutes after the
absorption chiller is started up.

Useful tips
Immediately after the absorption chiller is started up, the high temperature generator
will make a chattering sound for a short while. This is not a fault in fact it is an
indication that the machine has started up normally. It will soon go away.

Stopping operation
1) Press the STOP key.

Press this key.

STOP START BUZZER


STOP

2) When the STOP button is pressed:


The absorption chiller will begin dilution operation lasting about 15 minutes.
The steam control valve will gradually close and be completely shut in the end.
It is same even in the case of push
button style (Option).

STOP START BUZZER


STOP

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-1

Chapter 5 Maintenance and Treatment


This chapter is divided into the following sections:
Solution control (Adjustment) .
Water quality treatment and cleaning of tubes .
Action for long-term stoppage .
Periodic inspection .
Purge unit .
Refrigerant automatic operation reproduction circuit .
Solution filter .
Standard replacement periods for parts .
Valve operation .
Cautions for use .

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-2

. Solution control
About the solution
The absorption chiller uses a solution of lithium bromide (chemical formula LiBr)
This lithium bromide solution is referred to as the solution.
Important points in solution management
Corrosion suppressant and alkalinity adjustment agent are added to the solution.
These additives are gradually consumed. Therefore, the solution must be sampled
periodically, the samples analyzed for corrosion suppressant concentration, alkalinity
and sediment, etc., and the additives replenished as necessary according to the
analysis results.
CAUTION
Be sure to adjust the solution periodically. Prolonged operation without adjustment
of the solution will drastically curtail the machines service life.
Analysis of the solution should be performed by persons with specialist skills.

Performance enhancing agent (Octylalcohol)


A special alcohol should be added to the solution as a special enhancing agent to
enhance its absorption performance. This alcohol should be added to the solution
periodically. Have this operation performed by our companys specialist technicians.
Disposal of solution
The solution does not contain any harmful substances, but nevertheless it should be
disposed of by a specialist waste treatment company.
CAUTION
Be sure to consult with our company before disposing of the solution.

Analysis of solution in heavy load machines


In absorption chillers that operate form more than 1500 cooling hours per year, the
solution will have to be analyzed more frequently. Consult our company regarding the
required analysis frequency.
Especially ,sufficient care, such as solution control of every 750 hours for first 1,500
hours operation, should be paid to the heavy duty machines.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-3

Water quality treatment and cleaning of tubes


CAUTION
Be sure to treat the cooling water and chilled water.
Why is water quality treatment necessary?
If scale or slime adheres to the insides of the heat transmission tubes (due to
low water quality), the machines performance will fall.
Particular care must be taken with the cooling water, which is exposed to the
atmosphere in the cooling tower; if harmful substances (sulfur oxides, etc.) or
dust in the atmosphere get into the cooling water and become concentrated in it,
the result will be corrosion of the tubes and a marked shortening of the
absorption chillers service life.
Therefore, pay attention to the installation environment and the quality of the
supply water, and manage so that an adequate blow quantity (concentration
rate) is secured.
Manage the quality of the cooling water and chilled water to conform to the standard
values laid down by the Japan Refrigeration Association in their Water Quality
Guidelines for Refrigeration and Air Conditioning Equipment (JRA-GL-02-1994). As
summary of those standards is given in Table 5.1.
Cleaning of tubes
The tubes of the absorber, condenser and evaporator should be cleaned at least
once a year using brushes or chemical agents.
If the absorption chiller is operated with scale adhering to the tube insides, its
efficiency will be markedly reduced, and corrosion of the tubes, with consequent
loss of airtightness, could result.
If the scale adhering to the tube insides is light scale, i.e. calcium carbonate or silica,
etc., and cannot be removed with a brush, use a chemical cleaning agent to remove
it.

CAUTION
Cleaning of the tubes requires specialist skills, so have it performed by a specialist
company.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-4

Table 5.1 Water quality standard values (summary)


Cooling water system Chilled water system Tendencies

Item Circulating type


Circulation Scale
Circulation Feedwater Feedwater Corrosion
water genera-
water 20 or less tion

pH [24] 6.58.2 6.08.0 6.88.0 6.88.0

Electrical conductivity (S/cm) 800 or less 300 or less 400 or less 300 or less
Standard parameters

Chloride ions (mgCl/L) 200 or less 50 or less 50 or less 50 or less


2
Sulfuric acid ions (mgSO4 /L) 200 or less 50 or less 50 or less 50 or less

Acid consumption (pH4.8) (mgCaCO3/L) 100 or less 50 or less 50 or less 50 or less

Total hardness (mgCaCO3/L) 200 or less 70 or less 70 or less 70 or less

Calcium hardness (mgCaCO3/L) 150 or less 50 or less 50 or less 50 or less

Ionized silica (mgSiO2/L) 50 or less 30 or less 30 or less 30 or less

Iron (mgFe/L) 1.0 or less 0.3 or less 1.0 or less 0.3 or less
Reference parameters

Copper (mgCu/L) 0.3 or less 0.1 or less 1.0 or less 0.1 or less
2
Sulphate ions (mgS /L) not to be detected not to be detected
+
Ammonium ions (mgNH4 /L) 1.0 or less 0.1 or less 1.0 or less 0.1 or less

Residual chlorine (mgCl/L) 0.3 or less 0.3 or less 0.3 or less 0.3 or less

Free carbon dioxide (mgCO2/L) 4.0 or less 4.0 or less 4.0 or less 4.0 or less

Stability index 6.07.0

A circle in the Corrosion or Scale Production columns indicates that the


parameter is a factor tending to cause corrosion or scale.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-5

Action for long-term stoppage


If there is danger that the temperature around the absorption chiller will fall,
causing the water in it to freeze, completely purge the water systems (chilled water
and cooling water systems) of all their water.
Make sure that the master steam supply valve is fully closed.
Normally, the inside of the absorption chiller may be left under vacuum during
prolonged stoppage.

When the absorption chiller is to be left out of use for a prolonged period in the
wintertime, it may be necessary to take measures to prevent the main body from
freezing.
Ask our company for details of such measures.
During prolonged stoppage, periodically observe and record the readings of the
compound gauge attached to the high temperature generator, in order to check the
main bodys airtightness.
Should the readings indicate that the inside pressure is increasing, contact our
company.
If the chilled water is not chilled properly when operation is restarted after a
prolonged stoppage, use an auxiliary vacuum pump to draw out any remaining
uncondensible gas.
This vacuum extraction operation is covered by the Maintenance Contract.
Have our company perform it if you have a Maintenance Contract with us.

