You are on page 1of 312

Open Processor with

Liebert Sitelink Driver


Owners Manual
APOGEE Compatible
125-3006 Rev. 1, 1/00
Rev. 1.0, January, 2000

NOTICE

The information contained within this document is subject to change without notice and should not be construed as a
commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility
for any errors that may appear in this document.

All software described in this document is furnished under a license and may be used or copied only in accordance
with the terms of such license.

WARNING

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance
with the instructions manual, may cause interference to radio communications. It has been tested and found to
comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to
provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area is likely to cause interference in which case users at their own expense will be
required to take whatever measures may be required to correct the interference.

SERVICE STATEMENT

Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical
components must be regularly serviced to optimize their operation. All Siemens Building Technologies, Inc. branch
offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free
system performance.

For further information, contact your nearest Siemens Building Technologies, Inc. representative.

Copyright 2000 by Siemens Building Technologies, Inc.

TO THE READER

Your feedback is important to us. If you have comments about this manual, please submit them to
technical.editor@sbt.siemens.com
APOGEE is a trademark of Siemens Building Technologies, Inc.
BACnet is a trademark of American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE)
Insight for Minicomputers is a registered trademark of Siemens Building Technologies, Inc.
Insight for Personal Computers is a registered trademark of Siemens Building Technologies, Inc.
Printed in U.S.A.
Table of Contents

Table of Contents

How to Use This Manual .............................................................................................. I

Manual Conventions .................................................................................................. II


Manual Symbols ........................................................................................................ II
Where To Send Comments .................................................................................... III
Prerequisites.............................................................................................................. III

Introduction ...................................................................................................................1-1

Chapter Overview ...................................................................................................... 1-1


Compatibility .............................................................................................................. 1-1
Principles of Open Processor Operation ................................................................... 1-2
Gathering and Processing Field Inputs ................................................................... 1-2
Executing Control Programs ................................................................................... 1-2
Processing Operator Commands............................................................................ 1-3
Understanding Building Level Network ................................................................... 1-3
Hardware........................................................................................................................ 2-1

Chapter Overview ...................................................................................................... 2-1


System Configuration ................................................................................................ 2-1
System 600 APOGEE Components .......................................................................... 2-3
Modular Building Controller or Remote Building Controller Enclosure.................... 2-3
Open Processor with Liebert Sitelink Driver............................................................ 2-3
Other Open Processors .......................................................................................... 2-5
Power Module ......................................................................................................... 2-6
Expansion Module Kit ............................................................................................. 2-6
Point Termination Modules ..................................................................................... 2-6
Operator Interfaces ................................................................................................. 2-7
Black Box Components ............................................................................................. 2-9
IC109A RS-232 to RS-485 Converter ..................................................................... 2-9
Liebert Components .................................................................................................. 2-10
Sitelink DC12i or DC4i ............................................................................................ 2-10
IGMnet .................................................................................................................... 2-10
IGM ......................................................................................................................... 2-10
REPOPT ................................................................................................................. 2-10
Software......................................................................................................................... 3-1

Chapter Overview ...................................................................................................... 3-1

i
Open Processor with Liebert Sitelink Driver Owners Manual

Liebert Sitelink Driver................................................................................................. 3-1


Operator Interface...................................................................................................... 3-1
PPCL ......................................................................................................................... 3-2

Point Database .............................................................................................................. 4-1

Chapter Overview ...................................................................................................... 4-1


What is a Point Database? ........................................................................................ 4-2
Types of Points .......................................................................................................... 4-2
Logical Points .......................................................................................................... 4-2
Virtual Points ........................................................................................................... 4-3
Local Points............................................................................................................. 4-4
Point Characteristics.................................................................................................. 4-4
Point Name/Point System Name............................................................................. 4-4
Point Naming Conventions...................................................................................... 4-5
Tips for Entering Point Names ................................................................................ 4-6
Point Address.......................................................................................................... 4-6
Point Status ............................................................................................................. 4-7
Point Priority ............................................................................................................ 4-8
Point Values/State................................................................................................... 4-10
Point Attributes .......................................................................................................... 4-10
Point Name ............................................................................................................. 4-11
Point Type ............................................................................................................... 4-12
Point Descriptor....................................................................................................... 4-12
Engineering Units .................................................................................................... 4-12
Access Groups........................................................................................................ 4-13
Alarming .................................................................................................................. 4-13
Totalize.................................................................................................................... 4-14
Point Address.......................................................................................................... 4-14
State Text................................................................................................................ 4-15
Change of Value ..................................................................................................... 4-15
Other Analog Point Attributes.................................................................................. 4-16
Other Digital Point Attributes ................................................................................... 4-17
Point Database Guidelines ........................................................................................ 4-18
Modbus Protocol ..................................................................................................... 4-18
Liebert Modbus Register Mapping .......................................................................... 4-18
Understanding Metadrops....................................................................................... 4-22
Defining Sitelink Metapoints.................................................................................... 4-22
Required Points....................................................................................................... 4-22
Optional Points ........................................................................................................ 4-23
Applications................................................................................................................... 5-1

ii
Table of Contents

Chapter Overview ...................................................................................................... 5-1


Open Processor Applications.................................................................................. 5-2
Application 5360: C10 Unit
(Liebert Environmental Unit Australia/Atlas Air)......................................................... 5-4
Introduction ............................................................................................................. 5-4
C10 Status Drop Metapoint Characteristics ............................................................ 5-4
C10 Status Point Map ............................................................................................. 5-6
C10 Alarm Drop Metapoint Characteristics............................................................. 5-7
C10 Alarm Point Map .............................................................................................. 5-9
C10 Command Drop Metapoint Characteristics ..................................................... 5-10
C10 Control Points .................................................................................................. 5-13
Application 5361: CCM Unit (Liebert Contact Closure Modules)............................... 5-14
Introduction ............................................................................................................. 5-14
CCM Unit Status Drop Metapoint Characteristics ................................................... 5-14
Liebert Contact Closure Modules (CCM) Point Map ............................................... 5-17
Application 5362: CSU Unit (Liebert Mainframe Chiller)............................................ 5-19
Introduction ............................................................................................................. 5-19
CSU Unit Status Drop Metapoint Characteristics.................................................... 5-19
CSU Status Point Map ............................................................................................ 5-22
CSU Alarm Drop Metapoint Characteristics............................................................ 5-22
CSU Alarm Points ................................................................................................... 5-25
Application 5363: CSE Unit (Liebert Mainframe Chiller with Econocoil).................... 5-26
Introduction ............................................................................................................. 5-26
CSE Unit Status Drop Metapoint Characteristics.................................................... 5-26
CSE Unit Status Point Map ..................................................................................... 5-29
CSE Unit Alarm Drop Metapoint Characteristics .................................................... 5-29
CSE Unit Alarm Point Map...................................................................................... 5-32
Application 5364: EDS Unit (Liebert Static Switch PDU) ........................................... 5-33
Introduction ............................................................................................................. 5-33
EDS Unit Status Drop Metapoint Characteristics.................................................... 5-33
EDS Unit Status Point Map ..................................................................................... 5-36
EDS Unit Alarm Drop Metapoint Characteristics .................................................... 5-37
EDS Alarm Point Map ............................................................................................. 5-39
Application 5365: L00 Unit (Liebert Environmental UnitsLevels 0 and 1) .............. 5-41
Introduction ............................................................................................................. 5-41
L00 Unit Status Drop Metapoint Characteristics ..................................................... 5-41
L00 Status Point Map.............................................................................................. 5-44
L00 Unit Alarm Drop Metapoint Characteristics ...................................................... 5-44
L00 Alarm Point Map............................................................................................... 5-47
L00 Unit Command Drop Metapoint Characteristics............................................... 5-47
L00 Control Point Map ............................................................................................ 5-49

iii
Open Processor with Liebert Sitelink Driver Owners Manual

Application 5366: L0B Unit (Liebert Environmental Units Small Systems) ................ 5-50
Introduction ............................................................................................................. 5-50
L0B Unit Status Drop Metapoint Characteristics..................................................... 5-50
L0B Status Point Map ............................................................................................. 5-53
L0B Unit Alarm Drop Metapoint Characteristics ..................................................... 5-53
L0B Unit Alarm Point Map....................................................................................... 5-56
L0B Unit Command Drop Metapoint Characteristics .............................................. 5-56
L0B Command Point Map ....................................................................................... 5-58
Application 5367: L02, L03, L10 Unit
(Liebert Environmental UnitLevels 2, 3, and 10) .................................................... 5-59
Introduction ............................................................................................................. 5-59
L02, L03, L10 Unit Status Drop Metapoint Characteristics ..................................... 5-59
L02, L03, L10 Status Point Map.............................................................................. 5-62
L02, L03, L10 Unit Alarm Drop Metapoint Characteristics ...................................... 5-62
L02, L03, L10 Alarm Point Map............................................................................... 5-65
L02, L03, L10 Unit Command Drop Metapoint Characteristics............................... 5-66
L02, L03, L10 Control Point Map ............................................................................ 5-68
Application 5368: Liebert Environmental UnitLevel 15
with On/Off Control (LAM) ......................................................................................... 5-69
Introduction ............................................................................................................. 5-69
LAM Status Drop Metapoint Characteristics ........................................................... 5-69
LAM Status Point Map ............................................................................................ 5-71
LAM Alarm Drop Metapoint Characteristics ............................................................ 5-72
LAM Alarm Point Map ............................................................................................. 5-75
LAM Command Drop Metapoint Characteristics..................................................... 5-76
LAM Command Point Map ...................................................................................... 5-78
Application 5369: LSM Unit
(Liebert Environmental UnitLevels SM and O with On/Off control) ........................ 5-79
Introduction ............................................................................................................. 5-79
LSM Unit Status Drop Metapoint Characteristics.................................................... 5-79
LSM Status Point Map ............................................................................................ 5-81
LSM Unit Alarm Drop Metapoint Characteristic ...................................................... 5-82
LSM Alarm Point Map ............................................................................................. 5-85
LSM Command Drop Metapoint Characteristics..................................................... 5-85
LAM Command Point Map ...................................................................................... 5-88
Application 5370: MM4 Unit (Liebert Multi Module Series UPS)................................ 5-89
Introduction ............................................................................................................. 5-89
MM4 Unit Status Drop Metapoint Characteristics ................................................... 5-89
MM4 Unit Status Point Map .................................................................................... 5-92
MM4 Unit Alarm Drop Metapoint Characteristics .................................................... 5-93
MM4 Unit Alarm Point Map ..................................................................................... 5-95

iv
Table of Contents

Application 5371: MMS Unit (Liebert Multi Module Series UPS) ............................... 5-97
Introduction ............................................................................................................. 5-97
MMS Unit Status Drop Metapoint Characteristics................................................... 5-97
MMS Status Point Map ........................................................................................... 5-100
MMS Unit Alarm Drop Metapoint Characteristics ................................................... 5-101
MMS Alarm Point Map ............................................................................................ 5-103
Application 5372: MOR Unit (Liebert RCM 10U) ....................................................... 5-104
Introduction ............................................................................................................. 5-104
MOR Unit Status Drop Metapoint Characteristics................................................... 5-104
MOR Unit Status Point Map .................................................................................... 5-107
MOR Unit Alarm Drop Metapoint Characteristics ................................................... 5-108
MOR Alarm Point Map ............................................................................................ 5-110
Application 5373: PMP Unit
(Liebert Precision Power and Datawaves with PMP)................................................. 5-112
Introduction ............................................................................................................. 5-112
PMP Unit Status Drop Metapoint Characteristics ................................................... 5-112
PMP Unit Status Point Map..................................................................................... 5-114
PMP Unit Alarm Drop Metapoint Characteristics .................................................... 5-115
PMP Alarm Point Map............................................................................................. 5-118
Application 5374: RAC Unit (Liebert Remote Autochangeover Module) ................... 5-119
Introduction ............................................................................................................. 5-119
RAC Unit Status Drop Metapoint Characteristics.................................................... 5-119
RAC Status Point Map ............................................................................................ 5-121
RAC Alarm Drop Metapoint Characteristics............................................................ 5-122
Alarm Point Map...................................................................................................... 5-124
Application 5375: SC4 Unit (Liebert System Control Cabinet) .................................. 5-126
Introduction ............................................................................................................. 5-126
SC4 Unit Status Drop Metapoint Characteristics .................................................... 5-126
SC4 Status Point Maps ........................................................................................... 5-128
SC4 Unit Alarm Drop Metapoint Characteristics ..................................................... 5-129
SC4 Alarm Point Map.............................................................................................. 5-131
Application 5376. SCC Unit (Liebert System Control Cabinet) .................................. 5-134
Introduction ............................................................................................................. 5-134
SCC Unit Status Drop Metapoint Characteristics.................................................... 5-134
SCC Unit Status Point Map..................................................................................... 5-136
SCC Unit Alarm Drop Metapoint Characteristics .................................................... 5-137
SCC Alarm Point Map ............................................................................................. 5-140
Application 5377: SMM Unit (Liebert Multi Module Series UPS) ............................... 5-141
Introduction ............................................................................................................. 5-141
SMM Unit Status Drop Metapoint Characteristics................................................... 5-141
SMM Unit Status Point Map .................................................................................... 5-143

v
Open Processor with Liebert Sitelink Driver Owners Manual

SMM Unit Alarm Drop Metapoint Characteristics ................................................... 5-144


SMM Alarm Point Map ............................................................................................ 5-147
SMM Unit Command Drop Metapoint Characteristics ............................................ 5-149
SMM Command Point Map ..................................................................................... 5-151
Application 5378: SMS Unit
(Liebert Single Module Series UPS S300, S500, W600)........................................ 5-152
Introduction ............................................................................................................. 5-152
SMS Unit Status Drop Metapoint Characteristics ................................................... 5-152
SMS Unit Status Point Map..................................................................................... 5-154
SMS Unit Alarm Drop Metapoint Characteristics .................................................... 5-155
SMS Unit Alarm Point Map ..................................................................................... 5-158
Application 5379: SM3 Unit (Liebert Single Module Series UPS).............................. 5-159
Introduction ............................................................................................................. 5-159
SM3 Unit Status Drop Metapoint Characteristics.................................................... 5-159
SM3 Unit Status Point Map ..................................................................................... 5-161
SM3 Unit Alarm Drop Metapoint Characteristics .................................................... 5-162
SM3 Alarm Point Map ............................................................................................. 5-165
Application 5380: SM4 Unit (Liebert Single Module Series UPS).............................. 5-166
Introduction ............................................................................................................. 5-166
SM4 Unit Status Drop Metapoint Characteristics.................................................... 5-166
SM4 Unit Status Point Map ..................................................................................... 5-168
SM4 Unit Alarm Drop Metapoint Characteristics .................................................... 5-169
SM4 Unit Alarm Point Map...................................................................................... 5-171
Application 5381: SSC Unit (Liebert System Control Cabinet) .................................. 5-174
Introduction ............................................................................................................. 5-174
SSC Unit Status Drop ............................................................................................. 5-174
SSC Unit Status Point Map ..................................................................................... 5-176
SSC Unit Alarm Drop Metapoint Characteristics .................................................... 5-177
SSC Unit Alarm Point Map...................................................................................... 5-179
SSC Unit Command Drop Metapoint Characteristics ............................................. 5-182
SSC Unit Command Point Map............................................................................... 5-184
Application 5382. SSM Unit (Liebert Single Module Series UPS) ............................. 5-185
Introduction ............................................................................................................. 5-185
SSM Unit Status Drop Metapoint Characteristics ................................................... 5-185
SSM Unit Status Point Map..................................................................................... 5-187
SSM Unit Alarm Drop Metapoint Characteristics .................................................... 5-188
SSM Unit Alarm Point Map ..................................................................................... 5-191
SSM Unit Command Drop Metapoint Characteristics............................................. 5-193
SSM Unit Command Point Map Metapoint Characteristics .................................... 5-195
Application 5383. THM Unit (Liebert Temperature/Humidity Panel).......................... 5-196
Introduction ............................................................................................................. 5-196

vi
Table of Contents

THM Unit Device Drop Metapoint Characteristics .................................................. 5-196


THM Unit Status Point Map..................................................................................... 5-199
Application 5384: US3 Unit (Liebert UPS Station S3)................................................ 5-200
Introduction ............................................................................................................. 5-200
US3 Unit Status Drop Metapoint Characteristics .................................................... 5-200
US3 Unit Status Point Map ..................................................................................... 5-202
US3 Unit Alarm Drop Metapoint Characteristics ..................................................... 5-203
US3 Unit Alarm Point Map ...................................................................................... 5-206
Application 5385: VCM Unit (Liebert Volt Current Monitoring Panel) ........................ 5-207
Introduction ............................................................................................................. 5-207
VCM Unit Status Drop Metapoint Characteristics ................................................... 5-207
VCM Unit Status Point Map .................................................................................... 5-210
VCM Unit Alarm Drop Metapoint Characteristics .................................................... 5-210
VCM Unit Alarm Point Map ..................................................................................... 5-213
Application 5386: VCF Unit
(Liebert Volt Current Frequency Monitoring Panel) ................................................... 5-214
Introduction ............................................................................................................. 5-214
VCF Unit Status Drop Metapoint Characteristics .................................................... 5-214
VCF Unit Status Point Map ..................................................................................... 5-217
VCF Unit Alarm Drop Metapoint Characteristic ...................................................... 5-217
VCF Unit Alarm Point Map ...................................................................................... 5-220
Application 5387: WDU Unit
(Liebert Liquid Detection LDS750 or LDS1000) ........................................................ 5-221
Introduction ............................................................................................................. 5-221
WDU Unit Status Drop Metapoint Characteristics .................................................. 5-221
WDU Unit Alarm Drop Metapoint Characteristics ................................................... 5-223
WDU Unit Alarm Point map .................................................................................... 5-226
Application 5388: STS Unit
(Liebert Dual Output Breaker Static Switch PDU) ..................................................... 5-227
Introduction ............................................................................................................. 5-227
STS Unit Status Drop Metapoint Characteristics .................................................... 5-227
STS Status Point Map............................................................................................. 5-229
STS Unit Alarm Drop Metapoint Characteristics..................................................... 5-231
STS Unit Alarm Point Map ...................................................................................... 5-233
Diagnostic Points ....................................................................................................... 5-235
Core Control and Diagnostic Points ........................................................................ 5-235
Troubleshooting ........................................................................................................... 6-1

Chapter Overview ...................................................................................................... 6-1


Basic Service Information .......................................................................................... 6-1

vii
Open Processor with Liebert Sitelink Driver Owners Manual

Ordering Replacement Parts ..................................................................................... 6-2


Open Processor Troubleshooting.............................................................................. 6-2
Open Processor Operation ..................................................................................... 6-2
Point Operation ....................................................................................................... 6-4
Communications with Liebert System ..................................................................... 6-5
Replacing the Battery................................................................................................. 6-5

Glossary......................................................................................................................... Glossary-1

Index............................................................................................................................... Index-1

viii
How to Use This Manual
This manual is written for the owner and user of the Siemens Building Technologies Open
Processor with Liebert Sitelink Driver, referred to as Open Processor for the remainder of this
manual. It is designed to help you become familiar with the Open Processor and its
applications.

The manual contains the following chapters:

Chapter 1, Introduction, presents an overview of Open Processor operation.

Chapter 2, Hardware, describes the hardware components of the Open Processor,


equipment controllers and their functions.

Chapter 3, Software, describes the software used with the Open Processor.

Chapter 4, Point Database, defines the Open Processors point database.

Chapter 5, Applications, describes the applications available with the Open


Processor. Point maps, complete with slopes and intercepts, are included for each
supported Liebert equipment controller.

Chapter 6, Troubleshooting, describes basic corrective measures you can take if you
encounter a problem when using the Open Processor. This chapter is not meant to
be a full diagnostic guide, but is designed to help you address basic troubleshooting
issues. If you encounter a problem not covered in this chapter or require further
assistance, then consult your local Siemens Building Technologies representative.

A Glossary describes the terms and acronyms used in this manual.

An Index is provided to help you locate information presented in this manual.

Siemens Building Technologies, Inc. I


Open Processor With Liebert Sitelink Driver Owners Manual

Manual Conventions
The following table lists conventions to help you use this manual in a quick and efficient
manner.

Convention Example
Numbered Lists 1. Turn OFF power to the field panel. Turn ON power to the
(1,2,3) indicate a field panel.
procedure with
2. Contact your local Siemens Building Technologies
sequential steps.
representative.
Actions that you Type F for Field panels.
should perform are
specified in Click OK to save changes and close the dialog box.
boldface font.
Error and system The message Report Definition successfully
messages are renamed appears in the status bar.
displayed in Courier
New font.
New terms The Open Processor continuously executes a user-defined set of
appearing for the instructions called the control program.
first time are
italicized.

Manual Symbols
The following table lists the symbols used in this Owners Manual to draw your attention to
important information.

Notation Symbol Meaning


WARNING Indicates that personal injury or loss of life may occur to
the user if a procedure is not performed as specified.

CAUTION Indicates that equipment damage, or loss of data may


occur if the user does not follow a procedure as
specified.

Getting Help
For more information about the Liebert Sitelink Open Processor, contact your local Siemens
Building Technologies representative.

II Siemens Building Technologies, Inc.


How to Use This Manual

Where To Send Comments


Your feedback is important to us. If you have comments about this manual, please submit
them to technical.editor@sbt.siemens.com

Prerequisites
In addition to reading this owners manual, you should also become familiar with the following
Siemens Building Technologies technical documents. Each document has been written to
help you get the most out of your Open Processor.

Powers Process Control Language (PPCL) Users Manual (125-1896). This manual
describes Powers Process Control Language (PPCL), the language used to write the
control programs for the Open Processor.

System 600 APOGEE Field Panel Users Manual (125-3000). This manual describes
the operator interface program you use to communicate with the Open Processor and
other System 600 APOGEE field panels.

System 600 APOGEE Field Panel Users Quick Reference Guide (125-3001). This
guide is a pocket version of the System 600 APOGEE Field Panel Users Manual
(125-3000) written for experienced users of the operator interface. It contains a listing
of the operator interface prompt strings and the keystrokes an operator needs to
access the functions.

These manuals, along with information about other Siemens Building Technologies products,
technical training classes, and services, can be obtained from your local Siemens Building
Technologies representative.

For more information about the Liebert system, contact your local Liebert representative.

NOTE: This manual contains information specific to Open Processor applications. For
information regarding operation sequences for Liebert equipment controllers, refer
to the appropriate Liebert documentation.

Siemens Building Technologies, Inc. III


Open Processor With Liebert Sitelink Driver Owners Manual

IV Siemens Building Technologies, Inc.


1
Introduction

Chapter Overview
Chapter 1 covers the following topics:

Compatibility

Principles of Open Processor Operation

Gathering and Processing Field Inputs

Executing Control Programs

Processing Operator Commands

Understanding Building Level Network

Compatibility
The Open Processor is compatible with the following System 600 APOGEE products:

APOGEE Insight for Personal Computers

Stand-alone Control Unit (SCU), Revision 6.1 or greater

Local Area Network (LAN) Controller

Remote Control Unit Protocol 2 (RCU P2)

Modular Building Controller (MBC)

Remote Building Controller (RBC)

Floor Level Network (FLN) Controller

Siemens Building Technologies, Inc. 1-1


Open Processor with Liebert Sitelink Driver Owner's Manual

Principles of Open Processor Operation


Through the floor level network, the Open Processor establishes communication with and
gathers information about the Liebert equipment it monitors and controls. Updated information
received from the Liebert network is stored into a standard System 600 APOGEE point type.
The Open Processor also executes control programs, handles operator commands and
requests, and makes control management decisions.

Figure 1-1 shows an Open Processor.

Figure 1-1. The Open Processor

Gathering and Processing Field Inputs


The Open Processor samples the Liebert network inputs, or points, for information and stores
numerical representations of these values. The Open Processor then takes the required
action; that is, it either adds current information to the history file or sends an alarm message
to the proper location.

Executing Control Programs


The Open Processor continuously executes a user-defined set of instructions called the
control program. This program uses the most recent point values and the most recent clock
time. The control program performs the following functions:

Evaluates control strategies.

Uses an internal calendar and time clock for time-based functions.

Updates point values, and commands field points according to the program results.

Sends alarms, messages, or reports to proper terminal locations as needed.

1-2 Siemens Building Technologies, Inc.


Chapter 1 - Introduction

Processing Operator Commands


An operator can issue commands or requests to the Open Processor using an operator
terminal and the operator interface program that resides in the Open Processor. Reference
the System 600 APOGEE Field Panels Users Manual (125-3000) for more information on
access levels.

Valid operator commands to change point values or to command field points are handled
similarly to field input or control program commands. For example, if an operator issues an
ON command to a fan starter, the Open Processor issues the ON command to the field point
and updates the value in its memory. In this case, the operator overrides the control program.
The fan point would remain ON until the operator commands the fan OFF or until the operator
releases the point back to automatic control.

NOTE: Either the Open Processor or the Liebert system can command Liebert equipment
controllers.

Understanding Building Level Network


Up to 100 Open Processors and field panels (addressed 0-99) can be connected on a
building level network (BLN), also known as a Protocol 2, P2, or peer-to-peer network.
Information from any Open Processor or field panel on the BLN can be accessed and shared.
The BLN provides connections within or between buildings by using dedicated network wiring,
dedicated telephone lines, or dial-up telephone lines.

More than one operator can access the network at the same time. For example, as one
operator accesses the system, another operator can access the system at another terminal or
from a remote site by using a modem. Alarms are reported to the alarm printer even as an
operator accesses information.

When an operator issues a command over the network, the Open Processor or field panel at
which the operator issued the command validates the command, determines the commands
destination, and passes the command to the destination over the network. This process is
illustrated in Figure 1-2 as follows: a command, issued by the operator at the Open
Processor located in the lower level of the building, is sent through the BLN to the Open
Processor located on the penthouse to control the main air handling unit of the building.

For more information about networking, contact your local Siemens Building Technologies
representative.

Siemens Building Technologies, Inc. 1-3


Open Processor with Liebert Sitelink Driver Owner's Manual

Figure 1-2. Commanding Over a Network

1-4 Siemens Building Technologies, Inc.


2
Hardware

Chapter Overview
An Open Processor driver allows some control and monitoring functions that formerly required
hard-wired interfaces between the System 600 APOGEE and field equipment. Using an Open
Processor driver helps eliminate much of the expense of field wiring.

Chapter 2 covers the following topics:

System Configuration

System 600 APOGEEComponents

Black Box Components

Liebert Components

System Configuration
The Open Processor with Liebert Sitelink Driver enables the System 600 to monitor and/or
control the Liebert system. The integrated system consists of the Liebert system and the
System 600 APOGEE, linked by the Open Processor and either the REPOPT or the IC109A.

