Professional Documents
Culture Documents
CHAPTER.1
COGENERATION
1. Cogeneration -1
2. Introduction -1
3. Choice of site - 2
CHAPTER.2
MAIN REQUIREMENTS -3
1. Fuel -4
2. Feed water -4
4. Boiler - 4
5. Boiler furnace -6
6. Super heater -7
7. Economiser -8
9. Condenser - 11
10. Turbines - 16
11. Alternators - 17
11.1. Introduction - 17
11.3. Classification - 17
11.5. Construction - 19
11.6. Types of rotor - 19
12. Transformers
12.2. Construction - 21
12.4.1. ∆ -∆ Connection -
25
13. VFD - 29
14. ESP - 30
CHAPTER.3
CONCLUSION
BIBLIOGRAPHY
CO-GENERATION
2. Hydro electric power station: A generating station which utilizes the potential
energy of water at high level for the generation of electrical energy.
4. Gas turbine power plant: A generating station which employs Gas turbine as
the prime mover for the generation of electrical energy.
Mainly, we are generating power by using these power stations. By using Bagasse
(sugarcane waste) we can also generate electric power, this type of power plant is known as Co-
generation.
1.
CHOICE OF SITE FOR CO-GENERATION PLANT:
6. Land requirement: The land is required not only for setting of the plant
but for other purposes such as staff colony, disposal of ash or fuel
storage. Land should be also available for future extensions
7. Ash disposal: Ash is the main waste product of the steam power plant.
The ash may be purchased by building contractors, or it can be used for
brick making near plant site. The site is nearer to river or sea or lay ash
can be dumped into it. If the waste land is available near the site then the
area of 40 hectares excavated to a depth of 6.5 meters will be required
per year for a 2000 MW plant.
9. Type of the land: Land should be available such that it has good bearing
capacity to with stand not only the dead load of the plant but also the
forces transmitted to the foundation due to the operation of the plant and
this total land may amount to about 7kg/cm more over the land should be
reasonably level and not low lying.
2.
MAIN REQUIREMENTS
FUEL
FEED WATER PLANT
BOILER
SUPER HEATER
ECONOMIZER
AIRPREHEATER
CONDENSER
COOLING TOWER
INDUCED DRAUGHT FAN
FORCED DRAUGHT FAN
CHIMNEY
TURBINES
REDUCTION GEAR BOX
ALTERNATOR
TRANSFORMERS
3.
FUEL
The main source of energy is fuels. The fuels may be solid, liquid, or gases such as coal,
oil and coal gas.
FEED WATER
The condensate from the condenser is used as feed water to the boiler. Some water may
be lost in the cycle which is suitably made up from external source. The feed water on its way to
the boiler is heated by water heaters and economizer. This helps in raising the overall efficiency
of the plant.
The suspended impurities are removed through sedimentation, coagulation and filtration.
Dissolved gases are removed by aeration and degasification. The water is then softened by
removing temporary and permanent hardness through different chemical processes. The pure and
soft water thus available is fed to the boiler for steam generation.
Here we use reverse osmosis plant for removing the impurities in the raw water. This
method consists of thin permeable membrane for removing impurities.
BOILER:
Boilers or steam generators convert water into steam and form one of the major
equipments of the plant.
A boiler is a closed vessel in which water is converted into steam by utilizing the heat
combustion of Bagasse. Boilers are two Types. They are;
In the water tubes boilers the water is inside the tubes and the hot gases are outside the
tubes as the water and steam are in the same shell, higher pressure of steam are not possible. The
output steam has a pressure of 42Kg/cm2 and temperature of 4150c the temperature of boiler is
14000c.
Water tube boilers consist of drums and tubes. The tubes are always external to drum. In
comparison to fire tube boilers the drum in such boiler don’t contain any tubular heating surfaces
so they can be build in smaller diameters and consequently they will withstand the high pressure.
