You are on page 1of 6

ook Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI

ON 17-03-2017 09:00:59 (123.63.24.35) valid up

Supplied by Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid upto31-12-2017
2.2.7 Make-Up Water The water added to a pool to The basic principles of water supply, drainage and
replace that which is lost. sanitation are given below, and the design of water
2.2.8 Pool A swimming pool or other recreational supply should in general be guided by the applicable
water basin utilized in conjunction with or as an principles.
appurtenance to a swimming pool. 3.1.1 Potable Water
NOTE The term does not refer to spas and therapy pools not
designed or intended for swimming or to basins for individual All premises intended for human habitation, occupancy,
use that are drained after each use. or use shall be provided with supply of potable water.
2.2.9 Pool Depth The vertical distance between the This water supply shall not be connected with unsafe water
pool floor and the water level. resources, nor shall it be subject to the hazards of backflow.
2.2.10 Shallow Area An area in a swimming pool, in 3.1.2 Water Provision
which the water depth does not exceed 1.5 m at any point.
Plumbing fixtures, devices and appurtenances shall be
2.2.11 Skimmer A mechanical device connected to the provided with water in sufficient volume and at pressures
recirculation piping which is used to skim the pool surface. adequate to enable them to function properly and without
2.2.12 Swimming Pool User Load The number of undue noise under normal conditions of use.
bathers using the pool in a 24 h period for whicha There should be at least a residual head of 0.018 N/mm2
certain per capita capacity is often considered. at the consumers tap. There may be certain fixtures
NOTE The capacity of a swimming pool in terms of its user or appliances in the installation that may require a
load is dictated by the capacity of water treatment equipment. higher pressure, such as 0.05 N/mm2 or even higher
2.2.13 Transition Point A location in a shallow area (such as 0.1 N/mm2 in case of flush valves), in which
of a swimming pool where an area, having a floor case the system shall be designed using pumps, tanks
slope of no more than 300 mm vertical in 3.65 m or both to achieve the required minimum pressure.
horizontal, adjoins an area where the floor slope
NOTE The residual head shall be taken at the highest/farthest
exceeds 1 in 12. outlets in the building.
2.2.14 Turnover Period The time required to 3.1.3 Water Efficiency
recirculate a volume of water equivalent to the water
volume of the pool through the filtration system. Plumbing system shall be designed, installed and
2.2.15 Wading Pool A pool having a maximum water adjusted to use the optimum quantity of water consistent
depth not exceeding 76 cm. with proper performance and cleaning.

2.2.16 Water Level The level of the overflow lip of 3.1.4 Safety Devices
a perimeter overflow system or the mid-level of surge Plumbing system shall be designed and installed with
weirs, if present, or the mid-level of the skimmer safety devices to safeguard against dangers from
operating range. contamination, explosion, overheating, etc.
2.2.17 Zero-Depth Edge That portion of the
perimeter of a zero-depth pool where the pool floor 3.1.5 Minimum Water Amenities
intersects the pool water surface. It is recommended that each dwelling unit should have
2.2.18 Zero-Depth Pool A swimming pool where at least one water closet, one lavatory, one kitchen wash
the pool floor intersects the water surface along a place or a sink, and one bathing place or shower to
portion of its perimeter. meet the basic requirements of sanitation and personal
hygiene.
3 GENERAL
In case of a group housing, the requirements relating
3.1 Basic Principles
to toilet or sanitary room and kitchen as given in 13
The design of water supply takes the following into and B-9 of Part 3 Development Control Rules and
consideration: General Building Requirements of the Code shall also
a) Number of occupants; be complied with.
b) Minimum water requirements for different 3.1.6 Drainage System
purposes;
The drainage system shall be designed, installed and
c) Treatment of water based on the quality of maintained to guard against fouling, deposit of solids
water; and clogging and with adequate cleanouts so arranged
d) Quantity of water stored; and that the pipes may be readily cleaned.
e) Sizing of pipes. 3.1.7 Materials and Workmanship