Figure 2-1 diagrams a typical Liebert Sitelink and System 600 APOGEE configuration.

Siemens Building Technologies, Inc. 2-1


Open Processor with Liebert Sitelink Driver Owner's Manual

MANAGEMENT LEVEL NETWORK: ETHERNET

INSIGHT
OPERATOR
WORKSTATION

BUILDING LEVEL NETWORK: PROTOCOL 2 (P2)

MBC WITH
OPEN PROCESSOR
WITH MODBUS
MASTER DRIVER FOR
LIEBERT SITELINK

RS-485

MODBUS RTU,
EIA-232

IGM MAXIMUM
12 IGMS PER
SITELINK DEVICE
IGMNET IGM
REPOPT EIA-485
OR IGM
BLACK BOX
IGM
RS-422

SITELINK-DC12I

MODBUS RTU,
EIA-232

IGM

IGMNET IGM
REPOPT EIA-485
OR IGM
BLACK BOX
IGM
RS-422

SITELINK-DC12I

MODBUS RTU,
EIA-232

IGM

IGMNET IGM
REPOPT EIA-485
OR IGM
GW0356R1

BLACK BOX
IGM
RS-422

SITELINK-DC12I

Figure 2-1. Typical Liebert Sitelink and System 600 APOGEE Configuration.

2-2 Siemens Building Technologies, Inc.


Chapter 2 - Hardware

System 600 APOGEE Components

Modular Building Controller or Remote Building Controller Enclosure


The Open Processor can reside in any Modular Building Controller (MBC) or Remote Building
Controller (RBC) enclosure with an open slot on the communications BUS (C-BUS). In
addition, the Open Processor:

Supports Expansion Module Kits.

Does not require a Power Module in the enclosure unless the Open Processor
controls Point Termination Modules (PTMs).

Can reside in an enclosure that contains a Power Module and one or more other
Open Processors. Other Open Processors are those capable of supporting one of a
variety of communication drivers.

NOTE: An MBC or RBC enclosure is FCC-approved for a maximum of four Open


Processors.

Figure 2-2 shows an MBC enclosure with various modules.

Figure 2-2. MBC Enclosure with Door Removed.

Open Processor with Liebert Sitelink Driver


The Open Processor with Liebert Sitelink driver is a high-performance, independent controller
that is customized to meet your exact building control needs. It controls mechanical
equipment and performs specialized applications using Direct Digital Control (DDC). The
Open Processor with Liebert Sitelink driver can communicate with System 600 APOGEE field
panels and Insight workstations. It can be implemented as a central monitoring unit or remote
site equipment controller, and can communicate with the point modules in the field panel.

Siemens Building Technologies, Inc. 2-3


Open Processor with Liebert Sitelink Driver Owner's Manual

Data about Liebert equipment controllers for controlling, displaying, logging, alarming, and
trending on the System 600 APOGEE is made available by the Open Processor, shown in
Figure 2-3, Figure 2-4, and Figure 2-5. Points in the Open Processors database hold
information about Liebert equipment controllers.

The Open Processor with Liebert Sitelink driver cannot communicate with any other FLN
devices, e.g., Terminal Equipment Controllers. The Open Processor connects to the Liebert
Sitelink system using only the FLN 1 port. However, the Open Processor uses the address
space of FLN 1, FLN 2, and FLN 3.

Figure 2-3. Open Processor (Front View).

Figure 2-4. Open Processor Figure 2-5. Open Processor


(Left Side View). (Right Side View).

Open Processor LEDs


Eight LEDs are located on the front of the Open Processor, but only six are active. Each LED
is labeled according to its function. Refer to Table 2-1 and to Figure 2-6 for additional
information.

Table 2-1. Open Processor LEDs.

Color Label Description


Green FLN TX Open Processor is transmitting information over
the FLN 1 trunk.
Green FLN1 RX Open Processor is receiving information over
the FLN 1 trunk.
continued on next page...

2-4 Siemens Building Technologies, Inc.


Chapter 2 - Hardware

Table 2-1. Open Processor LEDs.

Color Label Description


Green FLN2 RX Open Processor is receiving information over
the FLN 2 trunk.
Green FLN3 RX Open Processor is receiving information over
the FLN 3 trunk.
Green BLN TX Open Processor is transmitting information over
the BLN trunk.
Green BLN RX Open Processor is receiving information over
the BLN trunk.
Green STATUS Open Processor is powered up and operating
properly when this LED is flashing.
Red BATT LOW The Open Processor backup battery is low.
Replace the battery.

Figure 2-6. Open Processor LEDs.

Other Open Processors


Other Open Processors are those capable of supporting one of a variety of communication
drivers.

Siemens Building Technologies, Inc. 2-5


Open Processor with Liebert Sitelink Driver Owner's Manual

Other Open Processors also gather information about building systems that they monitor and
sometimes control. The information from the building systems is then stored into standard
System 600 APOGEE point types.

For more information about other Open Processors and associated drivers, contact your local
Siemens Building Technologies representative.

Power Module
The Open Processor does not require a Power Module when it is in an MBC or RBC
enclosure. However, Power Modules can share an MBC or RBC enclosure with Open
Processors.

NOTE: If an Open Processor controls PTMs, a Power Module is required.

For more information about Power Modules, refer to the System 600 Modular Building
Controller and Remote Building Controller Owners Manual (125-1992).

Expansion Module Kit


Expansion Module Kits contain communication devices that join the Module BUS (M-BUS) of
two sets of MBC or RBC enclosures when the first enclosure reaches its maximum point
capacity.

For more information about Expansion Module Kits, refer to the System 600 Modular Building
Controller and Remote Building Controller Owners Manual (125-1992).

Point Termination Modules


Point Termination Modules (PTMs) are signal converters that have one, two, or four points.
PTMs are the interface between the field equipment and an Open Processor. Field equipment
includes devices that provide information to, or are controlled or monitored by an Open
Processor. All field input and output points are either digital points or analog points such as
4mA through 20mA sensors, 0Vdc10Vdc outputs to control actuators, and pulse
accumulators.

For more information about PTMs, refer to the System 600 Modular Building Controller and
Remote Building Controller Owners Manual (125-1992).

Figure 2-7 shows a PTM.

2-6 Siemens Building Technologies, Inc.


Chapter 2 - Hardware

Figure 2-7. Point Termination Module (PTM).

Operator Interfaces
Operator interfaces, such as operator terminals (PCs, laptops), video display terminals, and
printers, allow you to communicate with the Open Processor.

Operator Terminals
Operator terminals allow you to communicate interactively with the Open Processor. A
keyboard is used for input, and a video screen or printer is used to display (echo) your inputs
and the system responses. Operator terminals allow you to do the following:

Directly control or request information about Open Processor points.

Check the operation of Liebert building controls.

Change or override control programs in the Open Processor.

Request and receive a variety of Liebert system and point status reports.

Change the definition of points in the system.

Define the destinations of alarm messages and reports.

Control operator access to the system (set up operator access levels and
passwords).

Create backup copies of user-defined control programs (using a PC or a laptop).

Transmit messages between operator terminals.

Video Display Terminals and Printers


Video display terminals and printers transmit information from the Open Processor to the
operator. These two devices allow you to do the following:

Receive and print reports.

Siemens Building Technologies, Inc. 2-7


Open Processor with Liebert Sitelink Driver Owner's Manual

Receive alarms.

Receive and print alarm messages.

Modems
Modems can transmit data from an Open Processor to an operator interface over telephone
lines. Therefore, remote communication between the Open Processor and an operator
interface is possible using two modemsone at each end of the communication link. For
example, an alarm printer can be set up in a building manager's office to receive alarms from
an Open Processor that is in a remote location.

Modems can be used along with leased telephone lines to link remote Open Processors in a
networked system and to link remote Open Processors with a centrally located mass storage
device such as a personal computer running Insight for Personal Computers.

A modem approved for your application can be installed within the MBC or RBC enclosure. A
cable connects the modem's RS-232 port to the MMI/MODEM port on the Open Processor.
Refer to Figure 2-8. If you need more room for the modem, remove the literature pocket by
lifting up on the center of the pocket until the ends slide out from underneath the two tabs on
both sides.

NOTE: The communication speed (baud rate) of the modem and the MMI/MODEM port
must match.

For more information about modems approved for use with the Open Processor, contact your
local Siemens Building Technologies representative.

Figure 2-8. Typical Modem Installation.

2-8 Siemens Building Technologies, Inc.


Chapter 2 - Hardware

Black Box Components

IC109A RS-232 to RS-485 Converter


The IC109A converts RS-232 signals from the Liebert Sitelink into RS-485 signals for the
Open Processors use, and vice versa.

NOTE: The Liebert REPOPT can be used instead of the Black Box converter. See page
2-10 for details.

IC109A-R2 Switch settings:

Switch Setting
XW1B DTE
W8 B-C
W15 B-C
W5 A-B
W9 C
W17 C
W16 B
S1 Out
S2 On*
S3 Off

NOTE: When using multiple Black Boxes, Switch S2 of the Black Box furthest from the
Open Processor driver (assuming series connection) must be on. All other S2
switches must be off.

IC109A-R2 Jumper Connections:


At terminal block TB1, connect RXA to TXA and RXB to TXB. The negative lead of the FLN1
connects to terminal TXA; the positive lead of FLN1 connects to terminal TXB.

NOTE: See Liebert Sitelink Installation Instructions (565-938) for complete wiring details.

Siemens Building Technologies, Inc. 2-9


Open Processor with Liebert Sitelink Driver Owner's Manual

Liebert Components

Sitelink DC12i or DC4i


The Sitelink assembly provides a communication link between the Liebert Sitelink and the
IGM microprocessor controller. The Sitelink must be set for communication baud rate of 9600
bps, with :

Eight bits

No parity

One stop bit

The Sitelink DC 12i provides twelve communication ports for connection to a maximum of 12
Liebert compatible manufactured products, while the Sitelink DC4i provides only 4 ports.

IGMnet
The IGMnet is the medium the Sitelinks use to communicate with IGMs via RS-422. Up to 12
IGMs can exist on a single Sitelink.

IGM
An IGM is a Liebert equipment controller such as Environmental Units, Power Units, and UPS
Units.

For more information about specific Liebert equipment controllers and their applications,
request the associated documentation from your local Liebert representative.

REPOPT
NOTE: The Black Box device (IC109A-R2) can be used instead of the Liebert REPOPT.
See page 2-9 for details.

The Liebert REPOPT converts RS-232 signals from the Liebert Sitelink into RS-485 signals
for the Open Processors use, and vice versa. The REPOPT Net A Select must be set to RS-
232.

NOTE: See Liebert Sitelink Installation Instructions (565-938) for complete wiring details.

2-10 Siemens Building Technologies, Inc.


3
Software

Chapter Overview
Chapter 3 describes the software that comes installed in the Open Processor. The Open
Processor software runs automatically when the Open Processor is powered up. When
properly configured, the Open Processor establishes communications with the remainder of
the System 600 APOGEE and the Liebert system, and begins relaying data.

Chapter 3 discusses the following topics:

Liebert Sitelink driver

Operator Interface

Powers Process Control Language (PPCL)

Liebert Sitelink Driver


The Liebert Sitelink driver allows the Liebert system to communicate directly with the System
600 APOGEE.

Operator Interface
An operator issues commands or requests to the Open Processor using an operator terminal
and the operator interface. The operator interface is the software that allows the operator to
communicate interactively with the Open Processor.

The operator interface is described in detail in the System 600 APOGEE Field Panel User's
Manual (125-3000). This manual is designed to help you become familiar with and use the
operator interface. It describes the functions necessary for everyday operation of your system,
plus the higher level functions for commanding, displaying, editing, scheduling, networking,
alarm management, and others.

For experienced users of the operator interface, the Field Panel User's Manual Quick
Reference Guide (125-3001) contains a listing of the operator interface prompt strings and the
keystrokes necessary to access the functions.

Siemens Building Technologies, Inc. 3-1


Open Processor with Liebert Sitelink Driver Owner's Manual

PPCL
The programming language used with the Open Processor is called Powers Process Control
Language (PPCL). PPCL is a powerful programming language developed specifically for
controlling Heating, Ventilating, and Air Conditioning (HVAC) equipment.

The control configuration and control requirements of your system are customized into each
application by using PPCL. The applications that you can incorporate into the operation of
your system include the following:

Alarm Management

Auto-Dial/Dial-Up

Daylight Savings Time

Duty Cycling

Enthalpy and Dry Bulb Economizer Control

Field Panel/Equipment Controller Coordinator

Loop Tuning

Peak Demand Limiting (PDL)

Start/Stop Time Optimization (SSTO)

Equipment Scheduler

Trend Data Collection

The Powers Process Control Language (PPCL) User's Manual (125-1896), contains
information on designing, coding, and implementing PPCL programs. It lists and defines all
PPCL control commands, control applications, syntax, and functionality.

3-2 Siemens Building Technologies, Inc.


4
Point Database

Chapter Overview
Chapter 4 describes the Open Processor point database, including point definition
information, dynamic point information, point database structure, point addresses, and slopes
and intercepts.

Most tasks that the Open Processor performs involve either collecting data from Liebert
Sitelink equipment controllers or commanding them. Other tasks require communication and
calculations within the control programs using stored information. Operators also need a
practical method of commanding and examining points. With the Open Processor, operators
use the commands and menu-driven prompts of the operator interface.

The point database is created by supplying the Open Processor with logical points and
information about the Liebert point data. There are two basic classifications of point
information that make up the point database: Information used to define Liebert points, and
information that is updated or set during operation of the Liebert system.

In order to monitor and/or control Liebert Sitelink equipment controllers, points must be added
to the point database. For details about defining these points, refer to the point addressing
information that follows. For additional information about adding or modifying points in the
database, refer to the System 600 APOGEE Field Panel Users Manual (125-3000).

Information for specific Liebert equipment controllers is listed in Chapter 5 - Applications.

Chapter 4 discusses the following topics:

What is a Point Database?

Types of Points

Point Characteristics

Point Attributes

Point Database Guidelines

Siemens Building Technologies, Inc. 4-1


Open Processor with Liebert Sitelink Driver Owner's Manual

What is a Point Database?


The point database is a file containing all information defined for every point in the System
600 APOGEE. The system controls points according to their definition and their purpose..
Points are classified as follows:

Logical points A grouping of one to four physical and/or virtual point addresses under a
unique 30-character name. This name is referenced by operators, control programs, and the
other system features to command, examine, and store information for those points.

Physical points Points which the system uses to reference the actual physical devices
connected to a field input/output termination.

Virtual points Points residing in memory that do not represent a piece of equipment. Virtual
points generally store values such as set points and results from calculations.

Subpoints Points within an application, such as Equipment Scheduler or a TEC.

Local points Standard system points residing in a PPCL program that are specific to that
program (such as ALMCNT).

Types of Points

Logical Points
All logical points are composed of one or more of the following four basic point types:

Analog Input (AI)

Analog Output (AO)

Digital Input (DI)

Digital Output (DO)

Analog Input (AI)


Analog Input (AI) points provide variable-type information to the field panel. Some examples
of AI points are:

Temperature sensors

Relative humidity sensors

Analog Output (AO)


Analog Output (AO) points receive variable commands from the field panel. Some examples
of AO points are:

4-2 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Valve or damper actuators

Variable speed drives

Digital Input (DI)


Digital Input (DI) points provide two-state information to the field panel. Some examples of DI
points are:

Proof of operation switches

Filter alarms

Smoke alarms

Digital Output (DO)


Digital Output (DO) points receive two-state commands from the field panel. Some examples
of DO points are:

Fans and pumps

Electric/pneumatic switches

Virtual Points
A virtual point is a logical point without a physical device. Refer to the System 600 APOGEE
Field Panel Users Manual (125-3000).

Examples
The following examples demonstrate how virtual points can be used:

For set points:


Virtual points can store desired values such as temperature, relative humidity, and pressure.
For the system to make adjustments to control equipment, the system needs to compare the
actual value to the desired value. The field panel stores the desired value in memory as a
virtual analog output point.

For operational values:


Virtual points are often used to store operational data. For example, a virtual point can be
used to store the high and low temperatures for outside air. Applications such as Start/Stop
Time Optimization (SSTO) use virtual points for different types of values.

For a time/date:
PPCL uses times and dates to accomplish building control.

Siemens Building Technologies, Inc. 4-3


Open Processor with Liebert Sitelink Driver Owner's Manual

Local Points
Every PPCL program has a set of fixed local points. Local points are used primarily in PPCL
programming. Refer to the PPCL Editor chapter of the System 600 APOGEE Field Panel
Users Manual (125-3000) for more information on using local points.

Point Characteristics
Each point (logical or virtual) has characteristics that are viewed in monitoring mode. These
characteristics are:

Point name/point system name

Point address

Point status

Point priority

Point value/state

Point Name/Point System Name


The point name and point system name are the labels that identify a particular point in the
database. The point system name and point name can be the same. You may also define
them with different names. Both names, whether they are set equal or defined differently,
must be unique on the network.

Having two names provides the ability to customize the database without affecting the control
of the system. PPCL programs (which exclusively use the point system name) remain
unchanged if the point name is changed.

Each user account defines the type of name that is displayed in the interface. Those with User
access see the point name. Those with System access see the point system name. When
viewing PPCL programs, the system always displays the point system name regardless of the
access settings.

The following example illustrates a point name and a point system name:

Point name: BUILDING1.AHU1.SPACETEMP

Point system name: B1A1ST

For points on an FLN device, or in applications, a suffix is used with the device or application
name. For these types of points, the FLN device/application is referenced first, followed by a
colon, and then followed by the suffix (the name of the subpoint).

The following example illustrates referencing a point on an FLN device called BUILDING
1-VAV12:

4-4 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

BUILDING 1-VAV12:DO2

The following example illustrates referencing a local set point in a PPCL program called
WARMUPMODE:

WARMUPMODE:SETPOINT

Point Naming Conventions


Naming conventions provide a consistent and predictable organization for points. The
following guidelines are recommended:

When designing a point database, identify common segments or groupings for point
names. Larger facilities may use six or more segments to name points. Smaller
facilities may choose a simpler convention by using only three or four segments. The
most common segments and order are as follows:

State

Campus

Building or Department

Floor, Room, or Area

Equipment (boiler, chiller, air handler, etc.)

Device

The names should be structured hierarchically, moving from global (far left
characters), to specific (far right characters). For example:

LIB.CHILL02.CWT
(room, equipment, device)

BLD990.FLR01.AHU01.SAT
(building, floor, equipment, device)

Only alphanumeric characters and periods should be used in point names.

Do not use underscores.

Use periods only as separators between sections. Do not use periods in


abbreviations.

Do not begin a point name with a period.

Siemens Building Technologies, Inc. 4-5


Open Processor with Liebert Sitelink Driver Owner's Manual

If one or more points on a job lacks a section that you identified in your point naming
conventions, insert a period for the missing section. For example:

BLD990.FLR01.AHU01.SAT

BLD990.FLR01..SAT (The equipment section is missing in the second point name,


replaced by two periods.)

Program names should be the same as the point names and equipment they control,
but without the suffix. For example:

Equipment Building 990, Floor 1, Air Handling Unit 1


Program Name IL.BLD990.FLR01.AHU01
Points Controlled IL.BLD990.FLR01.AHU01.SAT
IL.BLD990.FLR01.AHU01.HVL
IL.BLD990.FLR01.AHU01.SFN

Tips for Entering Point Names


Instead of typing an entire point name, the system allows the following shortcuts:

Wildcards allow for easier selection for names of points.

Query for point names can provide a numeric list of points to select from.

The quick text key can be used to define part of the point name.

Use command key shortcuts (such as Ctrl-P and Ctrl-I from the paste buffer).

For examples of queries and wildcarding, refer to the Introduction chapter of the System 600
APOGEE Field Panel Users Manual (125-3000).

Point Address
The point address defines the location of the point in the field panel (whether on the M-BUS or
in an FLN device). Points on the M-BUS are addressed by:

Field panel The name or number.

FLN For points on the M-Bus, the FLN number is always 0.

Drop The number of the address key on the Point Termination Module (PTM).

Point The point number on the Point Termination Module (PTM).

NOTE: Virtual points only require a field panel number, and cannot be defined on FLN
devices.

4-6 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

FLN addresses for subpoints consist of:

Field panel The name or number.

FLN The number of the FLN connection on the field panel. A point on an FLN
device will always have an FLN number or 1, 2, or 3.

Drop The address number of the FLN device.

Point The number of the subpoint on the FLN device or on the point map.

Point Status
The point status indicates the current condition of a logical point as defined in the System 600
APOGEE database. It can also reflect two or more statuses. For example, a point may be in
alarm and failed at the same time, in which case the status would be *AF*. Table 4-1 gives an
explanation of each status.

Table 4-1. Point Status.

Status Meaning Explanation


-N- NORMAL The point is in regular operation. The value and alarm
conditions of the point can be updated by control programs
or operator commands.
*A* ALARM The condition of the point is outside its defined limits and an
alarm priority has been assigned to the point. An alarm
occurs when the following occurs:
The value of an analog point is outside a defined high or
low limit.

The value of a proof point does not correspond to the


commanded value of the associated output point within
the proof delay time.

An LDI or LDO point is ON and the point was defined to


go into alarm when it turns ON, for example, a smoke
detector point.

*An* ALARM The condition of the point is outside its defined limits and an
enhanced alarm priority has been assigned to the point. The
"n" represents the number of the alarm level.
*AC* ALARM-BY- The value of a point is its normal operating range; however,
COMMAND the point has been commanded into alarm by an operator or
by the control program. The point remains in this state until it
is commanded back to the Normal state by an operator or
control program.
continued on next page...

Siemens Building Technologies, Inc. 4-7


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 4-1. Point Status.

Status Meaning Explanation


*ACK* ACKNOWLEDGE The point is in alarm and has been acknowledged by a user.
*F* FAILED The field panel is unable to command or read any of the
physical points associated with the logical point. This may be
the result of hardware failure or a sensor reading outside of
its defined limits.
*O* OPERATOR The point has been disabled by an operator. The point value
DISABLED and alarm conditions are not reported to the BLN and cannot
be updated by operator commands or control programs until
the point is commanded back to Enabled.
*P* PROOFING The field panel is waiting to verify that the value of a proof
point corresponds to the commanded value of an associated
output point. The proof delay time defined for the point
determines the length of time the point will remain in this
state.
*HAND* HAND A PTM manual override switch has been used and the
system no longer has control of the point. The system will
not be able to control that point until the PTM is switched
back into AUTOMATIC mode.
*TBL* TROUBLE The point is in TROUBLE state. This status appears when a
PPCL program or user commands the point to this state.

Point Priority
The point priority determines if an operator or a particular control program is responsible for
controlling the point. The five priority levels are described in Table 4-2.

4-8 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Table 4-2. Point Priority.

Command Priority Description


OPER In this highest command priority, the control program is
overridden, and an operator has direct control for
(Operator)
commanding the point. A point commanded by an operator
must have its priority lowered in order for the control
program to resume control of the point. This change in
priority is known as releasing a point.
SMOKE A smoke control program commands the point. Smoke
control is a special control program that monitors smoke
alarms.
EMER An emergency control program commands the point.
Emergency control is a special control program that
(Emergency)
commands a point during emergency situations; for
example, a smoke detector goes into ALARM and turns on
the exhaust fan at EMER priority.
PDL The point is commanded by a Peak Demand Limiting (PDL)
control program. PDL control is a special energy
(Peak Demand Limiting)
management program that limits electrical demand by
turning off electrical loads when demand approaches a set
point (for example, shutting down an air handling unit if
demand approaches set point).
NONE The lowest command priority level: The point can be
commanded by the standard PPCL control program. The
point is not controlled by the operator or special control
programs. Most point commanding in a building system is
done automatically by PPCL programs commanding points
with the NONE priority.

In most cases, the priority of a point should be NONE (under general system control).
Depending on the type of application, the system can change point priority to prevent
interaction by other applications (either by PPCL or an application). For example:

A point at NONE priority can be commanded by any PPCL program or application.

A point at PDL priority is being used by the PDL application. The point can be
commanded by other higher level applications (such as smoke control or operator),
but not by general PPCL programs or applications.

A point in OPER priority was commanded by a user. The system cannot command
the point until released back to system control. At any time, you can override any
application. The result of this action can change system performance.

The following methods are used to change point priority:

User interaction the priority is changed manually via the interface.

A PPCL command PPCL uses a command to directly change the point priority.

Siemens Building Technologies, Inc. 4-9


Open Processor with Liebert Sitelink Driver Owner's Manual

Once the point priority changes to NONE, it is available for commanding by general PPCL and
applications.

Point Values/State
Analog points have numeric values, identifying temperatures, positions, flow rate, etc. The
point value is usually associated with an engineering unit that gives the value more meaning.

Digital points have states such as ON or OFF. A state is determined by the physical position
of one or more electronic switches. If a switch is energized, then the point is at a certain state
(for example, ON). For example:

Point State Default System Text


Energized state ON (value 1)
De-energized state OFF (value 0)

State text allows the text used by each digital point to be redefined with more meaningful text.
The following example illustrates the difference between the default text and alternate state
text labels:

Point State Default System Text Alternate State Text


Energized state ON DIRTY
De-energized state OFF CLEAN

Refer to the System Profile chapter of the System 600 APOGEE Field Panel Users Manual
(125-3000) for more information concerning the use of state text.

Point Attributes
Each point definition is composed of attributes. These attributes describe the point to the
system. Some attributes are used by all point types, while other attributes are specific to a
particular point type.

4-10 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Table 4-3. Summary of Point Information Categories by Point Type.

Category LAI LAO LDI LDO


Point name
Point type
Descriptor
Alarm information
Totalize
Engineering units
Point address
Slope
Intercept
Sensor type
COV limit
Initial value
Normally closed
Invert value
English units y/n
Override time
=supported

Point Name
The following attributes are used for the point name:

>Point system name


>Point name
The entries can contain from 1 to 30 characters. Valid characters include the following: A
through Z, a through z, 0 through 9, spaces ( ), periods (.), commas (,), dashes (-), underlines
(_), and apostrophes (').

Siemens Building Technologies, Inc. 4-11


Open Processor with Liebert Sitelink Driver Owner's Manual

NOTES: 1. If backward compatibility is required, the point system name must


follow the 6-character naming structure. Valid characters include the
following: A through Z, and 0 through 9.
2. If spaces, periods, commas, dashes, or underlines are used in the
point system name, they must have quotes around them when used
in PPCL.