The advantages of water tube boilers over the fire tube boilers are as under;
It is one of the best types of vertical multi-tubular boiler, and has a number of horizontal
fire tubes. Cochran boiler consists of a cylindrical shell with a dome shaped top where the space
is provided for steam. The furnace is one piece construction and seamless. Its crown has a
hemispherical shape and thus provides maximum volume of space.
The other factors which influence the choice of a boiler are availability, initial cost,
maintenance cost, labor cost, fuel cost and space requirements.
The water tube boilers are used where large amount of steam are to be produced at a high
temperature and pressure and weight and space considerations are important. To meet a required
demand, the choice between two boilers will be based on economic considerations I.e., total
annual; cost (fixed cost running cost). The worth nothing point is that the total cost of the fuel
used by the boiler in its life time may be 3 to 4 times the initial investment.
BOILER FURNACE
It is a chamber in which fuel is burnt to liberate the heat energy. The boiler furnace walls
are made of refractory materials such as fire clay, silica, kaolin etc; Bagasse is thrown into boiler
furnace through elevator.
The construction of boiler furnaces varies from plain refractory walls to completely to
water cooled walls, depending upon the characteristics of fuel used and ash produced, firing
methods , natural of load demand, combustion space required, excess air used, operating
temperature, initial and operating cost.
The plain refractory walls are suitable for small plants where the furnaces temperature
may not be high. The arrangement may consists of a single section of homogenous refractory or
insulation may be placed in between the refractory and casing.
For large plants, where the furnace temperature is quite high refractory walls are made
hallow and air is circulated through hallow space to keep the temperature of the furnace walls
low. This type of arrangement is no more preferred.
Practically water cooled walls similar to plain refractory type with a portion of surface
covered by water tubes. A proper balance can be made between the water cooled section and the
refractory section to give best results. This type is used for both stoker fired and pulverized fuel
fired boilers.
6.
The recent development is to use water walls. The water walls are built of tubes of
diameter ranging from 25mm to 100mm variously spaced with or without fins or studs and bear
or with different thickness of moldable refractory on the inner face. Heat transfer rates run from
0.5*106 to 1.4*106kcal/hour/m3of surface to meet these requirements of heat transmission,
circulation on the water side must be adequate, obtained by convection or by pumps. This type is
suitable for pulverized fuel fired boilers and high steaming rates can be maintained.
SUPERHEATER
A superheater is a device which superheats the steam. It raises the temperature of steam
above boiling point of water. A superheater consists of a group of tubes made of special alloy
steel such as chromium-molybdenum. These tubes are heated by the heat of flue gases during
their journey from the furnace to the chimney. The steam produced in the boiler is led through
the superheater where it is superheated by the heat of flue gases.
Super heaters consists of groups of tubes made of steel (carbon steel for steam
temperature up to 9500f, carbon-molybdenum steel for steam temperature of 10500f and stain less
steel for steam temperature of 12000f) with an outside diameter ranging from 25mm to 64mm.
tube handle location and arrangement, with counter current, and /or parallel flow is dictated by
type of firing, and required steam temperature, and steam temperature characteristic. The
superheater tubes are heated by heat of combustion gases during their passage from furnace to
chimney.
Super heaters are mainly classified into two types according to the system of heat transfer
from flue gases to steam. They are;
1. Radiant superheater
2. Convection superheater
The radiant superheater is placed in the furnace between the water walls and receives heat
from the burning fuel through radiation process. It has two main disadvantages firstly, owing to
high furnace temperature; it may get over heated and, therefore, requires a careful design.
Secondly it gives drooping characteristics i.e., the temperature falls with the increase in steam
output, the furnace temperature raises at a much less rapid rate then the steam output and the
radiant heat transfer being a function of furnace temperature increases slowly with the steam
flow or the steam temperature falls.
On the other hand, a convection superheater is placed in the boiler tube bank and receives
heat from flue gases entirely through the convention process. It gives raising characteristics i.e.,
the temperature of the superheat increases with the increase in steam output because with the
increase in steam output both gas flow over the super heater tubes and steam flows with the tubes
increases which cause increase in the rate of heat transfer and mean temperature difference.
