Professional Documents
Culture Documents
CONTENTS
TO SET
ERS091 1C APPROVED by CHECKED by DOCUMENT NAME
Naka REW ABS. CHILLER
Z.Z
ERS076 1C 4
Jul,16th,'15 DRAWING AND DOCUMENTS
3 APPROVED by PREPARED by
23 Jul,23th,'15 z.z L.Q DOCUMENT NO. REV
1
1 Jul,22th,'15 z.z L.Q T.SH L .Q ERS155Y-Q15714Q 2
YEA Ori. REV PAGE DATE APP'D BY Jul,20th,'15 Jul,14th,'15
NOTE.
16 CAPACITY 1
CONTROL VALVE
17 LITHIUM BROMIDE 1SET
SOLUTION
18 REFRIGERANT 1SET
(PURE WATER)
19 STANDARD ACCESSORIES 1SET LINER FOR SETTING
OIL FOR PURGE PUMP etc.
20 FACTORY TEST 1SET HYDRAULIC PRESS. TEST
AND INSPECTION (WATER BOX)
AIR TIGHTNESS TEST (MACHINE)
APPEARANCE INSPECTION etc.
21 SOLUTION FILTER UNIT 1SET
1 22
3. MATERIALS (REW)
13 TEMPERATURE REGULATION 1
STOPPAGE
14 CYCLE GUARD VALVE 1 CYCLE-GUARD VALVE OPEN
17 TEMPERATURE CONTROLLER 1
NAME DESCRIPTION
6 FOUNDATION 1SET
7 INSULATION 1SET
7.NOTES (REW)
(1) PERIODICALLY INSPECT THE CHILLER ONCE A YEAR. IT IS RECOMMENDED THAT THE REFRIGERANT PUMP
AND THE SOLUTION PUMP BE OVERHAULED EVERY 20,000 HOURS OF OPERATION OR 5 YEARS, WHICHEVER COMES FIRST.
IF THE CHILLER IS USED FOR CRITICAL PURPOSES, SHORTER OVERHAUL INTERVALS ARE RECOMMENDED.
(2) THE SPECIFICATION OF THE CAPACITY CONTROL RANGE ASSUMES THAT TEMPERATURE CONTROL IS
CARRIED OUT UNDER RATED CONDITIONS (THE CHILLED WATER OUTLET TEMPERATURE AND THE COOLING
(3) TO PREVENT CORROSION OF THE HEAT TRANSMISSION TUBES, INSTALL STRAINERS OF APPROXIMATELY 10 MESH IN
(4) THE CHILLER IS DESIGNED TO MAINTAIN A CONSTANT FLOW OF CHILLED WATER/COOLING WATER REGARDLESS OF
(5) PROPERLY CONTROL THE QUALITY OF CHILLED WATER AND COOLING WATER. ENSURE THAT THE WATER QUALITY
GUIDELINE OF THE JAPAN REFRIGERATION AND AIR CONDITIONING INDUSTRY ASSOCIATION (JRA-GL-02E-1994) IS MET.
(6) OUR STANDARD TUBE MATERIAL FOR THE HIGH TEMPERATURE GENERATOR IS JIS G3463 SUS430TB.
FOR THE QUALITY OF STEAM DRAIN WATER, ENSURE THAT THE WATER QUALITY GUIDELINE OF THE JAPAN
(7) THE STARTUP TIME OF THE ABSORPTION CHILLER IS TYPICALLY 20 TO 30 MINUTES, BUT IT MAY VARY DEPENDING
ON THE MODEL, CHILLED WATER/COOLING WATER CONDITIONS, THE TYPE OF THE STEAM DRAIN RECOVERY SYSTEM,
AND THE LEVEL OF APPLIED LOAD. THE STARTUP PROCESS CONSUMES A LARGER AMOUNT OF STEAM THAN THE RATED
LEVEL (130 TO 140 % OF THE RATED VALUE) AND MAY CAUSE DROP OF STEAM SUPPLY PRESSURE AND FAILURE OF
DISCHARGING THE STEAM DRAIN. IT IS ADVISABLE TO DESIGN THE SYSTEM WITH CONSIDERATION GIVEN TO THESE POINTS.
(8) CONTROL THE COOLING WATER INLET TEMPERATURE BETWEEN 15 AND 32 C. EQUIPMENT/PIPING REQUIRED FOR
CONTROLLING THE COOLING WATER TEMPERATURE ARE NOT IN OUR SCOPE OF SUPPLY. IN TRANSITIONAL SEASONS
OR DURING COOLING OPERATION IN WINTERTIME, THE COOLING WATER TEMPERATURE AND LOAD MAY BE LOW,
AND THE CHILLER MAY FREQUENTLY START/STOP. IN SUCH CASES, IT IS RECOMMENDED TO CONTROL THE COOLING WATER
TEMPERATURE WITH ITS LOWER LIMIT SET TO THE RATED VALUE - 5 C FOR THE STABLE SUPPLY OF CHILLED WATER.
(9) THE DESIGN DRAIN TEMPERATURE AND OUTLET PRESSURE OF THE CHILLER IS 90 C AND 0.2 TO 0.39 MPa (gage).
NOTE THAT THE PRESSURE FALLS TO APPROXIMATELY 0.05 MPa (gage) WITH LOAD REDUCTION.
WHEN SPECIAL SPECIFICATIONS FOR THE HOT WELL TANK POSITION OR THE DRAIN TEMPERATURE ARE
(10) AFTER ON-SITE INSTALLATION, AN AIR-TIGHTNESS TEST AND OPERATION CHECK ARE PERFORMED FOR THE CHILLER.
IF PERFORMANCE CONFIRMATION IS ADDITIONALLY REQUIRED, MAKE SURE THAT SUFFICIENT LOAD IS AVAILABLE.
YOU ARE ASKED TO PREPARE PERFORMANCE MEASUREMENT INSTRUMENTS AND DATA COLLECTION PERSONNEL,
AS WELL AS WATER, ELECTRICITY, AND OTHER UTILITIES NECESSITY FOR THE TEST RUN.
(11) UPON DELIVERY OF THE ABSORPTION CHILLER FROM US, THE UNIT IS TEST RUN AND ADJUSTED FREE OF CHARGE.
AN INSPECTION IS PERFORMED ONCE FREE OF CHARGE BY VISITING THE SITE WITHIN ONE YEAR AFTER
THE START OF OPERATION. IF THE PRODUCT FAILS DUE TO ANY DEFECT ATTRIBUTABLE TO US WITHIN
THE WARRANTY PERIOD, PART REPLACEMENT OR REPAIR IS CARRIED OUT WITHOUT CHARGE. OTHER SERVICES
ARE ALSO AVAILABLE AT YOUR COST. CONSULT US, IF REQUIRED. ESPECIALLY, NOTE THAT TUBE CLEANING
SERVICE IS OFFERED AT YOUR COST. THIS PROVISION IS SUBJECT TO FURTHER NEGOTIATION IN THE CASE OF
USING THE CHILLER FOR INDUSTRIAL PURPOSES.
(12) THE SELECTION OF CHILLER PARTS AND EQUIPMENT SHOULD BE LEFT TO US.
(15) INSTALL A VALVE ON THE STEAM SUPPLY LINE AND CLOSE IT WHEN STOPPING THE CHILLER.
IN THE CASE OF PROLONGED STOPPAGE OF THE CHILLER WITH THE STEAM SUPPLY VALVE OPEN FOR REMOTE
START/STOP CONTROL, IT IS RECOMMENDED TO INSTALL AN OPTIONAL STEAM SHUTOFF VALVE.
