SureCav CAVITY SPACER SYSTEM
STRUCTURAL CALCULATIONS FOR FOUNDATION AND
WALL ASSESSMENT ASH TREE HOUSE EAST RUDHAM
NORFOLK
FLINT,
Job No: 22134
Mr Charlie Ayers
SureCav Ltd
Holbrook Lodge
Wincanton
BA9 8BT
February 2013 lan Caldwell Bsc (Hons) C Eng MICE MI Struct E
SureCav Ltd Ash Tree House Cavity Spacer System February 2013CC Engineers Ltd
Consulting Civil Structural Engineers
3 Sawyers Close, Wraxall, Bristol, BS48 1LY
Tel/Fax 01275 854119 Mob 07850 371555 E Mail ccengineers@yahoo.co.uk
Structural Calculations:
1.0
2.0
3.0
4.0
5.0
6.0
INTRODUCTION
LOADING
ASSESSMENT OF LOADING AND PROPOSED TWO STOREY
DOMESTIC STRUCTURE FOUNDATION DESIGN
STABILITY
WALL LOAD ASSESSMENT
LATERAL LOAD ASSESSMENT
Appendix A: Sketch Details
SureCav Ltd Ash Tree House Cavity Spacer System February 2013CC Engineers Ltd
Consulting Civil Structural Engineers
3 Sawyers Close, Wraxall, Bristol, BS48 1LY
Tel/Fax 01275 854119 Mob 07850 371555 E Mail ccengineers@yahoo.co.uk
1.0 INTRODUCTION
The following calculations asses the structural calculations and the structural elements and
overall stabilty of cavity wall construction using the SureCav Ltd Cavity Spacer System for
proposed two storey domestic dwellings and assessment of proposed foundations to this
100mm fit build external skin and 100mm thick inner insulation block at this specific
location in Ash tree House The Green East Rudham Norfolk refer specifically to
section 6.0 lateral wall loading for this project. Designed spanning between wind
posts and other lateral walls max span between is 5.5m other are far less.
Design Philosophy:
Building Type: Two-storey domestic proposed houses constructed from load
bearing masonry, concrete ground floors.
Roof Construction: Trussed timber rafters supported on inner leaf of external
walls.
Floor Construction: Suspended conerete ground floor.
Wall Construction: Load bearing cavity masonry to all external walls and main
cross walls with 100mm thick flint external skin.
Foundations: 500mm wide trench fill mass concrete based on an average of
150kN/m2 for this location in Norfolk United Kingdom ref
Appendix A.
Refer to Appendix A for sketch details
SureCav Ltd ‘Ash Tree House Cavity Spacer System February 2013CC Engineers Ltd
Consulting Civil Structural Engineers
3 Sawyers Close, Wraxall, Bristol, BS48 1LY
Tel/Fax 01275 854119 Mob 07850 371555 E Mail ccengineers@yahoo.co.uk
2.0 LOADING
BS6399: Dead and imposed loads floor loads
BS6399: Wind Loads
BS6399: _ Imposed roof loads and snow loads
BS5628: Structural Use of Masonry
2.4 WIND LOAD
Location: Norfolk England
Basic wind speed = Vb= 21m/s
Factors Sat, S1, , Ss, Ssp = 21m/s
Site wind speed: Vs= Vb x Sa Sd Ss Ssp=21m/s
Terrain and building factor: Sb= 1.8
Effective wind speed: Ve= VsxSb
Ve = 21x 1.8 = 21mls
Dynamic wind pressure at He:
613 x 10-3 x Ve2
613 x 10-3 x 37.82 = 0.88kN/im2
2.2 STATIC LOADS:
Tiled Roof: Dead L¢ Tiles .66kN/m2.