7.
Desired control of characteristic is obtained by
ECONOMISER
It is a device which heats the feed water on its way to boiler by deriving heat from the
flue gases. This results in raising boiler efficiency, saving in fuel and reduced stresses in the
boiler due to higher temperature of feed water.
Economiser tubes are made of steel either smooth or covered with fins to increase the heat
transfer surface area. An economiser consists of large number of closely spaced parallel steel
tubes connected by headers of drums. The feed water flows through these tubes and the flue
gases flow outside. A part of the heat of flue gases is transferred to feed water, thus raising the
temperature. The transfer from flue gases to feed water is by convection. The feed water should
be sufficiently pure not to cause forming of scales and cause internal corrosion, and under boiler
pressure. The temperature of feed water entering the economiser should be high enough so that
moisture from the flue gases does not condense on the economiser tubes which may absorb so2
and co2 from the flue gases and form acid to corrode the tubes.
1. Independent type
2. Integral type.
8.
o The temperature range between various parts of the boiler is reduced which
results in reduction of stress due to unequal expansion.
o If the boiler is fed with cold water it may result in chilling the boiler metal. Hot
feed water checks it.
In the modern economiser the temperature of feed water is raised from about 2470c to
2760c
AIR PRE-HEATER
Super heaters and economizers generally cannot fully extract the heat from flue gases.
Therefore, pre-heaters are employed which recover some of the heat in the escaping gases.
The function of an air pre-heater is to extract heat from the flue gases and give it to the
air being supplied to furnace for fuel combustion. This raises the furnace temperature and
increases the thermal efficiency of the plant. Depending upon the method of transfer of heat from
flue gases to air, air pre-heaters are divided into the following two classes
1. Recuperative type
2. Regenerative type
The recuperative type air pre-heater consists of a group of steel tubes. The flue gases are
passed through the tubes while the air flows externally to the tubes. Thus heat of flue gases is
transferred to air.
There are two types of Air preheaters
1. Tubular type
2. Plate type
1. Tubular type
After leaving the boiler or economizer the gaseous products of combustion travel
through the inside of the tubes of air preheater in a direction opposite to that of air travel and
transfer some of their heat to the air to be supplied to the furnace. Thus the air gets initially
heated before being supplied to the furnace. The gases reverse their direction near the bottom of
the air heater, and a soot hopper is fitted to the bottom of air heater casing to collect soot
9.
2. Plate type
In the plate type Air preheater the air absorbs heat from the hot gases being swept
through the heater at high velocity on opposite side of a plate.
REGENERATIVE TYPE
The regenerative type air pre-heater consists of slowly moving drum made of corrugated
metal plates. The flue gases flow continuously on one side of the drum and air on the other side.
This action permits the transference of heat of flue gases to the air being supplied to the furnace
for fuel combustion.
10.
CONDENSER
Steam after expansion through the prime mover goes through the condenser which
condenses the exhaust steam and also removes air and other non condensable gases from steam
while passing through them. The recovery exhaust steam in the condenser reduces the make up
feed water that must be added to the system from 100% when exhausted to atmosphere to about
1-5% and there by reduce condensable the capacity of water treatment plant. The exhaust
pressure may be lowered from the standard atmospheric pressure to about 25mm of Hg absolute
and there by permitting expansion of steam in the prime mover to very low pressure and
increasing plant efficiency. Maintenance of high vacuum in the condenser is essential for
efficient operation. Any leakage of air in to the condenser destroys the vacuum and causes
i. Any increase in the condenser pressure which limits the useful heat drop in the
prime mover
ii. A lower of the partial pressure of the steam and of the saturation temperature
along with it. This means that the latent heat increase and therefore, more cooling
water are required. Also, the under cooling of the condensate is likely to be more
severe.