Point Type
The following attribute is used to identify the logical point type:

> Point type


Any of the 12 point types can be entered. However, when defining Liebert points, only LAO,
LAI, LDI, and LDO point types can be used. Typing ? displays a numerical list to choose from.
To select a point from a list, type the corresponding number and press Enter.

1) LAO 5) LDI 9) LOOAP


2) LAI 6) L2SL 10) LFSSL
3) LPACI 7) L2SP 11) LFSSP
4) LDO 8) LOOAL 12) LENUM

Point Descriptor
The following attribute is used for the point descriptor:

>Descriptor
This optional prompt identifies additional information for the point. The descriptor can contain
from 0 to 16 characters. Valid characters include the following: A through Z, a through z, 0
through 9, spaces ( ), periods (.), commas (,), dashes (-), underlines (_), and apostrophes (').
Pressing Enter without entering text leaves the descriptor blank.

Engineering Units
The following attribute is used for the engineering units of the point:

>Engineering units
This optional prompt identifies the units of measurement for the point value (called
engineering units). The descriptor can contain from 0 to 6 characters. Valid characters include
the following: A through Z, a through z, 0 through 9, spaces ( ), periods (.), commas (,),
dashes (-), underlines (_), and apostrophes (').

4-12 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Access Groups
The following attribute is used to identify access groups for the point:

>Access group(s)
This prompt identifies to which access group(s) a point belongs. Valid entries range from 1 to
30. Pressing Enter without entering a number(s), will default to all access groups. To define
more than one access group, you can use either of the following conventions:

Use commas to separate the access group numbers (1, 10, 22 - for access groups 1,
10, and 22).

Use double periods to define a range (1..8 - for access groups 1 through 8).

If the defined access groups are unknown, type ? and press Enter. The system displays a list
of all defined access groups.

Alarming
The following attributes are used for point alarming:

>Alarmable (Y/N)
This attribute specifies if the point will use standard alarming. Answering N will forego the
remaining alarm prompting.

>Enhanced alarms (Y/N)


This attribute specifies if the point will use enhanced alarming. Answering Y to this prompt
requires you to set up enhanced alarming information for the point at a later time. Answering
N to this prompt assigns the point to use standard alarming. Refer to the Alarm Management
chapter of System 600 APOGEE Field Panel Users Guide (125-3000) for more information
on alarming.

>Print alarms (Y/N)


This attribute specifies if the system should print an alarm message when the point condition
changes to ALARM, the point is commanded into ALARM or the point fails. Answer Y to print
alarms, otherwise, answer N to suppress alarm printing for the point.

>Alarm count 2 (Y/N)


This attribute specifies if the system should update the PPCL ALMCT2 resident point when
this point enters ALARM. This PPCL resident point allows for closer monitoring of critical
points. Answering Y causes both the ALMCNT and ALMCT2 counters to increment by 1 when
a point enters alarm. Answering N updates the ALMCNT resident point only.

>Normal ack enabled (Y/N)


This attribute specifies if the point requires acknowledgment from a user after it enters an
ALARM condition. If the alarm is not acknowledged, the system will be unable to change the
status point until a user acknowledges the alarm condition.

Siemens Building Technologies, Inc. 4-13


Open Processor with Liebert Sitelink Driver Owner's Manual

>High limit
For analog points that use standard alarming, the high limit represents the maximum value
before the point condition changes to ALARM.

>Low limit
For analog points that use standard alarming, the low limit represents the minimum value
before the point condition changes to ALARM.

Totalize
The following attributes are used for totalization of a point:

>Totalize (Y/N)
>Totalize in Hours, Minutes, Seconds
If the answer is Y, the system keeps track of the run time for the various states of the point
and prompts for how often the totalization value should be displayed: by second, minute, or
hour.

The totalization function accumulates the runtime value of a point. It can be used to:

Accumulate run time for fans and pumps.

Accumulate volume total from a flow rate sensor.

Calculate degree days (used in PPCL).

Point Address
The following attributes are used to address the point in the field panel:

>Field panel
Identifies the field panel where the point is defined. Field panel numbers can range from 0 to
99.

>Physical, Virtual Point address


>Physical, Virtual AUTO Point address
>Physical, Virtual FAST Point address
>Physical, Virtual OFF Point address
>Physical, Virtual ON OFF Point address
>Physical, Virtual ON Point address
>Physical, Virtual Proof Point address
>Physical, Virtual SLOW Point address
>Physical, Virtual STOP Point address

4-14 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Depending on the point being defined, the system will display any of the above prompts after
the field panel has been identified. Each point type has different characteristics, so the system
will display the appropriate prompt for the type being defined.

A physical point address means a point is associated to an actual termination in the field
panel. The virtual point address means the point resides in memory. If the point serves a
specific purpose (such as a complex digital requiring multiple points to control specific states),
then the system will identify which point (and state) is being defined. The system does not
prompt for the FLN, DROP and POINT numbers when defining virtual points.

> FLN
Indicates the number of the FLN (floor level network) that the point resides on. If the point
resides in the field panel, the FLN Number is 0. If the point resides in an FLN device, the FLN
Number can be 1, 2, or 3.

NOTE: Although the Open Processor only resides on FLN 1, it takes up the address
space of FLN 1, 2, and 3.

> Drop
Is a number from 000 to 255 that identifies the Point Termination Module (PTM) or an FLN
device address in which the point resides. If the point resides in the field panel, the Drop
Number is the number of the PTM address key. If the point resides in an FLN device, the
Drop Number is the FLN device number.

> Point
Is a number that identifies the physical point within the field panel or the point on the FLN
device. The valid values for point numbers are set by the actual layout of the hardware within
the field panel or FLN device.

State Text
The following attribute is used to define state text for digital and LENUM points:

>State text table


Designates the state text table assigned to a particular point by doing one of the following:

To use the default entry for a point, press Enter without typing a number.

To assign an alternate state text table, type the table name and press Enter.

If the name of a particular table is unknown, type ? and press Enter to display a list of
available state text tables.

Change of Value
The following attributes are used to define a Change of Value (COV) limit for a point:

Siemens Building Technologies, Inc. 4-15


Open Processor with Liebert Sitelink Driver Owner's Manual

>Dynamic COV limit (Y/N)


This attribute specifies if the system should use an internal algorithm to generate the point
COV limit. Type Y to use the algorithm, otherwise type N to specify a numeric value for the
COV limit.

>COV limit
This attribute indicates the amount of change, in engineering units, that a point can undergo
before a field panel reports the change to other field panels on the BLN.

Other Analog Point Attributes


The following attributes are used when defining analog points:

>Float, Integer, Time, Date, dAte/Time


This attribute identifies the point value format type. There are five different types of point
values for analog points:

Float Floating point values.

Integer Integer values.

Time A floating point value that represents the time of day (for example, 13.5 = 1:30
PM).

Date A floating point value identifying the number of minutes that have passed since
01/01/1970.

Date/Time A floating point value identifying the number of minutes that have passed
since January 1 at 00:00 in the current year.

>Sensor type
This attribute indicates the type of input that the sensor point receives. The sensor types are:

Thermistors (thermo-electric element with electrical resistance that falls with the rise
of temperature).

Current (4 to 20 mA).

Voltage (0 to 10 Vdc).

Pneumatic (3 to 15 psig).

L-type sensor (AI sensor terminated on a FLN device).

NOTE: Unless otherwise specified, all driver points should be defined as Current Type (I)
sensors.

>Number of decimal places


The system prompts for the number of decimal places for the point value if a float sensor type
is defined.

4-16 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

>Slope
>Intercept
Factors used to convert signals that the field panel uses for analog points into engineering
units that represent point values. Slope and intercept constants are determined by the type of
input or output device that is represented by the point, and whether the point is a physical
point or a virtual point. For points in the Open Processor, refer to Chapter 5 - Application, in
this manual. For other point types, see the Calculating Slopes and Intercepts section of the
System 600 APOGEE Field Panel Users Manual (125-3000) for more information.

>Initial value
This is used to set the point value when an analog point is first viewed by the field panel
(either by being defined or on a return from power loss).

>Wire resistance
This is used to adjust a point intercept value to compensate for long runs of wire.

Other Digital Point Attributes


The following attributes are used when defining digital points:

>Invert value (Y/N)


This attribute defines how a command should be applied to an output. If a point has an
inverted value, an ON command de-energizes the point and an OFF command energizes the
point. Conversely, a point with a value that is not inverted energizes when an ON command is
received, and de-energizes when an OFF command is received.

NOTE: For driver points, the answer to this prompt should be N (No) unless otherwise
stated in the point map.

>Normally closed (Y/N)


This attribute defines how a digital point will react during a power loss. If a point is normally
closed, the contacts for the DI point are wired to be closed when no energy is applied to the
point. A point that is normally open will have open contacts when no energy is applied to the
point.

NOTE: For driver points, the answer to this prompt should be N (No) unless otherwise
stated in the point map.

>Proof (Y/N)
This attribute defines if a point should be proofed. If the point does have a proof point, then
the system also asks for a proof delay.

>Proof delay (seconds)


This attribute defines (in seconds) how much time must pass after a point is commanded,
before the system will check if an alarm condition exists for the point.

Siemens Building Technologies, Inc. 4-17


Open Processor with Liebert Sitelink Driver Owner's Manual

>Count both edges (Y/N)


This attribute defines how the system interprets a pulse count. Gain is specified per pulse
edge count. If both edges are counted, each on/off pulse (momentary contact) of the point
produces two pulse counts. If only one edge is counted, each on/off pulse produces one pulse
count. If both pulse edges are counted, gain is doubled.

>Gain
This number is used to convert pulses from a pulse accumulator point into the engineering
units that represent point values. Gain defines the number of engineering units (ranging from
0.001 to 5000.0) represented by each pulse count.

Point Database Guidelines


This section provides some general guidelines for adding points to the Open Processors
database. These points monitor and/or control Liebert equipment operation. Define only the
points necessary for your application.

Modbus Protocol
Modbus is a protocol developed by Modicon and widely adopted by the industrial and now
HVAC industries. There are different implementations of Modbus which should be considered
when looking at a Modbus integration project.

Liebert SiteLink and the Open Processor with Liebert SiteLink Driver use RTU type Modbus to
share data. They communicate between each other at a speed of 9600 bps. The Open
Processor is the master, while the SiteLink is the slave. This simply means that all
communication is initiated by the Open Processor.

Modbus is a register-based protocol. The Liebert SiteLink and the Open Processor with
Liebert SiteLink driver each have a set of registers that they continually update. These are
known as Holding Registers, and are designated with as a number from 40,001 to 40,384. All
of their communication references these register numbers.

Liebert Modbus Register Mapping


Liebert groups their points into three types: status points, alarm points, and control points. Not
every device has all three types of points. Refer to Chapter 5 - Applications for specific
information on each type of device.

Each SiteLink is considered one Modbus device (one address per Sitelink) which connects to
up to 12 Liebert devices. They have 384 registers per Sitelink (ranging from 40001 to 40384).
Liebert maps their points into the SiteLink registers using the following three methods:

4-18 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Status Points
There are 24 Modbus registers allocated to each device for status points. Each Liebert status
point occupies one Modbus Holding Register; therefore each device may have up to 24 status
points. Consult Chapter 5 - Applications for the actual numbers of status points for each type
of device. Table 4-4 lists status points and their corresponding ranges.

Siemens Building Technologies, Inc. 4-19


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 4-4. Status Points.


*
Device Port Number Status Point Modbus Register Range
1 40001 - 40024
2 40025 - 40048
3 40049 - 40072
4 40073 - 40096
5 40097 - 40120
6 40121 - 40144
7 40145 - 40168
8 40169 - 40192
9 40193 - 40216
10 40217 - 40240
11 40241 - 40264
12 40265 - 40288
*Although the number of characters shown is reserved for the device, it may not
use all of the characters.

Alarm Points
There are 5 Modbus registers allocated to each device for alarm points. Each Liebert alarm
point occupies one bit of a 16 bit Modbus Holding Register, although Liebert only uses 11 bits
of these 16. Each device may have up to 11 times 5 status points, or 55 status points. Consult
Chapter 5 - Applications for the actual numbers of alarm points for each type of device. Table
4-5 lists alarm points and their corresponding ranges.

Table 4-5. Alarm Points.


*
Device Port Number Alarm Point Modbus Register Range
1 40289 - 40293
2 40294 - 40298
3 40299 - 40303
4 40304 - 40308
5 40309 - 40313
6 40314 - 40318
7 40319 - 40323
continued on next page...

4-20 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

Table 4-5. Alarm Points.


*
Device Port Number Alarm Point Modbus Register Range
8 40324 - 40328
9 40329 - 40333
10 40334 - 40338
11 40339 - 40343
12 40344 - 40348
*Although the number of characters shown is reserved for the device, it may not
use all of the characters.

Control Points
There are 3 Modbus registers allocated to each device for control points. Each Liebert control
point occupies one Modbus Holding Register, therefore each device may have up to 3 control
points. Consult Chapter 5 - Applications for the actual numbers of status points for each type
of device. Table 4-6 lists control points and their corresponding ranges.

Table 4-6. Control Points.


*
Device Port Number Control Point Modbus Register Range
1 40349 - 40351
2 40352 - 40354
3 40355 - 40357
4 40358 - 40360
5 40361 - 40363
6 40364 - 40366
7 40367 - 40369
8 40370 - 40372
9 40373 - 40375
10 40376 - 40378
11 40379 - 40381
12 40382 - 40384
*Although the number of characters shown is reserved for the device, it may not
use all of the characters.

Siemens Building Technologies, Inc. 4-21


Open Processor with Liebert Sitelink Driver Owner's Manual

Understanding Metadrops
A metadrop in System 600 APOGEE acts as a virtual FLN device. The values of the points in
this virtual device specify attributes for mapping the other drops into the Liebert Sitelink
system.

This scheme involves the dedication of one drop on FLN 3 drop 30 whose points will be used
to specify the mapping of the Liebert Sitelink points into System 600 APOGEE.

Each point in FLN 3 drop 30 will be allocated to provide mapping information for the remaining
drops. Point 1 in this drop will specify information for FLN 1 drop 1, point 2 will specify FLN 1
drop 2, . . . point 32 will specify FLN 2 drop 0, etc. Figure 4-1 illustrates this concept:

METADROP SYSTEM POINTS


LOCATED IN
FLN 3, DROP 30
POINT #
00 FLN 1, DROP 00
01 FLN 1, DROP 01
02 FLN 1, DROP 02
* *
* *
31 FLN 1, DROP 31
32 FLN 2, DROP 00
33 FLN 2, DROP 01
* *
* *
63 FLN 2, DROP 31
64 FLN 3, DROP 00
65 FLN 3, DROP 01
* *
* *
92 FLN 3, DROP 28
GW0322R1

93 FLN 3, DROP 29
94-99 NOT USED

Figure 4-1. Mapping Metadrops into S600 APOGEE FLN and Drop Numbers.

Defining Sitelink Metapoints


The status points, alarm points, or control points of each Sitelink device that you want to map
into the System 600 require one metapoint each. There are a maximum of 94 metapoints.
Consult Chapter 5 - Applications for more information on specific device metapoints.

Required Points
The following points are required to start up the Open Processor. It is recommended that a
small database (required points only) be created initially to prove communication with the
Liebert system. Then, the remainder of the database can be added later.

4-22 Siemens Building Technologies, Inc.


Chapter 4 - Point Database

A metapoint per device point group; i.e., each device port will have a metapoint
associated to a group of Status Points, a group of Alarm Points, and, in some cases,
a group of Control Points.

Response Interval . Defined as an LAO at address 3.31.06, with a slope of 1.0,


intercept of 0, and an initial value of 200.

Delay After Read. Defined as an LAO at address 3.31.64, with a slope of 1.0,
intercept of 0, and an initial value of 200.

Any LAI associated with the defined metapoint.

Optional Points
For a complete list of optional points specific to supported Liebert equipment controllers, refer
to Chapter 5 Applications.

Siemens Building Technologies, Inc. 4-23


Open Processor with Liebert Sitelink Driver Owner's Manual

4-24 Siemens Building Technologies, Inc.


5
Applications

Chapter Overview
Chapter 5 contains features, applications, and point mapscomplete with slopes and
interceptsfor all the Liebert equipment controllers supported by the Open Processor.
Chapter 5 covers the following topics:

Open Processor Applications

Application 5360: C10 Unit (Liebert Environmental Unit Australia/Atlas Air)

Application 5361: CCM Unit (Liebert Contact Closure Modules)

Application 5362: CSU Unit (Liebert Mainframe Chiller)

Application 5363: CSE Unit (Liebert Mainframe Chiller with Econocoil)

Application 5364: EDS Unit (Liebert Static Switch PDU)

Application 5365: L00 Unit (Liebert Environmental UnitsLevels 0 and 1)

Application 5366: L0B Unit (Liebert Environmental Units Small Systems)

Application 5367: L02, L03, L10 Unit (Liebert Environmental UnitLevels 2, 3, and
10)

Application 5368: LAM Unit (Liebert Environmental UnitLevel 15 with On/Off


Control)

Application 5369: LSM Unit (Liebert Environmental UnitLevels SM and 0 with


On/Off Control)

Application 5370: MM4 Unit (Liebert Multi Module Series UPS)

Application 5371: MMS Unit (Liebert Multi Module Series UPS)

Application 5372: MOR Unit (Liebert RCM 10U)

Application 5373: PMP Unit (Liebert Precision Power and Datawaves with PMP)

Application 5374: RAC Unit (Liebert Remote Autochangeover Module)

Application 5375: SC4 Unit (Liebert System Control Cabinet)

Siemens Building Technologies, Inc. 5-1


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5376: SCC Unit (Liebert System Control Cabinet)

Application 5377: SMM Unit (Liebert Multi Module Series UPS)

Application 5378: SMS Unit (Liebert Single Module Series UPS S300, S500, W600)

Application 5379: SM3 Unit (Liebert Single Module Series UPS)

Application 5380: SM4 Unit (Liebert Single Module Series UPS)

Application 5381: SSC Unit (Liebert System Control Cabinet)

Application 5382: SSM Unit (Liebert Single Module Series UPS)

Application 5383: THM Unit (Liebert Temperature/Humidity Panel)

Application 5384: US3 Unit (Liebert UPS Station S3)

Application 5385: VCM Unit (Liebert Volt Current Monitoring Panel)

Application 5386: VCF Unit (Liebert Volt Current Frequency Monitoring Panel)

Application 5387: WDU Unit (Liebert Liquid Detection LDS750 or LDS1000)

Application 5388: STS Unit (Liebert Dual Output Breaker Static Switch PDU)

Diagnostic Points

Open Processor Applications


Open Processor applications are an important part of the energy management capabilities of
your system. Open Processor applications are created using Powers Process Control
Language (PPCL) statements and, in some cases, additional hardware to perform specific
operations or functions. The control configuration and control requirements of your system are
customized into each application by using PPCL. The applications that you can incorporate
into the operation of your system depend upon the Liebert equipment controller the Open
Processor interfaces with. For a list of features, refer to the specific Liebert controller on the
following pages.

NOTE: The Open Processor has a maximum of 94 drops. Each application uses more
than one drop. Consult the description of the specific application for complete
information.

CAUTION:
Incorrect point commanding and operation can damage the
devices that are controlled by this Open Processor. Points that can
be commanded for specific devices must not be set to values other
than those recommended by Liebert. Refer to Liebert
documentation for specifics on Liebert equipment controller
operations.

5-2 Siemens Building Technologies, Inc.


Chapter 5 - Applications

CAUTION:
There can be more than one source of control for points in the
Liebert system. Be sure not to command points that are being
commanded by other Liebert equipment controllers.
Also, be sure that the real-times for the Liebert network and the
System 600 APOGEE network are synchronized.

Siemens Building Technologies, Inc. 5-3


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5360: C10 Unit (Liebert Environmental Unit


Australia/Atlas Air)

Introduction
This section contains information specific to C10 Unit controllers used with the Open
Processor. Figure 5-1 diagrams a C10 Unit.

REPOPT OR IC109A SITELINK


GW0443R1

C10

Figure 5-1. Configuration for C10 Unit.

The Liebert C10 unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains control
points.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

C10 Status Drop Metapoint Characteristics


In order to unbundle any of the status points for the Liebert C10 unit, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-4 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-1.
_ Indicates a space.

Table 5-1. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-5


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address:
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for more information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 24 indicates the number of points on the drop.

C10 Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. Table 5-2 shows the status points for the C10 Unit (Application 5360).

Table 5-2. C10 Status Points.


1,2
Point Type Description Range/Units Slope Intercept
00 LAI UNIT NUMBER 1.0 0
01 LAI AVERAGE RETURN AIR F 1.0 0
TEMPERATURE
02 LAI AVERAGE RETURN AIR % 1.0 0
HUMIDITY
03 LAI AVERAGE SUPPLY AIR F 1.0 0
TEMPERATURE
continued on next page...

5-6 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-2. C10 Status Points.


1,2
Point Type Description Range/Units Slope Intercept
04 LAI AVERAGE SUPPLY AIR % 1.0 0
HUMIDITY
05 LAI ACTIVATION MODE 1.0 0
06 LDI FAN STATUS Off/On
07 LDI COOL 1 STATUS Off/On
08 LDI COOL 2 STATUS Off/On
09 LDI HEAT 1 STATUS Off/On
10 LDI HEAT 2 STATUS Off/On
11 LDI HUMIDIFIER STATUS Off/On
12 LDI DE-HUMIDIFIER STATUS Off/On
13 LAI COOLING CAPACITY % 1.0 0
14 LAI HEATING CAPACITY % 1.0 0
15 LAI ACTIVE MODE OPERATION 1.0 0
16 LAI COOL MODE OPERATION 1.0 0
17 LAI HEAT MODE OPERATION 1.0 0
18 LDI TEMPERATURE CONTROL Off/On
STATUS
19 LAI BATTERY VOLTAGE LEVEL Volts 1.0 0
20 LDI REMOTE SHUTDOWN STATUS Off/On
21 LDI GENERAL ALARM STATUS Off/On
22 LDI AUDIBLE ALARM STATUS Off/On
23 LDI TEMPERATURE CONTROL Off/On
SELECT
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

C10 Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop for the Liebert Environmental Unit
Type C10, you must first enter a corresponding point (known as a metapoint) to describe that
drop.

Point Name
Although the name can be anything, it is suggested that you create a meaningful name, so
that you can associate the metapoint with the points on the drop.

Siemens Building Technologies, Inc. 5-7


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
The metapoint must be an LAO point.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must use all uppercase letters in the following
format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-3.
_ Indicates a space.

Table 5-3. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-8 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for more information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of alarm strings (not individual alarm points)
multiplied by 16. Individual alarm points are mapped 0-15 for alarm string 1, 16-31 for alarm
string 2, and 32-47 for alarm string 3.

C10 Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-4 shows the alarm points for Liebert C10 controllers (Application 5360).

Siemens Building Technologies, Inc. 5-9


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-4. C10 Alarm Points (Drop Two).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI FAULTY SENSOR Off/On
02 LDI HIGH TEMPERATURE Off/On
03 LDI LOW TEMPERATURE Off/On
04 LDI HIGH HUMIDITY Off/On
05 LDI LOW HUMIDITY Off/On
06 LDI LOSS OF AIRFLOW Off/On
07 LDI WATER UNDER FLOOR Off/On
08 LDI COOL 1 LOW PRESSURE 1 Off/On
09 LDI COOL 1 LOW PRESSURE 2 Off/On
10 LDI COOL 2 LOW PRESSURE 1 Off/On
2 16 LDI COOL 2 LOW PRESSURE 2 Off/On
17 LDI COOL SERVICE Off/On
18 LDI HUMIDIFIER SERVICE Off/On
19 LDI FILTER SERVICE Off/On
20 LDI HUMIDIFIER WATER LOW Off/On
21 LDI INTERNAL BATTERY LOW Off/On
22 LDI LOSS OF POWER Off/On
23 LDI SPARE 1 Off/On
24 LDI SPARE 2 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

C10 Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop for the C10 Unit, you must first
enter a corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-10 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In mmetadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must use all uppercase letters in the following
format:

xx.H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop.
H Indicates that you are writing to Holding
Registers
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-5.
_ Indicates a space.

Table 5-5. Starting Registers

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Siemens Building Technologies, Inc. 5-11


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 3 indicates the number of points on the drop.

5-12 Siemens Building Technologies, Inc.


Chapter 5 - Applications

C10 Control Points


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-6 shows the control points for Liebert C10 controllers (Application 5360).

Table 5-6. Type C10 Control Points.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO RETURN AIR TEMPERATURE F 1.0 0
SET POINT
01 LAO RETURN AIR HUMIDITY SET % 1.0 0
POINT
02 LAO SUPPLY AIR TEMPERATURE F 1.0 0
SET POINT
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-13


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5361: CCM Unit (Liebert Contact Closure


Modules)
Introduction
This section contains information specific to CCM controllers used with the Open Processor.
Figure 5-2 diagrams a CCM unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0417R1

CCM

Figure 5-2. Configuration for CCM Unit.

The Liebert CCM unit requires one drop to map all point information. The drop contains status
points.

CCM Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the drop (known as a metadrop) for the Liebert
Contact Closure Module Type CCM, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-14 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In mmetadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint is in the following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-7.
_ Indicates a space.

Table 5-7. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Siemens Building Technologies, Inc. 5-15


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 48 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, and from 26 to 32. Point locations 11 through
15 and 25 through 31 contain no significant information.

5-16 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Liebert Contact Closure Modules (CCM) Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-8 shows the point map for Liebert Contact Closure Modules (CCM),
Application 5361.

Table 5-8. CCM Status Points (Drop 1).


1,2
Status Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI CONTACT #1 Off/On
02 LDI CONTACT #2 Off/On
03 LDI CONTACT #3 Off/On
04 LDI CONTACT #4 Off/On
05 LDI CONTACT #5 Off/On
06 LDI CONTACT #6 Off/On
07 LDI CONTACT #7 Off/On
08 LDI CONTACT #8 Off/On
09 LDI CONTACT #9 Off/On
10 LDI CONTACT #10 Off/On
2 16 LDI CONTACT #11 Off/On
17 LDI CONTACT #12 Off/On
18 LDI CONTACT #13 Off/On
19 LDI CONTACT #14 Off/On
20 LDI CONTACT #15 Off/On
21 LDI CONTACT #16 Off/On
22 LDI CONTACT #17 Off/On
23 LDI CONTACT #18 Off/On
24 LDI CONTACT #19 Off/On
25 LDI CONTACT #20 Off/On
26 LDI CONTACT #21 Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-17


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-8. CCM Status Points (Drop 1).


