Professional Documents
Culture Documents
PH-IMS-SP08-WI1-FR03
REVISION / ISSUE:00/01
Generator Performance Report DATE:6/5/2015
Page | 1 OF 1
Model : Cat 3406 Client: Power House Report NO.: GPR (100) / 2017
Maximum LOAD : 220 KW \ 50 HZ Machine Code: 220 Work order NO: 17SO-043
Date of Inspection: 10/12/2017 Fuel type: Diesel Run hours: 24293 Hrs. KW.Hrs : N/A
Engine serial number : 2WB07713 Ambient temp : 20 C Sound proof: No CR code: N/A
15 57 81 402 25.4 1 161 161 162 50.4 401 112 51 0.546 NA Normal
15 53 84 560 25.4 1 312 314 313 49.4 401 217 99 0.546 NA Normal
Pressure
(Bar)
POINT X Y Z
1 NA NA NA
2 NA NA NA
3 NA NA NA
4 NA NA NA
5 NA NA NA
6 NA NA NA
7 NA NA NA
8 NA NA NA
Evaluation:
1- Generator test till 99% from its full load & 50% sudden load and all parameters are in the acceptance range.
2-Oil pressure is not preview on the screen.
3-Radiator fan belt need to be adjusted.
4-Dynamo belt need to be adjusted.
5-water level sensor cable need to be agjusted.
6-Flywheel rotating cover above the marsh is missing.
7-Air filter need to be cleaned.
8-Electrical wirinig need to be isolated.
Result:
Action
Page 1 of 1