Warning Daikin Industries, Ltd.

s products are manufactured for export to numerous countries throughout the


world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a
particular country. Prior to purchase, please therefore confirm with your local authorised importer,
distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for
use, in the region where the product will be used. This statement does not purport to exclude, restrict
or modify the application of any local legislation.
Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an
outdoor unit with anti-corrosion treatment.

Daikin Water Chillers are of the self-contained type. This means that they are assembled, internally wired and
charged with refrigerant at the factory for easy installation, only requiring external wiring and plumbing on site.
They are compatible with Daikin's Air Handling and/or Fan Coil Units.

JMI-0107 EC99J2044
About ISO9001 About ISO 14001
ISO 9001 is a plant certification system defined by the International ISO 14001 is the standard defined by the International Organization for
Organization for Standardization (ISO) relating to quality assurance. ISO Standardization (ISO) relating to environmental management systems. Our group
9001 certification covers quality assurance aspects related to the design, has been acknowledged by an internationally accredited compliance organisation
development, manufacture, installation, and supplementary service of as having an appropriate programme of environmental protection procedures and
products manufactured at the plant. activities to meet the requirements of ISO 14001.

Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
Printed in Japan 11/06/005 SW.HP.AD

Specifications, designs and other content appearing in this brochure are current as of November 2006 but subject to change without notice. Printed on 100% recycled paper with soy ink.
Daikin chilling units employ advanced technology that provides highly Lis t of Daikin Water C hiller Models
accurate temperature control to within 0.5 . They are widely used in
applications ranging from air conditioning to industrial equipment.
Recent changes have introduced new models with substantially
increased capacities of up to 480 HP and various model series,
50Hz C apacity R ange (kW)
20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1200 1400 P age

Water Chillers
including advanced inverter type units, year-round cooling type units, Air Cooled Water Chillers

Air Cooled
and units with brine-resistant specifications. By providing a full lineup 6.7 67 UWAP-AY3 9
Standard Unit
106 1260 UWAP-BY1 9 10
of heat source series choices, Daikin offers an even more flexible
Year - Round Cooling Only Unit 106 1260 UWAP-BY1K 11
array of solutions for a wide range of heat source applications.
Brine Cooling Unit 68 808 UWAP-BY1Z 12 13

Inverter Cooling Unit 12.5 75 UWAXP-AY1 14

H ig h -pe r fo r m a n c e D a ik in W a t e r C h ille r s a r e A v a ila ble in Standard Unit 106 1260 UWA-AY1 14 15

a B r o a d R a n g e o f M o d e ls t o S u it D iv e r s e A pplic a t io n s . For
High Outdoor Temperature Use
108.4 319.2 UWA-JAY1 17
351.6 791 UWA-JY1 18

Air Cooled Water Chillers


Air Cooled Water Chillers - Heat Pump Type

- Heat Pump Type


Air Cooled Water Chillers Standard Unit
11.2 67 UWYP-AY3 21
106 1260 UWYP-BY1 21 22
: UWAP S eries / UWAXP S eries
: UWA S eries / ( For High Outdoor Temperature Use ) Standard Unit 106 1260 UWY-AY1 23

Dedicated water chillers are able to operate year


round because they can accommodate a wide range Water Cooled Water Chillers
of outdoor temperatures. The high-performance models Standard Unit 8 80 UWP-AY3 27
with capacities of over 40 HP can deliver between
118 355 UWD-DY1 27
10% (12% ) and 100% of their capacities. They are Standard Unit
367 1450 ZUW-AY1 28
able to withstand the demanding conditions typical of

Water Chillers
Water Cooled
industrial applications. Brine Cooling Unit 190 715 ZUW-AY1Z 29

Air Cooled Water Chillers - Heat Pump Type


: UWY P S eries
60Hz C apacity R ange (kW)
20 40 60 80 100 150 200 250 300 350 450 500 600 700 800 900 1000 1200 1400 P age
: UWY S eries
Air Cooled Water Chillers
Air cooled heat pump system units are an ideal
7.5 75 UWAP-AY3 9
way to provide a reliable supply of hot and cold Standard Unit
118 355 UWAP-BYB 10
water. Of compact size because no cooling tower
is required, they are also suitable for office Year - Round Cooling Only Unit 118 355 UWAP-BYBK 12
building air conditioning. These high-end models Brine Cooling Unit 79 242 UWAP-BYBZ 13
provide an answer to a variety of air conditioning
Standard Unit 118 355 UWA-AYB 15
requirements.
For
79 370 UWA-JATJ 18
High Outdoor Temperature Use

Air Cooled Water Chillers - Heat Pump Type


Water Cooled Water Chillers 12.5 75 UWYP-AY3 21
Standard Unit
: UWP S eries 118 355 UWYP-BYB 22
: UWD S eries ZUW S eries
Standard Unit 118 355 UWY-AYB 24
Water cooled units provide a s table s upply of
chilled water year round and are unaffected by
Water Cooled Water Chillers
changes in the outdoor temperature. In addition
to air conditioning applications , they are als o a Standard Unit 9 90 UWP-AY3 27
highly reliable indus trial proces s cooling s olution Standard Unit 441 1040 ZUW-AYB 28
thanks to their s tability and wide temperature Brine Cooling Unit 233 555 ZUW-AYBZ 29
control range.

1 2
E quipped with an E fficient, Durable High Function Microcomputer C ontrol P anel and
S emi-hermetically S ealed S crew C ompres s or. Multifunctional R emote C ontroller R ealis e E fficient
10 Operation C ontrol.

2
1
*Applies to all models , with the exc eption of thos e lis ted below.
4
60,000 UWA37 109J AY 1, UWA120 270J Y 1,
UWA27 122J ATJ , UWP 90 900AY 3
Sales volume
7

Mic roc omputer C ontrol P anel Makes Operation A Multifunc tional L iquid C rys tal R emote
11
9 C ontrol E as y. C ontroller for E ffec tive G roup C ontrol.
1 C as ing
2 S crew rotor *For details , refer to the Operation Manual of each model.
3 S lide valve B R C 307 (Option)