FINAL USER
PROJECT SERVICE
TO SET
Refrigeration Products
ISSUED BY & System Division
S.Tanaka Feb.28.07
M. Agatsuma Feb.22.07
APPROVED BY
CHECKED BY M. Agatsuma Feb.22.07
CONTENTS
1. FOUNDATION P.2
2. INSTALLATION P.2
1. FOUNDATION
1) The running weight of the Absorption chiller (described in the attached OUTLINE
DIMENSIONS ) is distributed equally on the foundation contact surface
(shown by in the attached FOUNDATION DETAIL ).
3) Finished horizontal surface of the foundation should be within the accuracies noted in
the attached FOUNDATION DETAIL.
4) The foundation floor should have carry out waterproofing finish for machine of
maintenance making it easy.
2. INSTALLATION
2) Avoid a location liable to excessive moisture and dust to prevent future electrical
problems.
5) Pay attention to good lighting for convenient routine monitoring, maintenance and
inspection.
+20
7) Consider manufacturing allowances as -10
mm to the dimensions of OUTLINE
DIMENSIONS .
8) Prepare sufficient maintenance space (1m min. around the machine. 0.2m min. above
the machine) and a space for withdrawing the tubes referring to attached OUTLINE
DIMENSIONS , and FOUNDATION DETAIL.
9) Regarding the level of the machine, never exceed 1/1000 in both length and width
directions of the shell as below.
10) When installing machine, carry out machine leveling as above using shim liners and then
set anchor bolts and fill anchor holes firmly with mortar. Shim liners are standard
accessories.
3. WATER PIPING
1) Specify the chilled water inlet nozzle at the right side or the left side on the OUTLINE
DIMENSIONS. The inlet nozzle for cooling water is always to the left side of the
machine as shown in the OUTLINE DIMENSIONS. Refer to the OUTLINE
DIMENSIONS and the specification data sheet regarding the nozzle positions, nozzle
side and water pressure drop.
2) The specifications of nozzle flanges of chilled water and cooling water of the Absorption
chiller is stated in SPECIFICATION DATA SHEET. Companion flanges and bolts
shall be provided by vendor.
3) The maximum allowable working pressure of chilled water lines and cooling water lines
is stated in SPECIFICATION DATA SHEET. Regarding the installed positions of the
chilled water pump, the cooling water pump and the expansion tank or pressurization
unit, design their installed positions so that pressure does not exceed the above
maximum pressure on the Absorption chiller water box when considering both static
water head and pump head.
4) Install stainers of 10 meshes or more at the inlet lines of chilled water and cooling water
to prevent foreign objects entering tubes.
5) Keep the chilled water and the cooling water flow rate always at the specified flow rate.
Install thermometers and pressure gauges immediately adjacent to inlet and outlet of
chilled and cooling water connections to allow easy maintenance. It is recommended
that a flow meter should be provided on the chilled water lines in order to measure the
refrigerating capacity by comparing chilled water flowrate with inlet and outlet
temperatures.
6) Chilled water pump and cooling water pump should be designed specifically for use on
each Absorption chiller.
7) Install an expansion tank or pressurization unit on the chilled water line. ( Refer to the
attached PIPING FLOW SHEET ).
8) 3/4 sockets or Rc3/4 female screws are provided to fit an air vent and a drain valve on
each water box. Mount the respective stop valves to them and run piping into the drain
pit. Install air vent valves at suitable locations on the chilled water piping or the cooling
water piping to eliminate water hammer and air locks.
11) In hydraulic pressure tests of chilled water lines or cooling water lines, always confirm
the test pressure marked on water box flange section of each line and under no
circumstances exceed the marked test pressure. Further, never execute the pressure
test using gas. pressure tests using gas can be very dangerous due to the risk of broken
pieces scattering under failure.
12) Control the water quality according to the standard of the Japan Refrigeration and Air
Conditioning Industry Association (JRA-GL 02-94). Install bleed-off devices on the
cooling water lines. (Refer to an attached PIPING FLOW SHEET ).
JRA-GL 02-94
Standard Item
PH 25 deg C 6.58.2 6.08.0 6.88.0 7.08.0
referent Item
FERROUS (mgFe/l) < 1.0 < 0.3 < 1.0 < 1.0
COPPER (mgCu/l) < 0.3 < 0.1 < 1.0 < 1.0
2-
SULFIDE ION (mgS /l) traceless traceless traceless Traceless
AMMONIUM ION (mgNE4+/l) < 1.0 < 0.1 < 1.0 < 0.1
CHIORINE RESIDUE (mgCl/l) < 0.3 < 0.3 < 0.3 < 0.1
CARBONATION ISOLATED (mgCO2/l) < 4.0 < 4.0 < 4.0 < 0.4
13) If the cooling water inlet temperature can fall below 15 deg C at a steady load operation,
provide a by-pass valve for the cooling tower or contriol the cooling water temperature
by scheduling operation of the cooling tower fan(s) so that water does not fall below
15deg C.
14) Connect piping between the absorber and the condenser water box nozzle.
(16JSE032-080, RAW)
15) Install short bent pipes as shown in the drawing below, in the nozzle section of
each water box in order to enable opening of the water box cover.
16) Install a stop valve for chemical tube cleaning on the cooling water pump delivery line.
(Refer to an attached PIPING FLOW SHEET ).
17) Apply adequate supports and flexible piping etc, so that piping weight and vibration have
no direct effect on the Absorption chiller.
4. STEAM PIPING
1) If there is any possibility of the steam supply pressure exceeding 0.78MPaG, a pressure
reducing valve and a safety valve(blow off pressure : 0.88MPaG) should be furnished on
the steam pipe line. The exhaust pipe from the safety valve should be run to a safe
location external to the building.
3) Strainers having 80-100 meshes should be located on the up- stream side of the
capacity control valve together with a reducer valve (if provided ).
4) Steam traps should be installed in steam supply line up-stream of steam valve.
5) Allow a length of straight pipe of 1 metre or 10 pipe diameters, whichever is the longer,
before and after the control valve. Piping between the capacity control valve and
generator inlet should slope downwards least 0.2m to prevent flow - back of drain.
6) The capacity control valve (=the steam control valve) is sized by calculating rated supply
pressure ( inlet side of the capacity control valve) and the rated steam consumption. If
the valve size is smaller than the piping diameter, inlet and outlet piping diameter is to
be reduced gradually with pipe reducing fittings.
7) A pressure gauge (range : 0-1.5MPaG) are to be installed respectively before and after
the capacity control valve. It is recommended that by - pass piping around the capacity
control valve be provided for convenient maintenance and inspection of the control valve.
8) Installation of the nozzle flange of the generator should be detachable so that bolts can
be easily tightened after initial steam application.
9) Install short bent pipes as shown in the drawing below, in the nozzle section of the
steam box on the high temperature generator in order to enable opening of the steam
box cover.
1 10) Connect the generator nozzle using a flexible pipe or equivalent to prevent the nozzle
flange of the generator from excess force due to thermal expansion.
11) A check valve and a stop valve should be installed at the outlet of steam drain.
12) In applications employing electrical capacity control, install wiring between the capacity
control valve motor and the junction box mounted on Absorption chiller at job site. If
pneumatic capacity control is used, install air piping between the actuator of the capacity
control valve and the temperature controller mounted on the Absorption chiller.
13) Allowable back pressure on the steam condensate outlet of the chiller is 0.05MPaG
when the steam supply pressure is 0.78MPaG. Steam condensate piping shall be
designed suitable for those pressure.
14) In case of installation of any Absorption chiller, each Absorption chiller should be
installed the separate steam drain piping. If that piping should be used in common, it will
be possible to make troubles.
15) Control the water quality for steam according to the following table.