Periodic inspection
Periodic inspection of the absorption chiller is an effective form of preventive
maintenance, and will facilitate early detection of faults (should they occur) and
determination of fault causes. A list of items for periodic inspection is given in Table
5.2.
In order to maintain the efficiency of the absorption chiller at a high level and ensure
that it fully exploits its potential, you are recommended to establish methods for
inspection and management in advance, and conduct them according to such
methods.
Supplementary Table 1 on P 5-13 presents a sample daily inspection check sheet.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-6


Table 5.2 Periodic inspection items
No. Inspection item Notes
Timing
1 Collection of operation data Daily Refer to examples in log sheet
2 Oil change for vacuum pump (if Monthly
applicable)
Water tubing system inspection (by Whenever Chilled and cooling water tubes
3
user) required and auxiliary facility
Steam tubing system inspection (by Whenever Steam and drain tubes and
4
user) required auxiliary facility
Whenever Power supply, interlock wiring,
5 Electrical system facility (by user)
required etc.
6 High temperature generator inspection Yearly Compliance with regulations (*)
Auxiliary safety instruments
7 Safety instrument inspection Yearly
equipped to body (*)
8 Electrical system inspection Yearly Auxiliary control panel equipped
to body (*)
9 Setting data inspection Yearly Auxiliary control panel equipped
to body (*)
10 Thermometer and pressure gauge Yearly Auxiliary control panel equipped
inspection to body
11 Steam system instruments inspection Yearly Steam control valve (*)
12 Steam drain system inspection Yearly Drain trap, strainer (*)
13 Solution analysis (for inhibitors, Yearly Adjust them as required (*)
alkalinity, impurity)
14 Solution filter inspection Yearly Replace elements as required(*)
15 Performance enhancing agent Whenever Replenish as required (*)
replenishment required
16 Cooling water quality inspection Yearly Water quality must be observed
(*)
17 Cleaning and inspection of tubes Yearly Determine the inspection cycle
depending on degree of
contamination (*)
18 Automatic purging unit inspection (if Yearly (*)
applicable)
19 Vacuum recovery operation of At start-up At start-up after long period of
absorption chiller stoppage time (*)
Asterisked items require specialist skills. Have our company perform such
items.

CAUTION (for heavy load specification)


Carry out the following items in addition to those in the table above.
Perform analysis at least twice a year (the inspection cycle should increase
depending on degree of contamination.
Perform air purging at least twice a day, using the auto air purge unit (the
automatic purging unit is an option).
Perform filtering of the solution (the solution filter is an option).

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-7

Purge unit
The hydrogen gas generated in the absorption chiller is discharged from the purge
tank outside the machine with the purge pump.
Purge pump is driven in the automatic operation in setting it concerning the
automatic purge device at set intervals of time, and no condensation gas in the
purge tank is exhausted outside the machine
Please consult the field engineer of charge about the setting.
Please exchange the oil of the purge pump regularly while confirming the dirt
condition.
As a rule, the manual purge operation during the season is unnecessary.

Refrigerant automatic operation reproduction circuit


The solution mist mixes with the refrigerant side when it keeps driving the chiller
continuously for a long time. The purity of the refrigerant might decrease, and the
refrigerating capacity decrease.
Therefore, the refrigerant is by the refrigerant automatic operation
reproduction.
When the circuit use the refrigerant automatic operation reproduction circuit sets
the start time and the time of the refrigerant reproduction with the control board.
Please consult the field engineer of charge about the setting.
The dilution valve is compulsorily opened, and the refrigerant in the evaporator is
transported to the solution while the refrigerant is reproducing. Please note that the
refrigerating capacity will temporarily decrease.
Please set the refrigerant automatic operation reproduction driving time within a
day at time zone with few frozen loads.

Solution filter
An oxide generated due to the deterioration of the solution and in-flight impurities
can be removed by using the solution filter. A part of the exhaled solution is filtered
from the solution pump with the solution filter, and it returns it to the absorber.
Please regularly wash and exchange filters. Washing and the exchange time of the
filter are different according to the driving situation etc. of the absorption chiller.
Please consult the field engineer of charge.
It wishes the order to the service agency of charge because a special technology
is necessary for the clearing work of the filter.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-8

Standard replacement periods for parts


Table 5.4 gives average service lives of representative parts under ordinary air
conditioning operation conditions, and the periods at which they should be checked.

Table 5.4 Average years of service life of representative parts


(under ordinary air conditioning operation conditions)
Standard
Part replacement Replacement urgency Notes
period
Periodic As
replacement necessary
Major components
Solution, spray, and 5 years or Completely disassemble and
refrigerant pumps 20,000 inspect / replace after 5 years or
hours of 20,000 operation hours, whichever
operation is sooner
Tubes 12 years Conduct eddy current test
Solution heat exchanger 5 years
Drain heat exchanger 5 years
Refrigerant heat exchanger 5 years
Protective device and instrumentation related parts
Thermostats 5 years
Pressure switches 5 years
Flow switches 5 years
Compound gauge 5 years
Thermosensors 3 years
Solenoid valves 5 years
Electrodes 2 years
Pressuresensors 3 years
Float switches 3 years
Steam control valve 5 years
Steam cutoff valve 5 years OPTION
Electrical parts (control panel)
CPU circuit board 8 years
Power supply circuit board 5 years
AI / relay circuit board 5 years
Solenoid switch 8 years
Backup battery 5 years
Inverter 5 years
Inverter fan 2 years

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-9

Standard
Part replacement Replacement urgency Notes
period
Parts to be inspected/replaced during overhaul
Drain trap 5 years
Diaphragm valve rubber 5 years
Sight glass 5 years
Absorbent 5 years Regenerate or replace with new
Solution strainer 5 years
Steam system strainer 5 years
Refrigerant (water) 5 years
Automatic purge unit 5 years Vacuum pump and solenoid
Consumable parts
Water chamber gasket Opened Replace whenever chamber is
opened up after inspection
Steam chamber gasket Yearly Replace upon yearly inspection
Vacuum pump oil Monthly
Solution filter element 6 months

CAUTION
Be sure to completely disassemble and inspect the applicable parts every 5 years
or 20,000 hours of operation. Replace parts that the inspection shows are in need
of replacement, and those parts that must be replaced at periodic intervals. Have
these operations performed by our company.
Use only genuine Ebara products for replacement parts.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-10

Valve operation
The absorption chiller contains a large number of valves, both manually operated
valves and automatic control valves. Operating these valves incorrectly could lead
to equipment damage, air leaks and consequent deterioration of the absorption
chiller interior, or else to other trouble such as leakage of absorbent outside the
machine. Normally, you should avoid touching the valves.

Useful tips
Operate the chilled water and cooling water tubing system valves as necessary to
perform air vent and drainage.
Also operate the fuel system tubing valves as necessary to perform air vent and
drainage.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-11

Cautions for use


Do not place flammable substances in the machines vicinity
Do not place easily combustible substances such as gasoline, kerosene and
thinner in the machines surrounding area. Doing so could result in explosion or
fire.
Do not turn off the power
Leave the main circuit breaker (inside the control panel) permanently turned on. If
they are turned off, the control panel will stop functioning.
Leave the protective and control devices alone
Under normal circumstances, do not touch the protective and control devices. If
you have to touch them for some reason, be sure to obtain instructions from our
company beforehand.
Repair, and parts replacement
NEVER remodel or alter the machine, in whole or in part, without first obtaining
Ebaras approval. We are not liable for any remodeling or alteration made to the
machine without Ebaras approval.
For repair and replacement, use only genuine Ebara parts.
Cautions regarding use of transceiver, etc.
The absorption chiller is controlled by a microcomputer. Transceivers, mobile
phones and the like emit radio waves which will adversely affect (in the form of
noise) the control panel (which contains the microcomputer), the thermosensors
and other control equipment if such items are used bear to such control
equipment. Therefore, if such items must be used in the vicinity of the absorption
chiller, determine positions (areas) in which it will be safe to use them (i.e. where
they will not affect control equipment. Therefore, if such items must be used in the
vicinity of the absorption chiller, determine positions (areas) in which it will be safe
to use them (i.e. where they will not affect control equipment), and only use them
in such positions. As a rule of thumb, such items should only be used at a
distance of at least 10m from the machine.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-12

Supplementary Table 1 Sample Daily Log Sheet for Model REW Absorption Chiller
Date Checkers name
Time Units : : : : : :
Operation mode Cooling/ Cooling/ Cooling/ Cooling/ Cooling/ Cooling/
Heating Heating Heating Heating Heating Heating
Power supply
Voltage V
Current A
Chilled water system
Chilled water inlet temperature
Chilled water outlet
temperature
Chilled water pump discharge MPa
pressure
Chilled water pump suction MPa
pressure
Chilled water pump current A
Cooling water system
Cooling water inlet temperature
Cooling water outlet
temperature
Cooling water pump discharge MPa
pressure
Cooling water pump suction MPa
pressure
Cooling water pump current A
Cooling tower fan current A
Steam
Steam control valve inlet
MPa
pressure
High temperature generator
MPa
inlet pressure
Steam control valve open rate
High temp. generator pressure MPa
Drain water outlet temperature
Other
Solution pump Inverter Hz
frequency
Spray pump Inverter frequency Hz
Abnormal noise? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Abnormal vibration? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Remarks

Note: In the case of a Yes answer, contact your service agent.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-5

The DILUTION lamp is lit during dilution


operation.