PART 9 PLUMBING SERVICES (INCLUDING SOLID WASTE MANAGEMENT) SECTION 1 WATER SUPPLY 9
ook Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up

Supplied by Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid upto31-12-2017
The plumbing system shall have durable material, free 3.1.16 Accessibility for Persons with Disabilities
from defective workmanship and so designed and All doors, windows and fixtures, including WC, urinals,
installed as to give satisfactory service for its reasonable grab bars, washbasin, mirror and all other accessories
expected life. The accessories of the plumbing system for use by persons with disabilities shall be so installed/
should be of such specifications as to meet the functional located that they have proper access with appropriate
requirements of the installation, so as to also avoid any width, height, space, centerlines, and ease of operation
inconsistency leading to leakage and resultant seepage. (see 13 of Part 3 Development Control Rules and
3.1.8 Fixture Traps and Vent Pipes General Building Requirements of the Code).
Each fixture directly connected to the drainage system 3.1.17 Structural Safety
shall be equipped with a liquid seal trap. Trap seals
Plumbing system shall be installed with due regard to
shall be maintained to prevent sewer gas, other preservation of the structural members and prevention
potentially dangerous or noxious fumes, or vermin from of damage to walls and other surfaces.
entering the building. Further, the drainage system shall
be designed to provide an adequate circulation of air 3.1.18 Protection of Ground and Surface Water
in all pipes with no danger of siphonage, aspiration, or Sewage or other waste shall not be discharged into
forcing of trap seals under conditions of ordinary use surface or sub-surface water without acceptable form
by providing vent pipes throughout the system. of treatment.
3.1.9 Foul Air Exhaust
3.2 Water Supply Connection
Each vent terminal shall extend to the outer air and be so
3.2.1 Application for Obtaining Supply Connection
installed as to minimize the possibilities of clogging and
the return of foul air to the building, as it conveys potentially Every consumer, requiring a new supply of water or
noxious or explosive gases to the outside atmosphere. All any extension or alteration to the existing supply shall
vent pipes shall be provided with a cowl. apply in writing in the prescribed form (see Annex A)
to the Authority.
3.1.10 Testing
The plumbing system shall be subjected to required 3.2.2 Bulk Supply
tests to effectively disclose all leaks and defects in the In the case of large housing colonies or campuses, or
work or the material. where new services are so situated that it will be
3.1.11 Exclusion from Plumbing System necessary for the Authority to lay new mains or extend
an existing main, full information about the proposed
No substance that will clog or accentuate clogging of
scheme shall be furnished to the Authority. Information
pipes, produce explosive mixtures, destroy the pipes or
shall also be given regarding their phased requirements
their joints, or interfere unduly with the sewage-disposal of water supply with full justification. Such information
process shall be allowed to enter the drainage system. shall include site plans, showing the layout of roads,
3.1.12 Light and Ventilation footpaths, building and boundaries and indicating
Wherever water closet or similar fixture is located in a thereon the finished line and level of the roads or
room or compartment, it should be properly lighted and footpaths and water supply lines and appurtenances.
ventilated. 3.2.3 Completion Certificate
3.1.13 Individual Sewage Disposal Systems On completion of the plumbing work for the water
If water closets or other plumbing fixtures are installed supply system, the licensed/registered plumber shall
in buildings where connection to public sewer is not give a completion certificate in the prescribed form (see
possible, suitable provision shall be made for Annex B) to the Authority for getting the water
acceptable treatment and disposal. connection from the mains.
3.1.14 Maintenance 3.3 Licensing/Registration of Plumbers
Plumbing systems shall be maintained in a safe and 3.3.1 Execution of Work
serviceable condition.
The work which is required to be carried out under the
3.1.15 Approach for Use and Cleaning
provisions of this Section, shall be executed only by a
All plumbing fixtures shall be so installed with regard licensed/registered plumber under the control of the
to spacing as to be approachable for their intended use Authority and shall be responsible to carry out all lawful
and for cleaning. All doors, windows and any other directions given by the Authority. No individual shall
device needing access within the toilet shall be so engage in the business of plumbing unless so licensed/
located that they have proper approach. registered under the provisions of this Section.