+
AMMONIUM ION (mgNH 4/l) <0.1
-
CHLORIDE ION (mgCl /l) <20
2
SULFURIC ACID ION (mgSO4 -/l) <10
Rapture disk should be handled carefully to prevent external damage during transportation
or setting-up of Absorption chiller.
Install appropriate piping from the rupture disk to safety place where nobody is damaged
with spouted solution or refrigerant vapor from the rupture disk at the burst of the rupture
disk.
Accumulating tank to keep those liquids from the rupture disk is recommended to install at
the intermediate of exhaust piping line to prevent discharging to the surroundings.
1) Be sure not to loose the machine side thread of the fusible plug when the exhaust piping
work behind the fusible plug is performed. The loosen connection may cause air
tightness trouble .
2) Perform the exhaust piping work in order to assemble or disassemble itself easily. It
makes easy to do air tightness test around the fusible plug at periodical maintenance.
3) Apply adequate supports so that the fusible plug exhaust piping weight have no direct
effect on the fusible plug.
INSTRUCTION MANUAL
STEAM DOUBLE-EFFECT
ABSORPTION CHILLER
MODEL REW SERIES
Introduction
Introduction
Thank you for purchasing a REW Series Absorption Chiller from the Ebara
Refrigeration Equipment Systems
This Instruction Manual provides the information that is necessary for the operation,
maintenance of the absorption chiller, and describes its construction.
Prior to operate this absorption chiller, be sure to read and understand thoroughly
this manual and specified documents such as Specifications, Installation
Instructions, etc. The instructions in these documents are prepared to ensure correct
and safe operation of the absorption refrigerator, and to prolong its service life.
CAUTION
For safety:
Before using the machine, thoroughly read Chapter 1 Safety Instructions, so that
you will use the machine safely and correctly.
After reading this manual, keep it at the place where operators can
consult it at any time.
Introduction
Environmental Considerations
(Instructions for Operation)
Absorption chiller (models using a Molybdenum based absorbent
Considerations for environmental conservation
To pursue the purposes of the PRTR Law and the MSDS Law enacted/enforced to promote improvements
in the voluntary control of chemical substances by businesses and to prevent any impediment in
environmental protection, considerations for environmental conservation are given below.
Mishandling absorption chillers (generally referring to absorption chillers and chiller-heaters) and their
accessories may impose extra burden on the environment. To operate them or perform work/maintenance
for them, pay close attention to the following considerations.
Reference) PRTR Law: Law Concerning Reporting, etc. of Release of Specific Chemical
Substances to the Environment and Promotion of the Improvement of Their
Management (PRTR stands for Pollutant Release and Transfer Register.)
MSDS Law: Ministerial Ordinance to Define the Method of Offering
Information on the Properties and Handling of Specific Chemical Substances
(MSDS stands for Material Safety Data Sheet.)
1. Chemical substances
The following chemical substances are generally used for newly installed absorption chillers.
They are not specific chemical substances subject to the PRTR Law.
Absorbent (Molybdenum based): Lithium bromide solution (containing less than 0.1 % of inhibitor):
approx. 1000 kg/100 USRt
Performance enhancement agent:Octyl alcohol:approx. 3.8 L x 1 bottle/100USRT
Lubricant: Mineral oil (attached to models with a purge (vacuum) pump): 500 mL x 3 bottles/unit
Sealant: Anaerobic sealant: 50 mL x 1 to 2 bottles/unit
(attached for on-site welding if a split unit is carried in)
Pure water (ion-exchanged water) of 50 to 500 kg (per unit) may be attached as a refrigerant.
The quantities above are for reference only. For actual quantities required for specific chillers, contact
us or your service agent after checking the serial number written on the nameplate.
2. Packaging materials
For unnecessary packaging materials after carry-in/installation, have them disposed of by a specialist
company.
2-1 For cardboard boxes, wooden crates, and plastics, have them disposed of by a specialist company.
2-2 Steel materials, such as frames used for carry-in, can be disposed of by us at your cost.
3. Absorbent
An absorption chiller is filled with an absorbent (lithium bromide solution), a refrigerant (pure water), and a
small amount of performance enhancement agent (Octyl alcohol). The absorbent (lithium bromide
solution) contains a trace of inhibitor.
If the chiller is damaged or if its valves are mishandled, the undiluted absorbent may leak through the drain
to the outside of the building. To prevent it, pay attention to the following.
Introduction
3-2 Considerations upon carry-in/installation
When carrying in and installing the chiller filled with the absorbent, pay close attention not to damage
it. Particularly, small tubing and valves should be protected from being stepped on.
Introduction
4. Oil
To manage a lubricant for the purge pump (if provided with absorption chillers/chiller-heaters) or a fuel oil
for oil-fired chiller-heaters, pay attention to the following.
4-1 Lubricant
Add an appropriate amount of the lubricant to the purge pump while checking the oil gauge after
stopping the pump. If the proper level is exceeded, discharge the excessive lubricant from the drain
valve. Overfilling may cause the blowout of the lubricant from the pump discharge during pump
operation. If the accumulation of condensed water in the lubricant exceeds the proper level, the
lubricant may also blow out from the pump discharge during pump operation. Check the oil gauge
periodically and discharge the excessive lubricant from the drain valve, if required.
The lubricant should be replaced periodically. Use the specified lubricant only. Waste lubricant may
contain the absorbent, water, and performance inhibitor. Have it disposed of by a specialist company.
Do not discharge waste lubricant directly to the drain.
4-2 Fuel
Oil fired absorption chiller/heater damages the fuel oil piping etc. or mistakes the handling such as
valves and does the oil leakage etc. The fuel oil might flow out directly from the drain ditch outside
the building. Please note each item.
Asking in equipment
It must not flow directly into the drain ditch when the fuel oil leaks.
For Example, the outlet stopping lid is prepared. Or, the fuel equipment and piping are made a
coating that prevents oil. There is a method of setting up the side ditch and the oil retaining wall.
Asking under use
The fuel oil must use specified oil. Oil outside specification might interfere to pakkin used for the
oil piping and other parts. Please note it.
Please do not touch mistaking it to valves of the fuel oil piping. Please do not damage it by putting
the foot on the small piping and valves.
Please open a fuel oil supply former valve after confirming oil doesn't leak when
it starts every day first time. Please check the machine surroundings once or more a day going.
Please promptly stop the machine, intercept the fire, and close a former valve of the fuel oil
service tank when the fuel oil begins to leak from the fuel piping (The equipment side is laid, and
include it in equipment). Please contact the leakage location, the leakage condition, and the leak
rate, etc. our service technology member of charge.
Please close the upstream side valve in the vicinity of the leakage location.
Please do not throw the fuel oil directly to the drain ditch.
Please give the emergency measure such as damming up temporarily when flowing out
from the drain ditch.
Please spread the material that absorbs oil when leaking to the floor side.
Asking a long time stopping
The fuel oil supply valve is to close without fail and confirm that it is, please when you stop the
machine for a long time.
5. Exhaust gas
Absorption chiller-heaters are not legally defined as boilers. However, they may be deemed as
soot/smoke emitting facilities depending on the firing rate; in such cases, they are subject to the
emission standard of soot/dust, SOx, and NOx set by the Air Pollution Control Law. Consult your local
Introduction
Bureau of Environmental Protection since the emission of exhaust gas is regulated differently by each
prefecture's ordinances, and related laws/ordinances may be revised. The user may be required to
periodically submit the report of measurements after starting chiller operation.
For EBARAs absorption chiller-heaters, burner combustion has been adjusted to satisfy the emission
standard. Use the specified gas and operate the chiller within the rated firing rate. Using a fuel that
consists of different components or of low quality may cause poor combustion, and the exhaust gas may
impose extra burden on the environment.
