Resolucion examen final albailera Estructural

PROBLEMA 1
Disear el muro del eje A (1 Piso) en albailera confinada

3.00 1.00
X-2

Y-1 Y-2
Losa Aligerada 5.50
h=0.20 m

X-1
2.50

1.50 2.50

DATOS DE LA EDIFICACION:
Vivienda 3 pisos, ubicacin Arequipa
Suelo Intermedio
Muros solidos en soga (t=0.14)
f'm= 800 Ton/m2 v'm= 85 Ton/m2
f'c= 210 kg/cm2 fy= 4200 kg/cm2
h= 2.4 m Em= 400000 Ton/m2
Lx= 4.15 m
S/C = 0.25 Ton/m2 Tipico Ly= 5.65 m
S/C = 0.15 Ton/m2 Azotea

1. Calculo del peso total de la edificacion: Wi Wcm %W cv


Metrado de cargas
AREA= 23.45 m2
PISO TIPICO 1, 2 Y 3 25%S/C 100%S/C
MURO L E H PE Pg Pm
X1 2.50 0.25 2.4 1.9 2.85 2.85
X2 3.00 0.25 2.4 1.9 3.42 3.42
Y1 5.65 0.15 2.4 1.9 3.86 3.86
Y2 5.65 0.15 2.4 1.9 3.86 3.86
LOSA 5.65 4.15 0.3 7.03 7.03
Pt 5.35 3.85 0.1 2.06 2.06
S/C 5.35 3.85 0.25 1.29 5.15
Peso total 24.38 28.24
Peso por m2 1.04 1.20
PISO 4 (AZOTEA)
MURO L E H PE Pg Pm
X1 2.50 0.25 1.2 1.9 1.43 1.43
X2 3.00 0.25 1.2 1.9 1.71 1.71
Y1 5.65 0.15 1.2 1.9 1.93 1.93
Y2 5.65 0.15 1.2 1.9 1.93 1.93
LOSA 5.65 4.15 0.3 7.03 7.03
Pt 5.35 3.85 0.1 2.06 2.06
S/C 5.35 3.85 0.15 0.77 3.09
Peso total 16.87 19.18
Peso por m2 0.72 0.82

25%S/C 100%S/C
Piso hi Wg(ton/m2) Pg(ton) Wm(ton/m2) Pm(ton)
1 2.6 1.04 24.38 1.20 28.24
2 2.6 1.04 24.38 1.20 28.24
3 2.6 1.04 24.38 1.20 28.24
4 2.6 0.72 16.87 0.82 19.18
= 90.01 103.91

2. Densidad Minima de Muros:


Z 0.4
U 1.0
S 1.2
N 3
ZUSN/56 0.0257

Muros direccion X

MURO t (m) L (m) L*t (m)


X-1 0.24 2.500 0.600
X-2 0.24 3.000 0.720
= 1.3200 OK
L.t/Ap= 0.0563 NO PASA

0.0563 > 0.0257 OK

Muros direccion Y

MURO t (m) L(m) L*t (m)


Y-1 0.14 5.650 0.791
Y-2 0.14 5.650 0.791
= 1.500
L.t/Ap 0.0640

0.0640 > 0.0257 OK

3. Calculo del Cortante Basal

Z U C S
v Pi
R
Segn la Norma Tecnica de Edificacion E. 030

CALCULO DEL FACTOR DE ZONA (Z)

La edificacion se encuentra en Arequipa, por lo tanto se encuentra en una zona tipo 3


Segn eso :

Z= 0.4

CALCULO DE LA CATEGORIA DE USO (U)

Por ser una edificacin comun (Vivienda Multifamiliar) , es de categoria C


Segn eso:

U= 1.0
CALCULO DEL FACTOR DEL SUELO (S)

Por ser un suelo intermedio cuyos componentes principales son la arena y la grava,
es de tipo S2; Segn eso:

S= 1.2

CALCULO DEL FACTOR DE AMPLIFICACION SISMICA (C)

T
C 2 .5 P C 2.5 hn
T
T CT
Por ser suelo tipo S2, el periodo del suelo es :

Tp = 0.6

La altura de la edificacion es de :

hn = 10.40 m
Como en la edificacin hay predominio de muros de corte y elementos de concreto
armado, entonces:

Ct = 60

Entonces:

T= 0.17
C= 8.65

Como C no debe ser mayor de 2,5, entonces:

C= 2.50

CALCULO DEL COEFICIENTE DE REDUCCION DE FUERZA SISMICA (R)

Consideraremos un sismo moderado, entonces:

R= 6

Por ultimo se verifica que:

C
0.1
R

C/R = 0.42 OK ! ! !