This will result in lower efficiency. As it is not possible to eliminate air leakage
completely, a vacuum pump is necessary to remove the air leakage in to the condenser.
• Surface condenser
The essential differences between a jet condenser and surface condenser is that in the
former, the exhaust steam mixes with the cooling water and the temperature of the condensate
and the cooling water is the same when leaving the condenser; and the condensate cannot be
recovered for use as feed water to the boiler; heat transfer is by direct conduction; in the later i.e.
in surface condenser the exhaust steam and cooling water do not mix with each other, the water
being circulated through the nest of tubes, the heat transfer being by convection. The temperature
of the condensate may be higher than the temperature of the cooling water at outlet and the
condensate is recovered as feed water to the boiler.
11.
Both the cooling water and the condensate are separately with drawn. Advantages of jet
condensers are;
Disadvantages
Condensate is wasted
Hence the use of jet condenser is limited to small industrial applications (1000kW) where
high vacuum is not required (50mm-125mm Hg abs).
♦ Reaction turbines
16.
ALTERNATORS
Introduction
A synchronous machine is an ac machine in which the rotor moves at a speed which
bears a constant relationship to the frequency of currents, in the armature winding. A
synchronous machine is one of the important types of electrical machines. Large ac networks
operating at constant frequency of 50Hz (or60Hz) rely almost exclusively on synchronous
generators, also called the alternators.
Synchronous motors provide constant speed industrial drives with the possibility of
power factor correction.
Synchronous machines are generally constructed in larger sizes. Small sizes alternators
are not economical. The modern trend is to build alternators of very large sizes capable of
generating 500MVA or even more. The synchronous motor is rarely built in small sizes owing to
superior performance characteristics and economical construction of induction motors.
Operating principle
The operating principle of a synchronous machine is fundamentally is same that of a dc
machine, but ,unlike the latter, in the synchronous machine there is no need to rectify the time
varying emf which is induced in the armature winding consequently a synchronous machine does
not require a commutator it is , in fact quite possible to use a dc generator as an alternator by
placing a set of collector rings on the shaft and connecting these rings to the proper points on the
armature winding; brushes riding on the rings can be collected to the load but unlike dc generator
they are to be driven at a very definite constant speed as the frequency of a generated emf is
determined by that speed the latter is usually referred to as synchronous speed , for which reason
these machines are called frequently synchronous generators.
17.
(a) Based on the construction of the machines, the synchronous machines can be classified as
1. This type of alternator has stationary field poles and rotating armature
2. In this structure the rotor has slip rings and brushes to supply an excitation current from an
outside dc source.
3. The armature coils are placed in slots in a laminated core called the stator which is made up of
thin steel laminations and are placed in the frame of generators.
4. The amount of power delivered to the field circuit is relatively small that is 100-250 volts.
5. Most of the alternators are of this type and they are used for high KVA capacity and high
voltage rating.
1. The armature winding must be insulated for a high voltage while the voltage of field circuit is
low, because it is much easier insulate the high voltage winding. When it is mounted on
18.
Stationary structure
2. Only a small amount of power at low voltage is handled by the slip ring contacts.
3. It is easier to build and balance high speed rotor when they carry field structure.
4. The armature winding is cooled more readily because the stator can made up of many air
passages or ducts for forced air circulation.
Construction of an Alternator:
In alternator consists of two parts
1. Stator
2. Rotor
The stator of the alternator consist of the alternator consist of a cast iron or welded steel
frame which supports the armature core having slots on its periphery for similar
conductors are connected together in groups to form a winding of desired no. of faces.(generally
star connected).
♦ Ventilating ducts are provided parallel to the axis of frame to facilitate improved cooling
conditions.
♦ The stator is made up of steel alloy laminations and the laminations are insulated from
each other by a layer of oxide and enamel.
♦ Open windings are permitted because it is easy for the installation of stator coils and for
the removal in case of repair.
♦ A fractional rather than integral no. of slots for pole is used to eliminate the harmonics in
the waveform.