If the burner must be adjusted, have it adjusted by your service agent.
Introduction
7-2 Periodic inspection
For the details of periodic inspection and periodic replacement of consumable parts, see the
appropriate section of this Instruction Manual. Use the specified parts for replacement. Have repair
and replacement performed by your service agent.
8. Relocation/disposal of equipment
To relocate, dispose of, or scrap an absorption chiller, special knowledge and techniques, such as handling
the absorbent in the unit, are required. Never discharge the absorbent in the chiller directly to
the drain.
8-1 Relocation
To relocate the chiller to another site, consult your service agent on absorbent handling, vacuum
maintenance, equipment protection, etc.
8-3 Disposal/scrapping
Have the chiller disposed of/scrapped by a specialist company that separates materials, such as
copper and steel, for reusing them as resources.
CONTENTS
CONTENTS
Introduction
Environmental Considerations
Chapter1 Safety Instructions
Chapter2 Functions and Appearance
Chapter3 Control Panel
Chapter4 Operation
Chapter5 Maintenance and Treatment
Chapter6 Troubleshooting
Chapter7 Maintenance Contract
Chapter8 Others
WARNING
Instructions
Before cleaning or inspecting the cooling tower fan, or chilled water
pump, etc., (whose operation is coupled with that of the
absorption chiller) be sure to turn off the power to such
equipment.
Otherwise, you could be injured by electric shock or by the equipment
operating.
Stop the absorption chiller immediately if fire, earthquake or
lightning occurs.
Continuing operation in such situations could result in fire or electric
shock.
Do not touch the components or wiring inside the operation
panel, especially of your hands are wet.
You could receive an electric shock if you touch these items.
Carry out the periodic inspection on the high temperature
generator once a year.
The unit is defined as a second class pressure vessel in Industrial Safety
and Health Law.
Do not place inflammable hazardous substances (gasoline,
thinner, etc.) or easily combustible materials in the vicinity of the
absorption chiller.
Doing so could result in fire.
Do not put fingers or bars into the rotating parts of the fans or
pumps.
Such rotating parts will injure you.
Do not place materials in the operation panel or Ventilating hole
of outdoor cover.
Doing so could result in fire or breakdown.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001
CAUTION
Instructions
When a safety device or protective device is actuated, do not
restart operation until the cause of the actuation has been
eliminated.
Restarting operation without eliminating the cause of the fault could result
in fire.
Do not place heavy objects on the machine body or the operation
panel, and do not get on top of the equipment.
Falls could result in injury.
Have inspection and maintenance of the machine and equipment
performed by your service agent.
Erroneous or poor inspection/maintenance could result in electric shock,
fire or burn injury.
Put up signs forbidding unauthorized persons to touch the machine.
If there is danger that persons may touch the machine in spite of warning signs,
fence off the machine.
Misuse of the machine could result in injury.
Do not allow water to get onto or into the machine body or the
operation panel.
Presence of water could result in electric damage or electrical leakage.
Use only fuses of the correct capacity.
Incorrect capacity fuses will cause breakdown of the equipment, or fire.
Use only the power supply stipulated on the equipments
nameplate.
Use of an incorrect power supply will result in fire or electric damage.
Keep the chilled water, cooling water and steam at the prescribed
pressures at all times.
Other pressures could result in spouting or leaks, which could cause
injury.
During storage of the machine, do not touch the absorbent, or leaked
absorbent, with bare hands.
The absorbent will inflame skin, and will corrode metals that it comes into
contact with.
Do not alter the value settings of the safety devices and
protective devices.
Operation with incorrect value settings could lead to breakdown or fire.
Do not touch those parts where a Caution! High temperature!
sticker is affixed.
Touching such parts will result in burn injury.
Stop the operation of the purge pump before changing the oil
The oil will spout and may result in burn injury.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001
Where outer casings are installed: Some outdoor covers are very heavy; take
special care when installing or removing such covers in moderate gale. Securely
install fixtures so that they will not fall off.
Careless handling of such covers could result in injury.
Where outer casings are used: Do not run the machine with the covers
opened.
Exposure to wind and rain could cause breakdown or electrical leakage in
electrical components.
Instructions
Disassembly, repair and remodeling of the absorption chiller
should be performed by a specialist company only.
Errors in repair could result in electric shock or fire.
CAUTION
Instructions
Have shifting or transportation of the absorption chiller
performed by a specialist company.
Errors in shifting or transportation work could result in damage, water
leaks, electric shock or fire.
Have disposal of the absorption chiller performed by a
specialist company.
Incorrect disposal could lead to leaks of the absorbent from the
machines interior, which could cause skin inflammation and corrosion of
metals.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Abscrption Chiller) CRA605E-H001
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Functions
The REW series absorption chiller is a double-effect absorption chiller powered by steam.
It uses water as refrigerant and lithium bromide (LiBr) as absorbent. It uses an evaporator
to produce chilled water for cooling.
As can be seen from the appearance, the absorption chiller integrates an evaporator, an
absorber, a condenser and a low temperature generator inside a shell housing, with the
high- temperature generator deployed alongside the shell. The other components of the
machine are the solution heat exchanger, solution pump, spray pump, refrigerant pump,
steam control valve and control panel.
Major components and their functions
Evaporator
Refrigerant liquid is sprayed onto the evaporator tubes and vaporized under high vacuum;
the refrigerant on the surfaces of the tubes takes evaporation latent heat from the cold
water flowing inside the pipes, thus lowering the temperature of the chilled water.
Absorber
Absorbent is sprayed onto the absorber tubes by solution spray pump, where it absorbs
the refrigerant vaporized from the evaporator. The absorption heat generated by such
absorption is taken up by the cooling water flowing inside the tubes, enabling absorption to
continue on the outsides of the tubes. Absorbent that has absorbed refrigerant vapor and
been diluted thereby (referred to as weak solution below) is sent by the solution pump to
the high- temperature generator and low temperature generator, via the solution heat
exchanger.
High temperature generator
In the high temperature generator, the weak solution sent from the absorber by the solution
pump is heated by steam supplied from the high-temperature generator. When heated, the
weak solution gives off high-temperature refrigerant vapor, and thereby becomes
concentrated once again (referred to as strong solution below). This strong solution is
returned to the absorber via the solution heat exchanger.
Low temperature generator
The high-temperature refrigerant vapor generated by the high temperature generator is
drawn into the low temperature generator tubes, and heats the solution on the outsides of
the tubes, thereby concentrating the solution. The concentrated solution (absorbent) is
then returned to the absorber as strong solution, via the solution heat exchanger.
Condenser
In the condenser, the refrigerant vapor generated by the low temperature generator while
heating the solution is cooled by the cooling water flowing through the condensers heat
transmission tubes, and is thereby condensed into liquid refrigerant. The liquid refrigerant
is returned to the evaporator, where it is once more sprayed onto the evaporators heat
transmission tubes
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Appearance
z REW Absorption Chiller Front view (Shape may be different depending on model)
(015025)
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
z REW Absorption Chiller Rear view (Shape may be different depending on model)
(015025)
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
z REW Absorption Chiller Front view (Shape may be different depending on model)
(028050)
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
z REW Absorption Chiller Rear view (Shape may be different depending on model)
(028050)
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
CONT.VALVE CLOSED
POWER
STOP
RUNNING
DILUTION
FAILURE
SAFETY EQUIP.
PRE-ALARM
STOP RUN STOP RUN STOP RUN
SELECT. SET
MODE
BUZZER BUZZER
STOP START
STOP
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Names of displays
and controls
Absorption Chiller Control Panel
Operation displays
POWER
STOP
RUNNING
DILUTION
SAFETY EQUIP.