SAFETY EQUIP.
POWER

STOP

RUNNING

DILUTION

FAILURE
PRE-ALARM

CONT. VALVE CLOSED


STOP RUN STOP RUN STOP RUN

SOL. SOL. REF.


PUMP SPRAY PUMP
PUMP

The solution and spray pumps run during


dilution operation.
The refrigerant pump stops as soon as
dilution starts.

3) The 7-segment display will show the remaining length of time that dilution has to
run.
Remaining dilution time
countdown (in seconds)

The cooling water pump and


cooling tower fan stop after
about 5 minutes.

When the remaining dilution


time countdown ends (reaches
2, 1, then 0), the condition
display reappears.

At the end of about 15 minutes,


dilution operation will be
completed.

The chilled water,


solution, and spray pumps
4) Operation indicator lamps
will stop, then the
absorption chiller will stop


completely.
DILUTION

SAFETY EQUIP.
POWER

STOP

RUNING

PRE-ALARM

FAILURE

CONT .VALVE C LOSED

STOP RUN STOP RUN STOP RUN

SOL. SOL. REF.


PUMP SPRAY PUMP
PUMP

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-6

5) Other steps to perform


When the absorption absorption chiller has completed dilution and stopped, stop
the air conditioning equipment.
Do not turn off the control panels main circuit breaker (MCB) when the absorption
chiller stops. Leave them permanently turned on.
Close the steam supply valve.

Useful hints Temperature regulation stoppage


If the load falls below the absorption chillers control range, so that the chilled water
is too cold, the steam control valve closes completely and temporally stops the
supply of steam. This is called temperature regulation stoppage.
The supply of steam is resumed automatically when the chilled waters
temperature rises to an appropriate level. (The chilled water pump runs
continuously.)
Do not close the master steam supply valve when temperature regulation stoppage
occurs.

A indicates temperature regulation stoppage.

When temperature regulation stoppage occurs,


the chilled water pump continues running, but
the cooling water pump stops after about 5
minutes.

Fault stop
If some fault occurs during operation, a protective device will be activated, and the
machine will implement fault stop. When this happens:
The alarm buzzer will sound.
The absorption chiller will stop automatically.
Immediately carry out the corrective action procedure below:

Note down this number in the error


Step 1) Note down the error code display.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-7

Step 2) Carry out resetting.

Press the STOP key. (The STOP key also functions as


a reset button.)

It is same even in the case of push


BUZZER button style (Option).
STOP START
STOP

STOP START BUZZER


Stop the buzzer. STOP

CAUTION
Investigate and determine the cause of the fault. (If necessary, contact our
company for assistance.)
Eliminate the cause of the fault. Then restart operation, and check all parts of the
machine for abnormality.
If the cause cannot be determined, or operation cannot be restarted, or fault stop
occurs again after restart, contact our company as soon as possible.

Useful tips
Be sure to note down the error code.
Refer to Chapter 6 Troubleshooting to assist you in locating the cause of the
error.

Cautions for operation


Unloaded operation
Power failure
Cooling water temperature

1) No-load operation
Make sure that the absorption chiller has a chilled water load of some kind (e.g. by
running the air handling unit or air terminal) during operation or dilution.
If there is no load, the temperature of the chilled water will drop sharply, leading to
freezing of the machine.
During operation and dilution, do not make the cooling water pump stop for any
reason. Stopping the pump will result in freezing of the evaporator tubes.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 4 Operation P 4-8

If there are no interlocks between the absorption chiller and the chilled water
pump, cooling water pump and cooling tower fan:
Check that the OPERATING and
DILUTION lamps are off.





Check that the solution pump is
POWER

STOP

RUNNING

CONT .VALVE CLOSED


DILUTION

SAFETY EQUIP.

PRE-ALARM

FALURE
STOP RUN STOP RUN STOP RUN

SOL.
PUMP
SPRAY
PUMP
REF.
PUMP
stopped.

Provided that the conditions stipulated in the above checks are met, stop the
chilled water pump.
Stopping the chilled water pump without the conditions being met (i.e. before
operation/dilution and the solution pump have stopped) could lead to freezing
due to overcooling.
2) Power failure
Machines condition when outage occurs
1) If an outage occurs during operation, the absorption chiller will stop, unless
dilution is in progress.
2) If the solutions concentration is high when an outage occurs, it could crystallize
if it is left immobile inside the machine.
Action for power failure
Restart the absorption chiller as soon as possible after the power supply is
resumed.
In the case of an outage lasting 10 minutes or longer, the 7-segment display will
show:

When this display appears, carry out resetting and resume operation.
Should the solution crystallize, rendering operation impossible, contact our
company.
If the machine stops due to outage during remote control operation, go to the
machine and check for problems (crystallization, etc.)
3) Cooling water temperature
If the cooling water inlet temperature is extremely low when the machine is run in
cooling operation (in the winter and other cold times of the year), temperature
control will be necessary to regulate cooling tower bypass and/or the starting and
stopping of the cooling tower fan.
If the auxiliary equipment coupled operation circuits inside the control panel are
used, starting and stopping of the cooling tower fan can be controlled. Such control
is automatic.
Avoid rapid variations in cooling water temperature. Rapid variation will disturb the
absorption chiller and make stable operation impossible.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-1

Chapter 5 Maintenance and Treatment


This chapter is divided into the following sections:
Solution control (Adjustment) .
Water quality treatment and cleaning of tubes .
Action for long-term stoppage .
Periodic inspection .
Purge unit .
Refrigerant automatic operation reproduction circuit .
Solution filter .
Standard replacement periods for parts .
Valve operation .
Cautions for use .

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-2

. Solution control
About the solution
The absorption chiller uses a solution of lithium bromide (chemical formula LiBr)
This lithium bromide solution is referred to as the solution.
Important points in solution management
Corrosion suppressant and alkalinity adjustment agent are added to the solution.
These additives are gradually consumed. Therefore, the solution must be sampled
periodically, the samples analyzed for corrosion suppressant concentration, alkalinity
and sediment, etc., and the additives replenished as necessary according to the
analysis results.
CAUTION
Be sure to adjust the solution periodically. Prolonged operation without adjustment
of the solution will drastically curtail the machines service life.
Analysis of the solution should be performed by persons with specialist skills.

Performance enhancing agent (Octylalcohol)


A special alcohol should be added to the solution as a special enhancing agent to
enhance its absorption performance. This alcohol should be added to the solution
periodically. Have this operation performed by our companys specialist technicians.
Disposal of solution
The solution does not contain any harmful substances, but nevertheless it should be
disposed of by a specialist waste treatment company.
CAUTION
Be sure to consult with our company before disposing of the solution.