Rotor
The rotors are classified into two types.
3. The poles are laminated to reduce eddy currents losses. These types of rotors are employed
with water or hydro turbines and internal combustion engines.
2. Robust construction.
Synchronous machines are classified into two types based on the type of prime mover
1. Turbo generators
2. Hydro generators.
Turbo generators
If the generators are driven by steam turbines they are called as turbo generators. They
run at high speeds and the rotor will be of cylindrical type.
2. Hydro generators
If the generators are driven by water turbines then they are called as hydro generators.
They run at low operation speeds. The rotor is if salient pole type.
20.
The transformer is probably one of the most useful electrical devices ever invented .It can
raise or lower the voltage or current in an AC Circuit, it can isolate circuits from each other, & it
can increase or decrease the apparent value of capacitor, an in doctor or a resistor. Further more,
the transformer enables us to transmit electrical energy over great distances & to distribute it
safely in factories & homes.
The simplest elements of the transformer consist of two coils having mutual inductance
and a laminated steel core. The two coils are insulated from each other and the steel core. Other
necessary parts are:
→ A suitable medium for insulating the core & its windings from its
container
In all types of transformers, the core is constructed of transformer sheet steel laminations
assembled to provide continuous magnetic paths with minimum of air gap included. The steel
used is of high silicon content, some times heat treated to produce a high permeability and a low
hysteresis loss at usual operating flux densities. The eddy current loss is minimized by
laminating the core, the laminations being insulated from each other by a light coat of core plate
varnish or by an oxide layer on the surface.
21.
Transformer rating
Cu loss of a transformer depends on current and iron loss on voltage. Hence, total
transformer loss depends on volt-ampere (VA) and not on phase angle between voltage and
current i.e. it is independent of load power factor. That’s why rating of transformer is in KVA
and not in KW.
Years ago, it was a common practice to use suitably interconnected three single-phase
transformers instead of a single three phase transformer. But these days, the latter is gaining
popularity because of improvement in design and manufacture but principally because of better
acquaintance of operating men with the three phase type. As compared to a bank of single phase
transformer, the main advantages of a 3-phase transformer are that it occupies less floor space for
equal rating, weighs less, costs about 15% less and further, that only one unit is to be handled
and connected.
Like single phase transformers, the 3-phase transformers are also of the core type or shell
type. The basic principle of a 3-phase transformer is illustrated in figure 1in which only primary
windings have been shown inter connected in star and put across three phase supply. The three
cores are 1200 apart and their empty legs are shown in contact with each other. The center leg
formed by these three carries the flux produced by 3-phase currents IR, IY and IB. as at any instant
IR+ IY +IB=0
Hence the sum of three fluxes is also zero. Therefore, it will make no difference if the
common leg is removed. In that case any two legs will act as the return for the third just as in a
three phase system any two conductors act as the return current in the third conductor. This
improved design is shown in fig2. Where dotted rectangles indicate the 3 windings and numbers
in the cores and yokes represent the directions and magnitudes of fluxes at a particular instant. It
will be seen that at any instant, the amount of ‘up’ flux in any leg is equal to the sum of ‘down’
fluxes in the other two legs. The core type transformers are usually wound with circular
cylindrical coils.
22.
Fig.1
23.
Fig2
In a similar way, three 1-phase shell type transformers can be combined together to form
a 3-phase shell type unit. But some saving in iron can be achieved in constructing a single 3-
phase transformer. It does not differ from three 1-phase transformers put side by side. Saving in
iron is due to the joint use of magnetic paths between the coils. The three phases, in this case, are
more independent then they are in the core type transformers, because each phase has a magnetic
circuit independent of the other.
One main drawback in 3-phase transformer is that if any one phase becomes disabled,
then the whole transformer has to be ordinarily removed from service for repairs. However, in
the case of a 3-phase bank of 1-phase transformers if one transformer goes out of order, the
system can still be run open ∆ at reduced capacity or the faulty transformer can be readily
replaced by a single spare.
