Components[edit]
A switchgear has two types of components:
Power conducting components, such as switches, circuit breakers, fuses, and lightning
arrestors, that conduct or interrupt the flow of electrical power
Control systems such as control panels, current transformers, potential transformers, protective
relays, and associated circuitry, that monitor, control, and protect the power conducting
components
Functions[edit]
One of the basic functions of switchgear is protection, which is interruption of short-circuit and
overload fault currents while maintaining service to unaffected circuits. Switchgear also provides
isolation of circuits from power supplies. Switchgear is also used to enhance system availability by
allowing more than one source to feed a load.
History[edit]
Switchgears are as old as electricity generation. The first models were very primitive: all components
were simply fixed to a wall. Later they were mounted on wooden panels. For reasons of fire
protection, the wood was replaced by slate or marble. This led to a further improvement, because
the switching and measuring devices could be attached to the front, while the wiring was on the
back.[3]
Housing[edit]
Switchgear for lower voltages may be entirely enclosed within a building. For higher voltages (over
about 66 kV), switchgear is typically mounted outdoors and insulated by air, although this requires a
large amount of space. Gas-insulated switchgear saves space compared with air-insulated
equipment, although the equipment cost is higher. Oil insulated switchgear presents an oil spill
hazard.
Switches may be manually operated or have motor drives to allow for remote control.
Oil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil along the path of the
arc. The vapor released by the arcing consists of hydrogen gas. Mineral oil has better insulating
property than air. Whenever there is a separation of current carrying contacts in the oil, the arc in
circuit breaker is initialized at the moment of separation of contacts, and due to this arc the oil is
vaporized and decomposed in mostly hydrogen gas and ultimately creates a hydrogen bubble
around the electric arc. This highly compressed gas bubble around the arc prevents re-striking of the
arc after current reaches zero crossing of the cycle. The oil circuit breaker is one of the oldest type of
circuit breakers.
Air[edit]
Air circuit breakers may use compressed air (puff) or the magnetic force of the arc itself to elongate
the arc. As the length of the sustainable arc is dependent on the available voltage, the elongated arc
will eventually exhaust itself. Alternatively, the contacts are rapidly swung into a small sealed
chamber, the escaping of the displaced air thus blowing out the arc.
Circuit breakers are usually able to terminate all current flow very quickly: typically between 30 ms
and 150 ms depending upon the age and construction of the device.
Gas[edit]
Main article: Sulfur hexafluoride circuit breaker
Gas (SF6) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the
dielectric strength of the SF6 gas to quench the stretched arc.
Hybrid[edit]
Main article: Hybrid switchgear modules
Hybrid switchgear is a type which combines the components of traditional air-insulated switchgear
(AIS) and SF6 gas-insulated switchgear (GIS) technologies. It is characterized by a compact and
modular design, which encompasses several different functions in one module.
Vacuum[edit]
Circuit breakers with vacuum interrupters have minimal arcing characteristics (as there is nothing to
ionize other than the contact material), so the arc quenches when it is stretched by a small amount
(<28 mm). Near zero current the arc is not hot enough to maintain a plasma, and current ceases;
the gap can then withstand the rise of voltage. Vacuum circuit breakers are frequently used in
modern medium-voltage switchgear to 40,500 volts. Unlike the other types, they are inherently
unsuitable for interrupting DC faults. The reason vacuum circuit breakers are unsuitable for breaking
high DC voltages is that with DC there is no "current zero" period. The plasma arc can feed itself by
continuing to gasify the contact material.
Carbon dioxide (CO2)[edit]
Breakers that use carbon dioxide as the insulating and arc extinguishing medium work on the same
principles as a sulfur hexafluoride (SF6) breaker. Because SF6is a greenhouse gas more potent than
CO2, by switching from SF6 to CO2 it is possible to reduce the greenhouse gas emissions by 10 tons
during the product lifecycle.[4]
Protective circuitry[edit]
Circuit breakers and fuses
Circuit breakers and fuses disconnect when current exceeds a predetermined safe level. However
they cannot sense other critical faults, such as unbalanced currentsfor example, when a
transformer winding contacts ground. By themselves, circuit breakers and fuses cannot distinguish
between short circuits and high levels of electrical demand.