PRE-ALARM
FAILURE
CONT.VALVECLOSED
STOP RUN STOP RUN STOP RUN
Lamps indicating
SOL. SOL. REF. operating conditions.
PUMP SPRAY PUMP
PUMP
Digital display
Displays various setting
SELECT. SET values and operation
MODE conditions in digital form.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Detailed descriptions
Operation displays
POWER
STOP
RUNNING
DILUTION
SAFETY EQUIP.
PRE-ALARM
FAILURE
The term safety circuits refers to the following safety functions: external
emergency stop signal and seismometer.
Note that it is possible that there is abnormality in these items even when this
indicator is lit.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Description
Chilled water temperature is the item
selected
OPERATG STATUS H. GEN. TEMP. CYCLE TEMP b1 indicates chilled water inlet temperature.
CHILLED WATER TEMP. COO L. WATER TEMP. CONT. VALVE OPEN The current chilled water temperature is
OPERATG hrs. STEAM HEATING hrs. REF. PUMP hrs.
NO. OF RUN/STOP NO.OF STEAM HEATING SOL. PUMP hrs. b2 indicates chilled water outlet temperature.
CHILLER TEMP. SET DATE & TIME SET OPTIONAL SET The current chilled water temperature is
MAINTENANCE SETTING 1 SETTING 2
SETTING 3 SETTING 4 SETTING 5 7.0.
SETTING 6 SETTING 7 SETTING 8
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Combustion status
H: Heating A: Temperature regulation stopped
O: Stopped J: Checking safety circuits
Operation mode
C: Cooling
U: Automatic restart after power failure
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Should a fault occur, an error codes will be displayed. When an error code is
displayed:
Make a note of the error code.
Refer to Chapter 4 for details of what action to take for the error code.
Press the STOP button to reset the error.
Note down this
number.
Quote the number to
your service agent.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
ESC JUMP
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Purge pump
Display of purge pumps operation condition.
Pressing the button down for 2 seconds activates
the auto purge circuits. Pressing the button again
stops purging immediately.
Before performing this purging operation, make
sure the machines condition is appropriate for it.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Operation keys
Stops operation.
Pressing this when the absorption chiller is in the
remote control mode switches to the local control
mode.
Also used to reset the controls after a fault has been
cleared.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Chapter 4 Operation
Pre- operation checks P
Preparation for operation. P
Starting operation P
Items to monitor during operation. P
Stopping operatio P
Fault stop P
Cautions for operation P
Pre-operation checks
Before running the absorption chiller, carry out the following checks:
1) Make sure that the preparation has been made to supply steam. (Steam supply
valve should be open.)
2) Make sure that the chilled water pump, cooling water pump, cooling tower fan and
other auxiliary equipment are all normal, and that their interlocks with the absorption
chiller are correctly wired. Also check that the chilled water and cooling water
systems have been primed with water and purged of air.
3) Make sure that the air conditioning equipment is ready to operate.
4) Perform the startup of the absorption chiller with sufficient lead time. Under normal
usage, it takes 20 to 30 minutes for the absorption chiller to become normal
operating condition.
POWER
STOP
POWER
STOP
RUNNING
DILUTION
SAFETY EQUIP.
CONT.VALVE CLOSED
PRE-ALARM
FAILURE
SAFETY EQUIP.
CONT. VALVE CLOSED
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Starting operation
Follow the procedure described below to start operation.
BUZZER
STOP START
STOP
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Useful tips
Observe the operation condition lamps.
POWER
STOP
RUNNING
DILUTION
SAFETY EQUIP.
PRE-ALARM
FAILURE
CONT.VALVE CLOSED
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Useful tips
Immediately after the absorption chiller is started up, the high temperature generator
will make a chattering sound for a short while. This is not a fault in fact it is an
indication that the machine has started up normally. It will soon go away.
Stopping operation
1) Press the STOP key.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
. Solution control
About the solution
The absorption chiller uses a solution of lithium bromide (chemical formula LiBr)
This lithium bromide solution is referred to as the solution.
Important points in solution management
Corrosion suppressant and alkalinity adjustment agent are added to the solution.
These additives are gradually consumed. Therefore, the solution must be sampled
periodically, the samples analyzed for corrosion suppressant concentration, alkalinity
and sediment, etc., and the additives replenished as necessary according to the
analysis results.
CAUTION
Be sure to adjust the solution periodically. Prolonged operation without adjustment
of the solution will drastically curtail the machines service life.
Analysis of the solution should be performed by persons with specialist skills.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
CAUTION
Cleaning of the tubes requires specialist skills, so have it performed by a specialist
company.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Electrical conductivity (S/cm) 800 or less 300 or less 400 or less 300 or less
Standard parameters
Iron (mgFe/L) 1.0 or less 0.3 or less 1.0 or less 0.3 or less
Reference parameters
Copper (mgCu/L) 0.3 or less 0.1 or less 1.0 or less 0.1 or less
2
Sulphate ions (mgS /L) not to be detected not to be detected
+
Ammonium ions (mgNH4 /L) 1.0 or less 0.1 or less 1.0 or less 0.1 or less
Residual chlorine (mgCl/L) 0.3 or less 0.3 or less 0.3 or less 0.3 or less
Free carbon dioxide (mgCO2/L) 4.0 or less 4.0 or less 4.0 or less 4.0 or less
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
When the absorption chiller is to be left out of use for a prolonged period in the
wintertime, it may be necessary to take measures to prevent the main body from
freezing.
Ask our company for details of such measures.
During prolonged stoppage, periodically observe and record the readings of the
compound gauge attached to the high temperature generator, in order to check the
main bodys airtightness.
Should the readings indicate that the inside pressure is increasing, contact our
company.
If the chilled water is not chilled properly when operation is restarted after a
prolonged stoppage, use an auxiliary vacuum pump to draw out any remaining
uncondensible gas.
This vacuum extraction operation is covered by the Maintenance Contract.
Have our company perform it if you have a Maintenance Contract with us.
Periodic inspection
Periodic inspection of the absorption chiller is an effective form of preventive
maintenance, and will facilitate early detection of faults (should they occur) and
determination of fault causes. A list of items for periodic inspection is given in Table
5.2.
In order to maintain the efficiency of the absorption chiller at a high level and ensure
that it fully exploits its potential, you are recommended to establish methods for
inspection and management in advance, and conduct them according to such
methods.
Supplementary Table 1 on P 5-13 presents a sample daily inspection check sheet.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Purge unit
The hydrogen gas generated in the absorption chiller is discharged from the purge
tank outside the machine with the purge pump.
Purge pump is driven in the automatic operation in setting it concerning the
automatic purge device at set intervals of time, and no condensation gas in the
purge tank is exhausted outside the machine
Please consult the field engineer of charge about the setting.
Please exchange the oil of the purge pump regularly while confirming the dirt
condition.
As a rule, the manual purge operation during the season is unnecessary.
Solution filter
An oxide generated due to the deterioration of the solution and in-flight impurities
can be removed by using the solution filter. A part of the exhaled solution is filtered
from the solution pump with the solution filter, and it returns it to the absorber.
Please regularly wash and exchange filters. Washing and the exchange time of the
filter are different according to the driving situation etc. of the absorption chiller.
Please consult the field engineer of charge.
