You are on page 1of 5

COSTOS OPERATIVOS ANUALES DE LINEAS 3F-13.

8KV ACSR (7 HILOS)

2 1/0 2/0 3/0 4/0

12.0

10.0
COSTO (US$)

8.0

6.0

4.0

2.0

0.0
0.0 50.0 100.0 150.0 200.0 250.0 300.0 350.0
CORRIENTE DE OPERACION (A)
ESCUELA POLITCNICA NACIONAL
FACULTAD DE INGENIERA ELCTRICA Y ELECTRNICA
DEPARTAMENTO DE ENERGA ELCTRICA
LABORATORIO DE DISTRIBUCIN DE ENERGA ELCTRICA
2017-B
COSTOS ANUALES DE LNEAS TRIFSICAS - 13.8kV - CONDUCTOR ACSR

DATOS CALIBRE
CONDUCTOR ACSR 2 1/0 2/0 3/0 4/0
RESISTENCIA DEL CONDUCTOR (Ohm/km)
CAPACIDAD (LMITE TRMICO) (A)
FACTOR DE PRDIDAS (fper)
COSTO DE LA DEMANDA (US$/kW/ao)
COSTO DE LA ENERGA (US$/kWh)
COSTO DE LINEA (US$/km) (Ct/km)
TASA DE DESCUENTO (%) (Td)
COSTO OPERACIN Y MANTENIMIENTO (%) (Com)
VIDA TIL (aos) (n)
COSTO ANUAL DE LA LNEA (US$/km)
INTERVALO ECONMICO DESDE (A)
PORCENTAJE DEL LMITE TRMICO
INTERVALO ECONMICO DESDE (KVAs-3F)

I Corriente de operacin (A) 3 I2 R


R Resistencia del conductor por kilmetro (Ohmios/Km) Ppo
fper Factor de prdidas 1000
Ppo Prdidas de potencia (kW/ao)
Pen Prdidas de energa (kWh/ao) 3 I2 R
Cd Costo de la demanda (US$/kW-ao) Pen fper 8760
Ce Costo de la energa (US$/kwh) 1000
Cpo Costo de prdidas de potencia (US$/ao)
Cen Costo de prdidas de energa (US$/ao)
Cpo Ppo Cd
Ct Costo total de la configuracin del conductor (US$/Km) Cen Pen Ce
Cta Amortizacin de la inversin + Com*Inversin
Com Costo de operacin y mantenimiento (pu) Td
Td Tasa de descuento (pu) Cta Ct Com Ct
n vida til (aos) 1 1 Td n
Canual Costo operativo anual (US$/ao)
Canual Cpo Cen Cta

Proyecto INECEL-EMELMANABI-EPN
COSTOS ANUALES (US$.)
kVAc I (A) 2 1/0 2/0 3/0 4/0 2 1/0
1 1.0
239 10.0 10.0
478 20.0 20.0
717 30.0 30.0
956 40.0 40.0
1195 50.0 50.0
1434 60.0 60.0
1673 70.0 70.0
1912 80.0 80.0
2151 90.0 90.0
2390 100.0 100.0
2629 110.0 110.0
2868 120.0 120.0
3107 130.0 130.0
3346 140.0 140.0
3585 150.0 150.0
3824 160.0 160.0
4063 170.0 170.0
4302 180.0 180.0
4541 190.0 190.0
4780 200.0 200.0
760 5019 210.0 210.0
5259 220.0 220.0
5498 230.0 230.0
5737 240.0 240.0
5976 250.0 250.0
6215 260.0 260.0
6454 270.0 270.0
Ct Com Ct 6693 280.0 280.0
6932 290.0 290.0
Cta

Proyecto INECEL-EMELMANABI-EPN
2/0 3/0 4/0

Proyecto INECEL-EMELMANABI-EPN
CORRIENTE OPTIMA DE LNEAS TRIFSICAS - 13.8KV - CONDUCTOR ACSR

DATOS CALIBRE
CONDUCTOR ACSR 2 1/0 2/0 3/0 4/0
RESISTENCIA DEL CONDUCTOR (Ohm/km) 0.0000 0.0000 0.0000 0.0000 0.0000
CAPACIDAD (LMITE TRMICO) (A) 0 0 0 0 0
COSTO ANUAL DE LAS LINEAS POR km (US$) 0.0 0.0 0.0 0.0 0.0
FACTOR DE PERDIDAS 0 0 0 0 0
COSTO POR DEMANDA (US$/kW/ao) 0 0 0 0 0
COSTO POR ENERGIA (US$/kWh) 0 0 0 0 0
COSTO EQUIVALENTE DEL CONDUCTOR
COSTO EQUIVALENTE DE PERDIDAS
CORRIENTE OPTIMA (A)
CARGA OPTIMA (kVAs) 0.0 0.0 0.0 0.0 0.0
PORCENTAJE RESPECTO AL LIMITE TERMICO #DIV/0! #DIV/0! #DIV/0! #DIV/0! #DIV/0!