Analysis of solution in heavy load machines


In absorption chillers that operate form more than 1500 cooling hours per year, the
solution will have to be analyzed more frequently. Consult our company regarding the
required analysis frequency.
Especially ,sufficient care, such as solution control of every 750 hours for first 1,500
hours operation, should be paid to the heavy duty machines.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-3

Water quality treatment and cleaning of tubes


CAUTION
Be sure to treat the cooling water and chilled water.
Why is water quality treatment necessary?
If scale or slime adheres to the insides of the heat transmission tubes (due to
low water quality), the machines performance will fall.
Particular care must be taken with the cooling water, which is exposed to the
atmosphere in the cooling tower; if harmful substances (sulfur oxides, etc.) or
dust in the atmosphere get into the cooling water and become concentrated in it,
the result will be corrosion of the tubes and a marked shortening of the
absorption chillers service life.
Therefore, pay attention to the installation environment and the quality of the
supply water, and manage so that an adequate blow quantity (concentration
rate) is secured.
Manage the quality of the cooling water and chilled water to conform to the standard
values laid down by the Japan Refrigeration Association in their Water Quality
Guidelines for Refrigeration and Air Conditioning Equipment (JRA-GL-02-1994). As
summary of those standards is given in Table 5.1.
Cleaning of tubes
The tubes of the absorber, condenser and evaporator should be cleaned at least
once a year using brushes or chemical agents.
If the absorption chiller is operated with scale adhering to the tube insides, its
efficiency will be markedly reduced, and corrosion of the tubes, with consequent
loss of airtightness, could result.
If the scale adhering to the tube insides is light scale, i.e. calcium carbonate or silica,
etc., and cannot be removed with a brush, use a chemical cleaning agent to remove
it.

CAUTION
Cleaning of the tubes requires specialist skills, so have it performed by a specialist
company.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-4

Table 5.1 Water quality standard values (summary)


Cooling water system Chilled water system Tendencies

Item Circulating type


Circulation Scale
Circulation Feedwater Feedwater Corrosion
water genera-
water 20 or less tion

pH [24] 6.58.2 6.08.0 6.88.0 6.88.0

Electrical conductivity (S/cm) 800 or less 300 or less 400 or less 300 or less
Standard parameters

Chloride ions (mgCl/L) 200 or less 50 or less 50 or less 50 or less


2
Sulfuric acid ions (mgSO4 /L) 200 or less 50 or less 50 or less 50 or less

Acid consumption (pH4.8) (mgCaCO3/L) 100 or less 50 or less 50 or less 50 or less

Total hardness (mgCaCO3/L) 200 or less 70 or less 70 or less 70 or less

Calcium hardness (mgCaCO3/L) 150 or less 50 or less 50 or less 50 or less

Ionized silica (mgSiO2/L) 50 or less 30 or less 30 or less 30 or less

Iron (mgFe/L) 1.0 or less 0.3 or less 1.0 or less 0.3 or less
Reference parameters

Copper (mgCu/L) 0.3 or less 0.1 or less 1.0 or less 0.1 or less
2
Sulphate ions (mgS /L) not to be detected not to be detected
+
Ammonium ions (mgNH4 /L) 1.0 or less 0.1 or less 1.0 or less 0.1 or less

Residual chlorine (mgCl/L) 0.3 or less 0.3 or less 0.3 or less 0.3 or less

Free carbon dioxide (mgCO2/L) 4.0 or less 4.0 or less 4.0 or less 4.0 or less

Stability index 6.07.0

A circle in the Corrosion or Scale Production columns indicates that the


parameter is a factor tending to cause corrosion or scale.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-5

Action for long-term stoppage


If there is danger that the temperature around the absorption chiller will fall,
causing the water in it to freeze, completely purge the water systems (chilled water
and cooling water systems) of all their water.
Make sure that the master steam supply valve is fully closed.
Normally, the inside of the absorption chiller may be left under vacuum during
prolonged stoppage.

When the absorption chiller is to be left out of use for a prolonged period in the
wintertime, it may be necessary to take measures to prevent the main body from
freezing.
Ask our company for details of such measures.
During prolonged stoppage, periodically observe and record the readings of the
compound gauge attached to the high temperature generator, in order to check the
main bodys airtightness.
Should the readings indicate that the inside pressure is increasing, contact our
company.
If the chilled water is not chilled properly when operation is restarted after a
prolonged stoppage, use an auxiliary vacuum pump to draw out any remaining
uncondensible gas.
This vacuum extraction operation is covered by the Maintenance Contract.
Have our company perform it if you have a Maintenance Contract with us.

Periodic inspection
Periodic inspection of the absorption chiller is an effective form of preventive
maintenance, and will facilitate early detection of faults (should they occur) and
determination of fault causes. A list of items for periodic inspection is given in Table
5.2.
In order to maintain the efficiency of the absorption chiller at a high level and ensure
that it fully exploits its potential, you are recommended to establish methods for
inspection and management in advance, and conduct them according to such
methods.
Supplementary Table 1 on P 5-13 presents a sample daily inspection check sheet.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-6


Table 5.2 Periodic inspection items
No. Inspection item Notes
Timing
1 Collection of operation data Daily Refer to examples in log sheet
2 Oil change for vacuum pump (if Monthly
applicable)
Water tubing system inspection (by Whenever Chilled and cooling water tubes
3
user) required and auxiliary facility
Steam tubing system inspection (by Whenever Steam and drain tubes and
4
user) required auxiliary facility
Whenever Power supply, interlock wiring,
5 Electrical system facility (by user)
required etc.
6 High temperature generator inspection Yearly Compliance with regulations (*)
Auxiliary safety instruments
7 Safety instrument inspection Yearly
equipped to body (*)
8 Electrical system inspection Yearly Auxiliary control panel equipped
to body (*)
9 Setting data inspection Yearly Auxiliary control panel equipped
to body (*)
10 Thermometer and pressure gauge Yearly Auxiliary control panel equipped
inspection to body
11 Steam system instruments inspection Yearly Steam control valve (*)
12 Steam drain system inspection Yearly Drain trap, strainer (*)
13 Solution analysis (for inhibitors, Yearly Adjust them as required (*)
alkalinity, impurity)
14 Solution filter inspection Yearly Replace elements as required(*)
15 Performance enhancing agent Whenever Replenish as required (*)
replenishment required
16 Cooling water quality inspection Yearly Water quality must be observed
(*)
17 Cleaning and inspection of tubes Yearly Determine the inspection cycle
depending on degree of
contamination (*)
18 Automatic purging unit inspection (if Yearly (*)
applicable)
19 Vacuum recovery operation of At start-up At start-up after long period of
absorption chiller stoppage time (*)
Asterisked items require specialist skills. Have our company perform such
items.

CAUTION (for heavy load specification)


Carry out the following items in addition to those in the table above.
Perform analysis at least twice a year (the inspection cycle should increase
depending on degree of contamination.
Perform air purging at least twice a day, using the auto air purge unit (the
automatic purging unit is an option).
Perform filtering of the solution (the solution filter is an option).

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-7

Purge unit
The hydrogen gas generated in the absorption chiller is discharged from the purge
tank outside the machine with the purge pump.
Purge pump is driven in the automatic operation in setting it concerning the
automatic purge device at set intervals of time, and no condensation gas in the
purge tank is exhausted outside the machine
Please consult the field engineer of charge about the setting.
Please exchange the oil of the purge pump regularly while confirming the dirt
condition.
As a rule, the manual purge operation during the season is unnecessary.