24.
Three-phase transformer connections:
There are various methods available for transforming 3-phase voltages to higher or lower
3-phase voltages i.e. for handling a considerable amount of power. The most common
connections are
• Y-Y
• ∆ -∆
• Y-∆
• ∆ -Y
• Open ∆ or V-V
Delta-Delta or ∆ -∆ connection
1. To make the output voltage sinusoidal it is necessary that the magnetizing current
of the transformer must contain a third harmonic component. So, third harmonic
component can flow in a delta connected transformer primaries without flowing
in the line wires. The three phases are 1200 apart which is 3×1200=3600 with
respect to the third harmonic component; hence it merely circulates in the delta.
Therefore, the flux is sinusoidal which results in sinusoidal voltages.
25.
Wye/Delta or Y/∆ connection:
The main use of this connection is at the sub-station end of the transmission line where
the voltage is to be stepped down. The primary winding is Y connected with grounded neutral.
The ratio between secondary and primary line voltage is 1/√3 times the transformation ratio of
each transformer. There is a 300 shift between the primary and its secondary line voltages which
means that Y-∆ transformer bank cannot be paralleled with either a Y-Y or a ∆ -∆ bank.
Instrument transformers:
2. Potential transformers
26.
Current transformers:
These transformers are used with low range ammeters to measure currents in high voltage
AC circuits. The current transformer has a primary coil of one or more turns of thick wire
connected in series with the line whose current is to be measured. The secondary consists of a
large number of turns of fine wire and is connected across the ammeter terminals.
Here the voltage stepped up and current is stepped down. One of the most commonly
used current transformers is known as Clamp ON or Clip ON type. Since the ammeter resistance
is very less the current transformer normally works short-circuited. If it is not done large amount
of primary flux will be setup .It damages insulation and core gets saturated.
Potential Transformers:
These transformers are extremely accurate ratio step down transformers and are used in
conjunction with standard low range voltmeters. They are of shell type transformers but there
power rating is extremely small. Up to voltages of 5000, potential transformers are usually of the
dry type, between 5000 & 13800 V they are always oil immersed type. For safety, the secondary
should be completely insulated from the high voltage primary and should be, in addition,
grounded for affording protection to operator.
Losses in a transformer:
In a static transformer there are no friction or windage losses hence the only losses
occurring are
2. Copper Loss
It includes both Hysteresis and eddy current losses. Because the core flux in a
transformer remains practically constant for all loads hence the core losses are constant.
Hysteresis losses occur due to application of varying strengths of AC and eddy current
losses occur due to the flow of currents in a closed path due to induced emf. These currents are
called as eddy currents.
Hysteresis losses can be minimized by using steel of high Si content for the core and
eddy current loss can be minimized by using very thin laminations. Iron Loss can be found from
Open Circuit Test. 27.
Copper Losses:
It is clear that Cu loss is proportional to (current) 2. The value of Cu losses can be found
by Short Circuit test.
The losses appear in the form of it and a drop in efficiency. Normally, the efficiency of
transformers is high about 99.5%.Cu loss inversely vary with Power Factor because current is
inversely proportional to power factor.
Cooling Methods:
Indoor transformers below 200kVA can be directly cooled by the natural flow of the
surrounding air. The metallic housing is fitted with ventilating louvers so that convection
currents may flow over the windings and around the core. Large transformers can be built the
same way, but forced circulation of clean air must be provided. Such dry type transformers are
used inside buildings, away from hostile atmospheres.
Distribution transformers below 200 kVA are usually immersed in mineral oil and
enclosed in a steel tank. Oil carries the heat away to the tank, where it is dissipated by radiation
and convection to the outside air. Oil is much better insulator than air is; consequently, it is
invariably used on high voltage transformers. As power rating increases, external radiators are
added to increase the cooling surface of the oil filled tank. Oil circulates around the transformer
windings and move through radiators, where the heat is again released to surrounding air. For
still higher ratings cooling fans blow air over the radiators. For the transformers in megawatt
range cooling may be affected by an oil water heat exchanger. Hot air drawn from the
transformer tank is pumped to a heat exchanger where it flows through pipes that are in contact
with cool water. Such a heat exchanger is very effective and costly.