1,2
Status Point Type Descriptor Range/Units
String
3 32 LDI CONTACT #22 Off/On
33 LDI CONTACT #23 Off/On
34 LDI CONTACT #24 Off/On
35 LDI CONTACT #25 Off/On
36 LDI CONTACT #26 Off/On
37 LDI CONTACT #27 Off/On
38 LDI CONTACT #28 Off/On
39 LDI CONTACT #22 Off/On
40 LDI CONTACT #30 Off/On
41 LDI CONTACT #31 Off/On
42 LDI CONTACT #32 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-18 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5362: CSU Unit (Liebert Mainframe Chiller)

Introduction
This section contains information specific to CSU units used with the Open Processor. Figure
5-3 diagrams a CSU unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC108A SITELINK


GW0372R1

CSU

Figure 5-3. Liebert . Mainframe Chiller (CSU).

The CSU unit requires two drops to map all point information. The first drop contains status
information; the second drop contains alarm information.

CSU Unit Status Drop Metapoint Characteristics


In order to unbundle any of the status points for the Liebert Mainframe Chiller Type CSU, you
must first enter a corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-19


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-9.
_ Indicates a space.

Table 5-9. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-20 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address:
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 10 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-21


Open Processor with Liebert Sitelink Driver Owner's Manual

CSU Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-10 shows the status points for Liebert CSU controllers (Application
5362).

Table 5-10. Liebert Mainframe Chiller (CSU).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI NUMBER OF MODULES 1.0 0
01 LDI MODULE 1 START/STOP Stop/Start
02 LDI MODULE 1 PUMP ON/OFF Off/On
03 LDI MODULE 1 COOL ON/OFF Off/On
04 LDI MODULE 2 START/STOP Stop/Start
05 LDI MODULE 2 PUMP ON/OFF Off/On
06 LDI MODULE 2 COOL ON/OFF Off/On
07 LDI MODULE 3 START/STOP Stop/Start
08 LDI MODULE 3 PUMP ON/OFF Off/On
09 LDI MODULE 3 COOL ON/OFF Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

CSU Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop for the Liebert Environmental Unit
Type CSU, you must first enter a corresponding point (known as a metapoint) to describe that
drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-22 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be all uppercase letters in the following
format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-11.
_ Indicates a space.

Table 5-11. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-23


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of alarm strings (not individual alarm points)
multiplied by 16. Individual alarm points are mapped 0 through 15 for alarm string 1, 16
through 31 for alarm string 2, and 32 through 47 for alarm string 3.

5-24 Siemens Building Technologies, Inc.


Chapter 5 - Applications

CSU Alarm Points


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points Table 5-12 shows the alarm points for the Liebert CSU, Application 5362.

Table 5-12. Liebert Mainframe Chiller (CSU). Drop Two.


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI LOCAL ALARM 1 Off/On
02 LDI LOCAL ALARM 2 Off/On
03 LDI MODULE 1 HIGH HEAD PRESSURE Off/On
04 LDI MODULE 2 HIGH HEAD PRESSURE Off/On
05 LDI MODULE 3 HIGH HEAD PRESSURE Off/On
06 LDI MODULE 1 NO WATER FLOW Off/On
07 LDI MODULE 2 NO WATER FLOW Off/On
08 LDI MODULE 3 NO WATER FLOW Off/On
09 LDI MODULE 1 HIGH WATER TEMPERATURE Off/On
10 LDI MODULE 2 HIGH WATER TEMPERATURE Off/On
2 16 LDI MODULE 3 HIGH WATER TEMPERATURE Off/On
17 LDI MODULE 1 LOW WATER TEMPERATURE Off/On
18 LDI MODULE 2 LOW WATER TEMPERATURE Off/On
19 LDI MODULE 3 LOW WATER TEMPERATURE Off/On
20 LDI MODULE 1 NO POWER OTHER MOD Off/On
21 LDI MODULE 2 NO POWER OTHER MOD Off/On
22 LDI MODULE 3 NO POWER OTHER MOD Off/On
23 LDI MODULE 1 LIQUID DETECTED Off/On
24 LDI MODULE 2 LIQUID DETECTED Off/On
25 LDI MODULE 3 LIQUID DETECTED Off/On
26 LDI NONE Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-25


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5363: CSE Unit (Liebert Mainframe Chiller


with Econocoil)

Introduction

This section contains information specific to CSE units used with the Open Processor. Figure
5-4 diagrams a CSE unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0418R1

CSE

Figure 5-4. Liebert Mainframe Chiller with Econocoil (CSE).

The CSE unit requires two drops to map all point information. The first drop contains status
information; the second drop contains alarm information.

CSE Unit Status Drop Metapoint Characteristics


In order to unbundle any of the status points for the Liebert Mainframe Chiller with Econocoil
Type CSE, you must first enter a corresponding point (known as a metapoint) to describe that
drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-26 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-13.
_ Indicates a space.

Table 5-13. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Siemens Building Technologies, Inc. 5-27


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 14 indicates the number of points on the drop.

5-28 Siemens Building Technologies, Inc.


Chapter 5 - Applications

CSE Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database Chapter for more information on LAN and Drop
numbers for these points. Table 5-14 shows the Status Points for the Mainframe Chiller with
Econocoil (CSE), Application 5363.

Table 5-14. Mainframe Chiller with Econocoil (CSE).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LDI SYSTEM OF ECONOCYCLE Off/On
01 LAI NUMBER OF MODULES 1-3 1.0 0
02 LDI MODULE 1 START/STOP Stop/Start
03 LDI MODULE 1 PUMP ON/OFF Off/On
04 LDI MODULE 1 COOL ON/OFF Off/On
05 LDI MODULE 2 START/STOP Stop/Start
06 LDI MODULE 2 PUMP ON/OFF Off/On
07 LDI MODULE 2 COOL ON/OFF Off/On
08 LDI MODULE 3 START/STOP Stop/Start
09 LDI MODULE 3 PUMP ON/OFF Off/On
10 LDI MODULE 3 COOL ON/OFF Off/On
11 LDI MODULE 1 ECONOCYCLE Off/On
ON/OFF
12 LDI MODULE 2 ECONOCYCLE Off/On
ON/OFF
13 LDI MODULE 3 ECONOCYCLE Off/On
ON/OFF
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

CSE Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Mainframe Chiller with Econocoil Type CSE, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-29


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-15.
_ Indicates a space.

Table 5-15. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-30 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database Chapter further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 through 15 contain no
significant information.

Siemens Building Technologies, Inc. 5-31


Open Processor with Liebert Sitelink Driver Owner's Manual

CSE Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-16 shows the Alarm points for the Mainframe Chiller with Econocoil
(CSE), Application 5363.

Table 5-16. Mainframe Chiller with Econocoil (CSE).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI LOCAL ALARM 1 Off/On
02 LDI LOCAL ALARM 2 Off/On
03 LDI MODULE 1 HIGH HEAD PRESSURE Off/On
04 LDI MODULE 2 HIGH HEAD PRESSURE Off/On
05 LDI MODULE 3 HIGH HEAD PRESSURE Off/On
06 LDI MODULE 1 NO WATER FLOW Off/On
07 LDI MODULE 2 NO WATER FLOW Off/On
08 LDI MODULE 3 NO WATER FLOW Off/On
09 LDI MODULE 1 HIGH WATER TEMPERATURE Off/On
10 LDI MODULE 2 HIGH WATER TEMPERATURE Off/On
2 16 LDI MODULE 3 HIGH WATER TEMPERATURE Off/On
17 LDI MODULE 1 LOW WATER TEMPERATURE Off/On
18 LDI MODULE 2 LOW WATER TEMPERATURE Off/On
19 LDI MODULE 3 LOW WATER TEMPERATURE Off/On
20 LDI MODULE 1 NO POWER OTHER MOD Off/On
21 LDI MODULE 2 NO POWER OTHER MOD Off/On
22 LDI MODULE 3 NO POWER OTHER MOD Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-32 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5364: EDS Unit (Liebert Static Switch


PDU)

Introduction
This section contains information specific to EDS units used with the Open Processor. Figure
5-5 diagrams an EDS unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0419R1

EDS

Figure 5-5. Liebert Static Switch PDU (EDS).

The Liebert EDS unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

EDS Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Static Switch PDU Type EDS, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-33


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-17.
_ Indicates a space.

Table 5-17. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-34 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 24 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-35


Open Processor with Liebert Sitelink Driver Owner's Manual

EDS Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-18 shows the Status points for the Liebert Static Switch PDU (EDS),
Application 5364.

Table 5-18. Liebert Static Switch PDU (EDS).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TRANSFER COUNT 1.0 0
01 LAI PREFERRED SOURCE 1 = Source 1 1.0 0
0 = Source 2
02 LAI LOAD ON SOURCE 1 OR 2 1 = Source 1 1.0 0
2 = Source 2
03 LAI SOURCE 1 VOLTS A-B Volts 1.0 0
04 LAI SOURCE 1 VOLTS B-C Volts 1.0 0
05 LAI SOURCE 1 VOLTS C-A Volts 1.0 0
06 LAI SOURCE 1 AMPS A Amps 1.0 0
07 AI SOURCE 1 AMPS B Amps 1.0 0
08 LAI SOURCE 1 AMPS C Amps 1.0 0
09 LAI SOURCE 1 FREQUENCY Hz 0.1 0
10 LAI SOURCE 2 VOLTS A-B Volts 1.0 0
11 LAI SOURCE 2 VOLTS B-C Volts 1.0 0
12 LAI SOURCE 2 VOLTS C-A Volts 1.0 0
13 LAI SOURCE 2 AMPS A Amps 1.0 0
14 LAI SOURCE 2 AMPS B Amps 1.0 0
15 LAI SOURCE 2 AMPS C Amps 1.0 0
16 LAI SOURCE 2 FREQUENCY Hz 0.1 0
17 LAI KVA KVA 1.0 0
18 LAI KW KW 1.0 0
19 LAI AUTO TRANSFER TIME 1.0 0
20 LAI NOMINAL VOLTAGE DEVIATION Volts 1.0 0
21 LAI PHASE DIFFERENCE LIMIT 1.0 0
22 LAI FREQUENCY DEVIATION Hz 0.1 0
23 LDI DISABLED/ENABLED Disabled/Enabled
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-36 Siemens Building Technologies, Inc.


Chapter 5 - Applications

EDS Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Static Switch PDU Type EDS, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-19.
_ Indicates a space.

Table 5-19. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
continued on next page...

Siemens Building Technologies, Inc. 5-37


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-19. Starting Registers.

Port Number Starting Register (yyy)


4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

5-38 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Initial Value

The initial value of 64 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, from 26 to 32, and from 42 to 48. Point
locations 11 through 15, 27 through 31, and 43 through 48 contain no significant information.
Refer to the Point Database Guidelines section in Chapter 4 - Point Database for more
information.

EDS Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-20 shows the alarm points for the Liebert Static Switch PDU (EDS),
Application 5364.

Table 5-20. Liebert Static Switch PDU (EDS).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATION Off/On
01 LDI LOGIC FAILURE Off/On
02 LDI EQUIPMENT OVERTEMPERATURE Off/On
03 LDI POWER SUPPLY 1 FAULT Off/On
04 LDI SOURCE 1 OVERVOLTAGE Off/On
05 LDI SOURCE 1 UNDERVOLTAGE Off/On
06 LDI SOURCE 2 OVERVOLTAGE Off/On
07 LDI SOURCE 2 UNDERVOLTAGE Off/On
08 LDI SOURCE 1 OVERLOAD Off/On
09 LDI SHORTED SCR 1 Off/On
10 LDI SHORTED SCR 2 Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-39


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-20. Liebert Static Switch PDU (EDS).


1,2
Alarm Point Type Descriptor Range/Units
String
2 16 LDI OPEN SCR 1 Off/On
17 LDI OPEN SCR 2 Off/On
18 LDI FAN FAILURE Off/On
19 LDI SOURCE 2 OVERLOAD Off/On
20 LDI POWER SUPPLY 2 FAULT Off/On
21 LDI FREQUENCY DEVIATION Off/On
22 LDI TRANSFER INHIBIT Off/On
23 LDI AUTO RE-TRANSFER PRIMED Off/On
24 LDI OUT OF SYNC Off/On
25 LDI SOURCE 1 FAILURE Off/On
26 LDI SOURCE 2 FAILURE Off/On
3 32 LDI RE-TRANSFER FAILURE Off/On
33 LDI OVERLOAD Off/On
34 LDI CONTROL FUSE 1 BLOWN Off/On
35 LDI CONTROL FUSE 2 BLOWN Off/On
36 LDI SOURCE 1 CB 1 OPEN Off/On
37 LDI SOURCE 2 CB 2 OPEN Off/On
38 LDI OUTPUT CB 3 OPEN Off/On
39 LDI CUSTOM ALARM 1 Off/On
40 LDI CUSTOM ALARM 2 Off/On
41 LDI BYPASS CB4 CLOSED Off/On
42 LDI BYPASS CB5 CLOSED Off/On
4 48 LDI CUSTOM ALARM 3 Off/On
49 LDI CUSTOM ALARM 4 Off/On
50 LDI CUSTOM ALARM 5 Off/On
51 LDI CUSTOM ALARM 6 Off/On
52 LDI CUSTOM ALARM 7 Off/On
53 LDI CUSTOM ALARM 8 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-40 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5365: L00 Unit (Liebert Environmental


UnitsLevels 0 and 1)

Introduction
This section contains information specific to L00 units used with the Open Processor. Figure
5-6 diagrams an L00 unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0420R1

ENV UNIT

Figure 5-6. Liebert Environmental UnitsLevels 0 and 1 (L00).

The Liebert L00 unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains control
points.

L00 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Environmental Units, Levels 0 and 1 Type L00, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-41


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-21.
_ Indicates a space.

Table 5-21. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-42 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 13 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-43


Open Processor with Liebert Sitelink Driver Owner's Manual

L00 Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-22 shows the status points for the Liebert Environmental Units, Levels 0
and 1 (L00), Application 5365.

Table 5-22. Liebert Environmental UnitsLevels 0 and 1 (L00).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TEMPERATURE F 1.0 0
01 LAI HUMIDITY % 1.0 0
02 LDI COOLING Off/On
03 LDI HEATING Off/On
04 LDI HUMIDIFICATION Off/On
05 LDI DEHUMIDIFICATION Off/On
06 LDI ECON-O-CYCLE Off/On
07 LAI STAGES Number of stages 1.0 0
08 LAI CAPACITY % 1.0 0
09 LAI TEMPERATURE SET POINT F 1.0 0
STATUS
10 LAI TEMPERATURE TOLERANCE F 1.0 0
11 LAI HUMIDITY SET POINT STATUS % 1.0 0
12 LAI HUMIDITY TOLERANCE % 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

L00 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Environmental Units, Levels 0 and 1 Type L00, you must first enter a corresponding
point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-44 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-23.
_ Indicates a space.

Table 5-23. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Siemens Building Technologies, Inc. 5-45


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of points on the drop, rounded up to the nearest
multiple of 16

5-46 Siemens Building Technologies, Inc.


Chapter 5 - Applications

L00 Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-24 shows the Alarm Points for the Liebert Environmental Units, Levels 0
and 1 (L00), Application 5365.

Table 5-24. Liebert Environmental UnitsLevels 0 and 1 (L00).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI HIGH HEAD PRESSURE 1 Off/On
02 LDI HIGH HEAD PRESSURE 2 Off/On
03 LDI LOSS OF AIRFLOW Off/On
04 LDI LIQUID DETECTED Off/On
05 LDI CHANGE FILTERS Off/On
06 LDI HIGH TEMPERATURE Off/On
07 LDI LOW TEMPERATURE Off/On
08 LDI HIGH HUMIDITY Off/On
09 LDI LOW HUMIDITY Off/On
10 LDI CUSTOM ALARM 1 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

L00 Unit Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert Environmental Units, Levels 0 and 1 Type L00, you must first enter a corresponding
point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-47


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop
H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-25.
_ Indicates a space.

Table 5-25. Starting Registers.

Port Number Starting Register (yyy)


1 350
2 353
3 356
4 359
5 362
6 365
7 368
8 371
9 374
10 377
11 380
12 383

Alarmable
All metapoints are not alarmable.

5-48 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 2 indicates the number of points on the drop.

L00 Control Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database more information on LAN and Drop numbers for these
points. Table 5-26 shows the Control Points for Liebert Environmental UnitsLevels 0 and 1
(L00), Application 5365.

Table 5-26. Liebert Environmental UnitsLevels 0 and 1 (L00).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO TEMPERATURE SET POINT F 1.0 0
CONTROL
01 LAO HUMIDITY SET POINT % 1.0 0
CONTROL
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-49


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5366: L0B Unit (Liebert Environmental


Units Small Systems)

Introduction
This section contains information specific to LOB units used with the Open Processor. Figure
5-7 diagrams an L0B unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0421R1

LOB

Figure 5-7. Liebert Environmental Units Small Systems (L0B).

The Liebert LOB unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains
command points.

L0B Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Environmental Units for Small Systems Type L0B, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-50 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-27.
_ Indicates a space.

Table 5-27. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Siemens Building Technologies, Inc. 5-51


Open Processor with Liebert Sitelink Driver Owner's Manual

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 11 indicates the number of points on the drop.

5-52 Siemens Building Technologies, Inc.


Chapter 5 - Applications

L0B Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-28 shows the Status Points for Liebert Environmental Units Small
Systems (L0B), Application 5366.

Table 5-28. Liebert Environmental Units Small Systems (L0B).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TEMPERATURE F 1.0 0
01 LAI HUMIDITY % 1.0 0
02 LDI COOLING Off/On
03 LDI HEATING Off/On
04 LDI HUMIDIFICATION Off/On
05 LDI DEHUMIDIFICATION Off/On
06 LDI ECON-O-CYCLE Off/On
07 LAI STAGES 1.0 0
08 LAI CAPACITY % 1.0 0
09 LAI TEMPERATURE SCALE 1.0 0
10 LDI UNIT STATUS ON/OFF Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

L0B Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Environmental Units for Small Systems Type L0B, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-53


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-29.
_ Indicates a space.

Table 5-29. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-54 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of points on the drop rounded up to the nearest
multiple of 16.

Siemens Building Technologies, Inc. 5-55


Open Processor with Liebert Sitelink Driver Owner's Manual

L0B Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-30 shows the Alarm Points for the Liebert Environmental Units Small
Systems (L0B), Application 5366.

Table 5-30. Liebert Environmental Units Small Systems (L0B).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATION Off/On
01 LDI LOCAL OFF Off/On
02 LDI REMOTE OFF Off/On
03 LDI HIGH TEMPERATURE Off/On
04 LDI LOW TEMPERATURE Off/On
05 LDI HIGH HUMIDITY Off/On
06 LDI LOW HUMIDITY Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

L0B Unit Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert Environmental Units for Small Systems Type L0B, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-56 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop
H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-31.
_ Indicates a space.

Table 5-31. Starting Registers

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-57


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 1 indicates the number of points on the drop.

L0B Command Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-32 shows command points for Liebert Environmental Units Small
Systems (L0B), Application 5366.

Table 5-32. Liebert Environmental Units Small Systems (L0B).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO REMOTE ON/OFF CONTROL 2 = On, 1.0 0
1 = Off
0 = No Change
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-58 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5367: L02, L03, L10 Unit (Liebert


Environmental UnitLevels 2, 3, and 10)

Introduction
This section contains information specific to L02, L03, L10 units used with the Open
Processor. Figure 5-8 diagrams an L02, L03, L10 unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0420R1

ENV UNIT

Figure 5-8. Liebert Environmental UnitLevels 2, 3, and 10 (L10).

The Liebert L02, L03, L10 unit requires three drops to map all point information. The first drop
contains status information; the second drop contains alarm information; the third drop
contains control points.

L02, L03, L10 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Environmental Units, Levels 2, 3, and 10 Type L10, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-59


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-33.
_ Indicates a space.

Table 5-33. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

5-60 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database Chapter for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 13 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-61


Open Processor with Liebert Sitelink Driver Owner's Manual

L02, L03, L10 Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-34 shows the status points for Liebert Environmental UnitLevels 2, 3,
and 10 (L10), Application 5367.

Table 5-34. Liebert Environmental UnitLevels 2, 3, and 10 (L10) Point Map


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TEMPERATURE F 1.0 0
01 LAI HUMIDITY % 1.0 0
02 LDI COOLING ON Off/On
03 LDI HEATING ON Off/On
04 LDI HUMIDIFICATION ON Off/On
05 LDI DEHUMIDIFICATION ON Off/On
06 LDI ECON-O-CYCLE ON Off/On
07 LAI STAGES Number of stages 1.0 0
08 LAI CAPACITY % 1.0 0
09 LAI TEMPERATURE SET POINT F 1.0 0
10 LAI TEMPERATURE TOLERANCE F 0.1 0
11 LAI HUMIDITY SET POINT % 1.0 0
12 LAI HUMIDITY TOLERANCE % 0.1 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

L02, L03, L10 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Environmental Units Levels 2, 3, and 10 Type L10, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-62 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-35.
_ Indicates a space.

Table 5-35. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Siemens Building Technologies, Inc. 5-63


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 48 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16 and from 26 to 32. Point locations 11 - 15 and
27 - 31 contain no significant information.

5-64 Siemens Building Technologies, Inc.


Chapter 5 - Applications

L02, L03, L10 Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-36 shows the Alarm Points for the Liebert Environmental UnitLevels
2, 3, and 10 (L10), Application 5367.

Table 5-36. Liebert Environmental UnitLevels 2, 3, and 10 (L10) Point Map.


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATION Off/On
01 LDI HIGH HEAD PRESSURE 1 Off/On
02 LDI HIGH HEAD PRESSURE 2 Off/On
03 LDI LOSS OF AIRFLOW Off/On
04 LDI STANDBY GLYCOOL UNIT ON Off/On
05 LDI LIQUID DETECTED Off/On
06 LDI CHANGE FILTERS Off/On
07 LDI HIGH TEMPERATURE Off/On
08 LDI LOW TEMPERATURE Off/On
09 LDI HIGH HUMIDITY Off/On
10 LDI LOW HUMIDITY Off/On
2 16 LDI HUMIDIFIER PROBLEM Off/On
17 LDI NO WATER HUMIDIFIER PAN Off/On
18 LDI COMPRESSOR 1 OVERLOAD Off/On
19 LDI COMPRESSOR 2 OVERLOAD Off/On
20 LDI MAIN FAN OVERLOAD Off/On
21 LDI MANUAL OVERRIDE Off/On
22 LDI SMOKE DETECTED Off/On
23 LDI LOSS OF WATER Off/On
24 LDI STANDBY UNIT ON Off/On
25 LDI LOW SUCTION PRESSURE Off/On
26 LDI SHORT CYCLE Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-65


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-36. Liebert Environmental UnitLevels 2, 3, and 10 (L10) Point Map.


1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI LOSS OF POWER Off/On
33 LDI INVERTER ON BYPASS Off/On
34 LDI STANDBY FAN ON Off/On
35 LDI EMERGENCY POWER OFF Off/On
36 LDI LOCAL ALARM 1 Off/On
37 LDI LOCAL ALARM 2 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

L02, L03, L10 Unit Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert Environmental Units, Levels 2, 3, and 10 Type L10, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-66 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. indicates this will be a write-only drop.
H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-37.
_ Indicates a space.

Table 5-37. Starting Registers

Port Number Starting Register (yyy)


1 350
2 353
3 356
4 359
5 362
6 365
7 368
8 371
9 374
10 377
11 380
12 383

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-67


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 2 indicates the number of points on the drop.

L02, L03, L10 Control Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-38 shows the Control Points for the Liebert Environmental UnitLevels
2, 3, and 10 (L10) Point Map, Application 5367.

Table 5-38. Liebert Environmental UnitLevels 2, 3, and 10 (L10) Point Map.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO TEMPERATURE SET POINT F 1.0 0
CONTROL
01 LAO HUMIDITY SET POINT % 1.0 0
CONTROL
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-68 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5368: Liebert Environmental UnitLevel


15 with On/Off Control (LAM)

Introduction
This section contains information specific to LAM controllers used with the Open Processor.
Figure 5-9 diagrams a LAM unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0423R1

LAM

Figure 5-9. Liebert Environmental UnitLevel 15 with On/Off control (LAM).

The Liebert LAM unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains
command points.

LAM Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Environmental Unit, Level 15, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-69


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-39.
_ Indicates a space.

Table 5-39. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

5-70 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 18 indicates the number of points on the drop.

LAM Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-40 Shows the status points for the Liebert Environmental UnitLevel 15
with On/Off control (LAM), Application 5368.

Siemens Building Technologies, Inc. 5-71


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-40. Liebert Environmental UnitLevel 15 with On/Off control (LAM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TEMPERATURE F 1.0 0
01 LAI HUMIDITY % 1.0 0
02 LDI COOLING Off/On
03 LDI HEATING Off/On
04 LDI HUMIDIFICATION Off/On
05 LDI DEHUMIDIFICATION Off/On
06 LDI ECON-O-CYCLE Off/On
07 LAI STAGES Number of stages 1.0 0
08 LAI CAPACITY % 1.0 0
09 LAI TEMPERATURE SET POINT F 1.0 0
10 LAI TEMPERATURE TOLERANCE F 0.1 0
11 LAI HUMIDITY SET POINT % 1.0 0
12 LAI HUMIDITY TOLERANCE % 0.1 0
13 LAI HIGH TEMPERATURE SET F 1.0 0
POINT
14 LAI LOW TEMPERATURE SET F 1.0 0
POINT
15 LAI HIGH HUMIDITY SET POINT % 1.0 0
16 LAI LOW HUMIDITY SET POINT % 1.0 0
17 LDI UNIT STATUS ON/OFF Off/On
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

LAM Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Environmental Unit Level 15, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-72 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-41.
_ Indicates a space.

Table 5-41. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Siemens Building Technologies, Inc. 5-73


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 48 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16 and from 26 to 32. Point locations 11 - 15 and
27 - 31 contain no significant information.

5-74 Siemens Building Technologies, Inc.


Chapter 5 - Applications

LAM Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-42 shows the Alarm Points for the Liebert Environmental Unit Level
15 with On/Off control (LAM) Point Map, Application 5368.