Felt/Battens .O5kN/m2,
Rafters =0.15kN/m2_
‘BkN/m2
Susp ceilg joist ASKN/m2
Ceiling board -10KNIm2
Insulation& services = 0.05kN/m2
‘30kNim2
Live Loads: Rafters 60kN/m2
25kN/m2
Total = 1.95kN/m2
Walls: Dead Loads 215mmSolid .OKN/m2
Cavity Wall 100flint = 3.50kN/m2
Blockwork Wall BOkN/m2
Timber Stwk .50KN/m2
‘Suspended Floors: Dead Loads: Floorboards = 0.15kN/m2
Floor Joists 0.15kN/M2
Ceiling Board 40kN/m2
O.40kN/m2
Live Loads: Floor(domestic) = 1.50kN/m2
SureCav Ltd
Total = 1.90kN/m2
Ash Tree House Cavity Spacer System February 2013CC Engineers Ltd
Consulting Civil Structural Engineers
3 Sawyers Close, Wraxall, Bristol, BS48 1LY
Tel/Fax 01275 854119 Mob 07850 371555 E Mail ccengineers@yahoo.co.uk
Loading Cont'd
Supded Floors Concrete: Dead Loads: Screed BOkN/m2
Concrete 150 beam and block
= 2.50kNim2
Live Loads: Floor (domestic) 5kNim2
Total = 5.8kN/m2
3.0 ASSESSMENT OF LOADING AND CHECK ON PROPOSED
TWO STOREY EXTENSION FOUNDATION DESIGN
External wall loading to two storey domestic house with external 100mm flint skin in
grade 3 mortar
Walls gable x3.5x25 =27 kNim Unfactored
Floors x19 6 —_kNim Unfactored
Floors ground x58 18 N/m _Unfactored
Roof 4.x 1.95 = 8 kN/im_Unfactored
Total = 60 kN/m
Load to underside of foundation = 60/150 = 0.400 < 50mm.
Please note this is for an 500mm wide foundation and an allowable ground bearing
pressure of 150kN/m and typical for this location in the United Kingdom of very stiff
clays and chalk
PROVIDE 500MM WIDE TRENCH FILL C20 CONCRETE FOUNDATIONS
4.0 STABILITY
Stability of all the structures is provided by load bearing masonry walls in each
orthogonal direction or timber framing when applicable.
SureCav Ltd Ash Tree House Cavity Spacer System February 2013CC Engineers Ltd
Consulting Civil and Structural Engineers
3 Sawyers Close, Wraxall, Bristol, BS48 1LY
Tel/Fax 01275 854119 Mobile 07850 371555 E Mail ccengineers@yahoo.co.uk
5.0 WALL LOAD ASSESSMENT
The Following is a vertical load assessment of the proposed cavity wall at first floor
level using 50mm cavity and 100mm thick flint and 100mm thick internal skin and
assuming isolated 1m load bearing pier is to remain say adjacent to either a door or
a window and designed as a column taking two storey gable as the worst case.
Note wall above load bearing 250 thick masonry cavity with external 100mm flint skin
Blocks in high quality mortar fk = 5.0N/mm2
Loading:
Roof
Roof span Om Circa
Loading .0 x 1.95 =8.0 kNim
First floor
Floor span Om circa
Loading 0x 1.90 = 4.0 kNim
Wall
Wall ht say at gable = 5.0m circa
Loading = 5.0.x 3.5 with 100mm flint = 18 kNim
Reaction line ld. = 1.5x(8+4+18) = 30kNim
‘Supports
Load on foundation = (30 + 10 self wt)/150/1.5 = 0.17m proposed
500mm ok
Therefore adequate allowing for load spread assuming 150kN/m2 allowable bearing
pressure.