28.
VARIABLE FREQUENCY DRIVE MOTORS
The motor used in a variable frequency drive system is usually a three-phase induction
motor. Some types of single-phase motors can be used, but three-phase motors are usually
preferred. Various types of synchronous motors offer advantages in some situations, but
induction motors are suitable for most purposes and are generally the most economical choice.
Motors that are designed for fixed-speed mains voltage operation are often used, but certain
enhancements to the standard motor designs offer higher reliability and better variable frequency
drive performance. A variable frequency drive system generally consists of an AC motor, a
controller and an operator interface.
Constant Torque applications are where the same amount of torque is required at low
speed as at high speed. Some applications may include conveyors, mixers, screw feeders,
extruders and positive displacement pumps.
Constant power applications are where a high torque is required at low speed and a low
torque at high speed. Examples of applications are machine tools, tractions.
29.
Variable Torque Application
Variable torque is where a low torque is required at a low speed and higher torque at high
speed. Some applications are centrifugal loads such as fans, pumps and blowers. With these
applications we will see the most energy saving by using a variable frequency drive.
Working
At the heart of an electric motor are the stator and the rotor. A magnetic field is generated
when a current is applied and the north/south field rotates through the stationary stator as the
rotor spins to catch up to the rotating field. The spinning of the rotor provides the torque
necessary to drive a load.
An electric motor turns at a given speed depending on the number of poles in the motor
and the frequency of the alternating current applied. Motor speed can be changed by changing
the alternating current frequency.
Nearly all variable frequency drives manufactured today are referred to as pulse width
modulation drives. These drives contain electronic circuitry that converts the 60 Hertz line power
to direct current, then pulses the output voltage for varying lengths of time to mimic an
alternating current at the frequency desired.
The use of variable frequency drive application is use majority for centrifugal pumps and
fans. The savings potential is the largest in these devices since the theoretical input power varies
with the cube of fan/pump speed and volume. A fan operating a half speed will require only
about 13 percent of full speed power. Losses in the variable frequency drive will reduce saving
somewhat, but the saving are still very impressive.
ELECTRO-STATIC PRECIPITATOR
The electro-static precipitator consists of metal plates which are electrically charged.
Dust and grit in the flue gases are attracted on to these plates, so that they do not pass up the
chimney to pollute the atmosphere. Regular mechanical hammer blows because the
accumulations of ash, dust and grit to fall to the bottom of the precipitator, where they collect in
a hopper for disposal Additional accumulations of ash also collect in hoppers beneath the
furnace.
30.
SCHEMATIC ARRANGEMENT OF THE PLANT
Although steam power station simply involves the conversation of heat of bagasse into
electrical energy, it embraces many arrangements for proper working and efficiency. The whole
arrangement can be divided into the following stages for the sake of simplicity.
3. Steam turbine
4. Alternator
5. Feed water
6. Cooling arrangement
The bagasse coal is feed to the boiler by belt conveyers. The fuel is burnt in the boiler and the
ash produced after the complete combustion of bagasse is removed to the ash handling plant and
then delivered to the ash storage plant for disposal. The removal of the ash from the boiler
furnace is necessary for proper burning of fuel.
Here in this power generating station there is not much cost spent in purchasing the fuel. As
it is wastage of sugarcane left in sugar processing plant.
The Steam generating plant consists of a boiler for the production of steam and other
auxiliary equipment for the utilization of flue gases.
I. Boiler
The heat of combustion of bagasse in the boiler is utilized to convert water into a steam at
high pressure and temperature. The flue gases from the boiler make their journey through
superheater, economiser, air pre-heater and are finally exhausted to atmosphere though the
chimney.