Refrigerant automatic operation reproduction circuit


The solution mist mixes with the refrigerant side when it keeps driving the chiller
continuously for a long time. The purity of the refrigerant might decrease, and the
refrigerating capacity decrease.
Therefore, the refrigerant is by the refrigerant automatic operation
reproduction.
When the circuit use the refrigerant automatic operation reproduction circuit sets
the start time and the time of the refrigerant reproduction with the control board.
Please consult the field engineer of charge about the setting.
The dilution valve is compulsorily opened, and the refrigerant in the evaporator is
transported to the solution while the refrigerant is reproducing. Please note that the
refrigerating capacity will temporarily decrease.
Please set the refrigerant automatic operation reproduction driving time within a
day at time zone with few frozen loads.

Solution filter
An oxide generated due to the deterioration of the solution and in-flight impurities
can be removed by using the solution filter. A part of the exhaled solution is filtered
from the solution pump with the solution filter, and it returns it to the absorber.
Please regularly wash and exchange filters. Washing and the exchange time of the
filter are different according to the driving situation etc. of the absorption chiller.
Please consult the field engineer of charge.
It wishes the order to the service agency of charge because a special technology
is necessary for the clearing work of the filter.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-8

Standard replacement periods for parts


Table 5.4 gives average service lives of representative parts under ordinary air
conditioning operation conditions, and the periods at which they should be checked.

Table 5.4 Average years of service life of representative parts


(under ordinary air conditioning operation conditions)
Standard
Part replacement Replacement urgency Notes
period
Periodic As
replacement necessary
Major components
Solution, spray, and 5 years or Completely disassemble and
refrigerant pumps 20,000 inspect / replace after 5 years or
hours of 20,000 operation hours, whichever
operation is sooner
Tubes 12 years Conduct eddy current test
Solution heat exchanger 5 years
Drain heat exchanger 5 years
Refrigerant heat exchanger 5 years
Protective device and instrumentation related parts
Thermostats 5 years
Pressure switches 5 years
Flow switches 5 years
Compound gauge 5 years
Thermosensors 3 years
Solenoid valves 5 years
Electrodes 2 years
Pressuresensors 3 years
Float switches 3 years
Steam control valve 5 years
Steam cutoff valve 5 years OPTION
Electrical parts (control panel)
CPU circuit board 8 years
Power supply circuit board 5 years
AI / relay circuit board 5 years
Solenoid switch 8 years
Backup battery 5 years
Inverter 5 years
Inverter fan 2 years

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-9

Standard
Part replacement Replacement urgency Notes
period
Parts to be inspected/replaced during overhaul
Drain trap 5 years
Diaphragm valve rubber 5 years
Sight glass 5 years
Absorbent 5 years Regenerate or replace with new
Solution strainer 5 years
Steam system strainer 5 years
Refrigerant (water) 5 years
Automatic purge unit 5 years Vacuum pump and solenoid
Consumable parts
Water chamber gasket Opened Replace whenever chamber is
opened up after inspection
Steam chamber gasket Yearly Replace upon yearly inspection
Vacuum pump oil Monthly
Solution filter element 6 months

CAUTION
Be sure to completely disassemble and inspect the applicable parts every 5 years
or 20,000 hours of operation. Replace parts that the inspection shows are in need
of replacement, and those parts that must be replaced at periodic intervals. Have
these operations performed by our company.
Use only genuine Ebara products for replacement parts.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-10

Valve operation
The absorption chiller contains a large number of valves, both manually operated
valves and automatic control valves. Operating these valves incorrectly could lead
to equipment damage, air leaks and consequent deterioration of the absorption
chiller interior, or else to other trouble such as leakage of absorbent outside the
machine. Normally, you should avoid touching the valves.

Useful tips
Operate the chilled water and cooling water tubing system valves as necessary to
perform air vent and drainage.
Also operate the fuel system tubing valves as necessary to perform air vent and
drainage.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-11

Cautions for use


Do not place flammable substances in the machines vicinity
Do not place easily combustible substances such as gasoline, kerosene and
thinner in the machines surrounding area. Doing so could result in explosion or
fire.
Do not turn off the power
Leave the main circuit breaker (inside the control panel) permanently turned on. If
they are turned off, the control panel will stop functioning.
Leave the protective and control devices alone
Under normal circumstances, do not touch the protective and control devices. If
you have to touch them for some reason, be sure to obtain instructions from our
company beforehand.
Repair, and parts replacement
NEVER remodel or alter the machine, in whole or in part, without first obtaining
Ebaras approval. We are not liable for any remodeling or alteration made to the
machine without Ebaras approval.
For repair and replacement, use only genuine Ebara parts.
Cautions regarding use of transceiver, etc.
The absorption chiller is controlled by a microcomputer. Transceivers, mobile
phones and the like emit radio waves which will adversely affect (in the form of
noise) the control panel (which contains the microcomputer), the thermosensors
and other control equipment if such items are used bear to such control
equipment. Therefore, if such items must be used in the vicinity of the absorption
chiller, determine positions (areas) in which it will be safe to use them (i.e. where
they will not affect control equipment. Therefore, if such items must be used in the
vicinity of the absorption chiller, determine positions (areas) in which it will be safe
to use them (i.e. where they will not affect control equipment), and only use them
in such positions. As a rule of thumb, such items should only be used at a
distance of at least 10m from the machine.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 5 Maintenance and Treatment P 5-12

Supplementary Table 1 Sample Daily Log Sheet for Model REW Absorption Chiller
Date Checkers name
Time Units : : : : : :
Operation mode Cooling/ Cooling/ Cooling/ Cooling/ Cooling/ Cooling/
Heating Heating Heating Heating Heating Heating
Power supply
Voltage V
Current A
Chilled water system
Chilled water inlet temperature
Chilled water outlet
temperature
Chilled water pump discharge MPa
pressure
Chilled water pump suction MPa
pressure
Chilled water pump current A
Cooling water system
Cooling water inlet temperature
Cooling water outlet
temperature
Cooling water pump discharge MPa
pressure
Cooling water pump suction MPa
pressure
Cooling water pump current A
Cooling tower fan current A
Steam
Steam control valve inlet
MPa
pressure
High temperature generator
MPa
inlet pressure
Steam control valve open rate
High temp. generator pressure MPa
Drain water outlet temperature
Other
Solution pump Inverter Hz
frequency
Spray pump Inverter frequency Hz
Abnormal noise? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Abnormal vibration? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Remarks

Note: In the case of a Yes answer, contact your service agent.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-1

Chapter 6 Troubleshooting
6.1 Things to check before calling the service company .
6.2 Table of error codes, error causes and corrective action .
6.3 Table of pre-alarms, their causes and corrective action .

Things to check before calling the service company


When a problem occurs, it may not be necessary to seek outside help. Check the
items listed below before calling our company.