It wishes the order to the service agency of charge because a special technology
is necessary for the clearing work of the filter.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Standard
Part replacement Replacement urgency Notes
period
Parts to be inspected/replaced during overhaul
Drain trap 5 years
Diaphragm valve rubber 5 years
Sight glass 5 years
Absorbent 5 years Regenerate or replace with new
Solution strainer 5 years
Steam system strainer 5 years
Refrigerant (water) 5 years
Automatic purge unit 5 years Vacuum pump and solenoid
Consumable parts
Water chamber gasket Opened Replace whenever chamber is
opened up after inspection
Steam chamber gasket Yearly Replace upon yearly inspection
Vacuum pump oil Monthly
Solution filter element 6 months
CAUTION
Be sure to completely disassemble and inspect the applicable parts every 5 years
or 20,000 hours of operation. Replace parts that the inspection shows are in need
of replacement, and those parts that must be replaced at periodic intervals. Have
these operations performed by our company.
Use only genuine Ebara products for replacement parts.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Valve operation
The absorption chiller contains a large number of valves, both manually operated
valves and automatic control valves. Operating these valves incorrectly could lead
to equipment damage, air leaks and consequent deterioration of the absorption
chiller interior, or else to other trouble such as leakage of absorbent outside the
machine. Normally, you should avoid touching the valves.
Useful tips
Operate the chilled water and cooling water tubing system valves as necessary to
perform air vent and drainage.
Also operate the fuel system tubing valves as necessary to perform air vent and
drainage.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Supplementary Table 1 Sample Daily Log Sheet for Model REW Absorption Chiller
Date Checkers name
Time Units : : : : : :
Operation mode Cooling/ Cooling/ Cooling/ Cooling/ Cooling/ Cooling/
Heating Heating Heating Heating Heating Heating
Power supply
Voltage V
Current A
Chilled water system
Chilled water inlet temperature
Chilled water outlet
temperature
Chilled water pump discharge MPa
pressure
Chilled water pump suction MPa
pressure
Chilled water pump current A
Cooling water system
Cooling water inlet temperature
Cooling water outlet
temperature
Cooling water pump discharge MPa
pressure
Cooling water pump suction MPa
pressure
Cooling water pump current A
Cooling tower fan current A
Steam
Steam control valve inlet
MPa
pressure
High temperature generator
MPa
inlet pressure
Steam control valve open rate
High temp. generator pressure MPa
Drain water outlet temperature
Other
Solution pump Inverter Hz
frequency
Spray pump Inverter frequency Hz
Abnormal noise? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Abnormal vibration? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Remarks
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
SAFETY EQUIP.
POWER
STOP
RUNNING
DILUTION
FAILURE
PRE-ALARM
3) The 7-segment display will show the remaining length of time that dilution has to
run.
Remaining dilution time
countdown (in seconds)
completely.
DILUTION
SAFETY EQUIP.
POWER
STOP
RUNING
PRE-ALARM
FAILURE
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Fault stop
If some fault occurs during operation, a protective device will be activated, and the
machine will implement fault stop. When this happens:
The alarm buzzer will sound.
The absorption chiller will stop automatically.
Immediately carry out the corrective action procedure below:
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
CAUTION
Investigate and determine the cause of the fault. (If necessary, contact our
company for assistance.)
Eliminate the cause of the fault. Then restart operation, and check all parts of the
machine for abnormality.
If the cause cannot be determined, or operation cannot be restarted, or fault stop
occurs again after restart, contact our company as soon as possible.
Useful tips
Be sure to note down the error code.
Refer to Chapter 6 Troubleshooting to assist you in locating the cause of the
error.
1) No-load operation
Make sure that the absorption chiller has a chilled water load of some kind (e.g. by
running the air handling unit or air terminal) during operation or dilution.
If there is no load, the temperature of the chilled water will drop sharply, leading to
freezing of the machine.
During operation and dilution, do not make the cooling water pump stop for any
reason. Stopping the pump will result in freezing of the evaporator tubes.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
If there are no interlocks between the absorption chiller and the chilled water
pump, cooling water pump and cooling tower fan:
Check that the OPERATING and
DILUTION lamps are off.
Check that the solution pump is
POWER
STOP
RUNNING
SAFETY EQUIP.
PRE-ALARM
FALURE
STOP RUN STOP RUN STOP RUN
SOL.
PUMP
SPRAY
PUMP
REF.
PUMP
stopped.
Provided that the conditions stipulated in the above checks are met, stop the
chilled water pump.
Stopping the chilled water pump without the conditions being met (i.e. before
operation/dilution and the solution pump have stopped) could lead to freezing
due to overcooling.
2) Power failure
Machines condition when outage occurs
1) If an outage occurs during operation, the absorption chiller will stop, unless
dilution is in progress.
2) If the solutions concentration is high when an outage occurs, it could crystallize
if it is left immobile inside the machine.
Action for power failure
Restart the absorption chiller as soon as possible after the power supply is
resumed.
In the case of an outage lasting 10 minutes or longer, the 7-segment display will
show:
When this display appears, carry out resetting and resume operation.
Should the solution crystallize, rendering operation impossible, contact our
company.
If the machine stops due to outage during remote control operation, go to the
machine and check for problems (crystallization, etc.)
3) Cooling water temperature
If the cooling water inlet temperature is extremely low when the machine is run in
cooling operation (in the winter and other cold times of the year), temperature
control will be necessary to regulate cooling tower bypass and/or the starting and
stopping of the cooling tower fan.
If the auxiliary equipment coupled operation circuits inside the control panel are
used, starting and stopping of the cooling tower fan can be controlled. Such control
is automatic.
Avoid rapid variations in cooling water temperature. Rapid variation will disturb the
absorption chiller and make stable operation impossible.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
. Solution control
About the solution
The absorption chiller uses a solution of lithium bromide (chemical formula LiBr)
This lithium bromide solution is referred to as the solution.
Important points in solution management
Corrosion suppressant and alkalinity adjustment agent are added to the solution.
These additives are gradually consumed. Therefore, the solution must be sampled
periodically, the samples analyzed for corrosion suppressant concentration, alkalinity
and sediment, etc., and the additives replenished as necessary according to the
analysis results.
CAUTION
Be sure to adjust the solution periodically. Prolonged operation without adjustment
of the solution will drastically curtail the machines service life.
Analysis of the solution should be performed by persons with specialist skills.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
CAUTION
Cleaning of the tubes requires specialist skills, so have it performed by a specialist
company.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Electrical conductivity (S/cm) 800 or less 300 or less 400 or less 300 or less
Standard parameters
Iron (mgFe/L) 1.0 or less 0.3 or less 1.0 or less 0.3 or less
Reference parameters
Copper (mgCu/L) 0.3 or less 0.1 or less 1.0 or less 0.1 or less
2
Sulphate ions (mgS /L) not to be detected not to be detected
+
Ammonium ions (mgNH4 /L) 1.0 or less 0.1 or less 1.0 or less 0.1 or less
Residual chlorine (mgCl/L) 0.3 or less 0.3 or less 0.3 or less 0.3 or less
Free carbon dioxide (mgCO2/L) 4.0 or less 4.0 or less 4.0 or less 4.0 or less
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
When the absorption chiller is to be left out of use for a prolonged period in the
wintertime, it may be necessary to take measures to prevent the main body from
freezing.
Ask our company for details of such measures.
During prolonged stoppage, periodically observe and record the readings of the
compound gauge attached to the high temperature generator, in order to check the
main bodys airtightness.
Should the readings indicate that the inside pressure is increasing, contact our
company.
If the chilled water is not chilled properly when operation is restarted after a
prolonged stoppage, use an auxiliary vacuum pump to draw out any remaining
uncondensible gas.
This vacuum extraction operation is covered by the Maintenance Contract.
Have our company perform it if you have a Maintenance Contract with us.
Periodic inspection
Periodic inspection of the absorption chiller is an effective form of preventive
maintenance, and will facilitate early detection of faults (should they occur) and
determination of fault causes. A list of items for periodic inspection is given in Table
5.2.