Isolated wall say at door or window reveal therefore worst case situation 1000mm
long and 250mm wide designed as column with pressure only on intemal skin
Load on masonry pier= 30 x 10 3/ (100 x 1000) = 0.33N/mm2
Assuming column 1000mm long x 250mm deep conservative
Assume beta 6 for two skins of masonry cavity with 100mm flint
Allowable = 0.6 x 1000 x 100 x 5.0/ 3.5/ (1000 x 100) = 0.85N/mm2 ok
Conservative as does not include bond with adjoining walls and load spread into the
cross walls
PROVIDE 250 CAVITY WALL WITH 100MM THICK INNER SKIN OF
BLOCKWORK 50MM CAVITY AND 100MM EXTERNAL SKIN OF FLINT FORMED
WITH SURECAV CAVITY SPACER SYSTEM TIED TOGETHER WITH 3MM
GAUGE WALL TIES AT 750MM HORIZONTAL AND 450 VERTICAL
STAGGERED
‘SureCav Ltd Ash Tree House Cavity Spacer System Calculations Febuary 2013
atCC Engineers Ltd
Consulting Civil and Structural Engineers
3 Sawyers Close Wraxall Bristol BS48 1LY
Tel/Fax 01275 854119 Mob 07850 37155
E mail ccengineers@yahoo.co.uk
6.0: WALL LATERAL LOAD DESIGN ASH TREE HOUSE EAST
RUDHAM NORFOLK
4 adjacent to the eaves at first
above 2.7m high and sz wide s n wind [posts spanning from
undation up tp first floor then up to wall plate level. Refer specifically to.
‘engineers drawing numbers 12021 drawing sheets. Designed first as propped
‘cantilever conservatively then as_a wall panel
Allowable panel size
Wind load 0. 88 kNim2
Panel size = 55x25 = 13.75m2
t2ef (0.66 x 200)2 = 17.42 x 103
Allowable = 1500 x t2ef 2 or more sides continuous = 26.1m2
therefore more than adequate in accordance with the masonry code
Propped cantilever as first i
spanning slab
check conservative approach one way
Try 100mm inner skin designed as propped cantilever 1m wide with external skin of
100mm flint construction in grade 3 mortar
Tef = 0.66 x 200 =132
Allowable = 45tef = 7128mm ok
Moment = 1.5x0.88x2.72/8 = 1.215kN.m
thx. 0.20 Nimm2 grade 4 mortar in 100mm thick flint and 100mm,
thick blockwork inner skin highly conservative
z = 1000 x 1322/6 =2.95x 106
Moment of res= 0.20 x 2.95 x 106/3.5 = 168x103N.mm ok
‘Two way spanning slab
Assume highly conservative flexural strengths for Flint in Lime mortar Fk
perpendicular to bed joints =
mortar say grade 4
.6200NImm2 highly conservative in flint
SureCAV Ltd ‘Ash Tree House Cavity Spacer system Febuary 2013CC Engineers Ltd
Consulting Civil and Structural Engineers
3 Sawyers Close Wraxall Bristol BS48 1LY
TellFax 01275 854119 Mob 07850 37155
E mail ccengineers@yahoo.co.uk
Fk parallel to the bed joints = 0.31Nimm2 highly conservative flint in
grade 4 mortar
Say panel type H
H = 2700 circa be between dpc and first floor
L 500 circa between wind posts ref
engineers drawings all other cases significantly lower
hit = 2700/5500 = 0.49
Alpha .023
Beta = 0.2510.6 very conservative = 0.41
Moment perpendicular = 1.5 x 0.023alpa x 0.88 x 5.500 2= 0.91N.mmok
Moment parallel = 1.5.x 0.41 x beta 0.83 x 5.500 2= 15N.mmok
PROVIDED WIND POSTS AT MAX 5.5M CENTERS OR INTERNAL LATERAL.
RESTRAINT WALLS ALL OTHER LOCATIONS SIGNIFICANTLY LOWER THAN THIS
SUPPORTING 100mm THICK INNER SKIN OF MASONRY and 100mm THICK
EXTERNAL SKIN OF MASONRY REF APPENDIX A FOR LAYOUT OF ENGINEERS
DRAWINGS IN GRADE 3 MORTARS THROUGHOUT
SureCAV Ltd Ash Tree House Cavity Spacer system Febuary 2013CC Engineers Ltd
Consulting Structural Engineers
3 Sawyers Close, Wraxall, Bristol, BS48 1LY
Tel/Fax 01275 854119 Mob 07850 371555 E Mail ccengineers@yahoo.co.uk
APPENDIX A
STRUCTURAL DETAILS
SureCav Ltd Ash Tree House Cavity Spacer System February 2013iil
id
Hy
ili