FUERZA CORTANTE EN LA BASE

V= 18.00 Tn % Peso Total = 20 %

DISTRIBUCION DEL CORTANTE BASAL Pi hi


Fi v
Pi hi
Pi h i Fi Cortante
Piso Pi hi Pi x hi Pi h i por piso Vp
1 24.38 2.6 63.39 0.11 2.05 18.00
2 24.38 5.2 126.78 0.23 4.11 15.95
3 24.38 7.8 190.17 0.34 6.16 11.84
4 16.87 10.4 175.41 0.32 5.68 5.68
555.74 18.00

5.68
5.68
6.16
11.84

4.11
15.95

2.05
18.00

4. CENTRO DE MASAS

MURO t (m) L (m) h (m) (ton/m3) Peso (tn) Y X


X-1 0.25 2.500 2.4 1.9 2.85 0.075 2.825
X-2 0.25 3.000 2.4 1.9 3.42 5.575 1.575

Y-1 0.15 5.650 2.4 1.9 3.86 2.825 0.075


Y-2 0.15 5.650 2.4 1.9 3.86 2.825 4.075
14.00

Por lo tanto :

X cm = 2.11 m
Y cm = 2.94 m

5. CALCULO CENTRO DE RIGIDECES.


m t
K 3
h h
1er piso 4 3
L L

Direccin X
MURO t (m) h (m) L (m) Kx Y Kx*Y
X-1 0.24 2.4 2.500 14955.731 0.075 1121.680
X-2 0.24 2.4 3.000 21582.7338 5.575 120323.741
36538.4648 121445.421
Ycr =
Direccin Y
MURO t (m) h (m) L (m) Ky X Ky*X
Y-1 0.14 2.4 5.65 35422.4235 0.075 2656.682
Y-2 0.14 2.4 5.65 35422.4235 4.075 144346.376
70844.8471 147003.058
Xcr =

6. CORTANTE TRASLACIONAL.
Ki
VD V
Ki
Piso 1

Muros K Vp Vd Muros K
X-1 14955.73 18.00 7.37 Y-1 35422.42
X-2 21582.73 18.00 10.63 Y-2 35422.42
36538.46 70844.85

Piso 2

Muros K V Vd Muros K
X-1 2526.32 15.95 6.10 Y-1 10318.65
X-2 4081.89 15.95 9.85 Y-2 10318.65
6608.21 20637.29

Piso 3

Muros K V Vd Muros K
X-1 790.14 11.84 4.43 Y-1 4066.57
X-2 1321.70 11.84 7.41 Y-2 4066.57
2111.84 8133.13

Piso 4

Muros K V Vd Muros K
X-1 338.14 5.68 2.11 Y-1 1934.30
X-2 573.42 5.68 3.57 Y-2 1934.30
911.56 3868.61

7. EXCENTRICIDADES DE DISEO Y MOMENTOS TORSORES

Lx = 4.15 m Accidental
e x X cr X cm
Ly = 5.65 m e xacc 0 . 05 L y e x e xacc
e y Ycr Ycm e yacc 0.05 L y e y e yacc

Nivel Xcr Ycr Xcm Ycm ex ey


Piso Tipico(1,2y3) 2.075 3.324 2.106 2.937 -0.031 0.387

Exc. De Diseo en X Exc. De Diseo en Y Exc. De


caso 1 caso 2 ex caso 1 caso 2 ey Diseo
0.177 -0.238 0.177 0.669 0.104 0.669 0.669

Momentos Torsores por nivel

MT Vp e

Piso e Vp Mt (tn.m)
1 0.669 18.002 12.048
2 0.669 15.948 10.674
3 0.669 11.842 7.926
4 0.669 5.682 3.803

6. CORTANTE ROTACIONAL.
Rigidez d d x X X CR d y Y YCR
VT MT
Rigidez d 2

Distribuido por muros


PRIMER PISO MT = 12.05 Tn-m
H= 2.40 m.

