You are on page 1of 4

Contact

NYY-J 0.6/1 kV Contact


Phone: 49 2166 27 2467
info.centraleurope@nexans.com

Single- and multicore PVC-insulated copper cables

DESCRIPTION
Construction
Conductor of solid or stranded copper wires - PVC insulation-extruded or lapped inner
covering (multicore cables only) - PVC sheath

Application
In ground, outdoors, in water, in concrete, indoors, and in cable ducts where no
mechanical damage is to be expected

STANDARDS
National
DIN VDE 0276 part 603;
DIN VDE 0276 part 627

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 1 Generated 10/14/17 www.nexans.ua Page 1 / 4
Contact
NYY-J 0.6/1 kV Contact
Phone: 49 2166 27 2467
info.centraleurope@nexans.com

CHARACTERISTICS
Construction characteristics
With Green/Yellow core Yes
Armour type Unarmoured
Conductor material Copper
Outer sheath PVC
Insulation PVC
Screen No

PRODUCT LIST
Nexans Nb. Cross Ground Nom. Nom. Min. Max. Approx. Perm. Current
ref. of section cond. insulation outer outer outer weight current rating,
cor [mm] section thick. sheath diam. diam. [kg/km] rating buried
es [mm] [mm] thick. [mm] [mm] open air [A]
[mm] [A]
69203829 1 4 1.0 1.8 8.0 10.0 120 37 50
69204229 1 6 1.0 1.8 9.0 11.0 140 47 62
69204329 1 10 1.0 1.8 9.0 11.0 180 64 83
69204429 1 16 1.0 1.8 10.0 12.0 250 84 107
69204529 1 25 1.2 1.8 12.0 15.0 360 114 138
69204629 1 35 1.2 1.8 13.0 16.0 460 139 164
69204729 1 50 1.4 1.8 14.0 17.0 600 169 195
69204829 1 70 1.4 1.8 16.0 19.0 810 213 238
69204929 1 95 1.6 1.8 18.0 21.0 1090 264 286
69205029 1 120 1.6 1.8 19.0 22.0 1330 307 325
69205129 1 150 1.8 1.8 21.0 25.0 1620 352 365
69205229 1 185 2.0 1.8 23.0 27.0 1980 406 413
69205329 1 240 2.2 1.8 26.0 30.0 2560 483 479
69206029 1 300 2.4 1.9 28.0 32.0 3180 557 541
61233429 3 2.5 0.8 1.8 12.0 15.0 260 25 36
61233629 3 4 1.0 1.8 14.0 17.0 360 34 47
61233729 3 6 1.0 1.8 15.0 18.0 450 43 59
61233829 3 10 1.0 1.8 17.0 20.0 610 59 79
61233929 3 16 1.0 1.8 19.0 22.0 840 79 102
61252576 3 70 35 1.4 2.0 32.0 39.0 2940 199 232
61256776 3 25 16 1.2 1.8 25.0 31.0 1420 106 133
61256876 3 35 16 1.2 1.8 25.0 32.0 1690 129 159
61257276 3 50 25 1.4 1.9 28.0 35.0 2260 157 188
61258676 3 95 50 1.6 2.2 37.0 44.0 3960 246 280
61258776 3 120 70 1.6 2.3 40.0 47.0 4900 285 318
61258876 3 150 70 1.8 2.4 44.0 51.0 5870 326 359
61258929 3 185 95 2.0 2.6 49.0 56.0 7340 374 406
= Make to order, = In stock

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 1 Generated 10/14/17 www.nexans.ua Page 2 / 4
Contact
NYY-J 0.6/1 kV Contact
Phone: 49 2166 27 2467
info.centraleurope@nexans.com