4 B all bearing
5 Motor
5
Multi-display
6 G ate rotor
S imple key operation dis plays required operating and
7 High efficient oil s eparator
8 8 High-low pres s ure
s ettings data. Dis plays a complete of operating data for
6 eas y comprehens ion.
3 differential lubricating mechanis m
9 B earing lubricating oil for
models us ing new refrigerant Outdoor temp. H/L pressure of refrigerant
10 R efrigerant inlet
11 R efrigerant outlet Discharge gas temp. Centralized control Function for Equal Control
Water temp. setting Malfunction code display using Microcomputer Control Panel
Inlet/outlet water temp.
E quipped with a Newly Developed, L ow Vibration and S ound L evels .
Highly E ffic ient C ompac t C ompres s or. Daikin water chillers us e gate rotors made of high- Dis plays operating data for eas y c omprehens ion of
Optimization of the unit enhances efficient operation. A newly performance engineering plas tic for s mooth mes hing with the s ys tem s tatus .
developed denture mold enabled the production of a compact s crew rotor, thereby reducing s hock and vibration. while Remote Control by Remote Command
maintaining s table operation. The gate rotors are well Outdoor temperature High and low pres s ure
model with reduced volume and weight. E nables different types of remote control, s uch as control
balanced to equalize pres s ure, which reduces nois e and Inlet/Outlet temperature Water temperature s etting
by commands from the hos t computer, the Daikin
B uilding Air-C onditioning C ontrol S ys tem (D-B AC S ), or the Dis c harge gas temperature Malfunc tion c ode
High Operational E ffic ienc y R educ es E nergy Los s . L ightweight C ompac t Des ign S ave S pac e. multifunctional remote controller. E nables different types of remote c ontrol.
In addition to effic ient operation afforded by a 12- In addition to the s imple s ingle rotor cons truction, the
compres s ion s ingle cycle, the s ingle s crew cons truction compact, lightweight des ign eliminates the need for an oil On/Off c ontrol L ow nois e operation during
eliminates blow-by from high to low pres s ure s ections to cooler while incorporating the oil s eparator into a s ingle part On/Off remote c ontrol Water temperature s etting nighttime
reduce energy los s . Daikin water chillers are equipped with a to reduce the s pace required for s etup. R emote s etting of water temperature S witc hing of operating F orc ed fan operation
tightly s ealed gate rotor to reduce refrigerant los s from mode Demand c ontrol*
S etting for heat s torage operation
leakage. Our compres s ors are des igned for efficient operation *Demand control is not available
Y ou can s witch s ettings from normal operation to either Defros t c yc le s etting* with
Durable C ons truc tion Inc reas es Ins pec tion temperature s etting for heat s torage or control by the external *Applies to heat-pump type only.
R otation c ontrol
Heat s torage operation
High Ac c urac y and High Durability. Intervals thereby Dec reas ing Maintenanc e. L ower nois e operation for during nighttime Ins pec tion/Tes t operation
C areful cons truction features gate rotors pos itioned to the Durability of the equipment increas es the maintenance interval Y ou can reduce the operating nois e by s topping half the fan.
right and left of the s crew to eliminate eccentric load to approximately 40,000 hours (or about s even years ). The Note that the capacity control of the chiller s hould be limited to
les s than 70% .
produced by pres s ure differential. The orthogonal rotor s haft s implified lubrication s ys tem, including a high/low pres s ure
us es high-precis ion ball and roller bearings , which extends its differential lubrication s ys tem and ball and roller bearings , Controls Multiple Units Effectively
life compared to conventional types . In addition, power reduces the factors that can contribute to problems . Along F orc ed fan operation c ontrol*
trans mis s ion between rotors is reduced, thus eliminating with increas ing the maintenance and ins pection interval, the Y ou can force fan operation even when the unit is s topped, Up to eight units can be group controlled by a s ingle remote controller.
friction wear and maintaining s table operating performance careful cons truction of Daikin water chillers enhances which is convenient for removing the s now collected on the fan. E quipped with s imultaneous defros t prevention c ontrol for
over an extended period of time. reliability.
*This function is des igned for in areas where s now rarely falls . avoiding radic al water temperature c hange when operating
An optional s now hood s hould be us ed in areas prone to s now. multiple units .
*S imultaneous defros t can be carried out for up to two units when five or more
Discharge Pressure
Gate Rotor Demand c ontrol units are connected.
Suction
Pressure (1) Y ou can have Three demand controls are pos s ible thermos tat
R otation c ontrol
Off, les s than 40% or les s than 70% . (Factory s et:70% )
(2) Demand control may als o be achieved by s etting the operating Memorizes the number of s tops for each unit (therefore not
current of the compres s or. effective for s ys tems in continuous operation), and s mooths
*Demand control is available on all models , with the exception of operation by s tarting in order from the unit with the leas t
thos e lis ted below. number of s tarts and s tops to increas e the life time of all
Screw Suction UWAP 75 750AY 3, UWAXP 125 750AY 1, UWA37 109J AY 1,
Rotor Pressure UWA120 270J Y 1, UWA27 122J ATJ , UWY P 125 750AY 3,
apparatus in the s ys tem.
Discharge Pressure UWP 90 900AY 3
Note : C us tom orders may take more time for delivery.

3 4
Daikin's C ontrol S ys tem for C entral Air C onditioning Daikin's intelligent control s olution for the whole air-
S ys tem Offers Appropriate C ontrol for Us e conditioning s ys tem.
and S ize of B uilding.

Daikin's Control System for Daikin introduces its "C ontrol S ys tem for C entral Air C onditioning" The s ys tem lets I-Manager Control heat resources system by using I-Manager
you freely combine a number of optional controllers for centralized control to
Central Air Conditioning. cons truct the air conditioning control s ys tem that is appropriate for your needs . The
s ys tem executes total central control of chillers and air conditioners , to s ave
management labour while realizing ideal central air conditioning performance. System Structure(VRV+central conditioning)

D -NE T Features of I-Manager


System configuration E themet
1. C entral air-c onditioning s ys tem c an be c ontrolled
Unified ON/OFF controller together with VR V.
iPU
(R es erved 2. Operating interfac e is bas ed on the windows
for VR V) interfac e, whic h is eas y to us e.
I-Manager
New Version 3. 1024 units (groups ) of indoor unit or water
c ooled c hiller c an be c onnec ted.
4. Power dis tribution in proportions , c alc ulation the
power rate and other AC -related c os ts of us er.
Air handling unit Air handling unit Fan coil unit Possible 5. C an be c onnec ted with Air C onditioning Network
wireless remote controller
S ervic e S ys tem
Chilling unit VR V(4 ports ) 6. Ordinary 2-c ore c able is us ed for wiring, the field
R emote monitor 256 indoor units
Enables individual control from chillers to air conditioners by using a single line. c enter wiring work is very s imple.

D -NE T
Water c ooled c hiller (1 port)
Air-c ooling 240HP 2 units
D -NE T Water-c ooling 400US R T 1 unit
iPU wiring adaptor
(R eserved for central
air-conditioning
system)

R emote c ontroller
(units No. c ontrol)

Enables group control by remote controllers of both chillers and air conditioners. E quipment~pump of other
Dio Unit Dio Unit c ompany, c ooling tower(1
C ool/warm water pump 1
port)
C ool/warm water pump 3 C ooling tower 1 Pump 4 units

Max. 4 iPUs
are

* Please contact Daikin for detailed


Wiring adaptor is required for c onnec ting Dio unit to Airnet data for connection of Fan coil
and AC(terminal products)
Lets you develop a system that doesn't use individual remote controllers.(Central remote controller required)
Possible to link with Note: It is not pos s ible to c onnec t a high outdoor temperature s pec ific ation unit and the UWAP75 750.
host computer