Table 5-42. Liebert Environmental UnitLevel 15 with On/Off control (LAM) Point Map.
1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATION Off/On
01 LDI LOCAL OFF Off/On
02 LDI REMOTE OFF Off/On
03 LDI HIGH HEAD PRESSURE 1 Off/On
04 LDI HIGH HEAD PRESSURE 2 Off/On
05 LDI LOSS OF AIRFLOW Off/On
06 LDI STANDBY GLYCOOL UNIT ON Off/On
07 LDI LIQUID DETECTED Off/On
08 LDI CHANGE FILTERS Off/On
09 LDI HIGH TEMPERATURE Off/On
10 LDI LOW TEMPERATURE Off/On
2 16 LDI HIGH HUMIDITY Off/On
17 LDI LOW HUMIDITY Off/On
18 LDI HUMIDIFIER PROBLEM Off/On
19 LDI NO WATER IN HUMIDIFIER PAN Off/On
20 LDI COMPRESSOR 1 OERLOAD Off/On
21 LDI COMPRESSOR 2 OVERLOAD Off/On
22 LDI MAIN FAN OVERLOAD Off/On
23 LDI MANUAL OVERRIDE Off/On
24 LDI SMOKE DETECTED Off/On
25 LDI LOSS OF WATER Off/On
26 LDI STANDBY UNIT ON Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-75


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-42. Liebert Environmental UnitLevel 15 with On/Off control (LAM) Point Map.
1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI LOW SUCTION PRESSURE Off/On
33 LDI SHORT CYCLE Off/On
34 LDI LOSS OF POWER Off/On
35 LDI INVERTER ON BYPASS Off/On
36 LDI STANDBY FAN ON Off/On
37 LDI LOSS OF EMERGENCY POWER Off/On
38 LDI LOCAL ALARM 1 Off/On
39 LDI LOCAL ALARM 2 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

LAM Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop for the Environmental Unittype
LAM, you must first enter a corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

5-76 Siemens Building Technologies, Inc.


Chapter 5 - Applications

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. indicates this will be a write-only drop.
H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-43.
_ Indicates a space.

Table 5-43. Starting Registers

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Siemens Building Technologies, Inc. 5-77


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 3 indicates the number of points on the drop.

LAM Command Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-44 shows the command points for the Environmental UnitLevel 15
with On Off control (LAM), Application 5368.

Table 5-44. Environmental UnitLevel 15 with On/Off control (LAM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO REMOTE ON/OFF CONTROL 2 = On 1.0 0
1 = Off
0 = No Change
01 LAO TEMPERATURE SET POINT F 1.0 0
CONTROL
02 LAO HUMIDITY SET POINT % 1.0 0
CONTROL
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-78 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5369: LSM Unit (Liebert Environmental


UnitLevels SM and O with On/Off control)

Introduction
This section contains information specific to LSM controllers used with the Open Processor.
Figure 5-10 diagrams an LSM.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0424R1

LSM

Figure 5-10. Liebert Environmental UnitLevels SM and O with On/Off control (LSM).

The Liebert LSM unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains
command points.

LSM Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Environmental Unit, Levels SM and 0 with On/Off Control Type LSM, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-79


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-45.
_ Indicates a space.

Table 5-45. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-80 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 14 indicates the number of points on the drop.

LSM Status Point Map


Table 5-46 shows the status points for the Liebert Environmental Unit, type LSM. Once the
metapoint is unbundled, any of the following points may be unbundled on that drop. See
Chapter 4 - Point Database for more information on LAN and Drop numbers for these points,
Application 5369.

Siemens Building Technologies, Inc. 5-81


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-46. Liebert Environmental UnitLevels SM and O with On/Off control (LSM).
1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TEMPERATURE F 1.0 0
01 LAI HUMIDITY % 1.0 0
02 LDI COOLING Off/On 1.0 0
03 LDI HEATING Off/On 1.0 0
04 LDI HUMIDIFICATION Off/On 1.0 0
05 LDI DEHUMIDIFICATION Off/On 1.0 0
06 LDI ECON-O-CYCLE Off/On 1.0 0
07 LAI STAGES Number of Stages 1.0 0
08 LAI CAPACITY % 1.0 0
09 LAI TEMPERATURE SET POINT F 1.0 0
10 LAI TEMPERATURE TOLERANCE F 1.0 0
11 LAI HUMIDITY SET POINT % 1.0 0
12 LAI HUMIDITY TOLERANCE % 1.0 0
13 LDI UNIT STATUS ON/OFF Off/On 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

LSM Unit Alarm Drop Metapoint Characteristic


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Environmental Units, Levels SM and 0 with On/Off Control Type LSM, you must first
enter a corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-82 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-47.
_ Indicates a space.

Table 5-47. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-83


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 - 15 contain no significant
information.

5-84 Siemens Building Technologies, Inc.


Chapter 5 - Applications

LSM Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-48 shows alarm points for the Liebert Environmental Unit LSM,
Application 5369.

Table 5-48. Liebert Environmental UnitLevels SM and O with On/Off control (LSM).
1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI UNIT TURNED OFF LOCALLY Off/On
02 LDI UNIT TURNED OFF REMOTELY Off/On
03 LDI HIGH HEAD PRESSURE 1 Off/On
04 LDI HIGH HEAD PRESSURE 2 Off/On
05 LDI LOSS OF AIRFLOW Off/On
06 LDI LIQUID DETECTED Off/On
07 LDI CHANGE FILTERS Off/On
08 LDI HIGH TEMPERATURE Off/On
09 LDI LOW TEMPERATURE Off/On
10 LDI HIGH HUMIDITY Off/On
2 16 LDI LOW HUMIDITY Off/On
17 LDI CUSTOM ALARM 1 Off/On
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

LSM Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert Environmental Units, Levels SM and 0 with On/Off Control Type LSM, you must first
enter a corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-85


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop.
H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-49.
_ Indicates a space.

Table 5-49. Starting Registers

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Alarmable
All metapoints are not alarmable.

5-86 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 3 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-87


Open Processor with Liebert Sitelink Driver Owner's Manual

LAM Command Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-50 shows the command points for the Liebert Environmental Unit, type
LAM, Application 5369.

Table 5-50. Liebert Environmental UnitLevel 15 with On/Off control (LAM)


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO REMOTE ON/OFF CONTROL 2 = On 1.0 0
1 = Off
0 = No Change
01 LAO TEMPERATURE SET POINT F 1.0 0
CONTROL
02 LAO HUMIDITY SET POINT % 1.0 0
CONTROL
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-88 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5370: MM4 Unit (Liebert Multi Module


Series UPS)

Introduction
This section contains information specific to MM4 controllers used with the Open Processor.
Figure 5-11 diagrams an MM4.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0426R1

MM4

Figure 5-11. Liebert Multi Module Series UPS (MM4).

The Liebert MM4 unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

MM4 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Multi Module Series UPS Type MM4, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-89


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-51.
_ Indicates a space.

Table 5-51. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-90 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-91


Open Processor with Liebert Sitelink Driver Owner's Manual

MM4 Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-52 shows the status points for the Liebert Multi Module Series UPS
(MM4), Application 5370.

Table 5-52. Liebert Multi Module Series UPS (MM4).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-B Volts 1.0 0
01 LAI INPUT VOLTS B-C Volts 1.0 0
02 LAI INPUT VOLTS C-A Volts 1.0 0
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
09 LAI DC BUS VOLTAGE Volts 1.0 0
10 LAI BATTERY CURRENT Amps 1.0 0
11 LAI KVA KVA 1.0 0
12 LAI KW KW 1.0 0
13 LAI CRITICAL BUS FREQUENCY Hz 0.1 0
14 LAI CAPACITY PHASE A % 1.0 0
15 LAI CAPACITY PHASE B % 1.0 0
16 LAI CAPACITY PHASE C % 1.0 0
17 LAI INPUT AMPS PHASE A Amps 1.0 0
18 LAI INPUT AMPS PHASE B Amps 1.0 0
19 LAI INPUT AMPS PHASE C Amps 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-92 Siemens Building Technologies, Inc.


Chapter 5 - Applications

MM4 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Multi Module Series UPS Type MM4, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-53.
_ Indicates a space.

Table 5-53. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
continued on next page...

Siemens Building Technologies, Inc. 5-93


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-53. Starting Registers

Port Number Starting Register (yyy)


4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

5-94 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Initial Value

The initial value of 48 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16 and 26 to 32. Point locations 11 15 and 27
31 contain no significant information.

MM4 Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-54 shows alarm points for the Liebert Multi Module Series UPS (MM4),
Application 5370.

Table 5-54. Liebert Multi Module Series UPS (MM4).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BATTERY DISCHARGE Off/On
02 LDI INPUT FAILURE Off/On
03 LDI HARDWARE SHUTDOWN Off/On
04 LDI DC GROUND FAULT Off/On
05 LDI INPUT CB OPEN Off/On
06 LDI OUTPUT CB OPEN Off/On
07 LDI DC CAP FUSE BLOWN Off/On
08 LDI LOW BATTERY RESERVE Off/On
09 LDI OUTPUT OVERLOAD Off/On
10 LDI RECTIFIER FUSE BLOWN Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-95


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-54. Liebert Multi Module Series UPS (MM4).


1,2
Alarm Point Type Descriptor Range/Units
String
2 16 LDI EMERGENCY POWER OFF Off/On
17 LDI AMBIENT OVERTEMPERATURE Off/On
18 LDI BATTERY DISCONNECTED Off/On
19 LDI CONTROL POWER FAILURE Off/On
20 LDI OVERLOAD SHUTDOWN Off/On
21 LDI INVERTER FAULT Off/On
22 LDI INPUT CURRENT UNBALANCE Off/On
23 LDI INVERTER OUT OF SYNC Off/On
24 LDI REVERSE POWER Off/On
25 LDI LOW BATTERY SHUTDOWN Off/On
26 LDI DC OVERVOLTAGE SHUTDOWN Off/On
3 32 LDI BATTERY CYCLE BUFFER FULL Off/On
33 LDI EQUIPMENT Off/On
OVERTEMPERATURE
34 LDI BLOWER/FAN FAILURE Off/On
35 LDI OVERTEMPERATURE Off/On
SHUTDOWN
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-96 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5371: MMS Unit (Liebert Multi Module


Series UPS)

Introduction
This section contains information specific to MMS controllers used with the Open Processor.
Figure 5-12 diagrams a Liebert Multi Module Series UPS (MMS).

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0425R1

MMS

Figure 5-12. Liebert Multi Module Series UPS (MMS).

The Liebert MMS unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

MMS Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Multi Module Series UPS Type MMS, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

The point should have the following characteristics:

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-97


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-55.
_ Indicates a space.

Table 5-55. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

5-98 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-99


Open Processor with Liebert Sitelink Driver Owner's Manual

MMS Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-56 shows status points for the Liebert Multi Module Series UPS (MMS),
Application 5371.

Table 5-56. Liebert Multi Module Series UPS (MMS).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-B Volts 1.0 0
01 LAI INPUT VOLTS B-C Volts 1.0 0
02 LAI INPUT VOLTS C-A Volts 1.0 0
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT VOLTS A-N Volts 1.0 0
07 LAI OUTPUT VOLTS B-N Volts 1.0 0
08 LAI OUTPUT VOLTS C-N Volts 1.0 0
09 LAI OUTPUT AMPS PHASE A Amps 1.0 0
10 LAI OUTPUT AMPS PHASE B Amps 1.0 0
11 LAI OUTPUT AMPS PHASE C Amps 1.0 0
12 LAI DC BUS VOLTAGE Volts 1.0 0
13 LAI BATTERY CURRENT Amps 1.0 0
14 LAI KVA KVA 1.0 0
15 LAI KW KW 1.0 0
16 LAI OUTPUT FREQUENCY Hz 0.1 0
17 LAI CAPACITY PHASE A % 1.0 0
18 LAI CAPACITY PHASE B % 1.0 0
19 LAI CAPACITY PHASE C % 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-100 Siemens Building Technologies, Inc.


Chapter 5 - Applications

MMS Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Multi Module Series UPS Type MMS, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-57.
_ Indicates a space.

Siemens Building Technologies, Inc. 5-101


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-57. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

5-102 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of points on the drop, rounded up to the nearest
multiple of 16.

MMS Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-58 shows alarm points for the Liebert Multi Module Series UPS (MMS),
Application 5371.

Table 5-58. Liebert Multi Module Series UPS (MMS).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BATTERY DISCHARGE Off/On
02 LDI LOW BATTERY RESERVE Off/On
03 LDI OUTPUT OVERLOAD Off/On
04 LDI FUSE CLEARED Off/On
05 LDI AMBIENT OVERTEMPERATURE Off/On
06 LDI BATTERY GROUNDED Off/On
07 LDI BATTERY DISCONNECTED Off/On
08 LDI MODULE COOLING Off/On
09 LDI CONTROL POWER FAILURE Off/On
10 LDI OVERLOAD SHUTDOWN Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-103


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5372: MOR Unit (Liebert RCM 10U)

Introduction
This section contains information specific to MOR units used with the Open Processor. Figure
5-13 diagrams an MOR unit.

A Port Allocation Chart must be obtained from the local Liebert representative in order to
create the point database.

REPOPT OR IC109A SITELINK


GW0427R1

MOR

Figure 5-13. Liebert RCM 10U (MOR).

The Liebert MOR unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

MOR Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
RCM 10U Type MOR, you must first enter a corresponding point (known as a metapoint) to
describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-104 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-59.
_ Indicates a space.

Table 5-59. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-105


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

5-106 Siemens Building Technologies, Inc.


Chapter 5 - Applications

MOR Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-60 shows status points for the Liebert RCM 10U (MOR), Application
5372.

Table 5-60. Liebert RCM 10U (MOR).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI ANALOG 1 1.0 0
01 LDI DIGITAL 1 Off/On
02 LAI ANALOG 2 1.0 0
03 LDI DIGITAL 2 Off/On
04 LAI ANALOG 3 1.0 0
05 LDI DIGITAL 3 Off/On
06 LAI ANALOG 4 1.0 0
07 LDI DIGITAL 4 Off/On
08 LAI ANALOG 5 1.0 0
09 LDI DIGITAL 5 Off/On
10 LAI ANALOG 6 1.0 0
11 LDI DIGITAL 6 Off/On
12 LAI ANALOG 7 1.0 0
13 LDI DIGITAL 7 Off/On
14 LAI ANALOG 8 1.0 0
15 LDI DIGITAL 8 Off/On
16 LAI ANALOG 9 1.0 0
17 LDI DIGITAL 9 Off/On
18 LAI ANALOG 10 1.0 0
19 LDI DIGITAL 10 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-107


Open Processor with Liebert Sitelink Driver Owner's Manual

MOR Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert RCM 10U Type MOR, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-61.
_ Indicates a space.

5-108 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-61. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Siemens Building Technologies, Inc. 5-109


Open Processor with Liebert Sitelink Driver Owner's Manual

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 48 indicates the number of points on the drop, rounded up to the nearest
multiple of 16.

MOR Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-62 shows alarm points for the Liebert RCM 10U (MOR), Application
5372.

Table 5-62. Liebert RCM 10U (MOR).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI HIGH ALARM ANALOG 1 Off/On
01 LDI LOW ALARM ANALOG 1 Off/On
02 LDI DIGITAL ALARM 1 Off/On
04 LDI LOW ALARM ANALOG 2 Off/On
05 LDI DIGITAL ALARM 2 Off/On
06 LDI HIGH ALARM ANALOG 3 Off/On
07 LDI LOW ALARM ANALOG 3 Off/On
08 LDI DIGITAL ALARM 3 Off/On
09 LDI HIGH ALARM ANALOG 4 Off/On
10 LDI LOW ALARM ANALOG 4 Off/On
continued on next page...

5-110 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-62. Liebert RCM 10U (MOR).


1,2
Alarm Point Type Descriptor Range/Units
String
2 16 LDI DIGITAL ALARM 4 Off/On
17 LDI HIGH ALARM ANALOG 5 Off/On
18 LDI LOW ALARM ANALOG 5 Off/On
19 LDI DIGITAL ALARM 5 Off/On
20 LDI HIGH ALARM ANALOG 6 Off/On
21 LDI LOW ALARM ANALOG 6 Off/On
22 LDI DIGITAL ALARM 6 Off/On
23 LDI HIGH ALARM ANALOG 7 Off/On
24 LDI LOW ALARM ANALOG 7 Off/On
25 LDI DIGITAL ALARM 7 Off/On
26 LDI HIGH ALARM ANALOG 8 Off/On
3 32 LDI LOW ALARM ANALOG 8 Off/On
33 LDI DIGITAL ALARM 8 Off/On
34 LDI HIGH ALARM ANALOG 9 Off/On
35 LDI LOW ALARM ANALOG 9 Off/On
36 LDI DIGITAL ALARM 9 Off/On
37 LDI HIGH ALARM ANALOG 10 Off/On
38 LDI LOW ALARM ANALOG 10 Off/On
39 LDI DIGITAL ALARM 10 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-111


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5373: PMP Unit (Liebert Precision Power


and Datawaves with PMP)

Introduction
This section contains information specific to PMP units used with the Open Processor. Figure
5-14 diagrams a PMP unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0430R1

PMP

Figure 5-14. Liebert Precision Power and Datawaves with PMP (PMP).

The Liebert PMP unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

PMP Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Precision Power and Datawaves with PMP Type PMP, you must first enter a corresponding
point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-112 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-63.
_ Indicates a space.

Table 5-63. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Siemens Building Technologies, Inc. 5-113


Open Processor with Liebert Sitelink Driver Owner's Manual

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

PMP Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-64 shows status points for the Liebert Precision Power and Datawaves
with PMP, Application 5373.

Table 5-64. Liebert Precision Power and Datawaves with PMP.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-B Volts 1.0 0
01 LAI INPUT VOLTS B-C Volts 1.0 0
02 LAI INPUT VOLTS C-A Volts 1.0 0
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT VOLTS A-N Volts 1.0 0
07 LAI OUTPUT VOLTS B-N Volts 1.0 0
08 LAI OUTPUT VOLTS C-N Volts 1.0 0
continued on next page...

5-114 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-64. Liebert Precision Power and Datawaves with PMP.


1,2
Point Type Descriptor Range/Units Slope Intercept
09 LAI OUTPUT AMPS PHASE A Amps 1.0 0
10 LAI OUTPUT AMPS PHASE B Amps 1.0 0
11 LAI OUTPUT AMPS PHASE C Amps 1.0 0
12 LAI GROUND CURRENT Amps 0.1 0
13 LAI NUETRAL CURRENT Amps 1.0 0
14 LAI KVA KVA 1.0 0
15 LAI KW KW 1.0 0
16 LAI OUTPUT FREQUENCY Hz 0.1 0
17 LAI CAPACITY PHASE A % 1.0 0
18 LAI CAPACITY PHASE B % 1.0 0
19 LAI CAPACITY PHASE C % 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

PMP Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Precision Power and Datawaves with PMP Type PMP, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

Siemens Building Technologies, Inc. 5-115


Open Processor with Liebert Sitelink Driver Owner's Manual

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-65.
_ Indicates a space.

Table 5-65. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-116 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 15 contain no significant
information.

Siemens Building Technologies, Inc. 5-117


Open Processor with Liebert Sitelink Driver Owner's Manual

PMP Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-66 shows alarm points for the Liebert Precision Power and Datawaves
with PMP, Application 5373.

Table 5-66. Liebert Precision Power and Datawaves with PMP Drop.
1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI OUTPUT UNDERVOLTAGE Off/On
02 LDI OUTPUT OVERVOLTAGE Off/On
03 LDI OUTPUT OVERCURRENT Off/On
04 LDI FREQUENCY DEVIATION Off/On
05 LDI GROUND OVERCURRENT Off/On
06 LDI TRANSFORMER OVERTEMP Off/On
07 LDI GROUND FAULT Off/On
08 LDI GROUND FAILURE Off/On
09 LDI LIQUID DETECTED Off/On
10 LDI SECURITY ALARM Off/On
2 16 LDI PHASE ROTATION/LOSS Off/On
17 LDI DATAWAVE OVERTEMP Off/On
18 LDI EMERGENCY SHUTDOWN Off/On
19 LDI LOAD ON BYPASS Off/On
20 LDI LOCAL ALARM Off/On
21 LDI CUSTOM ALARM 1 Off/On
22 LDI CUSTOM ALARM 2 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-118 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5374: RAC Unit (Liebert Remote


Autochangeover Module)

Introduction
This section contains information specific to RAC units used with the Open Processor. Figure
5-15 diagrams a RAC unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0428R1

RAC

Figure 5-15. Liebert Remote Autochangeover Module (RAC).

The Liebert RAC unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

RAC Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Remote Autochangeover Module Type RAC, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-119


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-67.
_ Indicates a space.

Table 5-67. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

5-120 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 8 indicates the number of points on the drop.

RAC Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-68 shows status points for the Liebert Remote Autochangeover Module
(RAC), Application 5374.

Siemens Building Technologies, Inc. 5-121


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-68. Liebert Remote Autochangeover Module (RAC).


1,2
Point Type Descriptor Range/Units
00 LDI UNIT 1 STATUS Off/On
01 LDI UNIT 2 STATUS Off/On
02 LDI UNIT 3 STATUS Off/On
03 LDI UNIT 4 STATUS Off/On
04 LDI UNIT 5 STATUS Off/On
05 LDI UNIT 6 STATUS Off/On
06 LDI UNIT 7 STATUS Off/On
07 LDI UNIT 8 STATUS Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

RAC Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Remote Autochangeover Module Type RAC, you must first enter a corresponding
point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

5-122 Siemens Building Technologies, Inc.


Chapter 5 - Applications

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-69.
_ Indicates a space.

Table 5-69. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Siemens Building Technologies, Inc. 5-123


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 15 contain no significant
information.

Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-70 shows alarm points for the Liebert Remote Autochangeover Module
(RAC), Application 5374.

5-124 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-70. Liebert Remote Autochangeover Module (RAC).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI UNIT 1 COMMON ALARM Off/On
02 LDI UNIT 2 COMMON ALARM Off/On
03 LDI UNIT 3 COMMON ALARM Off/On
04 LDI UNIT 4 COMMON ALARM Off/On
05 LDI UNIT 5 COMMON ALARM Off/On
06 LDI UNIT 6 COMMON ALARM Off/On
07 LDI UNIT 7 COMMON ALARM Off/On
08 LDI UNIT 8 COMMON ALARM Off/On
09 LDI EMERGENCY POWER Off/On
OPERATION
10 LDI EPO ALL UNITS Off/On
2 16 LDI HIGH TEMPERATURE Off/On
17 LDI LOW TEMPERATURE Off/On
18 LDI HIGH HUMIDITY Off/On
19 LDI LOW HUMIDITY Off/On
20 LDI MANUAL OVERRIDE Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-125


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5375: SC4 Unit (Liebert System Control


Cabinet)

Introduction
This section contains information specific to SC4 units used with the Open Processor. Figure
5-16 diagrams an SC4 unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0429R1

SC4

Figure 5-16. System Control Cabinet (SC4).

The Liebert SC4 unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

SC4 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
System Control Cabinet Type SC4, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-126 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-71.
_ Indicates a space.

Table 5-71. Starting Registers.

Port Number Starting Register (yyy)

1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Siemens Building Technologies, Inc. 5-127


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

SC4 Status Point Maps


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-72 shows the status points for the System Control Cabinet (SC4),
Application 5375.

Table 5-72. Status Point Map for System Control Cabinet (SC4).
1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-B Volts 1.0 0
01 LAI INPUT VOLTS B-C Volts 1.0 0
continued on next page...

5-128 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-72. Status Point Map for System Control Cabinet (SC4).
1,2
Point Type Descriptor Range/Units Slope Intercept
02 LAI INPUT VOLTS C-A Volts 1.0 0
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
09 LAI KVA KVA 1.0 0
10 LAI KW KW 1.0 0
11 LAI CRITICAL BUS FREQUENCY Hz 0.1 0
12 LAI CAPACITY PHASE A % 1.0 0
13 LAI CAPACITY PHASE B % 1.0 0
14 LAI CAPACITY PHASE C % 1.0 0
15 LAI BYPASS VOLTS A-B Volts 1.0 0
16 LAI BYPASS VOLTS B-C Volts 1.0 0
17 LAI BYPASS VOLTS C-A Volts 1.0 0
18 LAI OUTPUT FREQUENCY Hz 0.1 0
19 LAI BYPASS FREQUENCY Hz 0.1 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SC4 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert System Control Cabinet Type SC4, you must first enter a corresponding point (known
as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-129


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-73.
_ Indicates a space.

Table 5-73. Starting Registers

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-130 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 64 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, from 26 to 32, and from 43 to 48. Point
locations 11 15, 27 31, and 44 47 contain no significant information.

SC4 Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-74 shows alarm points for the Liebert System Control Cabinet (SC4),
Application 5375.

Siemens Building Technologies, Inc. 5-131


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-74. Liebert System Control Cabinet (SC4).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI OUTPUT UNDERVOLTAGE Off/On
02 LDI OUTPUT OVERVOLTAGE Off/On
03 LDI FREQUENCY DEVIATION Off/On
04 LDI BYPASS CB OPEN Off/On
05 LDI OUTPUT CB OPEN Off/On
06 LDI STATIC SWITCH DISCONNECTED Off/On
07 LDI OUTPUT OVERLOAD Off/On
08 LDI EMERGENCY POWER OFF Off/On
09 LDI LOAD ON BYPASS Off/On
10 LDI STATIC SWITCH DISABLED Off/On
2 16 LDI CONTROL POWER FAILURE Off/On
17 LDI MODULE #1 SUMMARY ALARM Off/On
18 LDI MODULE #2 SUMMARY ALARM Off/On
19 LDI MODULE #3 SUMMARY ALARM Off/On
20 LDI MODULE #4 SUMMARY ALARM Off/On
21 LDI MODULE #5 SUMMARY ALARM Off/On
22 LDI MODULE #6 SUMMARY ALARM Off/On
23 LDI BYPASS NOT AVAILABLE Off/On
24 LDI NOT OK TO TRANSFER Off/On
25 LDI BYPASS PHASE ROTATION ERROR Off/On
26 LDI MANUAL RESET/TRANSFER Off/On
continued on next page...

5-132 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-74. Liebert System Control Cabinet (SC4).


1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI AUTO RETRANSFER PRIMED Off/On
33 LDI OVERLOAD TRANSFER Off/On
34 LDI MODULE #1 OFFLINE Off/On
35 LDI MODULE #2 OFFLINE Off/On
36 LDI MODULE #31 OFFLINE Off/On
37 LDI MODULE #4 OFFLINE Off/On
38 LDI MODULE #5 OFFLINE Off/On
39 LDI MODULE #6 OFFLINE Off/On
40 LDI CUSTOM ALARM #1 Off/On
42 LDI CUSTOM ALARM #2 Off/On
43 LDI CUSTOM ALARM #3 Off/On
4 48 LDI CUSTOM ALARM #4 Off/On
49 LDI CUSTOM ALARM #5 Off/On
50 LDI CUSTOM ALARM #6 Off/On
51 LDI CUSTOM ALARM #7 Off/On
52 LDI CUSTOM ALARM #8 Off/On
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-133


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5376. SCC Unit (Liebert System Control


Cabinet)

Introduction
This section contains information specific to SCC units used with the Open Processor. Figure
5-17 diagrams an SCC unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0431R1

SCC

Figure 5-17. System Control Cabinet (SCC).