Muros K dx K*dx K*dx^2 Vt


X-1 14955.73 2.00 29911.4621 59822.9241 0.52
X-2 21582.73 2.00 43165.4676 86330.9353 0.74
146153.859

Muros K dy K*dy K*dy^2 Vt


Y-1 35422.42 3.25 115079.28 373866.00 1.98
Y-2 35422.42 2.25 79744.05 179522.28 1.37
553388.27
K.dx^2+K.dy^2= 699542.13

SEGUNDO PISO MT = 10.67 Tn-m


h= 5.00

Muros K d Kxd Kd^2 Vt


X-1 2526.32 2.00 5052.63 10105.2632 0.29
X-2 4081.89 2.00 8163.78 16327.5591 0.46
26432.8222

Muros K d Kxd Kd^2 Vt


Y-1 10318.65 3.25 33522.9029 108908.171 1.91
Y-2 10318.65 2.25 23229.6577 52295.323 1.32
161203.494
K.dx^2+K.dy^2= 187636.32

TERCER PISO MT = 7.93 Tn-m


H= 7.60

Muros K d Kxd Kd^2 Vt


X-1 790.14 2.00 1580.2748 3160.5496 0.23
X-2 1321.70 2.00 2643.40902 5286.81804 0.38
8447.36764

Muros K d Kxd Kd^2 Vt


Y-1 4066.57 3.25 13211.3321 42920.5677 1.90
Y-2 4066.57 2.25 9154.77769 3791.67 1.32
46712.2377
K.dx^2+K.dy^2= 55159.61

CUARTO PISO MT = 3.80 Tn-m


H= 10.20

Muros K d Kxd Kd^2 Vt


X-1 338.14 2.00 676.27244 1352.54488 0.10
X-2 573.42 2.00 1146.84379 2293.68758 0.16
3646.23246

Muros K d Kxd Kd^2 Vt


Y-1 1934.30 3.25 6284.10722 20415.6134 0.90
Y-2 1934.30 2.25 4354.565 3791.67 0.63
24207.2834
K.dx^2+K.dy^2= 27853.52

RESUMEN CORTANTES POR TORSION EN MUROS (Tn)

Muros 1 Piso 2 Piso 3 Piso 4 Piso


X-1 0.52 0.29 0.23 0.10
X-2 0.74 0.46 0.38 0.16
Y-1 1.98 1.91 1.90 0.90
Y-2 1.37 1.32 1.32 0.63

RESUMEN CORTANTES POR TRASLACION EN MUROS (Tn)


Muros 1 Piso 2 Piso 3 Piso 4 Piso
X-1 7.37 6.10 4.43 2.11
X-2 10.63 9.85 7.41 3.57
Y-1 7.97 7.97 5.92 2.84
Y-2 7.97 7.97 5.92 2.84

CORTANTES FINALES PARA CADA MURO DE ALBAILERIA: VE ( Tn )=Vt+Vd

Muros 1 Piso 2 Piso 3 Piso 4 Piso


X-1 7.88 5.81 4.20 2.01
X-2 9.89 10.32 7.79 3.74
Y-1 9.96 9.88 7.82 3.74
Y-2 6.60 6.65 4.61 2.22

MOMENTOS FINALES PARA CADA MURO DE ALBAILERIA: ME ( Tn-m ).

Muros 1 Piso 2 Piso 3 Piso 4 Piso


X-1 51.36 30.86 15.75 4.83
X-2 81.76 56.05 29.23 8.97
Y-1 80.89 55.01 29.31 8.99
Y-2 51.75 34.59 17.29 5.32
7-Apr-09

LxE
0.6250
0.7500
0.8475
0.8475
3.0700 m2
ton/m2

9.975

ton/m2
P*Y P*X
0.21 8.05
19.07 5.39

10.92 0.29
10.92 15.75
41.12 29.48
3.32 m.

2.08 m.