SkyAir series Control Function List of I-Manager


VRV system Air-c ooling Unit Water-c ooling Unit C ommodity from other c ompanies
Model
Func tion UWAP,UWYP,UWA,UWY ZUW Pump, R efrigerating Unit, C ooling Tower
I-Manager option S tandard c onnec tion D adaptor DioUnit
Enables control of other air conditioning systems S top-running c ommand
such as VRV, SkyAir or HRV. C ooling/heating mode setting
Schedule timer
Central remote controller C ontrolling Temp. s etting
Possible to have a forced Note:The system shown above is applicable only to Series UWAJ-G, UWYJ-B, UWAP-G and UWYP-G. func tion S c hedule func tion
shut-down input Note:Air handling and Fan coil units can be connected by custom orders. Interloc k s etting
Power proportion limitation
S top-running
Different C ontrol Apparatus C ombinations E nable a Multipurpos e S ys tem. C ooling/heating mode
Daikin offers a lineup of c entral Temperature s et
R oom temp. (s uc tion inlet)
controllers equipped with a variety of
Water temp. (inlet/outlet)
functions . The unified ON/OFF controller
Monitoring Abnormal
lets you turn equipment on and off func tion Abnormal s ignal
individually or in groups . The s chedule
Filter s ignal
timer lets you program the time for
C ontinuous running period
connected equipment to be turned on Temp. upper/lower limit
and off for eac h week. C ontrol (Note1)
AIR NE T
apparatus with different functions can
( realis ed func tion irres pec tive item only data information, c an't be ac hieved up till now)
be freely combined, and up to 64
groups can be centrally controlled. C entral remote controller Unified ON/OFF controller S chedule timer Note1: C an realize partial func tion of Air C onditioning Network S ervic e S ys tem.

*N umber of units that c an be

5 6
Air Cooled Water Chillers
: UWAP S eries UWAXP S eries
: UWA S eries
Reduced Energy Wastage Multiple Operating Modes
Water Chillers

Water Chillers
UWAP 40 160B Y 1 (K )(Z ) UWAP 40 160B Y 1 (K )(Z ) UWA40 160AY 1
Air Cooled

Air Cooled
UWAP 40 120B Y B (K )(Z ) UWAP 40 120B Y B (K )(Z ) UWA40 120AY B
C ontinuous capacity control with a range from 10% to The us er can s elect to give priority to either precis ion or
100% helps to reduce energy was tage during low-load reduced power cons umption.
High-P rec is ion Mode L ow-P ower Mode

High Precision C ontinues operation to levels This mode can be used to re-
as low as 10(12)% of total duce power cons umption if
UWAXP 125 750AY 1 capacity to provide s table highly precise water temperature
Inverter control with high load compliance achieves highly water temperature c ontrol control is not necessary dur-
accurate outflow water temperature control to within 0.5 even during low-load peri- ing low-load periods. It shuts
ods . down the compressor when the
UWAP 40 160B Y 1 (K )(Z ) UWA40 160AY 1 load
Note: Switching between the above modes drops below
is accomplished using40% .
a control on
UWAP 40 120B Y B (K )(Z ) UWA40 120AY B the outdoor unit.
The outlet water temperature is precis ely controlled to within
0.5
UWAP 40 480B Y 1
UWAXP 750AY 1 UWAP 120B Y 1K UWAP 180B Y 1 (with a s table load) through the us e of electric expans ion UWA40 480AY 1
A choice of three control s ys tem is available.
E xample of Outlet Water Temperature C ontrol Outflow water temperature control
Water Temp. ( ) If outlet water temperature ris es above the upper limit s ignal, Provides precise control of the water temprerature.
the load s tarts to increas e in 10% increments
(UWAP40 160BY1, UWA40 160AY1)
10
Compressor count control
9 Controls the number of compressors operating depending on the load.
Upper Limit S ignal
Model Lineup 8
(UWAP40 480BY1, UWA40 480AY1)
Capacity (kW) In flow water temperature control
Refrigerant Units series Model No. page
6.7/7.5 11.2/12.5 17/19 22.4/25 33.5/37.5 45/50 56/63 67/75 106 132 160 212 265 Value S et 7
Performs duty cycling control.
50/60Hz UWAPAY3* 75 125 190 250 375 500 630 750 9
50Hz Standard Unit 50 60 80 100 9, 10
As the temperature As the temperature When changes in (UWAP40 480BY1, UWA40 480AY1)
UWAPBY1 40 falls below the upper falls below the s et outlet water
60Hz UWAPBYB 40 50 60 100 10 limit s ignal, the load value, the load temperature become
increas e increments increas e increments 1 or les s , the
50Hz Year - Round Cooling UWAPBY1K 40 50 60 80 100 11
60Hz
R-407C
Only Unit UWAPBYBK 40 50 60 100 12
are reduced to 5% . remain at 5% . thermos tat is turned off.
Easy Installation
50Hz UWAPBY1Z 40 50 60 80 100 12, 13 Note: In systems with one compressor installed and where the load factor is 30%
Brine Cooling Unit UWAXP 125 750AY 1
60Hz UWAPBYBZ 40 50 60 100 13 or more, and in systems with two or more compressors installed and where the
50Hz Inverter Cooling Unit UWAXPAY1 125 190 250 375 500 630 750 14 load factor is 30% or more, control to within 0.5 is possible. High load compliance and highly efficient inverter control provide highly precise
50Hz UWAAY1 40 50 60 80 100 14, 15 adjustment of the water temperature, making it possible to reduce the size of
R-22 Standard Unit
60Hz UWAAYB 40 50 60 100 15 the peripheral equipment.
Note: Capacity figures are provided for reference and assume a power supply frequency of 60 Hz.
Wide Water Temperature Control Range UWAP 40 480B Y 1 (K )(Z ) UWA40 480AY 1
Capacity (kW) UWAP 40 120B Y B (K )(Z ) UWAP 40 120AY B
Refrigerant Units series Model No.
315 370 420 480 530 580 630 740 840 960 1060 1160 1260
page Applies to All Models
The compact des ign of thes e units s ignificantly reduces the
50Hz UWAPBY1 120 140 160 180 200 220 240 280 320 360 400 440 480 9, 10 T he wide water temperature c ontrol range provides s pace required for ins tallation.
Standard Unit
60Hz UWAPBYB 120 10 compatibility with a variety of heat s ource requirements . In the outdoor unit, component parts of a small size have been used wherever
50Hz Year - Round Cooling UWAPBY1K 120 140 160 180 200 220 240 280 320 360 400 440 480 11
60Hz 120
A variety of brine-res is tant s pecification models are available possible to reduced its size and correspondingly reduce how much space it re-
R-407C Only Unit UWAPBYBK 12
that provide s table cooling operation at brine outflow quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has
50Hz UWAPBY1Z 120 140 160 180 200 220 240 280 320 360 400 440 480 12, 13
Brine Cooling Unit temperatures down to -10 . reduced the amount of space the outdoor unit needs even further.
60Hz UWAPBYBZ 120 13
50Hz UWAAY1 120 140 160 180 200 220 240 280 320 360 400 440 480 14, 15
60Hz
R-22 Standard Unit
UWAAYB 120 15 C apacity
Water Temperature C ontrol R ange UWAP 125AY 3 750AY 3
Models E mploying R -407C Models E mploying R -22
The horizontal linkup des ign increas es ins tallation flexibility.
5 to 16
3 30 This design provides the installation does not protrude so far, making it possible
4 to 25 (Inver C ooling Unit)
New Refrigerant Efficient and Reliable Compressors 4 to 25 4 to 16
to install water chillers along a wall or under a roof overhang.
40 480
-10 to 0 (B rine C ooling Unit)
Note: Water supply piping must be purchased separately.