Trouble What to check


Absorption chiller Are the main circuit breaker (inside control panel) turned on?
does not start up Do the chilled water pump and cooling water pump operate
normally?
Has an external emergency stop signal been received (from a
seismal sensor, for example)?
Lamps on display or If none of the lamps light, check the main power supply.
control part of Is the main circuit breaker (inside control panel) turned on?
control panel do not
light
Water is not chilled Are the chilled water / cooling water interlocks activated?
Is steam supplied with proper pressure?
Are the burners combusting gas?
Has the system stopped due to a fault?
Is the cooling water flowing at the prescribed rate?
Is the cooling water pumps discharge pressure normal?
Is the cooling water inlet temperature too high?
Is the cooling tower operating normally?
Is the fuel control valve closed?
Has air become trapped in the machine interior?
If it has, contact our company immediately.
Chilled water pump This may not be a fault. With a certain optional function, if the
runs while chilled water outlet temperature falls below 2, the pump runs
absorption chiller is automatically to prevent freezing. It will stop automatically when
stopped the chilled water temperature rises to 4. In addition, the chilled
water pump continuously runs during diluting operation at and
after temperature regulation stoppage.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-2

Table of error codes, error causes and corrective action


When an error code appears on the panels digital display, look it up in the table
below, investigate the cause and take the appropriate corrective action given.
Address any queries about errors and error codes to our company.

Error code Meaning Action


External emergency Check the external emergency stop switch.
stop
Seismoscope Reset seismoscope.
activated Check that seismoscope is installed in the correct position.
Power failure Outage 10 minutes or longer occurred during operation.
If the outage is prolonged, the absorbent may have
crystallized.
Determine the duration of the outage, and contact our
company.
Chilled water inlet Check the CHILLED WATER TEMP. display. Symbol: b1.
thermosensor error If the temperature display shows an abnormal value, the
sensor or circuit board needs replacing. Contact our
company for replacement.
Chilled water outlet Check the CHILLED WATER TEMP. display. Symbol: b2.
thermosensor error If the temperature display shows an abnormal value, the
sensor or circuit board needs replacing. Contact our
company for replacement.
Cooling water inlet Check the COOLING WATER TEMP. display. Symbol:
thermosensor error C1.
If the temperature display shows an abnormal value, the
sensor or circuit board needs replacing. Contact our
company for replacement.

High temperature Check the H.T. GEN. TEMP. display. Symbol: 3H.
generator dewpoint If the temperature display shows an abnormal value, the
thermosensor error sensor or circuit board needs replacing. Contact our
company for replacement.
High temperature Check the H.T. GEN. TEMP. display. Symbol: 4H.
generator return If the temperature display shows an abnormal value, the
thermosensor error sensor or circuit board needs replacing. Contact our
company for replacement.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-3

Error code Meaning Action


Low temperature Examine the liquid level detection electrode rod.
generator level error If the rod is faulty it must be replaced
Contact our company for replacement.
High temperature Check the Pressure measurement. display. Symbol: PS.
generator Pressure If the pressure display shows an abnormal value, the
sensor error sensor or circuit board needs replacing. Contact our
company for replacement.
Absorber outlet Check the TEMP. MEASURE display. Symbol: Ab.
thermosensor error If the temperature display shows an abnormal value, the
sensor or circuit board needs replacing.
Contact our company for replacement.
High temperature Examine the liquid level detection electrode rod.
generator the control If the rod is faulty it must be replaced
on the liquid side is in Contact our company for replacement.
a slump.
Electrode rod error Examine the liquid level detection electrode rod.
If the rod is faulty it must be replaced
Contact our company for replacement.
Refrigerant pump Wait until end of dilution operation. Then turn off the main
overload circuit breaker, and reset the magnet switch inside the
control panel by pressing the thermal reset button.
Solution pump fault Cause is activation of solution pump inverter or coil
thermostat.
Check inverter display. Contact our company if necessary.
Electrical leakage Electrical leakage from the control equipment has triggered
breaker actuated the electrical leakage breaker.
Contact our service agent.

Spray pump fault After dilution operation, turn off the main circuit breaker,
and reset the magnet switch inside the control panel by
pressing the thermal reset button.
Low temperature Examine the liquid level detection electrode rod.
generator the control If the rod is faulty it must be replaced
on the liquid side is in Contact our company for replacement.
a slump.

Chilled water pump Is the chilled water pump operating normally?


interlock error (startup Is the chilled water pumps magnet normal?
congestion) Is the chilled water pumps interlock wiring normal?

Chilled water pump Is the chilled water pump operating normally?


interlock error Is the chilled water pumps magnet normal?
Is the chilled water pumps interlock wiring normal?

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-4


Chilled water flow lack Is the chilled water pump operating normally?
/ stopped (startup Is the flow of chilled water sufficient?
congestion) Is there delay in the start-up of chilled water inverter that
results in taking too much time to gain the rated current?
Is there any problem resulting in inability of obtaining the
rated current by the operation of valve at facility side when
the chiller pump is operating normally?
Chilled water flow lack Is the chilled water pump operating normally?
/ stopped Is the flow of chilled water sufficient?
Is there delay in the start-up of chilled water inverter that
results in taking too much time to gain the rated current?
Is there any problem resulting in inability of obtaining the
rated current by the operation of valve at facility side when
the chiller pump is operating normally?
Chilled water Chilled water temperature has dropped.
temperature low Is the air conditioning equipment operating?
Is the flow of chilled water sufficient?
Is there abrupt change of load?
Is there abrupt change of coolant water temperature?
Cooling capacity drop Contact our company.

Refrigerant Refrigerant temperature has dropped.


temperature low Is the flow of refrigerant sufficient?
Cooling water pump Is the cooling water pump operating normally?
interlock error (startup
congestion)
Cooling water pump Is the cooling water pump operating normally?
interlock error Is the cooling water pumps magnet normal?
Cooling water flow Is the cooling water pump operating normally?
lack / stopped (startup Is the flow of cooling water sufficient?
congestion)
Chilled water flow lack Is the cooling water pump operating normally?
/ stopped Is the flow of cooling water sufficient?
Cooling water Cooling water inlet temperature has risen to the 40 level.
temperature high Is the cooling tower fan able to operate?
Check fan belt for breakage even if the operation display
shows normal for the cooling tower fan.
Cooling water The cooling water temperature is too low.
temperature low Check the cooling tower fan settings.
Absorber solution There is probably an accumulation of dirt, etc., in the
temperature high solution circulation system. Disassembly and inspection of
the interior may be necessary.
Contact our company.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-5


High temperature Is the flow (pressure) of steam excessive?
generator temperature Adjust the temperature and flow rate of cooling water,
high since uncondensable gas may be accumulated.
Contact our company.
High temperature Check the pressure reading of the high temperature
generator pressure generators compound gauge.
high Check the cooling water temperature and flow rate, since
uncondensable gas may be accumulated.
Is the flow (pressure) of steam excessive?
Drain temperature Check the Drain. TEMP. display. Symbol: d0.
error If the temperature display shows an abnormal value, the
sensor or circuit board needs replacing. Contact our
company for replacement.
High temperature The level of liquid in the high temperature generator has
generator dropped.
concentration level Check the solution pump and its inverter.
abnormal Contact our company.
Fuel control valve fault Contact our company.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-6

Table of pre-alarms, their causes and corrective action


When a pre-alarm code appears on the panels digital display, look it up in the table
below, investigate the cause and take the appropriate corrective action given.
Pre-alarms are not triggered by protective devices, and the absorption chiller does
not stop when pre-alarms occur.
However, if operation continues without action being taken for the pre-alarms:
operational efficiency could decline;
unexpected trouble could result;
operation may become impossible.
Accordingly, take prompt action when pre-alarms occur.
Address any queries about pre-alarms and pre-alarm codes to our company.