In order to maintain the efficiency of the absorption chiller at a high level and ensure
that it fully exploits its potential, you are recommended to establish methods for
inspection and management in advance, and conduct them according to such
methods.
Supplementary Table 1 on P 5-13 presents a sample daily inspection check sheet.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Purge unit
The hydrogen gas generated in the absorption chiller is discharged from the purge
tank outside the machine with the purge pump.
Purge pump is driven in the automatic operation in setting it concerning the
automatic purge device at set intervals of time, and no condensation gas in the
purge tank is exhausted outside the machine
Please consult the field engineer of charge about the setting.
Please exchange the oil of the purge pump regularly while confirming the dirt
condition.
As a rule, the manual purge operation during the season is unnecessary.
Solution filter
An oxide generated due to the deterioration of the solution and in-flight impurities
can be removed by using the solution filter. A part of the exhaled solution is filtered
from the solution pump with the solution filter, and it returns it to the absorber.
Please regularly wash and exchange filters. Washing and the exchange time of the
filter are different according to the driving situation etc. of the absorption chiller.
Please consult the field engineer of charge.
It wishes the order to the service agency of charge because a special technology
is necessary for the clearing work of the filter.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Standard
Part replacement Replacement urgency Notes
period
Parts to be inspected/replaced during overhaul
Drain trap 5 years
Diaphragm valve rubber 5 years
Sight glass 5 years
Absorbent 5 years Regenerate or replace with new
Solution strainer 5 years
Steam system strainer 5 years
Refrigerant (water) 5 years
Automatic purge unit 5 years Vacuum pump and solenoid
Consumable parts
Water chamber gasket Opened Replace whenever chamber is
opened up after inspection
Steam chamber gasket Yearly Replace upon yearly inspection
Vacuum pump oil Monthly
Solution filter element 6 months
CAUTION
Be sure to completely disassemble and inspect the applicable parts every 5 years
or 20,000 hours of operation. Replace parts that the inspection shows are in need
of replacement, and those parts that must be replaced at periodic intervals. Have
these operations performed by our company.
Use only genuine Ebara products for replacement parts.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Valve operation
The absorption chiller contains a large number of valves, both manually operated
valves and automatic control valves. Operating these valves incorrectly could lead
to equipment damage, air leaks and consequent deterioration of the absorption
chiller interior, or else to other trouble such as leakage of absorbent outside the
machine. Normally, you should avoid touching the valves.
Useful tips
Operate the chilled water and cooling water tubing system valves as necessary to
perform air vent and drainage.
Also operate the fuel system tubing valves as necessary to perform air vent and
drainage.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Supplementary Table 1 Sample Daily Log Sheet for Model REW Absorption Chiller
Date Checkers name
Time Units : : : : : :
Operation mode Cooling/ Cooling/ Cooling/ Cooling/ Cooling/ Cooling/
Heating Heating Heating Heating Heating Heating
Power supply
Voltage V
Current A
Chilled water system
Chilled water inlet temperature
Chilled water outlet
temperature
Chilled water pump discharge MPa
pressure
Chilled water pump suction MPa
pressure
Chilled water pump current A
Cooling water system
Cooling water inlet temperature
Cooling water outlet
temperature
Cooling water pump discharge MPa
pressure
Cooling water pump suction MPa
pressure
Cooling water pump current A
Cooling tower fan current A
Steam
Steam control valve inlet
MPa
pressure
High temperature generator
MPa
inlet pressure
Steam control valve open rate
High temp. generator pressure MPa
Drain water outlet temperature
Other
Solution pump Inverter Hz
frequency
Spray pump Inverter frequency Hz
Abnormal noise? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Abnormal vibration? Yes/No Yes/No Yes/No Yes/No Yes/No Yes/No
Remarks
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Chapter 6 Troubleshooting
6.1 Things to check before calling the service company .
6.2 Table of error codes, error causes and corrective action .
6.3 Table of pre-alarms, their causes and corrective action .
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
High temperature Check the H.T. GEN. TEMP. display. Symbol: 3H.
generator dewpoint If the temperature display shows an abnormal value, the
thermosensor error sensor or circuit board needs replacing. Contact our
company for replacement.
High temperature Check the H.T. GEN. TEMP. display. Symbol: 4H.
generator return If the temperature display shows an abnormal value, the
thermosensor error sensor or circuit board needs replacing. Contact our
company for replacement.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Spray pump fault After dilution operation, turn off the main circuit breaker,
and reset the magnet switch inside the control panel by
pressing the thermal reset button.
Low temperature Examine the liquid level detection electrode rod.
generator the control If the rod is faulty it must be replaced
on the liquid side is in Contact our company for replacement.
a slump.
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM15U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
B
Backup battery
Battery that supplies backup power to the control panel when a power failure occurs
and when the panels power is turned off, in order to protect the data in the panel
circuit board memories.
C
Chilled water pump
Pump for circulating the chilled water between the absorption chiller and the air
handling unit.
Chloride ions
The level of chloride ions in water is an important index of its corrosiveness. Chloride
ions are always present in natural water, usually in substantial quantity.
Cooling water pump
Pump for circulating the cooling water between the absorption chiller and the cooling
tower.
Cooling tower (fan)
Equipment that cools the cooling water during cooling mode operation. If ambient
temperature is high, the fan unable to cool down the temperature of coolant to the
specific value, resulting in poor performance of the absorption chiller.
Compound gauge
Pressure gauge that indicates the high temperature generators pressure. Able to
indicate a wide range of pressure, including vacuum pressure. The generators
pressure is an index of its operating condition.
Concentration control valve
This solenoid valve is for automatically directing the refrigerant inside the evaporator
to the absorber in order to prevent crystallization of solution when the cooling water
temperature is low.
Condenser
This is the device (in fact, a heat exchanger) that cools and condenses the
refrigerant vapor generated by the low temperature generator.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Conductivity
A liquids conductivity is a measure of the ease with which it conducts electricity. The
level of contamination of the cooling water is determined by measuring the waters
conductivity. The higher the conductivity is, the worse the contamination of coolant
is.
Control panel (microcomputer control panel)
Panel for control of the absorption chiller. Also called microcomputer control panel
due to the major role of its microcomputer in effecting control.
Corrosion suppressant
A very small quantity of this (molybdate) is added in the absorbent solution in order
to prevent corrosion of the absorption chiller. The solution must be analyzed
periodically to determine the amount of corrosion suppression in it, and the amount
adjusted if necessary.
Crystallization
What happens when the concentration of the absorbent (lithium bromide solution)
rises to the point where crystals of lithium bromide form in it. If the solutions water
content disappears completely, the lithium bromide will solidify (total crystallization).
This is essentially the same process as when salt separates out from brine when
brine is heated. Crystallization is liable to occur if the absorption cycle is maladjusted
or due to a power failure, etc.
If a large amount of crystallization occurs inside the chiller, it will be necessary to
dissolve the crystals by adding refrigerant or by applying heat to the solution from
outside.
D
Diaphragm valve rubber
The rubber element of the diaphragm valve.
Dilution (operation)
This consists of diluting the strong absorbent solution with refrigerant. It is mainly
carried out while the chiller is stopped. If it is not carried out, the absorbent will
crystallize, which will hinder operation.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Dilution valve
Valve located in the tubing that carries the refrigerant (water) to the absorbent
solution. It is open during dilution.
Drain heat exchanger
This is the device (in fact, a heat exchanger) that exchanges heat between high
temperature steam for heating and the solution to enhance thermal efficiency.
For reduction of heat loss, It is also possible to prevent flushing of the drain at the
drain recovery system by lowering the temperature of hot drain.
Drain purge (valve)
The operation of purging water from the chilled water or cooling water tubing. Drain
purge valves are the valves used for such purging.