UWAP 75 750AY 3 Applies to All Models (UWAP375AY3 750AY3)
UWAXP 125 750AY 1 To improve their operational reliability, 5 -- 30HP models
UWAP 40 480B Y 1 (K )(Z )
UWAP 40 120B Y B (K )(Z )
employ s croll compres s ors , while 40 -- 480HP models are
equipped with s emi-hermetic s ingle s crew compres s ors .
Wide Operation Range Reliability
E mploys the new refrigerant R -407C . Applies to All Models Applies to All Models Refrigerant
Refrigerant Water
R efrigerant inlet The wide outdoor air temperature range ens ures a s table S tainles s s teel heat ex- Inlet Water
Outlet
Inlet
s upply of chilled water year round. changer plates prevent rus t, Outlet
A variety of year-round cooling type models are available thereby improving their dura-
R efrigerant outlet that provide s table operation at outdoor temperatures down bility and the s ys tem's op-

C apacity
Outdoor Air Temperature R ange where C ooling P os s ible UWAP 40 480B Y 1 (Z ) Heat Exchanger with
Models E mploying R -407C Models E mploying R -22 UWAP 40 120B Y B (Z ) Stainless Steel Plates
3 30 -15 to 43 UWA40 480AY 1
S emi-hermetic s ingle
-5 to 43 -5 to 43 UWA40 120AY B
-15 to 43 C ompres s or duty cycling control together with emergency
s crew compres s or 40 480
( Y ear-R ound C ooling Only Unit )
operation and power-interruption auto-res tart functions pro-
0 to 43 ( B rine C ooling Unit )
vide enhanced air conditioning s ys tem reliability.

7 8
Air Cooled Water Chillers
Standard Unit Standard Unit
50/60Hz UWAP 75 750AY 3 50Hz UWAP 200 480B Y 1
6.7/7.5 67/75kW clas s 530 1,260kW clas s
Water Chillers

Water Chillers
S pecifications S pecifications
Air Cooled

Air Cooled
UWAP75AY3 UWAP125AY3 UWAP190AY3 UWAP250AY3 UWAP375AY3 UWAP500AY3 UWAP630AY3 UWAP750AY3 Model
UWAP200BY1 UWAP220BY1 UWAP240BY1 UWAP280BY1 UWAP320BY1 UWAP360BY1 UWAP400BY1 UWAP440BY1 UWAP480BY1
Model (240 )
(3 ) (5 ) (8 ) (10 ) (15 ) (20 ) (25 ) (30 ) (200 ) (220 ) (280 ) (320 ) (360 ) (400 ) (440 ) (460 )
kW 6.7/7.5 11.2/12.5 17.0/19.0 22.4/25.0 33.5/37.5 45.0/50.0 56.0/63.0 67.0/75.0 kW 530 580 630 740 840 960 1,060 1,160 1,260
Cooling capacity *1
Btu/h 22,900/25,600 38,200/42,700 58,000/64,900 76,500/85,400 114,000/128,000 154,000/171,000 191,000/215,000 229,000/256,000 Cooling capacity Btu/h 1,809,000 1,979,000 2,150,000 2,525,000 2,867,000 3,276,000 3,617,000 3,959,000 4,300,000
(50/60 Hz)
USRT 1.91/2.13 3.19/3.55 4.83/5.40 6.37/7.11 9.53/10.7 12.8/14.2 15.9/17.9 19.1/21.3 USRT 151 165 179 210 239 273 301 330 358
Power supply 3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system Power Supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
Chilled water flow rate Chilled Water Flow Rate /min 1,519 1,663 1,806 2,121 2,408 2,752 3,039 3,325 3,612
/min 19/22 32/36 49/54 64/72 96/108 129/143 161/181 192/215
(50/60 Hz) Capacity Steps % 100~10-0
Capacity steps % 100-0 100-67-34-0 100-50-0 100-80-60-40-20-0 100-67-34-0 Type Semi-hermetic sealed single-screw type
Compressor
Type Hermetically sealed scroll type Motor output kW 45 2+60 45+60 2 60 3 (45+60) 2 (60 2) 2 (45 3) 2 (45 2+60) 2 (45+60 2) 2 (60 3) 2
Compressor
Motor output kW 2.2 1 3.75 1 5.5 1 7.5 1 7.5+3.75 7.5 2 7.5 2+3.75 7.5 3 Evaporetor type Brazing Plate type
Evaporator type Brazed plate heat exchanger Comdenser type Cross fin coil
Condenser type Cross fin coil Type Propeller
Type Propeller Drive Direct drive
Condenser
Drive Direct drive m3/min 3,010 3,440 3,870 4,300 5,160 6,020 6,880 7,740
Condenser fan Air flow rate
Air flow rate m /min 75/85
3
90/95 140/160 175/185 265/280 350/370 440/465 525/555 cfm 106,253 121,432 136,611 151,790 182,148 212,506 242,864 273,222
fan
(50/60 Hz) cfm 2,650/3,000 3,180/3,350 4,940/5,650 6,180/6,530 9,350/9,880 12,400/13,100 15,500/16,400 18,500/19,600 Motor output kW 1.0 14 1.0 16 1.0 18 (1.0 10) 2 (1.0 12) 2 (1.0 14) 2 (1.0 16) 2 (1.0 18) 2
Motor output kW 0.14 1 0.20 1 0.215+0.14 0.215+0.22 (0.215+0.22)+0.2 (0.215+0.22) 2 (0.215+0.22) 2+0.2 (0.215+0.22) 3 Refrigerant R-407C
Refrigerant R-407C Pipe connections water 4B Flange
5B Flange (125A HG20593-97) 5B Flange (125A HG20593-97)
1B Flange (JIS10K) 1B Flange (JIS10K) inlet/outlet (100A HG20593-97)
Pipe connections water 1 1/2B Flange 1 1/2B Flange
1B Flange (JIS10K)(25A) 2 1 1/2B Flange (JIS10K)(40A) 2 (25A) 2+1 1/2B Flange (25A) 2+1 1/2B Flange 2,456 7,050 2,456 7,500 2,456 7,950 (2,456 4,850 (2,456 5,300 (2,456 6,600 (2,456 7,050 (2,456 7,500 (2,456 7,950
inlet/outlet (JIS10K)(40A) 4 (JIS10K)(40A) 6 Dimensions (H W D) mm
(JIS10K)(40A) 2 (JIS10K)(40A) 4 2,000 2,000 2,000 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000) 2
Dimensions (H W D) mm 1,450 635 (839) 690 1,450 1,280 690 1,500 1,925 690 1,500 2,570 690 1,550 3,230 758 1,550 3,870 758 Weight kg 6,000 6,500 7,005 4,125 2 4,590 2 5,500 2 6,000 2 6,500 2 7,005 2
Weight kg 136 140 248 260 400 515 680 800 Operation weight kg 6,198 6,719 7,245 4,196 2 4,661 2 5,691 2 6,198 2 6,719 2 7,245 2
Operating weight kg 138 142 253 264 407 525 695 820 Operation range 0 to 43
Operation range -15 to 43 Notes:
Notes: *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
*2 The following safety devices are equipped as standard. High pressure switch. Reverse-phase protector. Fusible plug. Freeze up thermostat. Overcurrent relay for compressor protector.
and fan motor. Overheat protection for discharge gas. fan thermal protector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*3 This product is manufactured in Japan. *3 The unit is equipped with standard water filter.
*4 This product is manufactured in China.