Pre-alarm code Meaning Action


Purge / internal There could be buildup of uncondensable gas generated in the
pressure rise interior.
Gas must be purged using vacuum pump.
Purge pump overload Stop the absorption chiller, turn off the main circuit breaker
(if applicable) (MCB), and reset the magnet switch inside the control panel by
pressing the thermal reset button.
Purge pump fault Purge pump cannot produce the prescribed vacuum.
(if applicable) Check pumps oil and water.
Main part replacement Solution pumps time counter has reached 5000 operation
alert hours.
See the Replacement Parts List for the parts to replace.
Refrigerant Check the TEMP. MEASURE display. Symbol: E0.
evaporation If the temperature display shows an abnormal value, the sensor
thermosensor fault or circuit board needs replacing.
Contact our company for replacement.
Chilled water inlet Check the CHILLED WATER TEMP. display. Symbol: b1.
thermosensor fault If the temperature display shows an abnormal value, the sensor
or circuit board needs replacing. Contact our company for
replacement.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter 6 Troubleshooting P 6-7

Pre-alarm code Meaning Action


Refrigerant Check the TEMP. MEASURE display. Symbol: C0.
condensation If the temperature display shows an abnormal value, the sensor
thermosensor fault or circuit board needs replacing.
Contact our company for replacement.
Cooling water outlet Check the COOLING WATER TEMP. display. Symbol: C2.
thermosensor fault If the temperature display shows an abnormal value, the sensor
or circuit board needs replacing. Contact our company for
replacement.
High temperature Check the H.T. GEN. TEMP. display. Symbol: 7H.
generator inlet If the temperature display shows an abnormal value, the sensor
thermosensor fault or circuit board needs replacing. Contact our company for
replacement.
Drain temperature Check the TEMP. MEASURE display. Symbol: d0.
sensor fault If the temperature display shows an abnormal value, the sensor
or circuit board needs replacing.
Contact our company for replacement.
Drain temperature rise Check the CYCLE TEMP. display. Symbol: d0.
If the temperature display shows an abnormal value, the sensor
or circuit board needs replacing.
Contact our company for replacement.
Cooling water LTD The insides of the cooling water tubes are dirty.
rise Clean the tubes.
Cooling water inlet Check the cooling water temperature settings.
temperature rise Check the cooling tower fan settings.
High temperature Examine the liquid level detection electrode rod.
generator liquid level If the rod is faulty it must be replaced
control fault Contact our company for replacement.
Solution adjustment It is time to adjust the solution.
alert Contact our company for adjustment.

PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter7 Maintenance Contract P 7-1

Chapter 7 Maintenance Contract


Why we recommend the Maintenance Contract .
How to order repairs .

Why we recommend the Maintenance Contract


Periodic inspection and maintenance is indispensable to ensure that the absorption
chiller operates safely at all times, and to keep its efficiency at high levels.
Accordingly, we strongly urge users to take out a Maintenance (after-sales
service) Contract with us.
Our company has a nationwide network of highly expert personnel with a wide
range of skills, ready to provide you with prompt after-sales service.
Under the terms of the Maintenance Contract, our company will take care of your
maintenance needs, to ensure long and trouble-free use of your machine.

Please contact our company for details of this contract.

How to order repairs


To order repairs under a Maintenance Contract, contact our company and quote
the following information:
1 Machine model Example: REW021
2 Machines serial number or code number Example: B07111101 (production No.)
3 Nature of the trouble (error number) Example: ER-0002
4 Your companys name, address and telephone number

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-1

Chapter 8 Definition of Terms


A
Absorbent (solution)
Liquid that absorbs the refrigerant. It is a solution of lithium bromide. Also simply
termed the solution.
Absorber
This is the device (in fact, a heat exchanger) where the absorbent absorbs the
refrigerant.
Air handling unit / air terminal
Equipment (air handling unit or fan-coil unit, etc.) that converts the chilled water
produced by the absorption chiller into a cold air current. Sometimes it also collects
dust from or humidifies the air current.
Alkalinity
A value expressing the concentration of alkaline substances in a solution, equivalent
to the solutions alkaline strength.
Alkalinity adjustment agent
A substance that adjusts the alkalinity of a solution. Added to the solution as
necessary.
Ammonium ions
Ions generated when ammonia is dissolved in water. They could cause corrosion if
they are present in the tubes.
Anticorrosive
Chemical for preventing corrosion of the chilled water and cooling water tubing
systems.
Automatic purging unit
A unit for purging the uncondensed gas accumulated inside of the purge tank with
automatic operation of the vacuum pump. The operation can be set at any given
time interval. This unit may be installed as an optional device.
Auxiliary equipment
The chilled water pump, cooling water pump and cooling tower fan.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-2

B
Backup battery
Battery that supplies backup power to the control panel when a power failure occurs
and when the panels power is turned off, in order to protect the data in the panel
circuit board memories.

C
Chilled water pump
Pump for circulating the chilled water between the absorption chiller and the air
handling unit.
Chloride ions
The level of chloride ions in water is an important index of its corrosiveness. Chloride
ions are always present in natural water, usually in substantial quantity.
Cooling water pump
Pump for circulating the cooling water between the absorption chiller and the cooling
tower.
Cooling tower (fan)
Equipment that cools the cooling water during cooling mode operation. If ambient
temperature is high, the fan unable to cool down the temperature of coolant to the
specific value, resulting in poor performance of the absorption chiller.
Compound gauge
Pressure gauge that indicates the high temperature generators pressure. Able to
indicate a wide range of pressure, including vacuum pressure. The generators
pressure is an index of its operating condition.
Concentration control valve
This solenoid valve is for automatically directing the refrigerant inside the evaporator
to the absorber in order to prevent crystallization of solution when the cooling water
temperature is low.
Condenser
This is the device (in fact, a heat exchanger) that cools and condenses the
refrigerant vapor generated by the low temperature generator.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-3

Conductivity
A liquids conductivity is a measure of the ease with which it conducts electricity. The
level of contamination of the cooling water is determined by measuring the waters
conductivity. The higher the conductivity is, the worse the contamination of coolant
is.
Control panel (microcomputer control panel)
Panel for control of the absorption chiller. Also called microcomputer control panel
due to the major role of its microcomputer in effecting control.
Corrosion suppressant
A very small quantity of this (molybdate) is added in the absorbent solution in order
to prevent corrosion of the absorption chiller. The solution must be analyzed
periodically to determine the amount of corrosion suppression in it, and the amount
adjusted if necessary.
Crystallization
What happens when the concentration of the absorbent (lithium bromide solution)
rises to the point where crystals of lithium bromide form in it. If the solutions water
content disappears completely, the lithium bromide will solidify (total crystallization).
This is essentially the same process as when salt separates out from brine when
brine is heated. Crystallization is liable to occur if the absorption cycle is maladjusted
or due to a power failure, etc.
If a large amount of crystallization occurs inside the chiller, it will be necessary to
dissolve the crystals by adding refrigerant or by applying heat to the solution from
outside.

D
Diaphragm valve rubber
The rubber element of the diaphragm valve.
Dilution (operation)
This consists of diluting the strong absorbent solution with refrigerant. It is mainly
carried out while the chiller is stopped. If it is not carried out, the absorbent will
crystallize, which will hinder operation.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-4

Dilution valve
Valve located in the tubing that carries the refrigerant (water) to the absorbent
solution. It is open during dilution.
Drain heat exchanger
This is the device (in fact, a heat exchanger) that exchanges heat between high
temperature steam for heating and the solution to enhance thermal efficiency.
For reduction of heat loss, It is also possible to prevent flushing of the drain at the
drain recovery system by lowering the temperature of hot drain.
Drain purge (valve)
The operation of purging water from the chilled water or cooling water tubing. Drain
purge valves are the valves used for such purging.
Drain trap
After steam is supplied to the high temperature generator, this device with internal
float separates the efficiently consumed steam (drain) from the rest and drains only
the former.