The Liebert SCC unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

SCC Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
System Control Cabinet Type SCC, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-134 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-75.
_ Indicates a space.

Table 5-75. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-135


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

SCC Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-76 shows status points for the Liebert System Control Cabinet (SCC),
Application 5376.

Table 5-76. Liebert System Control Cabinet (SCC). Drop One.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-B Volts 1.0 0
01 LAI INPUT VOLTS B-C Volts 1.0 0
02 LAI INPUT VOLTS C-A Volts 1.0 0
continued on next page...

5-136 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-76. Liebert System Control Cabinet (SCC). Drop One.


1,2
Point Type Descriptor Range/Units Slope Intercept
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT VOLTS A-N Volts 1.0 0
07 LAI OUTPUT VOLTS B-N Volts 1.0 0
08 LAI OUTPUT VOLTS C-N Volts 1.0 0
09 LAI OUTPUT AMPS PHASE A Amps 1.0 0
10 LAI OUTPUT AMPS PHASE B Amps 1.0 0
11 LAI OUTPUT AMPS PHASE C Amps 1.0 0
12 LAI KVA KVA 1.0 0
13 LAI KW KW 1.0 0
14 LAI OUTPUT FREQUENCY Hz 0.1 0
15 LAI CAPACITY PHASE A % 1.0 0
16 LAI CAPACITY PHASE B % 1.0 0
17 LAI CAPACITY PHASE C % 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SCC Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert System Control Cabinet Type SCC, you must first enter a corresponding point (known
as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-137


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-77.
_ Indicates a space.

Table 5-77. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-138 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 15 contain no significant
information.

Siemens Building Technologies, Inc. 5-139


Open Processor with Liebert Sitelink Driver Owner's Manual

SCC Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-78 shows alarm points for the Liebert System Control Cabinet (SCC),
Application 5376.

Table 5-78. Liebert System Control Cabinet (SCC).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI OUTPUT OVERLOAD Off/On
02 LDI EMERGENCY POWER OFF Off/On
03 LDI LOAD ON BYPASS Off/On
04 LDI STATIC SWITCH DISABLED Off/On
05 LDI OUTPUT OUT OF LIMITS Off/On
06 LDI MODULE #1 SUMMARY ALARM Off/On
07 LDI MODULE #2 SUMMARY ALARM Off/On
08 LDI MODULE #3 SUMMARY ALARM Off/On
09 LDI MODULE #4 SUMMARY ALARM Off/On
10 LDI MODULE #5 SUMMARY ALARM Off/On
2 16 LDI MODULE #6 SUMMARY ALARM Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-140 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5377: SMM Unit (Liebert Multi Module


Series UPS)

Introduction
This section contains information specific to SMM controllers used with the Open Processor.
Figure 5-18 diagrams an SMM unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0432R1

SMM

Figure 5-18. Liebert Multi Module Series UPS (SMM).

The Liebert SMM unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains
command points.

SMM Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Multi Module Series UPS Type SMM, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-141


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-79.
_ Indicates a space.

Table 5-79. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-142 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 22 indicates the number of points on the drop.

SMM Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-80 shows the status points for the Liebert Multi Module Series UPS
(SMM), Application 5377.

Table 5-80. Liebert Multi Module Series UPS (SMM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI OUTPUT VOLTS A-B Volts 1.0 0
01 LAI OUTPUT VOLTS B-C Volts 1.0 0
continued on next page...

Siemens Building Technologies, Inc. 5-143


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-80. Liebert Multi Module Series UPS (SMM).


1,2
Point Type Descriptor Range/Units Slope Intercept
02 LAI OUTPUT VOLTS C-A Volts 1.0 0
03 LAI OUTPUT AMPS L1 Amps 1.0 0
04 LAI OUTPUT AMPS L2 Amps 1.0 0
05 LAI OUTPUT AMPS L3 Amps 1.0 0
06 LAI POWER L1 KW 1.0 0
07 LAI POWER L2 KW 1.0 0
08 LAI POWER L3 KW 1.0 0
09 LAI BYPASS FREQUENCY Hz 0.1 0
10 LAI INVERTER FREQUENCY Hz 0.1 0
11 LAI BATTERY VOLTAGE Volts 1.0 0
12 LAI BATTERY CURRENT Amps 1.0 0
13 LAI APPARENT POWER L1 KW 1.0 0
14 LAI APPARENT POWER L2 KW 1.0 0
15 LAI APPARENT POWER L3 KW 1.0 0
16 LAI % LOAD L1 % 1.0 0
17 LAI % LOAD L2 % 1.0 0
18 LAI % LOAD L3 % 1.0 0
19 LAI % BATTERY CHARGE % 1.0 0
20 LAI BATTERY TEMPERATURE F 1.0 0
21 LAI BATTERY TIME REMAINING Number of hours 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SMM Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Multi Module Series UPS Type SMM, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-144 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-81.
_ Indicates a space.

Table 5-81. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Siemens Building Technologies, Inc. 5-145


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 80 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, from bit 26 to 32, from bit 42 to 48, and from
bit 58 to 64. Point locations 11 15, 27 31, 43 47, and 59 63 contain no significant
information.

5-146 Siemens Building Technologies, Inc.


Chapter 5 - Applications

SMM Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-82 shows the alarm points for the Liebert Multi Module Series UPS
(SMM), Application 5377.

Table 5-82. Liebert Multi Module Series UPS (SMM).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BYPAS SWITCH OPEN Off/On
02 LDI OUTPUT SWITCH OPEN Off/On
03 LDI RECTIFIER SWITCH OPEN Off/On
04 LDI BATTERY CB OPEN Off/On
05 LDI MANUAL BYPASS CLOSED Off/On
06 LDI BYPASS ABSENT Off/On
07 LDI BYPASS OVERVOLTAGE Off/On
08 LDI BYPASS UNDERVOLTAGE Off/On
09 LDI BYPASS FREQUENCY ERROR Off/On
10 LDI BYPASS PHASE ROTATION Off/On
ERROR
2 16 LDI BYPASS SCR FAILURE Off/On
17 LDI BYPASS OFF Off/On
18 LDI BYPASS OFF VIA DISPLAY Off/On
19 LDI LOAD ON BYPASS Off/On
20 LDI BYPASS OVERTEMPERATURE Off/On
21 LDI RECTIFIER OFF Off/On
22 LDI RECTIFIER OFF VIA DISPLAY Off/On
23 LDI RETIFIER BLOCK Off/On
24 LDI RECTIFIER CURRENT LIMIT Off/On
25 LDI RECTIFIER Off/On
OVERTEMPERATURE
26 LDI RECTIFIER FUSE FAILURE Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-147


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-82. Liebert Multi Module Series UPS (SMM).


1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI INVERTER OFF Off/On
33 LDI INVERTER OFF VIA DISPLAY Off/On
34 LDI INVERTER BLOCK Off/On
35 LDI INVERTER CURRENT LIMIT Off/On
36 LDI INVERTER Off/On
OVERTEMPERATURE
37 LDI INVERTER NOT Off/On
SYNCHRONIZED
38 LDI INVERTER OVERVOLTAGE Off/On
39 LDI INVERTER UNDERVOLTAGE Off/On
40 LDI INVERTER FUSE FAILURE Off/On
41 LDI OUTPUT OVERVOLTAGE Off/On
42 LDI OUTPUT UNDERVOLTAGE Off/On
4 48 LDI OUTPUT NO VOLTAGE Off/On
49 LDI OUTPUT WAVEFORM ERROR Off/On
50 LDI INVERTER FREQUENCY ERROR Off/On
51 LDI INVERTER PARALLEL ERROR Off/On
52 LDI CONTACT FAILURE Off/On
53 LDI BATTEY TEST Off/On
54 LDI BATTERY TEST FAILURE Off/On
55 LDI BATTERY ON LOAD Off/On
56 LDI BATTERY END OF DISCHARGE Off/On
57 LDI BOOST TIME EXPIRED Off/On
58 LDI DC SLOW OVERVOLTAGE Off/On
continued on next page...

5-148 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-82. Liebert Multi Module Series UPS (SMM).


1,2
Alarm Point Type Descriptor Range/Units
String
5 64 LDI DC UNDERVOLTAGE Off/On
65 LDI BATTERY FUSE FAILURE Off/On
66 LDI DC FAST OVERVOLTAGE Off/On
67 LDI TRANSFER COUNT BLOCK Off/On
68 LDI OVERLOAD SHUTDOWN Off/On
69 LDI OVERTEMP SHUTDOWN Off/On
TIMEOUT
70 LDI EMERGENCY STOP Off/On
71 LDI OVERLOAD PRESENT Off/On
72 LDI OVERLOAD SHUTDOWN Off/On
TIMEOUT
73 LDI BAD EEPROM Off/On
74 LDI DISPLAY ERROR Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SMM Unit Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert Multi Module Series UPS Type SSM, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In mmetadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

Siemens Building Technologies, Inc. 5-149


Open Processor with Liebert Sitelink Driver Owner's Manual

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop.
H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-83.
_ Indicates a space.

Table 5-83. Starting Registers.

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

5-150 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 1 indicates the number of points on the drop.

SMM Command Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-84 Shows the command points for the Liebert Multi Module Series UPS
(SMM), Application 5377.

Table 5-84. Liebert Multi Module Series UPS (SMM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO DATE/TIME SYNC CONTROL 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-151


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5378: SMS Unit (Liebert Single Module


Series UPS S300, S500, W600)

Introduction
This section contains information specific to SMS units used with the Open Processor. Figure
5-19 diagrams an SMS.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0433R1

SMS

Figure 5-19. Liebert Single Module Series UPS S300, S500, W600 (SMS).

The Liebert SMS unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

SMS Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Single Module Series UPS S300, S500, and W600 Type SMS, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-152 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-85.
_ Indicates a space.

Table 5-85. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Siemens Building Technologies, Inc. 5-153


Open Processor with Liebert Sitelink Driver Owner's Manual

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 20 indicates the number of points on the drop.

SMS Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-86 shows the status points for the Liebert Single Module Series UPS
S300, S500, and W600 Type SMS, Application 5378.

Table 5-86. Liebert Single Module Series UPS S300, S500, and W600 Type SMS.
1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI BYPASS VOLTS A-B Volts 1.0 0
01 LAI BYPASS VOLTS B-C Volts 1.0 0
continued on next page...

5-154 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-86. Liebert Single Module Series UPS S300, S500, and W600 Type SMS.
1,2
Point Type Descriptor Range/Units Slope Intercept
02 LAI BYPASS VOLTS C-A Volts 1.0 0
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT VOLTS A-N Volts 1.0 0
07 LAI OUTPUT VOLTS B-N Volts 1.0 0
08 LAI OUTPUT VOLTS C-N Volts 1.0 0
09 LAI OUTPUT AMPS PHASE A Amps 1.0 0
10 LAI OUTPUT AMPS PHASE B Amps 1.0 0
11 LAI OUTPUT AMPS PHASE C Amps 1.0 0
12 LAI DC BUS VOLTAGE Volts 1.0 0
13 LAI DC BUS CURRENT Amps 1.0 0
14 LAI KVA KVA 1.0 0
15 LAI KW KW 1.0 0
16 LAI OUTPUT FREQUENCY Hz 0.1 0
17 LAI CAPACITY PHASE A % 1.0 0
18 LAI CAPACITY PHASE B % 1.0 0
19 LAI CAPACITY PHASE C % 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SMS Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Single Module Series UPS S300, S500, and W600 Type SMS, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-155


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-87.
_ Indicates a space.

Table 5-87. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

5-156 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 15 contain no significant
information.

Siemens Building Technologies, Inc. 5-157


Open Processor with Liebert Sitelink Driver Owner's Manual

SMS Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-88 shows the Alarm points for the Liebert Single Module Series UPS
S300, S500, and W600 Type SMS, Application 5378.

Table 5-88. Liebert Single Module Series UPS S300, S500, and W600 Type SMS.
1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BATTERY DISCHARGE Off/On
02 LDI LOW BATTERY RESERVE Off/On
03 LDI OUTPUT OVERLOAD Off/On
04 LDI FUSE CLEARED Off/On
05 LDI EMERGENCY POWER OFF Off/On
06 LDI AMBIENT OVERTEMPERATURE Off/On
07 LDI LOAD ON BYPASS Off/On
08 LDI STATIC SWITCH DISABLED Off/On
09 LDI BATTERY DISCONNECTED Off/On
10 LDI MODULE COOLING FAILURE Off/On
2 16 LDI CONTROL POWER FAILURE Off/On
17 LDI OVERLOAD SHUTDOWN Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-158 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5379: SM3 Unit (Liebert Single Module


Series UPS)

Introduction
This section contains information specific to SM3 units used with the Open Processor. Figure
5-20 diagrams an SM3 unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0434R1

SM3

Figure 5-20. Liebert Single Module Series UPS (SM3).

The Liebert SM3 unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

SM3 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Single Module Series UPS Type SM3, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-159


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-89.
_ Indicates a space.

Table 5-89. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

5-160 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 24 indicates the number of points on the drop.

SM3 Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-90 shows the status points for the Liebert Single Module Series UPS
SM3, Application 5379.

Table 5-90. SM3 Status Points.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-N Volts 1.0 0
01 LAI INPUT VOLTS B-N Volts 1.0 0
02 LAI INPUT VOLTS C-N Volts 1.0 0
03 LAI OUTPUT VOLTS A-N Volts 1.0 0
04 LAI OUTPUT VOLTS B-N Volts 1.0 0
05 LAI OUTPUT VOLTS C-N Volts 1.0 0
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
continued on next page...

Siemens Building Technologies, Inc. 5-161


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-90. SM3 Status Points.


1,2
Point Type Descriptor Range/Units Slope Intercept
09 LAI DC BUS VOLTAGE Volts 1.0 0
10 LAI DC BUS CURRENT Amps 1.0 0
11 LAI KVA KVA 1.0 0
12 LAI KW KW 1.0 0
13 LAI OUTPUT FREQUENCY Hz 0.1 0
14 LAI CAPACITY PHASE % 1.0 0
15 LAI BYPASS VOLTS A-N Volts 1.0 0
16 LAI BYPASS VOLTS B-N Volts 1.0 0
17 LAI BYPASS VOLTS C-N Volts 1.0 0
18 LAI UNIT KVA SIZE KVA 1.0 0
19 LAI UNIT MODEL NUMBER 311 = Model 311/312 1.0 0
321 = Model 321/322
331 = Model 331/332
341= Model 341/342
346 = Model 346/347
356 = Model 356/357
361 = Model 361/362
366 = Model 366/367
376 = Model 376/377
381 = Model 381/382
20 LAI BATTERY TIME REMAINING 0 255 1.0 0
(Counter has a limit of
255. Counter will begin
when time reaches 254
or less. )
21 LDI LAST BATTERY TEST Failed/Passed 1.0 0
STATUS
22 LDI INVERTER STATUS Off/On 1.0 0
23 LDI BYPASS STATUS No/Yes 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SM3 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Single Module Series UPS Type SM3, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

5-162 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-91.
_ Indicates a space.

Siemens Building Technologies, Inc. 5-163


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-91. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

5-164 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 through 15 contain no
significant information.

SM3 Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-92 shows the alarm points for the Liebert Single Module Series UPS
Type SM3, Application 5379.

Table 5-92. SM3 Alarm Points.


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BYPASS FAILURE Off/On
02 LDI INPUT FAILURE Off/On
03 LDI BATTERY DISCHARGING Off/On
04 LDI LOW BATTERY Off/On
05 LDI OUTPUT OVERLOAD Off/On
06 LDI AMBIENT OVERTEMPERATURE Off/On
07 LDI OUTPUT UNDERVOLTAGE Off/On
08 LDI OUTPUT OVERVOLTAGE Off/On
09 LDI CHARGER FAILURE Off/On
10 LDI LOAD ON BYPASS Off/On
2 16 LDI UTILITY FAILURE Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-165


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5380: SM4 Unit (Liebert Single Module


Series UPS)

Introduction
This section contains information specific to SM4 units used with the Open Processor. Figure
5-21 diagrams an SM4 unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0435R1

SM4

Figure 5-21. Liebert Single Module Series UPS (SM4).

The Liebert SM4 unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

SM4 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Single Module Series UPS Type SM4, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-166 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-93.
_ Indicates a space.

Table 5-93. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-167


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 24 indicates the number of points on the drop.

SM4 Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-94 shows the status points for the Single Module Series UPS Type
SM4, Application 5379.

Table 5-94. SM4 Status Points.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-B Volts 1.0 0
01 LAI INPUT VOLTS B-C Volts 1.0 0
02 LAI INPUT VOLTS C-A Volts 1.0 0
continued on next page...

5-168 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-94. SM4 Status Points.


1,2
Point Type Descriptor Range/Units Slope Intercept
03 LAI OUTPUT VOLTS A-B Volts 1.0 0
04 LAI OUTPUT VOLTS B-C Volts 1.0 0
05 LAI OUTPUT VOLTS C-A Volts 1.0 0
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
09 LAI DC BUS VOLTAGE Volts 1.0 0
10 LAI BATTERY CURRENT Amps 1.0 0
11 LAI KVA KVA 1.0 0
12 LAI KW KW 1.0 0
13 LAI CRITICAL BUS FREQUENCY Hz 0.1 0
14 LAI CAPACITY PHASE A % 1.0 0
15 LAI CAPACITY PHASE B % 1.0 0
16 LAI CAPACITY PHASE C % 1.0 0
17 LAI BYPASS VOLTS A-B Volts 1.0 0
18 LAI BYPASS VOLTS B-C Volts 1.0 0
19 LAI BYPASS VOLTS C-A Volts 1.0 0
20 LAI INPUT AMPS PHASE A Amps 1.0 0
21 LAI INPUT AMPS PHASE B Amps 1.0 0
22 LAI INPUT AMPS PHASE C Amps 1.0 0
23 LAI BYPASS FREQUENCY Hz 0.1 0
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

SM4 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Single Module Series UPS Type SM4, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-169


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-95.
_ Indicates a space.

Table 5-95. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-170 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address indicates the mapping location of the points described by the metapoint.
The FLN number is 3, and the DROP number is 30. The Point number (ranging from 1 to 94)
indicates the FLN and DROP number where the status points are to be mapped. Refer to the
Point Database Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 80 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, from bit 26 to 32, from bit 43 to 48, and from
bit 58 to 64. Point locations 11 15, 27 31, 44 47, and 59 - 63 contain no significant
information.

SM4 Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-96 shows the alarm points for the Liebert Single Module Series UPS
Type SM4, Application 5380.

Siemens Building Technologies, Inc. 5-171


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-96. SM4 Alarm Points (Drop 2).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI OUTPUT UNDERVOLTAGE Off/On
02 LDI OUTPUT OVERVOLTAGE Off/On
03 LDI BATTERY DISCHARGE Off/On
04 LDI FREQUENCY DEVIATION Off/On
05 LDI INPUT FAILURE Off/On
06 LDI HARDWARE SHUTDOWN Off/On
07 LDI DC GROUND FAULT Off/On
08 LDI INPUT CB OPEN Off/On
09 LDI BYPASS CB OPEN Off/On
10 LDI OUTPUT CB OPEN Off/On
2 16 LDI STATIC SWITCH Off/On
DISCONNECTED
17 LDI DC CAP FUSE BLOWN Off/On
18 LDI LOW BATTERY RESERVE Off/On
19 LDI OUTPUT OVERLOAD Off/On
20 LDI RECTIFIER FUSE BLOWN Off/On
21 LDI EMERGENCY POWER OFF Off/On
22 LDI AMBIENT OVERTEMPERATURE Off/On
23 LDI LOAD ON BYPASS Off/On
24 LDI STATIC SWITCH DISABLED Off/On
25 LDI BATTERY DISCONNECTED Off/On
26 LDI CONTROL POWER FAILURE Off/On
continued on next page...

5-172 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-96. SM4 Alarm Points (Drop 2).


1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI INVERTER FAULT Off/On
33 LDI INPUT CURRENT INBALANCE Off/On
34 LDI BYPASS NOT AVAILABLE Off/On
35 LDI NOT OK TO TRANSFER Off/On
36 LDI BYPASS PHASE ROTATION Off/On
ERROR
37 LDI MANUAL RESET/ TRANSFER Off/On
38 LDI AUTO RETRANSFER PRIMED Off/On
39 LDI OVERLOAD TRANSFER Off/On
40 LDI REVERSE POWER Off/On
42 LDI LOW BATTERY SHUTDOWN Off/On
43 LDI DC OVERVOLTAGE Off/On
SHUTDOWN
4 48 LDI BATTERY CYCLE BUFFER FULL Off/On
49 LDI EQUIPMENT Off/On
OVERTEMPERATURE
50 LDI BLOWER/FAN FAILURE Off/On
51 LDI OVERTEMPERATURE Off/On
SHUTDOWN
52 LDI CUSTOM ALARM #1 Off/On
53 LDI CUSTOM ALARM #2 Off/On
54 LDI CUSTOM ALARM #3 Off/On
55 LDI CUSTOM ALARM #4 Off/On
56 LDI CUSTOM ALARM #5 Off/On
57 LDI CUSTOM ALARM #6 Off/On
58 LDI CUSTOM ALARM #7 Off/On
5 64 LDI CUSTOM ALARM #8 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-173


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5381: SSC Unit (Liebert System Control


Cabinet)

Introduction
This section contains information specific to SSC controllers used with the Open Processor.
Figure 5-22 diagrams an SSC.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0436R1

SSC

Figure 5-22. Liebert System Control Cabinet (SSC).

The Liebert SSC unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains control
points.

SSC Unit Status Drop


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
System Control Cabinet Type SSC, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-174 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-1.
_ Indicates a space.

Table 5-97. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Siemens Building Technologies, Inc. 5-175


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address indicates the mapping location of the points described by the metapoint.
The FLN number is 3, and the DROP number is 30. The Point number (ranging from 1 to 94)
indicates the FLN and DROP number where the status points are to be mapped. Refer to the
Point Database Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 22 indicates the number of points on the drop.

SSC Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-98 Shows the status points for the Liebert System Control Cabinet
(SSC), Application 5381.

Table 5-98. Liebert System Control Cabinet (SSC).Drop One.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI OUTPUT VOLTS A-B Volts 1.0 0
01 LAI OUTPUT VOLTS B-C Volts 1.0 0
02 LAI OUTPUT VOLTS C-A Volts 1.0 0
continued on next page...

5-176 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-98. Liebert System Control Cabinet (SSC).Drop One.


1,2
Point Type Descriptor Range/Units Slope Intercept
03 LAI OUTPUT AMPS L1 Amps 1.0 0
04 LAI OUTPUT AMPS L2 Amps 1.0 0
05 LAI OUTPUT AMPS L3 Amps 1.0 0
06 LAI POWER L1 1.0 0
07 LAI POWER L2 1.0 0
08 LAI POWER L3 1.0 0
09 LAI BYPASS FREQUENCY Hz 0.1 0
10 (UNUSED) 1.0 0
11 LAI BATTERY VOLTAGE Volts 1.0 0
12 LAI BATTERY CURRENT Amps 1.0 0
13 LAI APPARENT POWER L1 1.0 0
14 LAI APPARENT POWER L2 1.0 0
15 LAI APPARENT POWER L3 1.0 0
16 LAI % LOAD L1 % 1.0 0
17 LAI % LOAD L2 % 1.0 0
18 LAI % LOAD L3 % 1.0 0
19 LAI % BATTERY CHARGE % 1.0 0
20 LAI BATTERY TEMPERATURE F 1.0 0
21 LAI BATTERY TIME REMAINING 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SSC Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert System Control Cabinet Type SSC, you must first enter a corresponding point (known
as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-177


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-1.
_ Indicates a space.

Table 5-99. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

5-178 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 80 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, from bit 26 to 32, from bit 43 to 48, and from
bit 58 to 64. Point locations 11 15, 27 31, 44 47, and 59 - 63 contain no significant
information.

SSC Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-100 shows the alarm points for the Liebert System Control Cabinet
(SSC), Application 5381.

Siemens Building Technologies, Inc. 5-179


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-100. Liebert System Control Cabinet (SSC).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BYPASS SWITCH OPEN Off/On
02 LDI OUTPUT SWITCH OPEN Off/On
03 LDI RECTIFIER SWITCH OPEN Off/On
04 LDI BATTERY CB OPEN Off/On
05 LDI MANUAL BYPASS CLOSED Off/On
06 LDI BYPASS ABSENT Off/On
07 LDI BYPASS OVERVOLTAGE Off/On
08 LDI BYPASS UNDERVOLTAGE Off/On
09 LDI BYPASS FREQUENCY ERROR Off/On
10 LDI BYPASS PHASE ROTATION ERROR Off/On
2 16 LDI BYPASS SCR FAILURE Off/On
17 LDI BYPASS OFF Off/On
18 LDI BYPASS OFF VIA DISPLAY Off/On
19 LDI LOAD ON BYPASS Off/On
20 LDI BYPASS OVERTEMPERATURE Off/On
21 LDI RECTIFIER OFF Off/On
22 LDI RECTIFIER OFF VIA DISPLAY Off/On
23 LDI RECTIFIER BLOCK Off/On
24 LDI RECTIFIER CURRENT LIMIT Off/On
25 LDI RECTIFIER OVERTEMPERATURE Off/On
26 LDI RECTIFIER FUSE FAILURE Off/On
continued on next page...

5-180 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-100. Liebert System Control Cabinet (SSC).


1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI INVERTER OFF Off/On
33 LDI INVERTER OFF VIA DISPLAY Off/On
34 LDI INVERTER CURRENT LIMIT Off/On
35 LDI INVERTER OVERTEMPERATURE Off/On
36 LDI INVERTER NOT SYNCHRONIZED Off/On
37 LDI INVERTER OVERVOLTAGE Off/On
38 LDI INVERTER UNDERVOLTAGE Off/On
39 LDI INVERTER FUSE FAILURE Off/On
40 LDI OUTPUT OVERVOLTAGE Off/On
41 LDI OUTPUT UNDERVOLTAGE Off/On
4 48 LDI OUTPUT NO VOLTAGE Off/On
49 LDI OUTPUT WAVEFORM ERROR Off/On
50 LDI INVERTER FREQUENCY ERROR Off/On
51 LDI INVERTER PARALLEL ERROR Off/On
52 LDI CONTACTOR FAILURE Off/On
53 LDI BATTERY TEST Off/On
54 LDI BATTERY TEST FAILURE Off/On
55 LDI BATTERY ON LOAD Off/On
56 LDI BATTERY END OF DISCHARGE Off/On
57 LDI BOOST TIME EXPIRED Off/On
58 LDI DC SLOW OVERVOLTAGE Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-181


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-100. Liebert System Control Cabinet (SSC).