Standard Unit Standard Unit


50Hz UWAP 40 180B Y 1 60Hz UWAP 40 120B Y B
106 480kW clas s 118 355kW clas s
S pecifications S pecifications
Model
UWAP40BY1 UWAP50BY1 UWAP60BY1 UWAP80BY1 UWAP100BY1 UWAP120BY1 UWAP140BY1 UWAP160BY1 UWAP180BY1 UWAP40BYB UWAP50BYB UWAP60BYB UWAP100BYB UWAP120BYB
Model
(40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (140 ) (160 ) (180 ) (40 ) (50 ) (60 ) (100 ) (120 )
kW 106 132 160 210 265 320 370 420 480 kW 118 150 180 300 355
Cooling capacity Btu/h 362,000 450,000 546,000 717,000 904,000 1,092,000 1,263,000 1,433,000 1,638,000 Cooling capacity Btu/h 403,000 512,000 614,000 1,024,000 1,212,000
USRT 30 38 46 60 75 91 105 119 137 USRT 34 43 51 85 101
Power Supply 3 phase, 50 Hz 380/400/415 V, 4 wires system Power supply 3 phase, 60 Hz 400/440 V, 4 wires system
Chilled Water Flow Rate /min 304 378 459 602 760 917 1,061 1,204 1,376 Chilled water flow rate /min 338 430 516 860 1,018
Capacity Steps % 100~10-0 Capacity steps % 100~10-0
Type Semi-hermetic sealed single-screw type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 30 1 37 1 45 1 60 1 37 2 45 2 45+60 60 2 45 3 Motor output kW 30 1 37 1 45 1 37 2 45 2
Evaporetor type Brazing Plate type Evaporator type Brazing Plate type
Comdenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser Condenser
m3/min 780 860 1,290 1,600 1,720 2,150 2,580 m3/min 810 1,010 2,020
fan Air flow rate fan Air flow rate
cfm 27,534 30,358 45,537 56,480 60,716 75,895 91,074 cfm 28,593 35,653 71,306
Motor output kW 0.5 4 1.0 4 1.0 6 1.0 8 1.0 10 1.0 12 Motor output kW 0.5 4 1.0 4 1.0 8
Refrigerant R-407C Refrigerant R-407C
Pipe connections water 5B Flange Pipe connections water
3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97) 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
inlet/outlet (125A HG20593-97) inlet/outlet
2,456 2,650 2,456 4,850 2,456 5,300 2,456 6,600 Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000
Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000
2,000 2,000 2,000 2,000 Weight kg 1,690 1,810 1,870 3,500 3,605
Weight kg 1,690 1,810 1,870 2,375 3,500 3,605 4,125 4,590 5,500 Operating weight kg 1,723 1,846 1,910 3,551 3,662
Operation weight kg 1,723 1,846 1,910 2,422 3,551 3,662 4,196 4,661 5,691 Operation range 0 to 43
Operation range 0 to 43 Notes:
Notes: *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase protector.
protector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. *3 The unit is equipped with standard water filter.
*3 The unit is equipped with standard water filter. *4 This product is manufactured in China.
*4 This product is manufactured in China.

9 10
Air Cooled Water Chillers
Year - Round Cooling Only Unit Year - Round Cooling Only Unit
50Hz UWAP 40 180B Y 1K 60Hz UWAP 40 120B Y B K
106 480kW clas s 118 355kW clas s
Water Chillers

Water Chillers
S pecifications S pecifications
Air Cooled

Air Cooled
UWAP40BY1K UWAP50BY1K UWAP60BY1K UWAP80BY1K UWAP100BY1K UWAP120BY1K UWAP140BY1K UWAP160BY1K UWAP180BY1K UWAP40BYBK UWAP50BYBK UWAP60BYBK UWAP100BYBK UWAP120BYBK
Model Model
(40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (140 ) (160 ) (180 ) (40 ) (50 ) (60 ) (100 ) (120 )
kW 106 132 160 210 265 320 370 420 480 kW 118 150 180 300 355
Cooling capacity *1 Btu/h 362,000 450,000 546,000 717,000 904,000 1,092,000 1,263,000 1,433,000 1,638,000 Cooling capacity *1 Btu/h 403,000 512,000 614,000 1,024,000 1,212,000
USRT 30 38 46 60 75 91 105 119 137 USRT 34 43 51 85 101
Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system Power supply 3 phase, 60 Hz 400/440 V, 4 wires system
Chilled water flow rate /min 304 378 459 602 760 917 1,061 1,204 1,376 Chilled water flow rate /min 338 430 516 860 1,018
Capacity steps % 100~10-0 Capacity steps % 100~10-0
Type Semi-hermetic sealed single-screw type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 30 1 37 1 45 1 60 1 37 2 45 2 45+60 60 2 45 3 Motor output kW 30 1 37 1 45 1 37 2 45 2
Evaporator type Brazing Plate type Evaporator type Brazing Plate type
Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser Condenser
m3/min 780 860 1,290 1,600 1,720 2,150 2,580 m3/min 810 1,010 2,020
fan Air flow rate fan Air flow rate
cfm 27,534 30,358 45,537 56,480 60,716 75,895 91,074 cfm 28,593 35,653 71,306
Motor output kW 0.5 4 1.0 4 1.0 6 1.0 8 1.0 10 1.0 12 Motor output kW 0.5 4 1.0 4 1.0 8
Refrigerant R-407C Refrigerant R-407C
Pipe connections water 5B Flange
3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97) Pipe connections water
inlet/outlet (125A HG20593-97) 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
inlet/outlet
2,456 2,650 2,456 4,850 2,456 5,300 2,456 6,600
Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000
2,000 2,000 2,000 2,000 Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000
Weight kg 1,715 1.835 1,895 2,410 3,550 3,655 4,185 4,660 5,575 Weight kg 1,715 1,835 1,895 3,550 3,655
Operating weight kg 1,748 1.871 1,935 2,457 3,601 3,712 4,256 4,731 5,766 Operating weight kg 1,748 1,871 1,935 3,601 3,712
Operation range -15 to 43 Operation range -15 to 43
Notes: Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase *2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector. protector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*3 The unit is equipped with standard water filter. *3 The unit is equipped with standard water filter.
*4 This product is manufactured in China. *4 This product is manufactured in China.