Merz-Price circulating current scheme
Differential protection depends upon Kirchhoff's current law, which states that the sum of currents
entering or leaving a circuit node must equal zero. Using this principle to implement differential
protection, any section of a conductive path may be considered a node, The conductive path could
be a transmission line, a winding of a transformer, a winding in a motor, or a winding in the stator of
an alternator. This form of protection works best when both ends of the conductive path are
physically close to each other. This scheme was invented in Great Britain by Charles Hesterman
Merz and Bernard Price.[5]
Two identical current transformers are used for each winding of a transformer, stator, or other
device. The current transformers are placed around opposite ends of a winding. The current through
both ends should be identical. A protective relay detects any imbalance in currents, and trips circuit
breakers to isolate the device. In the case of a transformer, the circuit breakers on both the primary
and secondary would open.
Distance relays
A short circuit at the end of a long transmission line appears similar to a normal load, because of the
impedance of the transmission line limits the fault current. A distance relay detects a fault by
comparing the voltage and current on the transmission line. A large current along with a voltage drop
indicates a fault.
Classification
Several different classifications of switchgear can be made:[6]
Safety
See also
Arc flash
Circuit breaker
Disconnector
Electrical safety
Electric arc
High voltage
Remote racking system
Short circuit
GCK, GCS , MNS and GGD series low voltage switchgears apply to the distribution system of
power plant, substation, petrochemical industry, metallurgical industry, traffic energy and high-rise
buildings.
Working voltage: AC215V~ 660V 50 / 60Hz;
Bus-bar system up to 6300A;
Full range from 100A to 4000A
Steel Enclosure IP4X up to IP65 IP65 available upon request
GCK Low Voltage Draw able Switchgears
GGD Low Voltage Fixed Switchgears
HNGCS Low Voltage Withdraw able Switchgear
HNMNS Low Voltage Withdraw able Switchgear
XL-21 Low Voltage Power Distribution Cubicle is used in the 3-phase AC system of rated
frequency 50Hz, rated voltage 0.4kV, rated current 600A and below for power plants, substations,
civil buildings, industrial and mining enterprises. It can be used for power conversion, distribution,
field loading and local operation control, etc.
XGN2-12 Fixed AC Metal-enclosed Switchgears
XGN2-12 Fixed AC Metal-enclosed Switchgear, also called isolating breaker cubicle, is applied in
the 3-phase AC electric power system of rated voltage 10kV and rated frequency 50Hz for making
and breaking of load current. The main switches use the GN
READ MORE
Scope of application It is widely applied in the hydropower plant, the thermal power plant, the
substation and other fields needing DC devices (like power generation plant, substations, power
distribution station, petrifaction, steel, electrified
This product is used for rated voltage 400V, 1000kW hydro-generator units and below, one unit
only needs one cabinet, the Installation and maintenance for it is very convenient and simple.
Medium Voltage Switchgear
High-Voltage Substations
It takes smart approaches and powerful technologies to meet the worlds soaring demand for electrical
energy and to transmit power to where it is needed most. High-voltage substations are the node points of
the increasingly complex power transmission infrastructure. They play a key role in enabling the reliable
transmission of large amounts of power. As a turnkey contractor, Siemens offers the one-stop planning
and construction of customized, state-of-the-art high-voltage substations worldwide.
Fault calculation
Fault tree analysis (FTA) is a top down, deductive failure analysis in which an undesired state of a
system is analyzed using Boolean logic to combine a series of lower-level events. This analysis
method is mainly used in the fields of safety engineering and reliability engineering to understand
how systems can fail, to identify the best ways to reduce risk or to determine (or get a feeling for)
event rates of a safety accident or a particular system level (functional) failure. FTA is used in
the aerospace,[1] nuclear power, chemical and process,[2][3][4] pharmaceutical,[5] petrochemical and
other high-hazard industries; but is also used in fields as diverse as risk factor identification relating
to social service system failure.[6] FTA is also used in software engineering for debugging purposes
and is closely related to cause-elimination technique used to detect bugs.
In aerospace, the more general term "system Failure Condition" is used for the "undesired state" /
Top event of the fault tree. These conditions are classified by the severity of their effects. The most
severe conditions require the most extensive fault tree analysis. These "system Failure Conditions"
and their classification are often previously determined in the functional Hazard analysis.
Industrial and commercial power users are increasingly less tolerant to the frequency
and duration of outages. Some utilities have lost such customers to competitors offering
more reliable service.