The calorific value of the bagasse is 2400kCal/kg. The boiler is designed to produce 64 tones
of steam per hour at a temperature of 4150c and at a pressure of 42kg/cm2. The boiler
temperature is 14000c.
31.
32.
II. Superheater
The steam produced in the boiler is wet and is passed through a superheater where it is dried
and is superheated. (Steam temperature increased above that of boiling point of water) the flue
gases on their way to chimney. Superheating provides two principle benefits. Firstly, the overall
efficiency is increased. Secondly, too much condensation in the last stages of turbine (which
would cause blade corrosion) is avoided. The superheated steam from the superheater is fed to
steam turbine through the main valve.
III. Economiser
An economiser is essentially a feed water heater and derives heat from the flue gases for this
purpose. The feed water is fed to the economiser before supplying to the boiler. The economiser
extracts a part of heat of flue gases to increase the feed water temperature.
IV. Air-preheater
An air-preheater increase the temperature of the air supplied for bagasse burning by deriving
heat from the flue gases. Air is drawn from the atmosphere by forced draught fan and is passed
through air-preheater before supplying to the boiler furnace. The air-preheater extracts heat from
flue gases and increases the temperature of air used for bagasse combustion. The principle
benefits of preheating the air are:
In KBD sugars the forced draught fan is 75Hp and is one in number.
C. Steam turbine
The dry and superheated steam from the superheater is fed to the steam turbine through main
valve. The heat energy of steam when passing over the blades of turbine is the converted into
mechanical energy. After giving heat energy to the turbine, the steam is exhausted to the
condenser which condenses the exhausted steam by means of cold water circulation. The
governor mechanism is employed to control the fuel falling into the boiler. The speed of the
steam impulse turbine is 8250rpm.
D. Alternator
The steam turbine is coupled to an alternator. The alternator converts mechanical energy of
turbine into electrical energy. The electrical output from the alternator is delivered to the bus bars
through transformer, circuit breakers and isolators.
33.
The alternator rotates with the 1500rpm delivers the 6MW output at a voltage of 11Kv.
The steam turbine is coupled to the alternator by means of reduction gear box. The reduction
gear box reduces the speed to be matched with the alternator.
E. Feed water
The condensate from the condenser is used as feed water to the boiler. Some water may be
lost in the cycle which is suitably made up from external sources. The feed water on its way to
the boiler is heated by the water heaters and economizer. This help in rising overall efficiency of
the plant.
F. Cooling arrangement
In order to improve the efficiency of the plant, the steam exhausted from the turbine is
condensed by means of condenser. Water is drawn from a bore well and is circulated through the
condenser. The circulating water takes up the heat of exhausted steam and itself become hot.
Since the water availability is less, cooling towers are used. Hot water from the condenser is
passed on the cooling towers where it is cooled. The cold water from the cooling towers is
residue in the condenser.
34.
CONCLUSION
The survival of industrial undertakings and our social structures depends primarily upon
low cost and interrupted supply of electrical energy. In fact, the advancement of country is
measured in terms of per capita consumption of electrical energy.
The conversion of energy available in different forms in nature into electrical energy is
known as generation of electrical energy.
Energy is available in various forms from different natural sources such as pressure head
of water, chemical energy of fuels, nuclear energy of radioactive substances etc.
All these forms of energy can be converted into electrical energy by the use of suitable
arrangement. In this project we studied that the production of electrical energy from the wastage
of sugar cane i.e., bagasse.
The arrangement essentially employs an alternator coupled to a prime mover. The prime
mover is driven by the energy obtained from burning of bagasse. Heat energy of bagasse can be
used to produce steam at high temperature and pressure.
The steam is fed to steam turbine. The turbine converts heat energy of steam into
mechanical energy which is further converted into electrical energy by the alternator. The energy
produced is utilized for the operation the industrial plant.
BIBLIOGRAPHY