Year - Round Cooling Only Unit Brine Cooling Unit


50Hz UWAP 200 480B Y 1K 50Hz UWAP 40 180B Y 1Z
530 1,260kW clas s 68 303kW clas s
S pecifications S pecifications
UWAP200BY1K UWAP220BY1K UWAP240BY1K UWAP280BY1K UWAP320BY1K UWAP360BY1K UWAP400BY1K UWAP440BY1K UWAP480BY1K UWAP40BY1Z UWAP50BY1Z UWAP60BY1Z UWAP80BY1Z UWAP100BY1Z UWAP120BY1Z UWAP140BY1Z UWAP160BY1Z UWAP180BY1Z
Model Model
(200 ) (220 ) (240 ) (280 ) (320 ) (360 ) (400 ) (440 ) (480 ) (40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (140 ) (160 ) (180 )
kW 530 580 630 740 840 960 1,060 1,160 1,260 kW 68 83 101 135 166 205 236 269 303
Cooling capacity *1 Btu/h 1,809,000 1,979,000 2,150,000 2,525,000 2,867,000 3,276,000 3,617,000 3,959,000 4,300,000 Cooling capacity Btu/h 232,000 283,000 345,000 460,000 567,000 700,000 804,000 918,000 1,034,000
USRT 151 165 179 210 239 273 301 330 358 USRT 19 24 29 38 47 58 67 77 86
Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
Chilled water flow rate /min 1,519 1,663 1,806 2,121 2,408 2,752 3,039 3,325 3,612 Chilled water flow rate /min 428 522 635 848 1,044 1,290 1,483 1,693 1,906
Capacity steps % 100~10-0 Capacity steps % 100~10-0
Type Semi-hermetic sealed single-screw type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 40 2+60 45+60 2 60 3 (45+60) 2 (60 2) 2 (45 3) 2 (45 2+60) 2 (45+60 2) 2 (60 3) 2 Motor output kW 30 1 37 1 45 1 60 1 37 2 45 2 45+60 60 2 45 3
Evaporator type Brazing Plate type Evaporator type Brazing Plate type
Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser Condenser
m3/min 3,010 3,440 3,870 4,300 5,160 6,020 6,880 7,740 m3/min 780 860 1,290 1,600 1,720 2,150 2,580
fan Air flow rate fan Air flow rate
cfm 106,253 121,432 136,611 151,790 182,148 212,506 242,864 273,222 cfm 27,534 30,358 45,537 56,480 60,716 75,895 91,074
Motor output kW 1.0 14 1.0 16 1.0 18 (1.0 10) 2 (1.0 12) 2 (1.0 14) 2 (1.0 16) 2 (1.0 18) 2 Motor output kW 0.5 4 1.0 4 1.0 6 1.0 8 1.0 10 1.0 12
Refrigerant R-407C Refrigerant R-407C
Pipe connections water Pipe connections water 5B Flange
5B Flange (125A HG20593-97) 4B Flange (100A HG20593-97) 5B Flange (125A HG20593-97) 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
inlet/outlet inlet/outlet (125A HG20593-97)
2,456 7,050 2,456 7,500 2,456 7,950 (2,450 4,850 (2,456 5,300 (2,456 6,600 (2,456 7,050 (2,456 7,500 (2,456 7,950 2,456 2,650 2,456 4,850 2,456 5,300 2,456 6,600
Dimensions (H W D) mm Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000
2,000 2,000 2,000 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000 2,000 2,000 2,000
Weight kg 6,085 6,595 7,110 4,185 2 4,660 2 5,575 2 6,085 2 6,595 2 7,110 2 Weight kg 1,690 1,810 1,870 2,375 3,500 3,605 4,125 4,590 5,500
Operating weight kg 6,283 6,814 7,350 4,256 2 4,731 2 5,766 2 6,283 2 6,814 2 7,350 2 Operating weight kg 1,723 1,846 1,910 2,422 3,551 3,662 4,196 4,661 5,691
Operation range -15 to 43 Operation range ambient temp. 0 to 43, Brine temp. -10 to 16
Notes: Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB).
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase *2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector. protector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*3 The unit is equipped with standard water filter. *3 The unit is equipped with standard water filter.
*4 This product is manufactured in China. *4 This product is manufactured in China.

11 12
Air Cooled Water Chillers
Brine Cooling Unit Inverter Cooling Unit
50Hz UWAP 200 480B Y 1Z 50Hz UWAXP 125 750AY 1
337 808kW clas s 12.5 75kW clas s
Water Chillers