10 NATIONAL BUILDING CODE OF INDIA 2016


ook Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up

Supplied by Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid upto31-12-2017
3.3.1.1 No individual, firm, partnership or b) Other than residential buildings:
corporation shall engage in the business of installing,
Occupancy Population Requirement
repairing or altering plumbing unless the plumbing
work performed in the course of such business is Offices 1 person per 10 m2 of floor
under the direct supervision of a licensed/registered area (see Note 1)
plumber. Schools Strength of school +
3.3.2 Examination and Certification Teaching and non-teaching
The Authority shall establish standards and procedure staff
for the qualification, examination and licensing/ Hostels Number of beds + 4.5 x
registration of plumbers and shall issue licences to such (wardens residence) +
persons who meet the qualifications thereof and staff
successfully pass the examination. Hotels Number of beds + Staff +
3.3.3 For guidelines for registration of plumbers
Requirement of restaurant
seats
including the minimum standards for qualifications for
the grant of licences/registration, reference may be Hospitals Number of beds + Staff +
made to good practice [9-1(2)]. The Authority may also Patient attendants (generally
utilize the services of the certified plumbers who are population density per bed
in secondary care hospital is
certified for the required skill level under the
5, tertiary care is 7 and
appropriate scheme of the Government.
quaternary care is 9)
4 WATER SUPPLY Mercantile 1 person per 3 m2 of street
4.1 Water Supply Requirements for Buildings floor and sales basement
The total quantity of water per day is estimated based areas + 1 person per 6 m2
on the proposed occupancy and activities catered. of upper sale floors
Designer has to identify all the possible sources for (Total population may be
augmenting the shortfall in water supply. The segregated into 10 percent
for fixed and 90 percent
analysis of available water is done to decide the
for floating/visitors)
treatment for consumption and treatment process
depends on the quality of water and the purpose for Traffic Average number of users
which it is used. terminal per day (Total annual
stations passenger traffic/365) +
Projection of population for each building shall be made Staff + Vendors
on the basis of its usage. Population for each type of NOTES
building shall be estimated on the basis of information 1 Wherever there are multiple work shifts, the
obtained from the users. Alternatively, population may number of users within a 24 h period may be
considered as per actuals.
be worked on the following basis, for different type of 2 Population of 5 to 15 percent, depending on the
buildings: usage of building, shall be considered for visitors
a) Residential buildings: and floating popula tion likely to use the
buildings facilities.
Accommodation Population
Requirements 4.1.1 Water Supply for Residences
1 bedroom dwelling unit 4 A minimum of 70 to 100 litre per head per day may be
2 bedroom dwelling unit 5 considered adequate for domestic needs of urban
3 bedroom dwelling unit 6 communities, apart from non-domestic needs as
4 bedroom dwelling unit 7 flushing requirements (which varies based on type of
and above building occupancy). As a general rule the following
rates per capita per day may be considered for domestic
NOTES
1 The above figures consider a domestic house - and non-domestic needs:
hold including support personnel, wherever a) For communities with population up to 20 000:
applicable.
2 For plotted development, the population may be 1) Water supply through stand: 40 lphd (Min)
arrived at after due consideration of the expected post
number and type of domestic household units. 2) Water supply through house: 70 to 100 lphd
3 Dwelling unit under EWS category shall have
population requirement of 4 and studio apartment
service connection
shall have population requirement of 2. b) For communities with: 100 to 135 lphd
population 20 000 to 100 000
together with full flushing system
PART 9 PLUMBING SERVICES (INCLUDING SOLID WASTE MANAGEMENT) SECTION 1 WATER SUPPLY 11
ook Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up

Supplied by Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid upto31-12-2017
c) For communities with population: 150 to 200 lphd 4.1.1.1 Out of the 150 to 200 litre per head per day,
above 100 000 together with 45 litre per head per day may be taken for flushing
full flushing system requirements and the remaining quantity for other
NOTE The value of water supply given as 150 to 200 litre
domestic purposes.
per head per day may be reduced to 135 litre per head per day
4.1.2 Water Supply for Buildings Other than Residences
for houses for Medium Income Group (MIG) and Lower Income
Groups (LIG) and Economically Weaker Section of Society Minimum requirements for water supply for buildings
(EWS), depending upon prevailing conditions and availability
of water.
other than residences shall be in accordance with Table 1.

