1 SENSIBLE HEAT=1.08XCFMXT (T=CHANGE IN TE


2 LATENT HEAT=0.68XCFMXW (W=CHANGE IN PH
3 Q=UAT
CENTIGRADE AND FARENHEAT CONVERSION
4 CENTI C=5/9(F-32)
5 FAREN F=(9/5XC)+32
VENTILATION
6 EXHAUST AIR=M3XACH/1.7 (CMH)
7 EXHAUST AIR=FF3XACH/60 (CFH)
8 FRESH AIR= 80% OF EA

9 RH=MOISTURE CONTENT IN AIR/MAX MOISTURE THE AIR

10 RH%=DEGREE OF SATURATION X 100

HUMIDITY RATIO/SP HUMIDITY = GR/LB = HOW MUCH A


11 GRAIN OF MOISTURE PRESENT IN 1LB OF DRY AIR
12 ESHF=ERSH/ERTH SH/TH < 1

KITCHEN VENTILATION
13 WALL MOUNTED HOOD -PERIMETER=2(l)+w,
14 ISLAND TYPE HOOD:-PERIMETER=2l+2w

15 EXHAUST MAKEUP AIR 1500-2200FPM


16 l=L+0.8H RA=SA-FA
17 w=W+0.5H
18 FA CFM=(CFM/PERSON X NO. OF PPL) + (CFM/FT2 X
19 INFILTRATION=CRACK LENGTH(ft) X 0.37
20 INFILTRATION CFM=CRACK LENGTH X LEAKAGE RATE
21 T FOR PARTITION: INSIDE TEMP=(OUTSIDE DBT-5
22 (DAR): DEHUMIDIFIED AIR RISE=BYPASS FACTOR X (RO
FAN LAWS
23 1) Q2/Q1 = N2/N1 N- SPEED IN RPM
24 2) SP2/SP1 = (N2/N1)2 Q-CFM
25 3) HP2/HP1 = (N2/N1)3 SP-STATIC PRESSURE
HP-HORSE POWER
2-NEW VALUE
1-OLD VALUE
AIR SIDE SYSTEM
26 CFM = Qs/1.08XT
27 FAN CAPACITY: HP=CFMXSP(inch of wg) / 6356X% of effi
WATER SIDE SYSTEM
28 CHILLED WATER: GPM=TrX24 / T T=HWS-HWR
29 HOTWATER(CT): GPM=TrX30 / T

30 PUMP HP=GPM X HEAD(feet of wg) / 3960 X % of ef

PUMP SELECTION
31 GPM=Tr X 2.4 (CHILLER)
32 GPM=Tr X 3 (CT)
MAKE UP WATER TANK
33 BLEED OFF=EVP LOSS / COC-1 COC-CYCLE OF C
COIL SELECTION
34 Q=AV LMTD=LOG MEAN

35 NO. OF ROWS REQUIRED= TONS X 12000 / U X LMTD X


FACE AREA X OUTSIDE SURFACE AREA PREFACE AREA PER
ROW
36 1/U = 1/K + rm + R/K K-OUTSIDE

R-OUTSIDE
K-HEAT TRANSFE
37 FPS= GPM X 1.2 / NO. OF CIRCUITS

38 EAT= FA(CFM X TEMP) + RA(CFM X TEMP) / SA FLOW CFM

39 LAT= EAT-(1-BF)(EAT-ADP) LAT-LEAVING AIR TEM

40 LMTD= GTD-LTD / LOG(GTD/LTD) GTD=EAT-LWT


LTD=LAT-EWT
HVAC FORMULAS

T=CHANGE IN TEMP)
W=CHANGE IN PHASE)

NVERSION

ACH=6 to 8(TOILET)
CAR PARKING: ACH=15 to 30(IND)
ACH=6 to 10(INT)

OISTURE THE AIR CAN HOLD

ATION X 100

B = HOW MUCH AMT OF


N 1LB OF DRY AIR
ER=2(l)+w, 200XP-HEAVY COOKING
=2l+2w 150XP-MEDIUM COOKING
100XP-LIGHT COOKING
00FPM
RA=SA-FA

PL) + (CFM/FT2 X FT2)


GTH(ft) X 0.37
H X LEAKAGE RATE/60
P=(OUTSIDE DBT-5)
ASS FACTOR X (ROOM TEMP-ADP)

D IN RPM NEW RPM = NEW CFM X EXISTING RPM / EXISTIN


CFM
C PRESSURE
SE POWER
W VALUE
D VALUE

g) / 6356X% of efficiency

T=HWS-HWR

960 X % of ef piping law:


1)2" < 4FPS (up to 50gpm)
2)2"> 4ft/100ft(above 50gpm)
COC-CYCLE OF CONCENTRATION

MTD=LOG MEAN TEMP DIFFERENCE

0 / U X LMTD X
EFACE AREA PER

K-OUTSIDE FILM COEFFICIENT(FOR DRY COIL)


rm-METAL RESISTANCE
R-OUTSIDE TO INSIDE SURFACE AREA RATIO
K-HEAT TRANSFER COEFFICIENT(FOR WATER INSIDE TUBE

/ SA FLOW CFM EAT-EENTERING AIR TEMP

LEAVING AIR TEMP BF-BYPASS FACTOR ADP-AFFECTIVE DEW


POINT

GTD=EAT-LWT