Water Chillers
S pecifications S pecifications
Air Cooled

Air Cooled
UWAP200BY1Z UWAP220BY1Z UWAP240BY1Z UWAP280BY1Z UWAP320BY1Z UWAP360BY1Z UWAP400BY1Z UWAP440BY1Z UWAP480BY1Z UWAXP125AY1 UWAXP190AY1 UWAXP250AY1 UWAXP375AY1 UWAXP500AY1 UWAXP630AY1 UWAXP750AY1
Model Model
(200 ) (220 ) (240 ) (280 ) (320 ) (360 ) (400 ) (440 ) (480 ) (5 ) (8 ) (10 ) (15 ) (20 ) (25 ) (30 )
kW 337 370 404 472 538 606 674 740 808 kW 12.5 19.0 25.0 37.5 50.0 63.0 75.0
Cooling capacity Btu/h 1,149,000 1,263,000 1,379,000 1,611,000 1,836,000 2,068,000 2,300,000 2,525,000 2,757,000 Cooling capacity *1 Btu/h 42,700 64,900 85,400 128,000 171,000 215,000 256,000
USRT 96 105 115 134 153 172 192 210 230 USRT 3.55 5.40 7.11 10.7 14.2 17.9 21.3
Power supply 3 phase,50 Hz 380/400/415 V, 4 wires system Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
Chilled water flow rate /min 2,119 2,328 2,542 2,970 3,385 3,813 4,241 4,656 5,084 Chilled water flow rate /min 36 54 72 108 143 181 215
Capacity steps % 100~10-0 Capacity steps % 100~35 100~20
Type Semi-hermetic sealed single-screw type Type Hermetically sealed scroll type
Compressor Compressor
Motor output kW 45 2+60 45+60 2 60 3 (45+60) 2 (60 2) 2 (45 3) 2 (45 2+60) 2 (45+60 2) 2 (60 3) 2 Motor output kW 3.5 1 (3.5+2.2) 1 (3.5+3.75) 1 (5.5+5.5) 1 (5.5+7.5) 1 (3.5+3.75)+(5.5+5.5) (3.5+3.75)+(5.5+7.5)
Evaporator type Brazing Plate type Evaporator type Blazing plate heat exchangers
Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive (Inverter system)
Condenser Condenser
m3/min 3,010 3,440 3,870 4,300 5,160 6,020 6,880 7,740 m3/min 80 150 170 265 340 170+265 170+340
Fans Air flow rate fan Air flow rate
cfm 106,253 121,432 136,611 151,790 182,148 212,506 242,864 273,222 cfm 3,180 4,940 6,180 9,350 12,400 6,180+9,350 6,180+12,400
Motor output kW 1.0 14 1.0 16 1.0 18 (1.0 10) 2 (1.0 12) 2 (1.0 14) 2 (1.0 16) 2 (1.0 18) 2 Motor output kW 0.20 1 (0.20+0.14) 1 (0.20+0.18) 1 0.20 3 (0.14+0.20) 2 (0.20+0.18)+0.20 3 (0.20+0.18)+(0.14 2+0.20 2)
Refrigerant R-407C Refrigerant R-407C
Pipe connections water Pipe connections water 1B Flange
5B Flange (125A HG20593-97) 4B Flange (100A HG20593-97) 5B Flange (125A HG20593-97) 1 1/2B Flange (JIS10K)(25A) 2B Flange (JIS10K)(50A) 2 1/2B Flange (JIS10K)(65A)
inlet/outlet inlet/outlet (JIS10K)(25A)
2,456 7,050 2,456 7,500 2,456 7,950 (2,456 4,850 (2,456 5,300 (2,456 6,600 (2,456 7,050 (2,456 7,500 (2,456 7,950 Dimensions (H W D) mm 1,450 835 690 1,450 1,280 690 1,500 1,925 690 1,500 2,570 690 1,550 3,230 758 1,550 3,870 758
Dimensions (H W D) mm
2,000 2,000 2,000 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000) 2 2,000) 2 Weight kg 150 250 260 440 510 715 790
Weight kg 6,000 6,500 7,005 4,125 2 4,590 2 5,500 2 6,000 2 6,500 2 7,005 2 Operating weight kg 152 252 263 446 517 730 820
Operating weight kg 6,198 6,719 7,245 4,196 2 4,661 2 5,691 2 6,198 2 6,719 2 7,245 2 Operation range -15 to 43
Operation range ambient temp. 0 to 43, Brine temp. -10 to 16 Notes:
Notes: *1 Cooling capacity is based on the following conditions : Entering water temp.12 (53.6 F), Ieaving chilled water temp.7 (44.5 F), and outdoor temp. 35 DB (95 FDB).
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB). *2 The following safety devices are equipped as standard. High / pressure switch. Reverse-phase protector. Fusible plug. Freeze-up thermostat. Overcurrent relay for
compressor
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
and fan motor. Overheat protection for discharge gas. Fan thermal protector.
protector. *3 This product is manufactured in Japan.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*3 The unit is equipped with standard water filter.
*4 This product is manufactured in China.

Brine Cooling Unit Standard Unit


60Hz UWAP 40 120B Y B Z 50Hz UWA40 180AY 1
79 242kW clas s 106 480kW clas s
S pecifications S pecifications
UWAP40BYBZ UWAP50BYBZ UWAP60BYBZ UWAP100BYBZ UWAP120BYBZ UWA40AY1 UWA50AY1 UWA60AY1 UWA80AYAY1 UWA100AY1 UWA120AY1 UWA140AY1 UWA160AY1 UWA180AY1
Model Model
(40 ) (50 ) (60 ) (100 ) (120 ) (40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (140 ) (160 ) (180 )
kW 79 94 121 188 242 kW 106 132 160 210 265 320 370 420 480
Cooling capacity Btu/h 270,000 321,000 413,000 642,000 826,000 Cooling capacity *1 Btu/h 362,000 450,000 546,000 717,000 904,000 1,092,000 1,263,000 1,433,000 1,638,000
USRT 22 27 34 53 69 USRT 30 38 46 60 75 91 105 119 137
Power supply 3 phase,60 Hz 400/440 V, 3 wires system Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
Chilled water flow rate /min 497 591 761 1,183 1,523 Chilled water flow rate /min 304 378 459 602 760 917 1,061 1,204 1,376
Capacity steps % 100~10-0 Capacity steps % 100~10-0 (continuous capacity control)
Type Semi-hermetic sealed single-screw type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 30 1 37 1 45 1 37 2 45 2 Motor output kW 30 1 37 1 45 1 60 1 37 2 45 2 45+60 60 2 45 3
Evaporator type Brazing Plate type Evaporator type Blazing Plate type
Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser Condenser
m3/min 810 1,010 2,020 m3/min 700 710 840 940 1,420 1,680 1,780 1,880 2,520
Fans Air flow rate fan Air flow rate
cfm 28,593 35,653 71,306 cfm 24,710 25,063 29,652 33,182 50,126 59,304 62,834 66,364 88,956
Motor output kW 0.5 4 1.0 4 1.0 8 Motor output kW 0.5 4 0.8 4 1.2 4 0.8 8 1.2 8 1.2 12
Refrigerant R-407C Refrigerant R-22
Pipe connections water Pipe connections water 5B Flange
3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97) 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
inlet/outlet inlet/outlet (125A HG20593-97)
Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000 Dimensions (H W D) mm 2,395 2,200 2,000 2,395 4,400 2,000 2,460 6,600 2,000
Weight kg 1,690 1,810 1,870 3,500 3,605 Weight kg 1,500 1,650 1,750 1,820 3,300 3,500 3,620 3,640 5,605
Operating weight kg 1,723 1,846 1,910 3,551 3,662 Operating weight kg 1,517 1,670 1,773 1,852 3,336 3,542 3,684 3,704 5,670
Operation range ambient temp. 0 to 43, Brine temp. -10 to 16 Operation range -5 to 43
Notes: Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), and outdoor air temp. 35 DB(95 FDB). *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase *2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector. protector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*3 The unit is equipped with standard water filter. *3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.
*4 This product is manufactured in China. *4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).

13 14
Air Cooled Water Chillers
Standard Unit Option L is t
50Hz UWA200 480AY 1 Model
UWAP40BY1 UWAP50BY1 UWAP60BY1
UWAP80BY1
UWAP100BY1 UWAP120BY1
UWAP140BY1 UWAP160BY1 UWAP180BY1
UWAP40BYB UWAP50BYB UWAP60BYB UWAP100BYB UWAP120BYB
530 1,260kW clas s Remote controller BRC307D503
Chilling water supply interrupting relay GWEL-UWYP40B GWEL-UWYP100B GWEL-UWYP180B
Water Chillers

Water Chillers
S pecifications Water high pressure (1.6 MPa) upgrader GWP-UWYP40B GWP-UWYP80B GWP-UWYP100B GWP-UWYP180B
Air Cooled