Table 1 Water Requirements for Buildings Other than Residences


(Clause 4.1.2)
Sl Type of Building Domestic Flushing Total
No. Per Day Per Day Consumption
litre litre Per Day
litre
(1) (2) (3) (4) (5)
i) Factories including canteen where bath rooms are required to be provided 30 per head 15 per head 45 per head
ii) Factories including canteen where no bath rooms are required to be 20 per head 10 per head 30 per head
provided
iii) Hospital (excluding laundry and kitchen) (see Note 2):
a) Number of beds not exceeding 100 230 per head 110 per head 340 per head
b) Number of beds exceeding 100 300 per head 150 per head 450 per head
c) Out patient department (OPD) 10 per head 5 per head 15 per head
iv) Nurses homes and medical quarters 90 per head 45 per head 135 per head
v) Hostels 90 per head 45 per head 135 per head
vi) Hotel (up to 3 star) excluding laundry, kitchen, staff and water bodies 120 per head 60 per head 180 per head
vii) Hotel (4 star and above) excluding laundry, kitchen, staff and water 260 per head 60 per head 320 per head
bodies
viii) Offices (including canteen) 25 per head 20 per head 45 per head
ix) Restaurants and food court including water requirement for kitchen:
a) Restaurants 55 per seat 15 per seat 70 per seat
b) Food court 25 per seat 10 per seat 35 per seat
x) Clubhouse 25 per head 20 per head 45 per head
xi) Stadiums 4 per head 6 per head 10 per head
xii) Cinemas, concert halls and theatres and multiplex 5 per seat 10 per seat 15 per seat
xiii) Schools/Educational institutions:
a) Without boarding facilities 25 per head 20 per head 45 per head
b) With boarding facilities 90 per head 45 per head 135 per head
xiv) Shopping and retail (mall)
a) Staff 25 per head 20 per head 45 per head
b) Visitors 5 per head 10 per head 15 per head
xv) Traffic terminal stations (see Notes 3 and 4)
a) Airports 40 per head 30 per head 70 per head
b) Railway stations (Junctions) with bathing facility 40 per head 30 per head 70 per head
c) Railway stations (Junctions) without bathing facility 30 per head 15 per head 45 per head
d) Railway Stations (Intermediate) with bathing facility 25 per head 20 per head 45 per head
e) Railway Stations (Intermediate) without bathing facility 15 per head 10 per head 25 per head
f) Interstate bus terminals 25 per head 20 per head 45 per head
g) Intrastate Bus Terminals/Metro Stations 10 per head 5 per head 15 per head

NOTES
1 For calculating water demand for visitors, consumption of 15 litre per head per day may be taken.
2 The water demand includes requirement of patients, attendants, visitors and staff. Additional water demand for kitchen, laundry and
clinical water shall be computed as per actual requirements.
3 The number of persons shall be determined by average number of passengers handled by stations, with due considerations given to
the staff and vendors who are using these facilities.
4 Consideration should be given for seasonal average peak requirements.
5 The hospitals may be categorized as Category A (25 to 50 beds), Category B (51 to 100 beds), Category C (101 to 300 beds),
Category D (301 to 500) and Category E (501 to 750 beds).

12 NATIONAL BUILDING CODE OF INDIA 2016


ook Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up

Supplied by Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid upto31-12-2017
The water demand for the laboratory facilities will be collected as it falls as rain before it reaches the
depend on actual requirements based on functional ground; or as surface water when it flows over the
point of view. ground or is pooled in lakes or ponds; or as ground
4.1.3 Water Supply Requirements of Traffic Terminal water when it percolates into the ground and flows or
Stations collects as ground water; or from the sea.