E
Earth Leakage detector
This is an equipment that perceives the abnormality when the leak occurs, intercepts
the circuit automatically, and cuts the power supply. It is built into the substrate of
the control board.
Evaporator
This is the device (in fact, a heat exchanger) that vaporizes the refrigerant to
produce chiller water.

F
Feedwater
Water that is supplied to replenish the cooling tower water tank when its level is low.
The water is usually supplied through the ball tap (automatic supply valve) at the
cooling tower water tank.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-5

This is indispensable because shutting off this valve may cause fault such as .
corrosion of heat transmission tubes due to condensation of cooling water or dry run
of cooling water pump.
Flow switches
Protective devices that sense the flow of the chilled water and cooling water.

H
Heat transmission tubes
Tubes that pass through the absorption chillers interior and through which heat is
transmitted.
Heavy load
This refers to more than 2000 hours of operation per year. It also refers to prolonged
continuous operation at 100% capacity. If machine is operated under this condition,
it could result in result in reduced durability and performance. Heavy load operation
necessitates addition of options such as automatic purging unit and solution filter,
and very thorough maintenance, carried out with increased frequency.
High temperature generator
A heat exchanger where the lithium bromide solution is heated by steam and then
used to evaporate (regenerate) the refrigerant.

I
Interlock
Mechanism that prevents operation of certain components unless specific conditions
are met.
An example of such a condition is that the RUN signals for the chilled water pump or
cooling water pump.
Ionized silica
Substance present in water that can cause formation of scale.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-6

L
LED lamps
Acronym for Light Emitting Diodes.
Lithium bromide solution
Solution used as the absorption chillers absorbent.
Low temperature generator
A heat exchanger that uses the refrigerant vapor generated by the high temperature
generator to heat the absorbent.

M
Magnet switches
Switches for operating equipment with large capacitance.
Main circuit breaker (MCB)
Power switch that has a mechanism for shutting of all power to the absorption chiller
if overcurrent occurs.

O
Overcurrent (overload)
This refers to when the electrical current to the motor is higher than the rated
current, due to a fault, or overload.

P
Performance enhancement agent
Substance (usually a special alcohol) that is added to the absorbent in small
quantities to enhance the efficiency of the absorption chiller.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-7

pH
This is an index of hydrogen ion concentration, or in other words, of the degree of
acidity or alkalinity.
pH = log10 [H+] [H+] is the molar concentration of H+
When pH < 7, the substance is acidic; the lower the value below 7, the stronger
the acid.
When pH > 7, the substance is alkaline; the higher the value above 7, the
stronger the alkali.
When pH = 7, the substance is neutral.
Pre-alarms
These are indicated by EA + code number appearing on the control panels
display. Pre-alarms do not necessitate stoppage of the machine, but they indicate
that control operation or functions are being impeded, or could be impeded soon.
Pressure gauge
Indicates the high temperature generators pressure or steam supply pressure.
Pressure switches
Monitors the high temperature generators pressure. One of the high temperature
generators safety devices.
Protective circuits
Circuits for detection of high temperature generator low liquid level, seismoscope
signals, and external emergency stop signals.
Protective devices (instruments)
Accessory equipment for the absorption chiller that assures safety during its
operation.
Purge tank
Tank into which the uncondensible gas that accumulates inside the absorption chiller
is drawn, and where it is stored.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-8

R
Refrigerant
Medium (pure water) used by the absorption chillers internal cycle in the production
of chilled water.
Refrigerant pump
Pump for circulation of the refrigerant.
Refrigerant heat exchanger
This is a heat exchanger to which the refrigerant is cooled with cooling water.

S
Scale
Film consisting of impurities and metal oxides, etc., that forms on metal surfaces.
Seismoscope
Device that senses seismic activity and stops the absorption chiller in the event of an
earthquake. One of the optional protective devices.
7-segment LED (digital display)
LED display made up of spaces each consisting of 7 segments plus dots, and able
to display letters and digits.
Sight glass
Glass window in the absorption chiller that allows personnel to monitor the internal
operation condition.
Silica
Common name for silicon dioxide. High concentrations of silica in the cooling water
could lead to formation of hard scale.
Slime
Viscous accretion composed of microorganisms.
Solenoid valve
Valve that is opened and closed by magnets. Also called a magnet valve.
Solution analysis
Analysis of the composition of the absorbent solution, i.e. analysis to determine the
level of corrosion suppressant and alkali, etc. in the solution.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-9

Solution filter
This filter is necessary for removing oxides that are formed due to deterioration of
solution or foreign particles inside equipment. Filter element needs to be replaced
periodically.
Solution heat exchanger
Heat exchanger that exchanges heat between high and low temperature solution,
this enhancing the absorption chillers efficiency.
Solution pump
Pump that sends the solution from the absorber to the generator.
Spray pump
This pump is hermetic canned type pump that sprays the solution to absorbers heat
transfer tubes.
Startup congestion
Failure of the absorption chiller to start up, due to activation of protective device, etc.
If this condition is not cleared (the absorption chiller fails to start up) within a certain
period of time, an alarm is issued.
Steam control valve
An electric valve for adjusting the amount of steam to be supplied in response to the
requirements of the load.
Steam cutoff valve
An electric valve that opens completely with all closes according to driving and the
stop.
Strainers
These are fitted to the steam, solution and water tubing, from which they filter out dirt
and other foreign matter.
Sulfide ions
Sulfide compound ions dissolved in the water, liable to cause corrosion damage if
present in high concentrations.
Sulfuric acid ions
Ions of sulfur trioxide dissolved in the water. If sulfur is present in the fuel, it will be
turned into sulfur oxide by combustion, and sulfuric acid ions occur in the cooling

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-10

water when exhaust gas containing sulfur oxide is dissolved in it. If these ions are
allowed to remain, they will damage the absorption chiller.
Sulfur oxides
General terms for compounds of sulfur and oxygen, often written as SOx. SOx are
generated by the sulfur present in the fuel. They are harmful substances and cause
atmospheric pollution.

T
Temperature regulation startup/stop
These terms refer to startup or stop of steam supply in response to the requirements
of the load.
Thermal relay
One of the protective devices. Its contacts open when overcurrent occurs. It is fitted
to the motor solenoid switch inside the control panel. Also called a temperature
relay.
Thermosensors
There are various types of thermosensors, including thermocouples and resistance
thermometers. The absorption chiller employs thermistors, platinum resistance
temperature sensors, and other varieties of resistance thermometers as its
thermosensors.
Thermostat
A type of switch that turns on/off when a certain temperature is reached.
Total hardness
Index representing the total quantity of calcium ions and magnesium ions (which
cause hardness) in water.

U
Uncondensed gas
Gases (other than refrigerant vapor) that accumulate inside the absorption chillers

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001

Chapter8 Definition of Terms P 8-11

shell, e.g. hydrogen and air. If these gases are allowed to build up, they will cause a
marked fall in the absorption chillers refrigerating capacity, and impede its
operation.
Unloaded operation
This refers to running of the absorption chiller without any air handling unit or other
load. The absorption chiller should NEVER be run without any load, or its evaporator
tubes will freeze. Also make sure that the air handling unit is never turned off during
dilution operation.

V
Vacuum extraction
The operation of extracting uncondensed gas that has built up inside the absorption
chiller, by means of a vacuum pump.

W
Water chamber gaskets
The gaskets between the chilled water and cooling water chambers and their covers.

PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.

You might also like