1,2
Alarm Point Type Descriptor Range/Units
String
5 64 LDI DC UNDERVOLTAGE Off/On
65 LDI BATTERY FUSE FAILURE Off/On
66 LDI DC FAST OVERVOLTAGE Off/On
67 LDI TRANSFER COUNT BLOCK Off/On
68 LDI OVERLOAD SHUTDOWN Off/On
69 LDI OVERTEMP SHUTDOWN TIMEOUT Off/On
70 LDI EMERGENCY STOP Off/On
71 LDI OVERLOAD PRESENT Off/On
72 LDI OVERLOAD SHUTDOWN TIMEOUT Off/On
73 LDI BAD EEPROM Off/On
74 LDI DISPLAY ERROR Off/On
Includes:
ERROR LRC PAR P1
ERROR LRC PAR P2
ERROR LRC PAR P3
ERROR LRC ALARM HISTORY
ERROR LRC EVENT HISTORY
INTERNAL BATTERY LOW
ERROR LRC TABLE
ERROR LRC PANEL
CAN BUS NO RESPONSE
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SSC Unit Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert System Control Cabinet Type SSC, you must first enter a corresponding point (known
as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-182 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx.H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop
H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-101.
_ Indicates a space.

Table 5-101. Starting Registers.

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Siemens Building Technologies, Inc. 5-183


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 1 indicates the number of points on the drop.

SSC Unit Command Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-102 Shows the command points for the Liebert System Control Cabinet
(SSC), Application 5381.

Table 5-102. Liebert System Control Cabinet (SSC).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO DATE/TIME SYNC CONTROL 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-184 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5382. SSM Unit (Liebert Single Module


Series UPS)

Introduction
This section contains information specific to SSM controllers used with the Open Processor.
Figure 5-23 diagrams an SSM.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0437R1

SSM

Figure 5-23. Liebert Multi-Module Series UPS (SSM).

The Liebert SSM unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains control
points.

SSM Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Single Module Series UPS Type SSM, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-185


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-103.
_ Indicates a space.

Table 5-103. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

5-186 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 22 indicates the number of points on the drop.

SSM Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-104 Shows the status points for the Liebert Multi-Module Series UPS
(SMM), Application 5382.

Table 5-104. Liebert Multi-Module Series UPS (SMM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI OUTPUT VOLTS A-B Volts 1.0 0
01 LAI OUTPUT VOLTS B-C Volts 1.0 0
continued on next page...

Siemens Building Technologies, Inc. 5-187


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-104. Liebert Multi-Module Series UPS (SMM).


1,2
Point Type Descriptor Range/Units Slope Intercept
02 LAI OUTPUT VOLTS C-A Volts 1.0 0
03 LAI OUTPUT AMPS L1 Amps 1.0 0
04 LAI OUTPUT AMPS L2 Amps 1.0 0
05 LAI OUTPUT AMPS L3 Amps 1.0 0
06 LAI POWER L1 1.0 0
07 LAI POWER L2 1.0 0
08 LAI POWER L3 1.0 0
09 LAI BYPASS FREQUENCY Hz 0.1 0
10 LAI INVERTER FREQUENCY Hz 0.1 0
11 LAI BATTERY VOLTAGE Volts 1.0 0
12 LAI BATTERY CURRENT Amps 1.0 0
13 LAI APPARENT POWER L1 1.0 0
14 LAI APPARENT POWER L2 1.0 0
15 LAI APPARENT POWER L3 1.0 0
16 LAI % LOAD L1 % 1.0 0
17 LAI % LOAD L2 % 1.0 0
18 LAI % LOAD L3 % 1.0 0
19 LAI % BATTERY CHARGE % 1.0 0
20 LAI BATTERY TEMPERATURE F 1.0 0
21 LAI BATTERY TIME REMAINING 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SSM Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Single Module Series UPS Type SSM, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-188 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-1.
_ Indicates a space.

Table 5-105. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-189


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 80 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16, from bit 26 to 32, from bit 43 to 48, and from
bit 58 to 64. Point locations 11 15, 27 31, 44 47, and 59 - 63 contain no significant

5-190 Siemens Building Technologies, Inc.


Chapter 5 - Applications

SSM Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-106 Shows the alarm points for the Liebert Multi-Module Series UPS
(SMM), Application 5382.

Table 5-106. Liebert Multi-Module Series UPS (SMM).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BYPASS SWITCH OPEN Off/On
02 LDI OUTPUT SWITCH OPEN Off/On
03 LDI RECTIFIER SWITCH OPEN Off/On
04 LDI BATTERY CB OPEN Off/On
05 LDI MANUAL BYPASS CLOSED Off/On
06 LDI BYPASS ABSENT Off/On
07 LDI BYPASS OVERVOLTAGE Off/On
08 LDI BYPASS UNDERVOLTAGE Off/On
09 LDI BYPASS FREQUENCY ERROR Off/On
10 LDI BYPASS PHASE ROTATION Off/On
ERROR
2 16 LDI BYPASS SCR FAILURE Off/On
17 LDI BYPASS OFF Off/On
18 LDI BYPASS OFF VIA DISPLAY Off/On
19 LDI LOAD ON BYPASS Off/On
20 LDI BYPASS OVERTEMPERATURE Off/On
21 LDI RECTIFIER OFF Off/On
22 LDI RECTIFIER OFF VIA DISPLAY Off/On
23 LDI RECTIFIER BLOCK Off/On
24 LDI RECTIFIER CURRENT LIMIT Off/On
25 LDI RECTIFIER Off/On
OVERTEMPERATURE
26 LDI RECTIFIER FUSE FAILURE Off/On
continued on next page...

Siemens Building Technologies, Inc. 5-191


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-106. Liebert Multi-Module Series UPS (SMM).


1,2
Alarm Point Type Descriptor Range/Units
String
3 32 LDI INVERTER OFF Off/On
33 LDI INVERTER OFF VIA DISPLAY Off/On
34 LDI INVERTER CURRENT LIMIT Off/On
35 LDI INVERTER Off/On
OVERTEMPERATURE
36 LDI INVERTER NOT Off/On
SYNCHRONIZED
37 LDI INVERTER OVERVOLTAGE Off/On
38 LDI INVERTER UNDERVOLTAGE Off/On
39 LDI INVERTER FUSE FAILURE Off/On
40 LDI OUTPUT OVERVOLTAGE Off/On
41 LDI OUTPUT UNDERVOLTAGE Off/On
4 48 LDI OUTPUT NO VOLTAGE Off/On
49 LDI OUTPUT WAVEFORM ERROR Off/On
50 LDI INVERTER FREQUENCY Off/On
ERROR
51 LDI INVERTER PARALLEL ERROR Off/On
52 LDI CONTACTOR FAILURE Off/On
53 LDI BATTERY TEST Off/On
54 LDI BATTERY TEST FAILURE Off/On
55 LDI BATTERY ON LOAD Off/On
56 LDI BATTERY END OF DISCHARGE Off/On
57 LDI BOOST TIME EXPIRED Off/On
58 LDI DC SLOW OVERVOLTAGE Off/On
continued on next page...

5-192 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-106. Liebert Multi-Module Series UPS (SMM).


1,2
Alarm Point Type Descriptor Range/Units
String
5 64 LDI DC UNDERVOLTAGE Off/On
65 LDI BATTERY FUSE FAILURE Off/On
66 LDI DC FAST OVERVOLTAGE Off/On
67 LDI TRANSFER COUNT BLOCK Off/On
68 LDI OVERLOAD SHUTDOWN Off/On
69 LDI OVERTEMP SHUTDOWN Off/On
TIMEOUT
70 LDI EMERGENCY STOP Off/On
71 LDI OVERLOAD PRESENT Off/On
72 LDI OVERLOAD SHUTDOWN Off/On
TIMEOUT
73 LDI BAD EEPROM Off/On
74 LDI DISPLAY ERROR Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

SSM Unit Command Drop Metapoint Characteristics


In order to unbundle any of the points in the Command drop (known as a metadrop) for the
Liebert Single Module Series UPS Type SSM, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

Siemens Building Technologies, Inc. 5-193


Open Processor with Liebert Sitelink Driver Owner's Manual

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


. Indicates this will be a write-only drop.
H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-107.
_ Indicates a space.

Table 5-107. Starting Registers.

Port Number Starting Register (yyy)


1 349
2 352
3 355
4 358
5 361
6 364
7 367
8 370
9 373
10 376
11 379
12 382

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

5-194 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 1 indicates the number of points on the drop.

SSM Unit Command Point Map Metapoint Characteristics


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-108 shows the Command points for the Liebert Multi-Module Series
UPS (SMM), Application 5382.

Table 5-108. Liebert Multi-Module Series UPS (SMM). Drop Three.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAO DATE/TIME SYNC CONTROL 1.0 0
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-195


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5383. THM Unit (Liebert


Temperature/Humidity Panel)

Introduction
This section contains information specific to THM controllers used with the Open Processor.
Figure 5-24 diagrams a THM.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0438R1

THM

Figure 5-24. Liebert Temperature/Humidity Panel (THM).

The Liebert THM unit requires one drop to map all point information. The drop contains status
information.

THM Unit Device Drop Metapoint Characteristics


In order to unbundle any of the points in the drop (known as a metadrop) for the Liebert
Temperature/ Humidity Panel Type THM, you must first enter a corresponding point (known
as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

5-196 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-109.
_ Indicates a space.

Table 5-109. Starting Registers

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Siemens Building Technologies, Inc. 5-197


Open Processor with Liebert Sitelink Driver Owner's Manual

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of points on the drop.

5-198 Siemens Building Technologies, Inc.


Chapter 5 - Applications

THM Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-110 shows the alarm points for THM Unit controllers, Application 5383.

Table 5-110. Liebert Temperature/Humidity Panel (THM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TEMPERATURE SENSOR #1 F 1.0 0
01 LAI HUMIDITY SENSOR #1 % 1.0 0
02 LAI TEMPERATURE SENSOR #2 F 1.0 0
03 LAI HUMIDITY SENSOR #2 % 1.0 0
04 LAI TEMPERATURE SENSOR #3 F 1.0 0
05 LAI HUMIDITY SENSOR #3 % 1.0 0
06 LAI TEMPERATURE SENSOR #4 F 1.0 0
07 LAI HUMIDITY SENSOR #4 % 1.0 0
08 LAI TEMPERATURE SENSOR #5 F 1.0 0
09 LAI HUMIDITY SENSOR #5 % 1.0 0
10 LAI TEMPERATURE SENSOR #6 F 1.0 0
11 LAI HUMIDITY SENSOR #6 % 1.0 0
12 LAI TEMPERATURE SENSOR #7 F 1.0 0
13 LAI HUMIDITY SENSOR #7 % 1.0 0
14 LAI TEMPERATURE SENSOR #8 F 1.0 0
15 LAI HUMIDITY SENSOR #8 % 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-199


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5384: US3 Unit (Liebert UPS Station S3)

Introduction
This section contains information specific to US3 controllers used with the Open Processor.
Figure 5-25 diagrams a US3.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0439R1

US3

Figure 5-25. Liebert UPS Station S3 (US3).

The Liebert US3 unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

US3 Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
UPS Station S3 Type US3, you must first enter a corresponding point (known as a metapoint)
to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-200 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-111.
_ Indicates a space.

Table 5-111. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Siemens Building Technologies, Inc. 5-201


Open Processor with Liebert Sitelink Driver Owner's Manual

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 24 indicates the number of points on the drop.

US3 Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-112 shows the status points for Liebert US3 controllers, Application
5384.

Table 5-112. UPS Station S3 Type US3.


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS A-N Volts 1.0 0
01 LAI INPUT VOLTS B-N Volts 1.0 0
02 LAI INPUT VOLTS C-N Volts 1.0 0
03 LAI OUTPUT VOLTS A-N Volts 1.0 0
04 LAI OUTPUT VOLTS B-N Volts 1.0 0
05 LAI OUTPUT VOLTS C-N Volts 1.0 0
continued on next page...

5-202 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-112. UPS Station S3 Type US3.


1,2
Point Type Descriptor Range/Units Slope Intercept
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
09 LAI DC BUS VOLTAGE Volts 1.0 0
10 LAI DC BUS CURRENT Amps 1.0 0
11 LAI KVA KVA 1.0 0
12 LAI KW KW 1.0 0
13 LAI OUTPUT FREQUENCY Hz 0.1 0
14 LAI CAPACITY % 1.0 0
15 LAI BYPASS VOLTS A-N Volts 1.0 0
16 LAI BYPASS VOLTS B-N Volts 1.0 0
17 LAI BYPASS VOLTS C-N Volts 1.0 0
18 LAI UNIT KVA SIZE KVA 1.0 0
19 LAI BATTERY TIME REMAINING 0 255 1.0 0
(Counter will begin
when value is 254
or less)
20 LAI INVERTER TEMPERATURE F 1.0 0
21 LAI PFC TEMPERATURE F 1.0 0
22 LAI BATTERY TEMPERATURE F 1.0 0
23 LAI BYPASS FREQUENCY Hz 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

US3 Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert UPS Station S3 Type US3, you must first enter a corresponding point (known as a
metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-203


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-1.
_ Indicates a space.

Table 5-113. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-204 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 32 indicates the number of points on the drop, rounded up to the nearest
multiple of 16. Since the Liebert registers are 12 bit, while the driver was designed for 16 bit
registers, you will see a jump from bit 10 to 16. Point locations 11 15 contain no significant
information.

Siemens Building Technologies, Inc. 5-205


Open Processor with Liebert Sitelink Driver Owner's Manual

US3 Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-114 shows the alarm points for the Liebert UPS Station S3 (US3),
Application 5384.

Table 5-114. Liebert UPS Station S3 (US3). Drop Two.


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI BYPASS FAILURE Off/On
02 LDI INPUT FAILURE Off/On
03 LDI UTILITY FAILURE Off/On
04 LDI BATTERY DISCHARGING Off/On
05 LDI LOW BATTERY Off/On
06 LDI OUTPUT OVERLOAD Off/On
07 LDI AMBIENT OVERTEMPERATURE Off/On
08 LDI OUTPUT UNDERVOLTAGE Off/On
09 LDI OUTPUT OVERVOLTAGE Off/On
10 LDI CHARGER FAILURE Off/On
2 16 LDI LOAD ON BYPASS Off/On
17 LDI INPUT OVERVOLTAGE Off/On
18 LDI UPS OFF Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-206 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5385: VCM Unit (Liebert Volt Current


Monitoring Panel)

Introduction
This section contains information specific to VCM controllers used with the Open Processor.
Figure 5-26 diagrams a VCM.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0440R1

VCM

Figure 5-26. Liebert Volt Current Monitoring Panel (VCM).

The Liebert VCM unit requires three drops to map all point information. The first drop contains
status information; the second drop contains alarm information; the third drop contains control
points.

VCM Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Volt Current Monitoring Panel Type VCM, you must first enter a corresponding point (known
as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-207


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-115.
_ Indicates a space.

Table 5-115. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-208 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 12 indicates the number of points on the drop.

Siemens Building Technologies, Inc. 5-209


Open Processor with Liebert Sitelink Driver Owner's Manual

VCM Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-116 shows the status points for Liebert VCM controllers, Application
5385.

Table 5-116. Liebert Volt Current Monitoring Panel (VCM).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS X-Y Volts 1.0 0
01 LAI INPUT VOLTS Y-Z Volts 1.0 0
02 LAI INPUT VOLTS Z-X Volts 1.0 0
03 LAI OUTPUT VOLTS X-N Volts 1.0 0
04 LAI OUTPUT VOLTS Y-N Volts 1.0 0
05 LAI OUTPUT VOLTS Z-N Volts 1.0 0
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
09 LAI GROUND CURRENT Amps 1.0 0
10 LAI NEUTRAL CURRENT Amps 1.0 0
11 LAI KVA KVA 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

VCM Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Volt Current Monitoring Panel Type VCM, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-210 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-117.
_ Indicates a space.

Table 5-117. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Siemens Building Technologies, Inc. 5-211


Open Processor with Liebert Sitelink Driver Owner's Manual

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of points on the drop, rounded up to the nearest
multiple of 16.

5-212 Siemens Building Technologies, Inc.


Chapter 5 - Applications

VCM Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-118 shows the alarm points for Liebert VCM controllers, Application
5385.

Table 5-118. Liebert Volt Current Monitoring Panel (VCM).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI OUTPUT UNDERVOLTAGE Off/On
02 LDI OUTPUT OVERVOLTAGE Off/On
03 LDI TRANSFORMER OVERTEMP Off/On
04 LDI LOCAL ALARM 1 Off/On
05 LDI LOCAL ALARM 2 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

Siemens Building Technologies, Inc. 5-213


Open Processor with Liebert Sitelink Driver Owner's Manual

Application 5386: VCF Unit (Liebert Volt Current


Frequency Monitoring Panel)

Introduction
This section contains information specific to VCF controllers used with the Open Processor.
Figure 5-27 diagrams a Liebert Volt Current Frequency Monitoring Panel (VCF).

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0441R1

VCF

Figure 5-27. Liebert Volt Current Frequency Monitoring Panel (VCF).

The Liebert VCF unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

VCF Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Volt Current Frequency Monitoring Panel Type VCF, you must first enter a corresponding
point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

5-214 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-119.
_ Indicates a space.

Table 5-119. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Siemens Building Technologies, Inc. 5-215


Open Processor with Liebert Sitelink Driver Owner's Manual

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 13 indicates the number of points on the drop.

5-216 Siemens Building Technologies, Inc.


Chapter 5 - Applications

VCF Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-120 shows the status points for the Liebert Volt Current Frequency
Monitoring Panel (VCF), Application 5386.

Table 5-120. Liebert Volt Current Frequency Monitoring Panel (VCF). Drop One.
1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI INPUT VOLTS X-Y Volts 1.0 0
01 LAI INPUT VOLTS Y-Z Volts 1.0 0
02 LAI INPUT VOLTS Z-X Volts 1.0 0
03 LAI OUTPUT VOLTS X-N Volts 1.0 0
04 LAI OUTPUT VOLTS Y-N Volts 1.0 0
05 LAI OUTPUT VOLTS Z-N Volts 1.0 0
06 LAI OUTPUT AMPS PHASE A Amps 1.0 0
07 LAI OUTPUT AMPS PHASE B Amps 1.0 0
08 LAI OUTPUT AMPS PHASE C Amps 1.0 0
09 LAI GROUND CURRENT Amps 1.0 0
10 LAI NEUTRAL CURRENT Amps 1.0 0
11 LAI KVA KVA 1.0 0
12 LAI FREQUENCY Hz 0.1 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

VCF Unit Alarm Drop Metapoint Characteristic


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Volt Current Frequency Monitoring Panel Type VCF, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-217


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-121
_ Indicates a space.

Table 5-121. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

5-218 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of points on the drop, rounded up to the nearest
multiple of 16.

Siemens Building Technologies, Inc. 5-219


Open Processor with Liebert Sitelink Driver Owner's Manual

VCF Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-122 shows the alarm points for the Liebert Volt Current Frequency
Monitoring Panel Type VCF, Application 5386.

Table 5-122. Liebert Volt Current Frequency Monitoring Panel Type VCF Alarm Points.
1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS Off/On
01 LDI OUTPUT UNDERVOLTAGE Off/On
02 LDI OUTPUT OVERVOLTAGE Off/On
03 LDI TRANSFORMER OVERTEMP Off/On
04 LDI LOCAL ALARM 1 Off/On
05 LDI LOCAL ALARM 2 Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-220 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5387: WDU Unit (Liebert Liquid Detection


LDS750 or LDS1000)

Introduction
This section contains information specific to WDU controllers used with the Open Processor.
Figure 5-28 diagrams a WDU.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0442R1

WDU

Figure 5-28. Liebert Liquid Detection LDS750 or LDS1000 (WDU). Application 5387.

The Liebert WDU unit requires three drops to map all point information. The first drop
contains status information; the second drop contains alarm information; the third drop
contains control points.

WDU Unit Status Drop Metapoint Characteristics


In order to unbundle any of the status points for the Liebert Liquid Unit, you must first enter a
corresponding point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Siemens Building Technologies, Inc. 5-221


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In mmetadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-123.
_ Indicates a space.

Table 5-123. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

Alarmable
All metapoints are not alarmable.

5-222 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 2 indicates the number of points on the drop.

WDU Unit Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-124 shows the status points for the Liebert Liquid Detection LDS750 or
LDS1000 (WDU), Application 5387.

Table 5-124. Liebert Liquid Detection LDS750 or LDS1000 (WDU).


1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI DISTANCE (See next point) 1.0 0
01 LDI UNITS FOR DISTANCE ABOVE Meters/Feet 1.0 0
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

WDU Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the WDU alarm points, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Siemens Building Technologies, Inc. 5-223


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Register.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-125.
_ Indicates a space.

5-224 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-125. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Siemens Building Technologies, Inc. 5-225


Open Processor with Liebert Sitelink Driver Owner's Manual

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 16 indicates the number of alarm strings (not individual alarm points)
multiplied by 16. Individual alarm points are mapped 0-15 for alarm string 1, 16-31 for alarm
string 2, and 32-47 for alarm string 3.

WDU Unit Alarm Point map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-126 shows the alarm points for Liebert WDU controllers, Application
5387.

Table 5-126. Liebert Liquid Detection LDS750 or LDS1000 (WDU).


1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI OMMUNICATIONS Off/On
01 LDI CABLE FAULT Off/On
02 LDI LIQUID DETECTED Off/On
1 Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2 This column indicates the value/range or engineering units or both, if known.

5-226 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Application 5388: STS Unit (Liebert Dual Output


Breaker Static Switch PDU)

Introduction
This section contains information specific to STS units used with the Open Processor. Figure
5-29 diagrams an STS unit.

NOTE: A Port Allocation Chart must be obtained from the local Liebert representative in
order to create the point database.

REPOPT OR IC109A SITELINK


GW0479R1

STS

Figure 5-29. Liebert Dual Output Breaker Static Switch PDU (STS).

The Liebert STS unit requires two drops to map all point information. The first drop contains
status information; the second drop contains alarm information.

STS Unit Status Drop Metapoint Characteristics


In order to unbundle any of the points in the first drop (known as a metadrop) for the Liebert
Dual Output Breaker Static Switch PDU Type STS, you must first enter a corresponding point
(known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Siemens Building Technologies, Inc. 5-227


Open Processor with Liebert Sitelink Driver Owner's Manual

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_H_yyy

where: xx is the address of the Sitelink.


H Indicates you are reading Holding Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-127.
_ Indicates a space.

Table 5-127. Starting Registers.

Port Number Starting Register (yyy)


1 001
2 025
3 049
4 073
5 097
6 121
7 145
8 169
9 193
10 217
11 241
12 265

5-228 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 24 indicates the number of points on the drop.

STS Status Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-128shows the Status Points for Liebert Dual Output Breaker Static
Switch PDU (STS), Application 5388.

Siemens Building Technologies, Inc. 5-229


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-128. Liebert Dual Output Breaker Static Switch PDU (STS), Status Point Map.
1,2
Point Type Descriptor Range/Units Slope Intercept
00 LAI TRANSFER COUNT 1.0 0
01 LDI PREFERRED SOURCE Source 2/ Source 1
02 LAI LOAD ON SOURCE 1 OR 2 1 = Source 1 1.0 0
2 = Source 2
03 LAI SOURCE 1 VOLTS A-B Volts 1.0 0
04 LAI SOURCE 1 VOLTS B-C Volts 1.0 0
05 LAI SOURCE 1 VOLTS C-A Volts 1.0 0
06 LAI SOURCE 1 AMPS A Amps 1.0 0
07 LAI SOURCE 1 AMPS B Amps 1.0 0
08 LAI SOURCE 1 AMPS C Amps 1.0 0
09 LAI SOURCE 1 FREQUENCY Hz 0.1 0
10 LAI SOURCE 2 VOLTS A-B Volts 1.0 0
11 LAI SOURCE 2 VOLTS B-C Volts 1.0 0
12 LAI SOURCE 2 VOLTS C-A Volts 1.0 0
13 LAI SOURCE 2 AMPS A Amps 1.0 0
14 LAI SOURCE 2 AMPS B Amps 1.0 0
15 LAI SOURCE 2 AMPS C Amps 1.0 0
16 LAI SOURCE 2 FREQUENCY Hz 0.1 0
17 LAI KVA KVA 1.0 0
18 LAI KW KW 1.0 0
19 LAI AUTO TRANSFER TIME 1.0 0
20 LAI NOM. VOLTAGE DEVIATION Volts 1.0 0
21 LAI PHASE DIFF. LIMIT 1.0 0
22 LAI FREQUENCY DEVIATION Hz 0.1 0
23 LDI AUTO-TRANSFER ENABLED Disabled/Enabled
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

5-230 Siemens Building Technologies, Inc.


Chapter 5 - Applications

STS Unit Alarm Drop Metapoint Characteristics


In order to unbundle any of the points in the second drop (known as a metadrop) for the
Liebert Dual Output Breaker Static Switch PDU (STS), you must first enter a corresponding
point (known as a metapoint) to describe that drop.

Point Name
The point name of the metapoint may be any name. It is suggested, however, that you use a
name which helps describe the point, making it easy to associate the points on the drop with
the name.

Point Type
All metapoints are LAO.

Point Descriptor

NOTE: Unlike other System 600 APOGEE points, the Descriptor field for the points in the
metadrop is not optional. Neither is it left to the user to determine the contents of
this field. In metadrop points, the Descriptor field is used to identify the Liebert
Sitelink device being described by that point.

The eight-character descriptor of the metapoint must be in all uppercase letters in the
following format:

xx_P_yyy

where: xx is the address of the Sitelink.


P Indicates you are reading bits from a Holding
Registers.
yyy is the starting register, which is dependent upon
the port to which the device is attached. See
Table 5-129.
_ Indicates a space.

Siemens Building Technologies, Inc. 5-231


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-129. Starting Registers.

Port Number Starting Register (yyy)


1 289
2 294
3 299
4 304
5 309
6 314
7 319
8 324
9 329
10 334
11 339
12 344

Alarmable
All metapoints are not alarmable.

Totalize
All metapoints cannot be totalized.

Engineering Units
Engineering units do not apply to metapoints.

Point Address
The point address should reflect which Trunk and Field Panel Number for the Open
Processor to Liebert Sitelink Driver. The LAN is 3, and the Drop is 30. The Point Number is
the drop number (1 to 94) to which the points will be mapped. Refer to the Point Database
Guidelines section in Chapter 4 - Point Database for further information.

Slope
All metapoints have a slope of 1.0.

5-232 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Intercept
All metapoints have an intercept of 0.

Initial Value

The initial value of 48 indicates the number of points on the drop rounded up to the nearest
multiple of 16.