The water supply requirements of traffic terminal stations Contamination of water supplies can occur in the source
(railway stations, bus stations, harbours, airports, etc) water as well as in the distribution system after water
include provisions for waiting rooms and waiting halls. treatment has already occurred. There are many sources
They do not, however, include requirements for retiring of water contamination, including naturally occurring
rooms. Requirements of water supply for traffic terminal chemicals and minerals (for example, arsenic, radon,
stations shall be as per Table 1. uranium), local land use practices (fertilizers,
pesticides, concentrated animal feeding operations),
4.1.4 Water Supply for Fire Fighting Purposes manufacturing processes, and sewer overflows or
4.1.4.1 The Authority shall make provision to meet the wastewater releases. The presence of contaminants in
water supply requirements for fire fighting in the city/ water can lead to adverse health effects, including
area, depending on the population density and types of gastrointestinal illness, reproductive problems, and
occupancy. See also Part 4 Fire and Life Safety of the neurological disorders.
Code. 4.2.2 The water supplied shall be free from pathogenic
4.1.4.2 Provision shall be made by the owner of the organisms, clear, free from undesirable taste and odour,
building for water supply requirements for fire fighting neither corrosive nor scale forming and free from
purposes within the building, depending upon the height minerals which could produce undesirable
and occupancy of the building, in conformity with the physiological effects. The quality of water to be used
requirements laid down in Part 4 Fire and Life Safety for drinking shall be as per accepted standard [9-1(3)].
of the Code.
4.2.3 For purposes other than drinking water if
4.1.4.3 The requirements regarding water supply in supplied separately, shall be absolutely safe from
storage tanks, capacity of fire pumps, arrangements of bacteriological contamination so as to ensure that there
wet riser-cum-down comer and wet riser installations is no danger to the health of the users due to such
for buildings, depending upon the occupancy use and contaminants.
other factors, shall be in accordance with Part 4 Fire
and Life Safety of the Code. For purposes other than drinking, where there is an
overall risk of legionella growth, it is advisable that
4.1.5 Water Supply for Other Purposes for cold water supplies, the temperature does not exceed
4.1.5.1 Water supply in many buildings is also required 20C and a minimum temperature of 55C for hot water
for many other applications other than domestic use, supplies be maintained at all points of network so as to
which shall be identified in the initial stages of ensure that it is absolutely safe from bacteriological
planning so as to provide the requisite water quantity, contamination and there is no danger to the health of
storage capacity and pressure as required for each the users due to such contaminants.
application. In such instances information about the
4.2.4 Waste Water Reclamation
water use and the quality required may be obtained
from the users. Some typical uses other than domestic Treated sewage or other waste water of the community
use and fire fighting purposes are air conditioning, may be utilized for non-domestic purposes such as
swimming pools and water bodies, and gardening. water for flushing, landscape irrigation, cooling towers
Treated water from sewage treatment plant, with of HVAC system, in fountains and recreational lakes
suitable tertiary treatment, should be used for flushing where swimming is not allowed, and for certain
purpose (with dual piping system), gardening purpose, industrial purposes after its necessary treatment to suit
cooling tower make up, and/or for other non potable the nature of the use. This supply system shall be
usage. allowed in residences only if proper provision is made
4.1.5.2 The water demand for landscaping purposes is to avoid any cross-connection of this treated waste
generally taken as 6 to 8 litre/m2/day for lawns. For water with domestic water supply system. During use
shrubs and trees the above value can be reduced of treated waste water, it is recommended to have dual
considerably. piping system to avoid cross-contamination.
4.2.4.1 Treatment of waste water and usage of recycled
4.2 Water Sources and Quality
water
4.2.1 Sources of Water
Waste water is generated by residential and other
The origin of all sources of water is rainfall. Water can establishments like institutional, business, mercantile

PART 9 PLUMBING SERVICES (INCLUDING SOLID WASTE MANAGEMENT) SECTION 1 WATER SUPPLY 13
ook Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid up