The system uses specially configured S&C Remote Supervisory Vista Underground
Distribution Switchgear. Each fault interrupter way of the gear associated with the
backbone feeder is equipped with a multifunction, microprocessor-based relay. Each
substation circuit breaker feeding the loop of switchgear units is also equipped with
such a relay.
The relays communicate with each other through a high-speed fiber-optic cable
network. Relays use the established transmission relaying concepts of Permissive
Overreaching Transfer Trip (POTT) and Directional Comparison Blocking (DCB) to
ensure that only the fault interrupters on either side of a faulted backbone cable section
open. SCADA isnt required but can be readily integrated.
Any number of switchgear units can be used in the system, applied in a closed-loop or
an open-loop configuration. In either case, a backbone feeder fault is cleared in 6 cycles
or less; there's no need to trip the substation circuit breakers.
In a closed-loop application, both ends of the loop must be fed from the same
substation. Load will not be lost while a fault is being cleared, although some customers
may experience a voltage dip.
Such faults due to insulation flashover are many times temporary, i.e. if the arc path is
allowed to deionize, by interrupting the electrical supply for a sufficient period, then the arc
does not re-strike after the supply is restored. This process of interruption followed by
intentional re-energization. In low-voltage systems up to three reclosure are attempted, after
which the breaker is locked out. The repeated attempts at reclosure, at times, help in
burning out the object which is causing the breakdown of insulation. The reclosure may also
be done automatically. In EHV systems, where the damage due to short circuit may be very
large and the system stability at stake, only one reclosure is allowed.
At times the short circuit may be total (sometimes called a dead short circuit), or it may
be a partial short circuit. A fault which bypasses the entire load current through itself, is
called a metallic fault. A metallic fault presents a very low, practically zero, fault resistance.
A partial short circuit can be modelled as a non-zero resistance (or impedance) in parallel
with the intended path of the current. Most of the times, the fault resistance is nothing but
the resistance of the arc that is formed as a result of the flashover. The arc resistance is
highly nonlinear in nature. Early researchers have developed models of the arc resistance.
One such widely used model is due to Warrington, which gives the arc resistance as :
where
S is the spacing in feet
u is the velocity of air in mph
t is the time in seconds
I is the fault current in amperes.
1.2 Causes of Shunt Faults
Shunt faults are basically due to failure of insulation. The insulation may fail because of
its own weakening, or it may fail due to overvoltage. The weakening of insulation may be
due to one or more of the following factors:
Ageing
Temperature
Rain, hail, snow
Chemical pollution
Foreign objects
Other causes
The overvoltage may be either internal (due to switching) or external (due to lightening).
1.3 Effects of Shunt Faults
If the power system just consisted of isolated alternators feeding their own loads, then
the steady-state fault currents would not be qpch of a concern. Consider an isolated
turboalternator with a three-phase short circuit on its terminals as shown in Figure.2.
Assuming the internal voltage to be 1 p.u. and a value of synchronous impedance, Xd = 2
p.u., the steady-state short-circuit current would only be 0.5 p.u. which is too small to cause
any worry. However considering subtransient impedance, Xd'' = 0.1, the subtransient
current would be 10 p.u. We must not, however, forget that in an interconnected power
system all the generators (and even motors) will contribute towards the fault current, thus
building up the value of the fault current to couple of tens of times the normal full-load
current.
Faults, thus, cause heavy currents to flow. If these fault currents persist even for a short
time, they will cause extensive damage to the equipment that carry these currents. Over-
currents, in general, cause overheating and attendant danger of fire. Overheating also
causes deterioration of the insulation, thus weakening it further. Not SO apparent is the
mechanical damage due to excessive mechanlcal forces developed during a over-current.
Transformers are known to have suffered mechanical damage to their windings, due to
faults. This is due to the fact that any two current-carrying conductors experience a force.
This force goes out of bounds during faults, causing mechanical distortion and damage.
Further, in an interconnected system, there is another dimension to the effect of faults.
The generators in an interconnected power system must operate in synchronism at all
instants. The electrical power output from an alternator near the fault drops sharply.
However the mechanical power input remains substantially constant at its prefault value.
This causes the alternator to accelerate. The rotor angle 6 starts increasing. Thus, the
alternators start swinging with respect to each other. If the swing goes out of control, the
alternators will have to be tripped out. Thus, in an interconnected power system, the system
stability is at stake. Therefore, the faults need to be isolated as selectively and as speedily
as possible.