STS Unit Alarm Point Map


Once the metapoint is unbundled, any of the following points may be unbundled on that
drop. See Chapter 4 - Point Database for more information on LAN and Drop numbers for
these points. Table 5-130shows the Alarm Points for the Liebert Dual Output Breaker Static
Switch PDU (STS), Application 5388.

Table 5-130. Liebert Dual Output Breaker Static Switch PDU (STS), Alarm Point Map.
1,2
Alarm Point Type Descriptor Range/Units
String
1 00 LDI COMMUNICATIONS No/Yes
01 LDI LOGIC FAILURE No/Yes
02 LDI EQUIPMENT OVERTEMPERATURE No/Yes
03 LDI POWER SUPPLY 1 FAULT No/Yes
04 LDI SOURCE 1 OVERVOLTAGE No/Yes
05 LDI SOURCE 1 UNDERVOLTAGE No/Yes
06 LDI SOURCE 2 OVERVOLTAGE No/Yes
07 LDI SOURCE 2 UNDERVOLTAGE No/Yes
08 LDI SOURCE 1 OVERLOAD No/Yes
09 LDI SHORTED SCR 1 No/Yes
10 LDI SHORTED SCR 2 No/Yes
continued on next page...

Siemens Building Technologies, Inc. 5-233


Open Processor with Liebert Sitelink Driver Owner's Manual

1,2
Alarm Point Type Descriptor Range/Units
String
2 16 LDI OPEN SCR 1 No/Yes
17 LDI OPEN SCR 2 No/Yes
18 LDI FAN FAILURE No/Yes
19 LDI SOURCE 2 OVERLOAD No/Yes
20 LDI POWER SUPPLY 2 FAULT No/Yes
21 LDI FREQUENCY DEVIATION No/Yes
22 LDI TRANSFER INHIBIT No/Yes
23 LDI AUTO RE-TRANSFER PRIMED No/Yes
24 LDI OUT OF SYNC No/Yes
25 LDI SOURCE 1 FAILURE No/Yes
26 LDI SOURCE 2 FAILURE No/Yes
3 32 LDI RE-TRANSFER FAILURE No/Yes
33 LDI OVERLOAD No/Yes
34 LDI CONTROL FUSE 1 BLOWN No/Yes
35 LDI CONTROL FUSE 2 BLOWN No/Yes
36 LDI SOURCE 1 CB 1 OPEN No/Yes
37 LDI SOURCE 2 CB 2 OPEN No/Yes
38 LDI OUTPUT CB 3A OPEN No/Yes
39 LDI CUSTOM ALARM 1 No/Yes
40 LDI CUSTOM ALARM 2 No/Yes
41 LDI BYPASS CB4 CLOSED No/Yes
42 LDI BYPASS CB5 CLOSED No/Yes
4 48 LDI OUTPUT CB 3B OPEN No/Yes
49 LDI CUSTOM ALARM #4 Off/On
50 LDI CUSTOM ALARM #5 Off/On
51 LDI CUSTOM ALARM #6 Off/On
52 LDI CUSTOM ALARM #7 Off/On
53 LDI CUSTOM ALARM #8 Off/On
1. Values noted for LDIs and LDOs are in the following format: OFF text/ON text.
2. This column indicates the value/range or engineering units or both, if known.

5-234 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Diagnostic Points

Core Control and Diagnostic Points


For troubleshooting in the field, diagnostic points are available on FLN 3, Drop 31. During
startup and subsequent operation, these points can be used to determine whether the Open
Processor is operational and, if not, the source of the problem.

CAUTION:
Changing any of these diagnostic points can adversely affect your control and
communication. It is not recommended to change these points except by the
direction of Field Support.

Table 5-131 defines the use of the standard diagnostic and control points on FLN 3, Drop 31.
The Diagnostic Control (Point 20) controls the counters (points 22 to 30) by using settings 0
through 2.

Siemens Building Technologies, Inc. 5-235


Open Processor with Liebert Sitelink Driver Owner's Manual

Table 5-131. Liebert Sitelink Reserved Diagnostic Points.

Point Type Name Descriptor Slope Intercept


02 LDI COMFAL Communications failure = On
Communications normal = Off
06 LAO RSPINT Maximum time (ticks) to receive response from 1.0 0
sitelink in 1/64ths of a second
20 LAO DIAGCL Diagnostic control: 1.0 0
0 disable diagnostic counts (pts 21-35)
1 enable diagnostic counts
2 reset and enable diagnostic counts
10 disable datascope to debug port
11 enable datascope to debug port (raw)
12 enable datascope to debug port (hex)
13 enable datascope to debug port (ASCII)
20 disable events to datascope
21 enable events to datascope
30 disable gw_printf() output
31 enable gw_printf() output
40 disable debug port
41 debug port output to AUX port
42 debug port output to MMI/MODEM port
21 LAI RESPON Total number of responses 1.0 0
22 LAI GOODPK Number of times Driver returned 1.0 0
GOOD_PACKET
23 LAI NAK Number of times Driver returned 1.0 0
NAK_RESPONSE
24 LAI BADSEQ Number of times Driver returned 1.0 0
BAD_SEQUENCE
25 LAI UNKNPK # of times Driver returned 1.0 0
UNKNOWN_PACKET
26 LAI BADPTY Number of times driver indicated parity error 1.0 0
27 LAI BADPK Number of times Driver returned 1.0 0
BAD_PACKET
28 LAI NORESP Number of times Driver returns 1.0 0
NO_RESPONSE
continued on next page...

5-236 Siemens Building Technologies, Inc.


Chapter 5 - Applications

Table 5-131. Liebert Sitelink Reserved Diagnostic Points.

Point Type Name Descriptor Slope Intercept


29 LAI TX Total number of transmissions 1.0 0
30 LAI BADTX Number of times error occurred in sending 1.0 0
packet
31 LAI OVRRUN Number of times driver indicated overrun 1.0 0
32 LAI FRAME Number of times driver indicated framing error 1.0 0
33 LAI HWERR Number of times driver indicated hardware 1.0 0
error
34 LAI BREAK Number of times break received 1.0 0
64 LAO Maximum Maximum wait time (ticks) in 1/64ths of a 1.0 0
Delay second for a response when performing a read
after Read operation from a Modbus slave

Siemens Building Technologies, Inc. 5-237


Open Processor with Liebert Sitelink Driver Owner's Manual

5-238 Siemens Building Technologies, Inc.


6
Troubleshooting

Chapter Overview
Chapter 6 describes corrective measures you can take if you encounter a problem with the
Open Processor. If you encounter a symptom or a problem not covered in this manual,
contact your local Siemens Building Technologies representative.

Chapter 6 covers the following topics:

Basic Service Information

Ordering Replacement Parts

Open Processor Troubleshooting

Open Processor Operation

Point Operation

Communications with Liebert Sitelink System

Replacing the Battery

WARNING:
The Point Termination Module (PTM) manual override switch is not
intended to be used as a safety device when performing maintenance. If
you use the PTM manual override switch as a safety device, it may
result in serious injury to personnel and may damage property in the
area. Continue to follow safety procedures when performing
maintenance.

Basic Service Information


To determine that the Open Processor is powered up and communicating properly, verify that
the STATUS LED on the Open Processor is flashing ON and OFF once per second. (Upon
power-up, it may take five to six seconds for the STATUS LED to begin flashing.)

Siemens Building Technologies, Inc. 6-1


Open Processor with Liebert Sitelink Driver Owner's Manual

NOTE: When you troubleshoot, record what the problem is and what actions you
performed immediately before the problem occurred. Being able to describe the
problem in detail is important should you need assistance from your local Siemens
Building Technologies representative.

When you turn off power to an Open Processor to perform maintenance or service, make
sure that the person in charge of the facility is aware of this and that appropriate steps are
taken to keep the building in control.

To view the status of the Open Processor and to call up reports for troubleshooting, you can
use an operator's terminal and the operator interface or an Insight workstation. For more
information, refer to the following manual(s):

System 600 APOGEE Field Panel User's Manual (125-3000).

System Management volume of the Insight for Personal Computers User's Set (125-
1854).

Advanced Operations volume of the Insight for Minicomputers User's Set (125-1910).

CAUTION:
To prevent damage to the Open Processor, wear an anti-static wrist
strap when you install or service an Open Processor. Failure to do
so may allow an electrostatic discharge to pass from your body to
the equipment, causing irreparable damage.

Ordering Replacement Parts


If an Open Processor, Controller Module, Power Module, or PTM is not operating correctly, it
should be replaced. Contact your local Siemens Building Technologies representative for
ordering and replacement information.

Open Processor Troubleshooting


Find the symptom (in boldface type) that best describes the problem. Perform the corrective
action that follows. If the problem persists or other symptoms are present, contact your local
Siemens Building Technologies representative.

NOTE: Ensure that you back up your Open Processor database before continuing.

Open Processor Operation


Which of the following best describes the problem?

6-2 Siemens Building Technologies, Inc.


Chapter 6 - Troubleshooting

A. No LEDs on the Open Processor are illuminated.

1. Check that there is power to the MBC or RBC enclosure.


2. Check that power to the field panel is turned ON.
3. Turn OFF power to the field panel. Turn ON power to the field panel.
4. Contact your local Siemens Building Technologies representative.

B. The STATUS LED is illuminated (steadily) on the Open Processor.

WARNING:
To avoid injuring either personnel or equipment, be sure that all
equipment is in manual mode.

1. Turn OFF power to the field panel. Turn ON power to the field panel.
2. Contact your local Siemens Building Technologies representative.

C. The BATT LOW LED is illuminated (steadily). Battery low warning


displayed at operators terminal (optional).

1. Check that the mylar insert has been removed from the battery holder.
2. Check that the battery is properly installed (+ to + and to ) and that it is seated
properly in its holder.
3. Refer to the Replacing the Battery section later in this chapter.
4. Turn OFF power, and then remove and reinstall the Open Processor. Turn ON
power.
5. Contact your local Siemens Building Technologies representative.

D. The MMI prompt line does not appear.

1. Verify baud rates of operator terminal. Change them to match the MMI port.
2. Make sure that the memory board is properly seated.
3. Contact your local Siemens Building Technologies representative.

E. The FLN TX and FLN1 RX LEDs on the front of the Open Processor
do not flash.

1. Verify that there is at least one point in the Open Processor.


2. Disconnect the FLN 1 Trunk cable that connects the Open Processor to the Trunk
Interface II to see if the problem disappears. If the LEDs start flashing, the wiring
may be bad. Check the wiring polarity between the Trunk Interface II and the Open
Processor: + to +, to , shield connected at the Open Processor, but
disconnected at the Trunk Interface II.

Siemens Building Technologies, Inc. 6-3


Open Processor with Liebert Sitelink Driver Owner's Manual

3. Contact your local Siemens Building Technologies representative.

Point Operation
Which of the following best describes the problem?

A. All the Point Termination Module (PTM) points in an enclosure read


failed (*F*).

1. Check that the power to the field panel is turned ON.


2. Check that all electrical connections are secure.
3. Ensure that only one Open Processor or Controller Module has the M-bus enabled.
4. Contact your local Siemens Building Technologies representative.

B. All points addressed in the Open Processor appear as failed (*F*).

1. Verify that the points have the correct addresses and that there are no duplicate
addresses.
2. Check that points are defined with the proper type, slope, and intercept. Refer to
Chapter 5 - Applications, for more information.
3. Verify that all physical connections are secure.
4. Verify baud rates of FLN port.
5. Contact your local Siemens Building Technologies representative.

C. Some or all points addressed in the Open Processor display


incorrect values.

1. Verify that the points have the correct addresses and that there are no duplicate
addresses.
2. Check that the points are defined with the proper type, slope, intercept, etc. Refer to
Chapter 5 - Applications, for more information.
3. Contact a Liebert representative to ensure that the Liebert Sitelink system has been
installed and certified, and that it is operating according to their procedures.
4. Contact your local Siemens Building Technologies representative.

D. A group of points associated with a specific Liebert equipment


controller appears as failed (*F*).

1. Verify that the points have the correct address and that there are no duplicate
addresses.
2. Check that the points are defined with the proper type, slope, intercept, etc. Refer to
Chapter 5 - Applications, for more information.

6-4 Siemens Building Technologies, Inc.


Chapter 6 - Troubleshooting

3. Check that the communication status points appear as normal (-N-).


4. Contact a Liebert representative to ensure that the Liebert system has been
installed and certified, and that it is operating according to their procedures.
5. Contact your local Siemens Building Technologies representative.

Communications with Liebert System


Which of the following best describes the problem?

A. No communications with the Liebert system.

1. Check the FLN trunk connectors for proper orientation. The screws for the
connectors should face down at the Open Processor.
2. Verify that the Black Box (IC109A) switch settings are correct.
3. Verify that the wiring terminations between the open processor driver and the
REPOPT or Black Box (IC109A) are correct. Refer to the Installation Instructions.
4. Verify that the wiring terminations between the REPOPT/Black Box (IC109A) and the
Liebert Sitelink are correct. Refer to the Installation Instructions.
5. Verify that the metapoints for each Liebert Equipment Controller are defined
properly.
6. Verify that the points for each Liebert Equipment Controller have addresses
associated with the appropriate metapoint.
7. Verify that the cabinet is made ready.
8. Check that points are defined with the proper type, slope, and intercept. Refer to
Chapter 5, Applications, for more information.
9. Contact your local Siemens Building Technologies representative.

B. Limited or no communication with one or more Liebert Equipment


Controllers.

1. Check that the points have the correct address and that there are no duplicate
addresses.
2. Verify that the Liebert Equipment Controllers are connected to the correct port on the
Liebert Sitelink and that the connectors have the proper orientation.
3. Contact your local Siemens Building Technologies representative.

Replacing the Battery


Replacement battery kits with ten, non-rechargeable lithium batteries and pull tabs are
available only from your local Siemens Building Technologies representative.

Order using product number 545-710.

Siemens Building Technologies, Inc. 6-5


Open Processor with Liebert Sitelink Driver Owner's Manual

CAUTION:
Use only factory-authorized replacement batteries. Failure to do so may
result in equipment damage or data loss.
Leave the AC power to the Open Processor ON during battery
replacement. You will lose data if power is turned OFF and the battery is
low or is removed.

Required tools
None.

Instructions
Follow these procedures to replace the battery backup of the Open Processor:

1. With the AC power to the Open Processor turned ON, lift up the front cover of the Open
Processor to expose the battery. Refer to Figure 6-1.

2. Remove the old battery from holder by pulling on the tab.

3. Properly discard the old battery and tab.

4. Insert the new battery through the loop of the new pull tab.

5. Insert the battery and pull tab combination back into the battery holder with the plus (+)
and minus () ends aligned as shown in Figure 6-1.

6. Close the cover of the Open Processor.

Figure 6-1. Battery Replacement.

6-6 Siemens Building Technologies, Inc.


Glossary
Overview
The glossary contains terms and acronyms that are used in this manual. For definitions of
point database descriptors, refer to Chapter 4 - Point Database, of this manual. For definitions
of commonly used terms as well as acronyms and abbreviations associated with the System
600 APOGEE, refer to the Siemens Building Technologies Technical Glossary of Building
Controls Terminology and Acronyms (125-2185). This glossary is available from your local
Siemens Building Technologies representative.

address key
Point Termination Module (PTM) component that provides the PTM address for the Open
Processor and the point database.

alarm priority
Ranking of a point alarm.

analog input-electric
Analog input point that receives either a current, voltage, or resistance input signal.

analog output-pneumatic
Analog output point that outputs a pneumatic signal.

BLN
See Building Level Network.

Building Level Network


(BLN, also known as Protocol 2, P2, or peer-to-peer network). A data communications
network providing connections within or between buildings for building controllers and
workstations.

C-BUS
Communications BUS. The low voltage power pathway between the Open Processor and the
Power Module.

Siemens Building Technologies, Inc. Glossary-1


Open Processor with Liebert Sitelink Driver Owner's Manual

command priority
Ranking of a point command.

current value
Last commanded or sensed value of a logical point.

digital value
Integer value used by the Open Processor to determine the logical value, state, and the
condition of logical points.

drop
Address of an electronic device that can communicate with a field panel through a direct
connection to either the local point termination or to one of three FLN ports. When associated
with a point that has no physical device, the drop serves as an address of a memory location
for the point.

dynamic point information


Information stored in the point database that may change during system operation and that is
not part of the data entered when defining points.

enclosure
Metal case that houses the Open Processor and other MBC or RBC components.

English units
The foot-pound-second system of units for weights and measurements.

Enhanced Alarming
An application that allows multiple alarm limits, specific alarm reporting locations, and variable
alarm limit set points.

FLN
Floor level network. A data communications network (either Protocol 1 or other vendor
protocols) providing connections within a room or building for application-specific controllers.

Glossary-2 Siemens Building Technologies, Inc.


Glossary

IGM
Information Gathering Module. Used to describe the various Liebert devices such as Air
Conditioning Unit, UPS, and Power Unit.

IGMnet
Information Gathering Network. The media (RS-422 or RS-485) that Control Modules use to
communicate with the various IGMs.

Liebert driver
Software contained in the Open Processor that allows the Liebert system to communicate
directly with the System 600 APOGEE.

literature pocket
Metal slipcase in the MBC or RBC enclosure for storing layout sheets or documentation.

Metadrop
Drop 30 of FLN 3 in the System 600 point addressing scheme, used to define metadrop
points (metapoints) 00 through 94 for an equipment controller or device from another vendor's
system.

Metadrop Point
See Metapoint.

Metapoint
Logical point in an Open Processor that identifies an equipment controller or device and
defines the address location of its associated point.

MBC
Modular Building Controller. A System 600 field panel with replaceable Open Processors, and
Power, Controller, and Point Termination Modules.

M-BUS
Module BUS. The low voltage and communication pathway between the Open Processor and
the Point Termination Modules.

Siemens Building Technologies, Inc. Glossary-3


Open Processor with Liebert Sitelink Driver Owner's Manual

M-BUS rail
Low voltage and communication hardware pathway between the Open Processor and the
Point Termination Modules.

mounting rail
The hardware on which the MBC modules are installed.

Open Processor
Modular component that contains the brains of the MBC or RBC enclosure. The Open
Processor holds the processor, memory chips, analog-to-digital converter, supporting
circuitry, and operator terminal ports. The Open Processor is capable of supporting various
protocol drivers.

point condition
State of a point such as normal, alarm, alarm-by-command, failed or operator disabled.

point module
Component of a PTM which provides the signal conversion between the MBC or RBC
enclosure and the field input or output point.

PTM
Point Termination Module. The interface between the Open Processor and the field device.

RBC
Remote Building Controller. A System 600 field panel with replaceable Open Processors, and
Power, Controller, and Point Termination Modules.

REPOPT
Liebert communication accessory which converts the Sitelink RS-232 signal to RS-485.

service box
An MBC or RBC enclosure component that receives the line power for the field panels.

Glossary-4 Siemens Building Technologies, Inc.


Glossary

Sitelink
Liebert communication interface which utilizes Modbus RTU protocol. There are two types of
Sitelink; the DC12I version which allows connection of up to 12 Liebert devices, and the DC4
which allows connection of up to 4 Liebert devices.

termination block
The component of the PTM at which the field devices are terminated.

text-based terminal
Operator terminal which displays and accepts text only.

totalized value
Sum of information (in hours or minutes) about logical points such as run time, total volume,
and, degree days.

unbundle
Term used to describe the action of entering a point that resides in an equipment controller's
database into the field panel's database so that it can be monitored at and/or controlled from
the field panel.

Siemens Building Technologies, Inc. Glossary-5


Open Processor with Liebert Sitelink Driver Owner's Manual

Glossary-6 Siemens Building Technologies, Inc.


Index

A D
access group.................................................4-13 Database
address point address............................................... 4-6
FLN..............................................................4-7 Date attribute ................................................ 4-16
point.............................................................4-6 Date/Time attribute ....................................... 4-16
Alarm Management.........................................3-2 Daylight Savings Time .................................... 3-2
alarming ........................................................4-13 Dial-Up............................................................ 3-2
Analog Input (AI) .............................................4-2 Digital Input (DI).............................................. 4-3
Analog Output (AO) ........................................4-2 Digital Output (DO) ......................................... 4-3
analog point attributes...................................4-16 digital point attributes
Date ...........................................................4-16 other digital point....................................... 4-17
Date/Time..................................................4-16 drop................................................................. 4-6
Float...........................................................4-16 Duty Cycling.................................................... 3-2
Integer .......................................................4-16
Time ..........................................................4-16 E
applications .....................................................5-2 EMER point priority......................................... 4-9
Applications, by name engineering units .......................................... 4-12
Liebert Environmental Unit Australia/Atlas Air Enthalpy and Dry Bulb Economizer Control.... 3-2
(C10)........................................................5-4 Equipment Controller Coordinator .................. 3-2
Auto-Dial .........................................................3-2 Expansion Module Kits ................................... 2-6
B F
BATT LOW .....................................................2-5 field equipment ............................................... 2-7
battery backup.................................................2-5 field input/output points................................... 2-6
battery replacement ........................................6-5 Field Panel Coordinator .................................. 3-2
product number ...........................................6-5 FLN ..................................See floor level network
BLN ............................ See building level network FLN address ................................................... 4-7
BLN RX ...........................................................2-5 FLN TX ........................................................... 2-4
BLN TX ...........................................................2-5 Troubleshooting .......................................... 6-3
building level network......................................1-3 FLN1 RX ..................................................2-4, 2-5
C Troubleshooting .......................................... 6-3
Float attribute................................................ 4-16
C-BUS .............................................................2-3 floor level network........................................... 1-2
Change of Value (COV) limit.........................4-15
commanding over the network........................1-3 G
communications gathering and processing field inputs ............. 1-2
troubleshooting system ...............................6-5
compatibility ....................................................1-1 I
Components
Liebert........................................................2-10 IC109A RS-232 to RS-485 Converter............. 2-9
control program Integer attribute............................................. 4-16
execution of .................................................1-2 L
control strategy................................................1-2
LEDs ............................................................... 2-4
Liebert

Siemens Building Technologies, Inc. Index-1


Open Processor with Liebert Sitelink Driver

IGMnet.......................................................2-10 peer-to-peer network ..See building level network


Liebert Environmental Unit Australia/Atlas Air physical point address .................................. 4-15
(C10) physical points ................................................ 4-2
C10 (Liebert Environmental Unit point address .........................................4-6, 4-14
Australia/Atlas Air ) ..................................5-4 drop ............................................................. 4-6
literature pocket ..............................................2-8 point alarming ............................................... 4-13
Local Area Network (LAN) Controller..............1-1 point attributes .............................................. 4-10
local points ...............................................4-2, 4-4 access group............................................. 4-13
Logical ENUMerated (LENUM) point ............4-15 Change of Value (COV) limit..................... 4-15
logical points ...................................................4-2 engineering units....................................... 4-12
types of ........................................................4-2 other analog point attributes...................... 4-16
Loop Tuning ....................................................3-2 other digital point....................................... 4-17
point address............................................. 4-14
M point alarming............................................ 4-13
MBC .................. See Modular Building Controller point descriptor.......................................... 4-12
M-BUS..................................... See Modular BUS point name ................................................ 4-11
Metadrops .....................................................4-22 point totalization ........................................ 4-14
MMI/modem port.............................................2-8 point type................................................... 4-12
communication speed of .............................2-8 state .......................................................... 4-15
modem ............................................................2-8 point characteristics ........................................ 4-4
Modular Building Controller.............................2-3 point database ................................................ 4-1
compatibility.................................................1-1 point naming conventions ........................... 4-5
Modular BUS...................................................2-6 point descriptor ............................................. 4-12
point name .............................................4-4, 4-11
N Point operation
troubleshooting............................................ 6-4
naming conventions ........................................4-5 point priority .................................................... 4-8
NONE point priority .........................................4-9 EMER.......................................................... 4-9
O NONE.......................................................... 4-9
OPER .......................................................... 4-9
Open Processor PDL ............................................................. 4-9
applications..................................................5-2 SMOKE ....................................................... 4-9
battery backup .............................................2-5 point states ................................................... 4-10
connections .................................................2-4 point status ..................................................... 4-7
description ...................................................2-3 point system name.......................................... 4-4
LEDs............................................................2-4 Point Termination Modules ......................2-3, 2-6
memory .......................................................1-3 troubleshooting............................................ 6-4
multiple Open Processors in one enclosure 2-3 point totalization ............................................ 4-14
operation of .................................................1-2 point type ...................................................... 4-12
other ............................................................2-5 point values................................................... 4-10
software.......................................................3-1 points
troubleshooting ............................................6-2 local......................................................4-2, 4-4
OPER point priority .........................................4-9 logical .......................................................... 4-2
operator commands ........................................1-3 naming conventions .................................... 4-5
operator interface.....................................2-7, 3-1 physical ....................................................... 4-2
operator terminals ...........................................2-7 subpoints..................................................... 4-2
Other Open Processors ..................................2-5 virtual....................................................4-2, 4-3
Power Module..........................................2-3, 2-6
P Powers Process Control Language ................ 3-2
P2............................... See building level network PPCL .... See Powers Process Control Language
parts, ordering replacement ............................6-2 printer
PDL point priority.............................................4-9 alarm ........................................................... 1-3
Peak Demand Limiting (PDL) .........................3-2 priority

Index-2 Siemens Building Technologies, Inc.


Index

point.............................................................4-8 subpoints ........................................................ 4-2


Protocol 2 ................... See building level network system configuration....................................... 2-1
PTM ...................See Point Termination Modules
T
R
thermistors .................................................... 4-16
RBC....................See Remote Building Controller Time attribute................................................ 4-16
Remote Building Controller .............................2-3 Time-Of-Day (TOD) Scheduling ..................... 3-2
compatibility.................................................1-1 Totalize ......................................................... 4-14
operation of .................................................1-1 Trend Data Collection ..................................... 3-2
replacement parts, ordering ............................6-2 troubleshooting ............................................... 6-2
RS-232 port.....................................................2-8 battery replacement .................................... 6-5
Open Processor .......................................... 6-2
S Point Termination Modules ......................... 6-4
slope and intercept constants .......................4-17 points........................................................... 6-4
SMOKE point priority.......................................4-9 system communications.............................. 6-5
Stand-alone Control Unit (SCU)......................1-1 V
Start/Stop Time Optimization ..........................3-2
state ..............................................................4-15 video display terminals ................................... 2-7
STATUS..........................................................2-5 virtual point address...................................... 4-15
STATUS LED...........................................6-1, 6-3 virtual points.............................................4-2, 4-3
status lights
Open Processor ..........................................2-4

Siemens Building Technologies, Inc. Index-3


Open Processor with Liebert Sitelink Driver

Index-4 Siemens Building Technologies, Inc.