V Vd
18.00 9.00
18.00 9.00

V Vd
15.95 7.97
15.95 7.97

V Vd
11.84 5.92
11.84 5.92

V Vd
5.68 2.84
5.68 2.84

Diseo (La mayor)

e x e xacc e x e xacc
e y e yacc
e y e yacc

exacc eyacc
0.208 0.283

y Y YCR
VERIFICACION DE LOS ESFUERZOS AXIALES EN EL PRIMER PISO

Pm Pm= 103.91 ton OK


m 0 .15 f m L.t= 3.07 m2 NO PASA
L .t
fm= 800 ton/m2
0.15xfm= 120 ton/m2
Pm/L.t= 33.85 ton/m2
OK
Chequeo para cada muro

Si m 0.05 f m entonces requiere refuerzo horizontal


m= 40 ton/m2 NO
rh=0.1%
MURO X1 X2 Y1 Y2
A tributaria 2.19 2.39 8.65 7.36
Pm 9.71 10.59 38.33 32.62
Lt 0.63 0.75 0.85 0.85
m 15.53 14.12 45.23 38.49
Ref.horiz. NO NO rh=0.1% NO

RESISTENCIA AL CORTE (VR) DE LOS MUROS CONFINADOS, VERIFICACION DE RESISTENCIA AL CORTE ANTE EL SIMO MOD
Y SEVERO, Y CALCULO DE FUERZAS INTERNAS AMPLIFICADAS(Vu,Mu)

VR 0.5vmtL 0.23Pg
vm= 85 ton/m2

Reduccion de resistencia por esbeltez del muro

Ve . L
0 . 33 1
Me

PISO 1 Ve1= 36.00 ton

MURO Pg (ton) Ve(ton) Me(ton.m) L(m) VR(ton) VR/2 VR/Ve


X1 8.41 7.88 51.36 2.50 0.38 12.13 6.06 1.54
X2 9.17 9.89 81.76 3.00 0.36 13.68 6.84 1.38
Y1 33.20 9.96 80.89 5.65 0.70 32.68 16.34 3.28
Y2 28.25 6.60 51.75 5.65 0.72 32.46 16.23 4.92

Verificacion de la resistencia ante sismo severo:


VR>Ve1
VR(X-X)= 25.80 NO PASA Se tiene que considerar el aporte de la columna de confinamiento
VR(Y-Y)= 65.14 OK

CONTROL DE FISURACION
MURO Ve(ton) 0.55VR Ve<0.55VR
X1 7.88 6.67 NO PASA
X2 9.89 7.52 NO PASA
Y1 9.96 17.98 OK
Y2 6.60 17.85 OK

DISEO DE LOS MUROS DEL PRIMER PISO

DISEO DE COLUMNAS DE CONFINAMIENTO DEL MURO X-2 DEL EJE 2

fy= 4200 kg/cm2 fc= 210 kg/cm2

MURO X-2 H1= 2.4 m


C1 C2
EXTREMA INTERNA
1 Pg(ton) 9.17
2 VR(ton) 13.68
3 Mu(ton-m) 113.07
4 L(m.) 3.00
5 Lm(m) 3.00
6 Nc 2
7 M(ton-m) 96.66
8 F(ton) 32.22
9 Pc(ton) 4.59
11 T(ton) 27.63
12 C(ton) 36.81 -0.88
13 Vc(ton) 6.84 4.56
14 As(cm2) 9.66 1.28
15 As a usar 45/8"+21/2" 43/8"
10.46 2.84
16 0.8 0.8
17 An(cm2) 71.03 -89.53
18 Acf(cm2) 232.59 155.06
19 Usar 24*20 14x20
20 Ac(cm2) 480 280
21 An(cm2) 285 135
22 Asmin(cm2) 2.4 1.4
23 s1 7.28
24 s2 12.46 No predomina la
25 s3 8.00 compresion (C/<0.1*f
c*Ac)
26 s4 10
27 Zona de conf 51.4285714286
28 Estribos a: 3/8": 1@.05,6@0.075, 1/4":1@.05,
rto @.25 4@.10,rto@.25
VIGA SOLERA
29 Ts (ton) 6.84
30 As(cm2) 1.81
31 As a usar 43/8"
2.84

1/4":1@.05, 4@.10,rto@.25
CORTE ANTE EL SIMO MODERADO

OK
NO PASA
Vu (ton) Mu (ton.m) Ve<VR/2
12.13 79.00 NO PASA
13.68 113.07 NO PASA
32.68 265.56 OK
32.46 254.45 OK

de confinamiento