Multifunction IEDs

C264-R Application
Modular Remote Terminal Unit

Sophisticated remote terminal unit for


substation control, monitoring, distributed
IEDs data concentration and gateway
communication with SCADAs.
The MiCOM C264-R combines the usual RTUs features with the benefits
of fast Ethernet communication. Its intrinsic high-performance is further
expanded through the modular I/Os acquisition racks. This up to date
design helps the user to simplify the engineering and installation, improve
reliability and quality as well as increase efficiency through space and cost
reductions in wiring, testing, maintenance and management. The MiCOM
C264-R offers natively an on-board 100Mb Ethernet communication for
SCADA communication, simple maintenance access and the connection
of many I/Os acquisition racks. This is in addition of the serial ports for
every application using multiple standard protocols. Each port is able to
communicate with a protocol including IEC60870-5-103, IEC 60870-5-101,
MODBUS, DNP3.0, or with a SOE serial printer. The MiCOM C264-R with
high-performance, large capacity, expandable is well adapted for turnkey
applications as well as retrofit installations. MiCOM C264-R is also to be
considered as a step on the way of Digital Control Systems.

Field of application
The MiCOM C264-R modular Remote Terminal Unit (RTU) provides a
powerful solution for SCADA communication, Sequence of Event Recorder
(SER), and can be integrated to digital substation control systems. It is
Customer Benefits designed for a wide range of applications:
Electrical utility
Modular RTU for electrical substations
requiring large capacities Transmission and distribution substations
IEDs and Sub-RTUs concentrator
Power Plant substations
SCADA interfaces with serial and Ethernet
protocols Industry
A step for a smooth transition to Digital Process control, including manufacturing, transit, telecommunications,
Control Systems testing, etc...
LCD graphical display for user-friendly
Oil and gas, including pipelines
local control, monitoring, and maintenance
Water and wastewater
Expandable design with single or multiple
racks architectures Transportation electrical supervision and control
High availability and reliability with
Railways
redundant communication facilities
Airport
02
Multifunction IEDs MiCOM C264RTU

Application profile Technical Data


Stand-alone RTU (Single or Multiple I/Os Hardware
racks) Case
Sequence of Event Recorder (SER) SOE
MiCOM C264C
printing
WxHxD 40T(206 mm) x 4U(177 mm) x 168 mm
IEDs and remote sub-RTUs data concentrator Slots 6 free assignment

Substation Gateway and protocol converter MiCOM C264


WxHxD 80T(405 mm) x 4U(177 mm) x 168 mm
Integrated into the Schneider Electric DCS and
Slots 15 free assignment
SCADA solutions
Control panel
General functions
Large graphical LCD (optional)
Data acquisition and processes for digital,
analogue values inputs and outputs Display 72 x 72 mm (optional)

Control and monitoring of switching devices Buttons (12) : 7 for operations


5 for control (optional)
Configurable indications on local LCD screen,
graphical Mimics and LEDs LEDs 17, 12 free configurable

Standardised and proprietary communication Power supply board


protocols
UN 24VDC, 48//60VDC, 110->125VDC,
Local storage of events, counters and 220/250 VDC,
measurement values 100 - 250 VAC 50/60 Hz
Download of the configuration thru Ethernet or Watchdog, Digital Input and Output relays for
from SCADA (IEC101 serial communication) redundancy management
Maintenance facilities over Ethernet (I/O values
Processor board
visualisation, hardware status, software and
database download), with convivial software 32-bit Power PC-based processor
tool, on standard PC. Internal Watchdog
Clock 80 Mhz
RAM 64 Mbytes
Flash 16 Mbytes
Ethernet-Based 10/100Base-FX or
10/100Base-TX
up to 4 serial interfaces RS232/485/optical
fibre on each rack
IRIG-B interface, BNC plug, Amplitude
modulated. Standard : NF- 5 85-500, May 1987
Digital input board (16 DI)

16 optically insulated inputs with one common


for 2 DI.
UN 24, 48/60, 110/125, 220/250 VDC
with DIU200 board
or
UN 24VDC, 250 VDC
with multi-voltage DIU210 board
MiCOM C264-R architecture
03
Multifunction IEDs MiCOM C264RTU

Digital output board (10 DO) Communications


8 outputs NO + 2 outputs NO/NC Standard ethernet SCADA protocols
UN 250 VDC / 230 VAC IEC 60870-5-104, DNP3/IP (option)
Continuous current : 2,5A Ethernet 10/100Base-FX or 10/100Base-TX
Short duration current : 30A for 500ms, Standard serial SCADA protocols
100A for 30ms.
IEC 60870-5-101, MODBUS, HNZ, DNP3 (option)
Breaking capacity:
DC: 50W resistive Interfaces
15 W inductive Optical / RS232 / RS422 / RS485
(L/R = 20ms) Standard IEDs protocols
IEC 60870-5-103, MODBUS,
Mixed board (8 DI / 4 DO) IEC 60870-5-101, DNP3 (option)
Circuit breaker control board (CCU200)
Synchronisation
8 optically insulated inputs with one common External synchronisation using IRIG-B
for 2 DI.
UN 24, 48/60, 110/125, and 220/250 VDC RTU capacity
4 power outputs relay (2 NO contacts) Multiple acquisition racks over Ethernet
UN 250 VDC / 230 VAC
Continuous current : 5A Up to 240 Digital Input signals per rack (15 slots)
short duration current : 250A for 30ms Up to 4 serial links on a rack (RS232/RS485/
Breaking capacity: optical)
(double pole contacts wired in serial)
Up to 2 SCADAs simultaneous connections
DC: 100W resistive
30W inductive Double lines management over IEC60870-5-101
SCADA connections
Analogue input board (4 AI / 8 AI)
Up to 16 IEDs on the RS485 legacy buses
4 isolated analogue inputs for measuring
Global data management of up to 5012 digital
transducer connection (AIU201).
datapoints, 1024 Analog values, 1024 Digital
Current: 1 / 2 / 5 / 10 / 20 mA / 4-20 mA
outputs, 100 Setpoints, 100 Tap Position
Voltage: 1.25 / 2.5 / 5 / 10 V
Indication on the C264-R
8 analogue inputs for measuring transducer
Redundancy of SCADA interface (option)
connection (AIU210).
Current: 1 / 2 / 5 / 10 / 20 mA / 4-20 mA SOE records
Analogue output board (4 AO) 1ms time tagging
4 analogue outputs with 4 read inhibit output Chronological order
relays (AOU200).
1 standard serial printer
Current: 5 / 10 / 20 mA / 4-20mA
External power supply (48V 5%) 2000 events recorded in non volatile memory
Output maintained in case of C264 power (Flash disk)
supply failure
The 200 most recent events readable on
optional LCD screen

Standard compliance
MiCOM C264 : a compact, powerful and Superior construction : environment, EMC,
innovative RTU for electrical applications isolations in accordance with IEC Standards.
04
Multifunction IEDs MiCOM C264RTU

2010 Schneider Electric - All rights reserved

Schneider Electric
35, rue Joseph Monier As standards, specifications and designs change from time to time, please ask for confirmation
CS 30323 of the information given in this publication.
92506 Rueil-Malmaison Cedex, France
This document has been printed
RCS Nanterre 954 503 439 on ecological paper
Capital social 896 313 776
www.schneider-electric.com Publishing: Schneider Electric
Design: Schneider Electric
Printing:

EnergyAutomation-DS-C264RTU-1287b-EN
10-2010