Supplied by Book Supply Bureau Under the License from BIS for LARSEN AND TOUBRO CONSTRUCTION - MANAPAKKAM, CHENNAI ON 17-03-2017 09:00:59 (123.63.24.35) valid upto31-12-2017
and industrial. It includes household waste liquid from 4.3.2 In making assessment of water supply
toilets, baths, showers, kitchens and sinks that is requirements of large complexes, the future occupant
disposed of via sewers. Waste water treatment is the load shall be kept in view. The following methods may
process of removing contaminants from wastewater, be used for estimating future requirements:
including household sewage and runoff (effluents). It
a) Demographic method of population
includes physical, chemical, and biological processes
projection,
to remove contaminants. Treatment of waste water and
usage of recycled waste water may be done to make it b) Arithmetic progression method,
usable for appropriate applications. The objective is to c) Geometrical progression method,
produce an environmentally safe fluid waste stream (or d) Method of varying increment or incremental
treated effluent) and a solid waste (or treated sludge) increase,
suitable for disposal or reuse. e) Logistic method,
Separation of household waste into grey water and black f) Graphical projection method, or
water (and draining of black water into sewerage system) g) Graphical comparison method.
is becoming more common with grey water being
permitted to be used for watering plants or recycled for 4.4 Storage of Water
flushing toilets after proper treatment. Waste water 4.4.1 In a building, provision is required to be made
collection and treatment is typically subject to statutory for storage of water for the following reasons:
regulations. Treatment depends on the characteristics of
influent and the treatment requirements that are needed a) To provide against interruptions of the supply
for treating the same. Waste water treatment generally caused by repairs to mains, etc;
involves the following three stages: b) To reduce the maximum rate of demand on
the mains;
a) Primary treatment It consists of
temporarily holding the wastewater for c) To tide over periods of intermittent supply;
settlement of heavy solids at the bottom while and
oil, grease and lighter solids float to the d) To maintain a storage for the fire fighting
surface. requirement of the building
b) Secondary treatment It removes dissolved 4.4.2 The water may be stored in overhead tanks (OHT)
and suspended biological matter. and/or underground tanks (UGT).
c) Tertiary treatment It is more intensive
4.4.3 Materials Used
treatment done in order to allow rejection into
a highly sensitive or fragile ecosystem. The Reservoirs and tanks for the storage of water shall be
tertiary treatment is generally followed by constructed of reinforced concrete, brick masonry,
disinfection. ferrocement, mild steel, stainless steel, plastic or glass
4.2.5 Water Conservation, Water Balance and Use of reinforced panels.
Recycled Water 4.4.3.1 Tanks made of steel may be of welded, riveted
Water conservationencompasses the policies, strategies or panel/pressed construction. The metal shall be
and activities to manage fresh wateras a sustainable galvanized or coated externally with a good quality anti-
resource, to protect the waterenvironment and to meet corrosive weather-resisting paint. Lead-based paint
current and future demand. Population, household size, shall not be used in the tank. Lead-lined tanks shall not
and growth and affluence all affect the quantity of water be used. Rectangular pressed steel tanks shall conform
used. Water balance studies should be carried out to to good practice [9-1(4)].
study the availability of water from different sources 4.4.4 Each tank shall be provided with the following:
and its usage for different purposes.
a) Manholes Adequate number of manholes
4.2.6 Whenever a building is used after long intervals, for access and repair. The manholes shall be
the water quality of the stored water shall be checked made of corrosion resistant material (for
so as to ensure that the water is safe for use as per example, cast iron, reinforced cement
water quality requirements specified in this Code. concrete, steel fibre reinforced concrete,
galvanized steel, high density polyethylene,
4.3 Estimate of Demand Load fibre glass reinforced plastic or such other
4.3.1 Estimates of total water supply requirements for materials) acceptable to the Authority.
buildings shall be based on the occupant load consistent Manholes shall be provided with locking
with the provisions of 4.1. arrangement to avoid misuse and tampering.

14 NATIONAL BUILDING CODE OF INDIA 2016

You might also like