Nexans Nb. Cross Ground Nom. Nom. Min. Max. Approx. Perm. Current
ref. of section cond. insulation outer outer outer weight current rating,
cor [mm] section thick. sheath diam. diam. [kg/km] rating buried
es [mm] [mm] thick. [mm] [mm] open air [A]
[mm] [A]
61259029 3 240 120 2.2 2.8 56.0 63.0 9440 445 473
61233386 3 1.5 0.8 1.8 11.0 14.0 210 20 27
61257029 4 2.5 0.8 1.8 13.0 17.0 310 25 36
61257329 4 16 1.0 1.8 21.0 25.0 1030 79 102
61257829 4 4 1.0 1.8 15.0 19.0 430 34 47
61257929 4 6 1.0 1.8 16.0 20.0 540 43 59
61258029 4 10 1.0 1.8 18.0 22.0 740 59 79
61259229 4 25 1.2 1.8 25.0 32.0 1540 106 133
61259429 4 35 1.2 1.8 25.0 32.0 1800 129 159
61259629 4 50 1.4 1.9 29.0 36.0 2400 157 188
61259829 4 70 1.4 2.1 33.0 40.0 3310 199 232
61260329 4 120 1.6 2.4 41.0 49.0 5450 285 318
61260529 4 150 1.8 2.5 46.0 54.0 6700 326 359
61260729 4 185 2.0 2.7 51.0 59.0 8300 374 406
61261429 4 1.5 0.8 1.8 12.0 16.0 250 20 27
61267629 4 95 1.6 2.2 38.0 45.0 4450 246 280
69260929 4 240 0.8 1.8 10780
61271529 5 1.5 0.8 1.8 13.0 16.0 280 15 19
61271929 5 25 1.2 1.8 27.0 33.0 1890 80 93
61272029 5 16 1.0 1.8 22.0 25.0 1260 59 71
61272129 5 4 1.0 1.8 16.0 19.0 500 26 33
61272229 5 2.5 0.8 1.8 14.0 17.0 350 19 25
61272486 5 10 1.0 1.8 20.0 23.0 880 44 55
61273329 5 6 1.0 1.8 18.0 21.0 630 32 41
69271829 5 35 16 0.8 1.8 0.0 0.0 312 0 0
69287229 7 1.5 0.8 1.8 17.0 340 13 16
69288429 7 2.5 0.8 1.8 18.0 430 16 22
69286529 8 1.5 16 0.8 1.8 0.0 0.0 713 0 0
69293629 10 1.5 0.8 1.8 21.0 460 11 14
69294429 10 2.5 0.8 1.8 22.0 590 14 18
69293829 12 1.5 0.8 1.8 21.0 510 10 12
69294629 12 2.5 0.8 1.8 23.0 650 13 16
69293929 14 1.5 0.8 1.8 22.0 560 10 12
69294729 14 2.5 0.8 1.8 24.0 730 13 16
69292129 19 1.5 0.8 1.8 25.0 690 9 11
69295129 19 2.5 0.8 1.8 27.0 920 11 14
69287129 21 15 0.8 1.8 0.0 0.0 0 0 0
69287739 24 1.5 0.8 1.8 28.0 860 8 9
69299139 24 2.5 0.8 1.8 30.0 1140 10 13
= Make to order, = In stock

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 1 Generated 10/14/17 www.nexans.ua Page 3 / 4
Contact
NYY-J 0.6/1 kV Contact
Phone: 49 2166 27 2467
info.centraleurope@nexans.com

Nexans Nb. Cross Ground Nom. Nom. Min. Max. Approx. Perm. Current
ref. of section cond. insulation outer outer outer weight current rating,
cor [mm] section thick. sheath diam. diam. [kg/km] rating buried
es [mm] [mm] thick. [mm] [mm] open air [A]
[mm] [A]
69299039 30 2.5 0.8 1.8 32.0 1340 7 8
69299439 30 1.5 0.8 1.8 29.0 1000 9 11
69288239 40 1.5 0.8 1.8 33.0 1260 7 8
69298939 40 2.5 0.8 1.8 36.0 1720 9 11
= Make to order, = In stock

SELLING INFORMATION
Dimensions
These dimensions are also deliverable in the standart lengths 500 and 1000m as well in 250m and 100m coil.
Other dimensions on request.

Notes
The current carrying capacity of the cables depends on the number of cores loaded. (vide DIN VDE 0276-627)
Trefoil touching arrangement for single-core cables

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Version 1 Generated 10/14/17 www.nexans.ua Page 4 / 4

You might also like