General Purpose Transformers 6

Electrical Connections (Three Phase)

208 D Volt Primary 208Y/120 Volt Secondary 240 D Volt Primary, 208Y/120 Volt Secondary 240 D Volt Primary, 208Y/120 Volt Secondary
Taps: 2, 2% FCAN; Taps: 2, 5% FCBN Taps: 2, 2% FCAN; 4, 2% FCBN
4, 2% FCBN 17 18 19

Primary H1-H2-H3 Secondary Voltage


Primary H1-H2-H3 Secondary Voltage Primary C o n n ect
Connect Taps @ Tap Voltage X 1, X 2, X 3 X0-X1, X2, X3
@ Tap Voltage X 1, X 2, X 3 X0-X1, X2, X3 Voltage Lines To
1 252
1 218 240 1-H1 & 2-H2 & 3-H3 H1, H2, H3
2 246
2 213 228 4-H1 & 5-H2 & 6-H3 H1, H2, H3
3 240
3 208 216 7-H1 & 8-H2 & 9-H3 H1, H2, H3 4 234 208 120
4 203 208 120 Secondary C o n n ect 5 228
5 198 Voltage Lines To
6 222
6 192 208 X 1, X 2, & X 3
7 216
7 187 120 X 0, X 1, X 2, X 3

480 D Volt Primary, 208Y/120 Volt Secondary 480 D Volt Primary 208Y/120 Volt Secondary
Taps: 2, 5%% FCBN Taps: 2, 2% FCAN; 4, 2% FCBN
20 21

Primary H1-H2-H3 Secondary Voltage

@ Tap Voltage X 1, X 2, X 3 X0-X1, X2, X3


Primary
Interconnect Connect Lines to 1 504
Voltage

480 1-H1 & 2-H2 & 3- H3 H1, H2, H3 2 492


456 4-H1 & 5-H2 & 6- H3 H1, H2, H3 3 480
432 7-H1 & 8-H2 & 9- H3 H1, H2, H3 4 468 208 120
Secondary
Connect Lines to 5 456
Voltage

208 X 1, X 2, & X 3 6 444

120 X 0, X 1, X 2, X 3 7 432

Notes:
Connect the electrostatic shield to the equipment ground (green) or to
both the equipment ground and the system ground (white). Specifications
are subject to change without notice.

Visit our website at www.solaheviduty.com or


contact Technical Services at (800) 377-4384 with any questions. 159
6 General Purpose Transformers

Electrical Connections (Three Phase)

480 D Volt Primary 240 D w/120 CT Volt Secondary 480 D Volt Primary 240 D w/120 CT Volt Secondary
Taps: 2, 5% FCBN Taps: 2, 2% FCAN; 4, 2% FCBN
22 23

Primary H 1-H 2-H 3 Secondary Voltage

X1-X6-X3
@ Tap Voltage X 1, X 2, X 3
X6 to
Primary
Connect Taps Connect Lines To 1 504
Voltage
2 492
480 1-H1 & 2-H2 & 3-H3 H1, H2, H3
3 480
456 4-H1 & 5-H2 & 6-H3 H1, H2, H3
4 468 240 120-0-120
432 7-H1 & 8-H2 & 9-H3 H1, H2, H3
5 456
Secondary
Interconnect Connect Lines To 6 444
Voltage
7 432
240 X 1, X 2, X 3

120-0-120 X6 to X1-X6-X3

480 D Volt Primary 480Y/277 Volt Secondary 600 D Volt Primary 208Y/120 Volt Secondary
Taps: 2, 2% FCAN; 4, 2% FCBN Taps: 2, 5% FCBN
24 25

Primary H1-H2-H3 Secondary Voltage


Primary
@ Tap Voltage X 1, X 2, X 3 X 0- X 1, X 2, X 3 Connect Taps Line Leads
Voltage
1 504 600 1-H1 & 2-H2 & 3-H3 H1, H2, H3
2 492 570 4-H1 & 5-H2 & 6-H3 H1, H2, H3
3 480 540 7-H1 & 8-H2 & 9-H3 H1, H2, H3
4 468 480 277 Secondary
Line Leads
5 456 Voltage

6 444 208 X 1, X 2, X 3

7 432 120 X 0, X 1, X 2, X 3

Visit our website at www.solaheviduty.com or


160 contact Technical Services at (800) 377-4384 with any questions.
General Purpose Transformers 6
Electrical Connections (Three Phase)

600 D Volt Primary 208Y/120 Volt Secondary 480 D Volt Primary 380Y/220 Volt Secondary
Taps: 2, 2% FCAN; 4, 2% FCBN Taps: 2, 5% FCBN
26 27

Primary H1-H2-H3 Secondary Voltage

@ Tap Voltage X 1, X 2, X 3 X 0- X 1, X 2, X 3

1 630
Primary
2 615 Interconnect Connect Lines to
Voltage
3 600 480 1-H1 & 2-H2 & 3-H3 H1, H2 & H3

4 585 208 120 456 4-H1 & 5-H2 & 6-H3 H1, H2 & H3

5 570 432 7-H1 & 8-H2 & 9-H3 H1, H2 & H3

6 555 Secondary
Interconnect Connect Lines to
Voltage
7 540
380 X 1, X 2, X 3

220 X 0, X 1, X 2, X 3

480 D Volt Primary 380Y/220 Volt Secondary


Taps: 2, 2% FCAN; 4, 2% FCBN
28

Primary H1-H2-H3 Secondary Voltage

@ Tap Voltage X 1, X 2, X 3 X 0- X 1, X 2, X 3

1 504

2 492

3 480

4 468 380 220

5 456

6 444

7 432

Visit our website at www.solaheviduty.com or