Drain trap
After steam is supplied to the high temperature generator, this device with internal
float separates the efficiently consumed steam (drain) from the rest and drains only
the former.
E
Earth Leakage detector
This is an equipment that perceives the abnormality when the leak occurs, intercepts
the circuit automatically, and cuts the power supply. It is built into the substrate of
the control board.
Evaporator
This is the device (in fact, a heat exchanger) that vaporizes the refrigerant to
produce chiller water.
F
Feedwater
Water that is supplied to replenish the cooling tower water tank when its level is low.
The water is usually supplied through the ball tap (automatic supply valve) at the
cooling tower water tank.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
This is indispensable because shutting off this valve may cause fault such as .
corrosion of heat transmission tubes due to condensation of cooling water or dry run
of cooling water pump.
Flow switches
Protective devices that sense the flow of the chilled water and cooling water.
H
Heat transmission tubes
Tubes that pass through the absorption chillers interior and through which heat is
transmitted.
Heavy load
This refers to more than 2000 hours of operation per year. It also refers to prolonged
continuous operation at 100% capacity. If machine is operated under this condition,
it could result in result in reduced durability and performance. Heavy load operation
necessitates addition of options such as automatic purging unit and solution filter,
and very thorough maintenance, carried out with increased frequency.
High temperature generator
A heat exchanger where the lithium bromide solution is heated by steam and then
used to evaporate (regenerate) the refrigerant.
I
Interlock
Mechanism that prevents operation of certain components unless specific conditions
are met.
An example of such a condition is that the RUN signals for the chilled water pump or
cooling water pump.
Ionized silica
Substance present in water that can cause formation of scale.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
L
LED lamps
Acronym for Light Emitting Diodes.
Lithium bromide solution
Solution used as the absorption chillers absorbent.
Low temperature generator
A heat exchanger that uses the refrigerant vapor generated by the high temperature
generator to heat the absorbent.
M
Magnet switches
Switches for operating equipment with large capacitance.
Main circuit breaker (MCB)
Power switch that has a mechanism for shutting of all power to the absorption chiller
if overcurrent occurs.
O
Overcurrent (overload)
This refers to when the electrical current to the motor is higher than the rated
current, due to a fault, or overload.
P
Performance enhancement agent
Substance (usually a special alcohol) that is added to the absorbent in small
quantities to enhance the efficiency of the absorption chiller.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
pH
This is an index of hydrogen ion concentration, or in other words, of the degree of
acidity or alkalinity.
pH = log10 [H+] [H+] is the molar concentration of H+
When pH < 7, the substance is acidic; the lower the value below 7, the stronger
the acid.
When pH > 7, the substance is alkaline; the higher the value above 7, the
stronger the alkali.
When pH = 7, the substance is neutral.
Pre-alarms
These are indicated by EA + code number appearing on the control panels
display. Pre-alarms do not necessitate stoppage of the machine, but they indicate
that control operation or functions are being impeded, or could be impeded soon.
Pressure gauge
Indicates the high temperature generators pressure or steam supply pressure.
Pressure switches
Monitors the high temperature generators pressure. One of the high temperature
generators safety devices.
Protective circuits
Circuits for detection of high temperature generator low liquid level, seismoscope
signals, and external emergency stop signals.
Protective devices (instruments)
Accessory equipment for the absorption chiller that assures safety during its
operation.
Purge tank
Tank into which the uncondensible gas that accumulates inside the absorption chiller
is drawn, and where it is stored.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
R
Refrigerant
Medium (pure water) used by the absorption chillers internal cycle in the production
of chilled water.
Refrigerant pump
Pump for circulation of the refrigerant.
Refrigerant heat exchanger
This is a heat exchanger to which the refrigerant is cooled with cooling water.
S
Scale
Film consisting of impurities and metal oxides, etc., that forms on metal surfaces.
Seismoscope
Device that senses seismic activity and stops the absorption chiller in the event of an
earthquake. One of the optional protective devices.
7-segment LED (digital display)
LED display made up of spaces each consisting of 7 segments plus dots, and able
to display letters and digits.
Sight glass
Glass window in the absorption chiller that allows personnel to monitor the internal
operation condition.
Silica
Common name for silicon dioxide. High concentrations of silica in the cooling water
could lead to formation of hard scale.
Slime
Viscous accretion composed of microorganisms.
Solenoid valve
Valve that is opened and closed by magnets. Also called a magnet valve.
Solution analysis
Analysis of the composition of the absorbent solution, i.e. analysis to determine the
level of corrosion suppressant and alkali, etc. in the solution.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
Solution filter
This filter is necessary for removing oxides that are formed due to deterioration of
solution or foreign particles inside equipment. Filter element needs to be replaced
periodically.
Solution heat exchanger
Heat exchanger that exchanges heat between high and low temperature solution,
this enhancing the absorption chillers efficiency.
Solution pump
Pump that sends the solution from the absorber to the generator.
Spray pump
This pump is hermetic canned type pump that sprays the solution to absorbers heat
transfer tubes.
Startup congestion
Failure of the absorption chiller to start up, due to activation of protective device, etc.
If this condition is not cleared (the absorption chiller fails to start up) within a certain
period of time, an alarm is issued.
Steam control valve
An electric valve for adjusting the amount of steam to be supplied in response to the
requirements of the load.
Steam cutoff valve
An electric valve that opens completely with all closes according to driving and the
stop.
Strainers
These are fitted to the steam, solution and water tubing, from which they filter out dirt
and other foreign matter.
Sulfide ions
Sulfide compound ions dissolved in the water, liable to cause corrosion damage if
present in high concentrations.
Sulfuric acid ions
Ions of sulfur trioxide dissolved in the water. If sulfur is present in the fuel, it will be
turned into sulfur oxide by combustion, and sulfuric acid ions occur in the cooling
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
water when exhaust gas containing sulfur oxide is dissolved in it. If these ions are
allowed to remain, they will damage the absorption chiller.
Sulfur oxides
General terms for compounds of sulfur and oxygen, often written as SOx. SOx are
generated by the sulfur present in the fuel. They are harmful substances and cause
atmospheric pollution.
T
Temperature regulation startup/stop
These terms refer to startup or stop of steam supply in response to the requirements
of the load.
Thermal relay
One of the protective devices. Its contacts open when overcurrent occurs. It is fitted
to the motor solenoid switch inside the control panel. Also called a temperature
relay.
Thermosensors
There are various types of thermosensors, including thermocouples and resistance
thermometers. The absorption chiller employs thermistors, platinum resistance
temperature sensors, and other varieties of resistance thermometers as its
thermosensors.
Thermostat
A type of switch that turns on/off when a certain temperature is reached.
Total hardness
Index representing the total quantity of calcium ions and magnesium ions (which
cause hardness) in water.
U
Uncondensed gas
Gases (other than refrigerant vapor) that accumulate inside the absorption chillers
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.
INSTRUCTION MANUAL (for Model REW Absorption Chiller) CRA605E-H001
shell, e.g. hydrogen and air. If these gases are allowed to build up, they will cause a
marked fall in the absorption chillers refrigerating capacity, and impede its
operation.
Unloaded operation
This refers to running of the absorption chiller without any air handling unit or other
load. The absorption chiller should NEVER be run without any load, or its evaporator
tubes will freeze. Also make sure that the air handling unit is never turned off during
dilution operation.
V
Vacuum extraction
The operation of extracting uncondensed gas that has built up inside the absorption
chiller, by means of a vacuum pump.
W
Water chamber gaskets
The gaskets between the chilled water and cooling water chambers and their covers.
PM10U
EBARA REFRIGERATION EQUIPMENT & SYSTEMS CO.,LTD.