Air Cooled
IPU DAM602A5
UWA200AY1 UWA220AY1 UWA240AY1 UWA280AY1 UWA320AY1 UWA360AY1 UWA400AY1 UWA440AY1 UWA480AY1
Model Dio unit DEC102A
(200 ) (220 ) (240 ) (280 ) (320 ) (360 ) (400 ) (440 ) (480 )
530 580 630 740 D Air unit DAM101A
kW 840 960 1,060 1,160 1,260
1,979,000 2,150,000 Interface for use in LONWORKS DMS504B51
Cooling capacity *1 Btu/h 1,809,000 2,525,000 2,867,000 3,276,000 3,617,000 3,959,000 4,300,000
165 179 Interface for use in BACnet DMS502A51
USRT 151 210 239 273 301 330 358
3 phase, 50 Hz 380/400/415 V, 4 wires system Central remote controller DCS302CA61
Power supply
1,663 1,806 Unified ON/OFF controller DCS301BA61
Chilled water flow rate /min 1,519 2,121 2,408 2,752 3,039 3,325 3,612
100~10-0 (continuous capacity control) Schedule timer DST301BA61
Capacity steps %
Type Semi-hermetic sealed single-screw type
Compressor
Motor output kW 45 2+60 45+60 2 60 3 (45+60) 2 (60 2) 2 (45 3) 2 (45 2+60) 2 (45+60 2) 2 (60 3) 2 Model UWAP200BY1 UWAP220BY1 UWAP240BY1 UWAP280BY1 UWAP320BY1 UWAP360BY1 UWAP400BY1 UWAP440BY1 UWAP480BY1
Evaporator type Blazing Plate type
Condenser type Cross fin coil Remote controller BRC307D503
Type Propeller Chilling water supply interrupting relay GWEL-UWYP180B GWEL-UWYP280B GWEL-UWYP360B
Drive Direct drive Water high pressure (1.6 MPa) upgrader GWP-UWYP180B GWP-UWYP280B GWP-UWYP360B
Condenser IPU DAM602A5
m3/min 2,620 2,720 2,820 3,560 3.760 5,040 5,240 5,440 5,640
fan Air flow rate Dio unit DEC102A
cfm 92,486 96,016 99,546 125,668 132,728 177,912 184,972 192,032 199,092
Motor output kW 1.2 12 (1.2 8) 2 (1.2 12) 2 D Air unit DAM101A
Refrigerant R-22 Interface for use in LONWORKS DMS504B51
Pipe connections water Interface for use in BACnet DMS502A51
5B Flange (125A HG20593-97) 4B Flange (100A HG20593-97) 5B Flange (125A HG20593-97) Central remote controller DCS302CA61
inlet/outlet
Unified ON/OFF controller DCS301BA61
Dimensions (H W D) mm 2,460 6,600 2,000 (2,395 4,400 2,000) 2 (2,460 6,600 2,000) 2 Schedule timer DST301BA61
Weight kg 5,660 5,695 5,750 3,620 2 3,640 2 5,605 2 5,660 2 5,695 2 5,750 2
Operating weight kg 5,737 5,782 5,850 3,684 2 3,704 2 5,670 2 5,737 2 5,782 2 5,850 2 Model UWAP75AY3 UWAP190AY3 UWAP250AY3 UWAP375AY3 UWAP500AY3 UWAP630AY3 UWAP750AY3
UWAP125AY3
Operation range -5 to 43
Remote controller *1 BRC307C50
Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). Communication I/F P.C. board BRP66B3 1
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase Communication I/F P.C. B storage box BRP66A97 1(external) BRP66A100 1(internal) Not required (S.Box installed)
protector. Transmission wire BER66A5 1 BER66A7 1
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. Central remote controller *1 DCS302CA61
*3 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required.
*4 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery). Unified ON/OFF controller *1 DCS301BA61
Schedule timer *1 DST301BA61
Notes:
*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission wire are also required.

Model UWAXP125AY1 UWAXP190AY1 UWAXP250AY1 UWAXP375AY1 UWAXP500AY1 UWAXP630AY1 UWAXP750AY1


Remote controller *1 BRC307C50
Standard Unit Communication I/F P.C. board BRP66B3 1 BRP66B3 2

60Hz UWA40 120AY B


Communication I/F P.C. B storage box
Transmission wire
Notes:
BER66A5
BPR66A97
BER66A6

BER66A7
BRP66A96
BER66A8

*1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
118 355kW clas s
UWA40AY1 UWA50AY1 UWA60AY1 UWA100AY1 UWA120AY1
S pecifications Model UWA80AY1 UWA140AY1 UWA160AY1 UWA180AY1
UWA40AYB UWA50AYB UWA60AYB UWA100AYB UWA120AYB
UWA40AYB UWA50AYB UWA60AYB UWA100AYB UWA120AYB Remote controller BRC307D503
Model
(40 ) (50 ) (60 ) (100 ) (120 ) Chilling water supply interrupting relay GWEL-UWY40A GWEL-UWY80A GWEL-UWY180A
kW 118 150 180 300 355 Water high pressure (1.6 MPa) upgrader GWP-UWY40A GWP-UWY80A GWP-UWY100A GWP-UWY180A
Cooling capacity *1 Btu/h 403,000 512,000 614,000 1,024,000 1,212,000 IPU DAM602A5
USRT 34 43 51 85 101 Dio unit DEC102A
Power supply 3 phase, 60 Hz 400/440 V, 4 wires system D Air unit DAM101A
Chilled water flow rate /min 338 430 516 860 1,018 Interface for use in LONWORKS DMS504B51
Capacity steps % 100~10-0 (continuous capacity control) Interface for use in BACnet DMS502A51
Type Semi-hermetic sealed single-screw type Central remote controller DCS302CA61
Compressor
Motor output kW 30 1 37 1 45 1 37 2 45 2 Unified ON/OFF controller DCS301BA61
Evaporator type Blazing Plate type Schedule timer DST301BA61
Condenser type Cross fin coil
Type Propeller
Drive Direct drive Model UWA200AY1 UWA220AY1 UWA240AY1 UWA280AY1 UWA320AY1 UWA360AY1 UWA400AY1 UWA440AY1 UWA480AY1
Condenser
m3/min 800 810 940 1,620 1,880 Remote controller BRC307D503
fan Air flow rate
cfm 28,240 28,593 33,182 57,186 66,364 Chilling water supply interrupting relay GWEL-UWY180A GWEL-UWY280A GWEL-UWY360A
Motor output kW 0.5 4 0.8 4 1.2 4 0.8 8 1.2 8 Water high pressure (1.6 MPa) upgrader GWP-UWY180A GWEL-UWY281A GWP-UWY360A
Refrigerant R-22 IPU DAM602A5
Pipe connections water Dio unit DEC102A
3B Flange (80A) 4B Flange (100A) D Air unit DAM101A
inlet/outlet
Interface for use in LONWORKS DMS504B51
Dimensions (H W D) mm 2,395 2,200 2,000 2,395 4,400 2,000 Interface for use in BACnet DMS502A51
Weight kg 1,500 1,650 1,750 3,300 3,500 Central remote controller DCS302CA61
Operating weight kg 1,517 1,670 1,773 3,336 3,542 Unified ON/OFF controller DCS301BA61
Operation range -5 to 43 Schedule timer DST301BA61
Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*2 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*3 The unit is equipped with standard water filter.
*4 The limited length of wire represents its max. length when the pressure is lower than 2%.
*5 This product is manufactured in China.

15 16
Air Cooled Water Chillers F or High Outdoor Temperature Us e

For High Outdoor Temperature Use


: UWA S eries 50Hz UWA120 270J Y 1
351.6 791kW clas s
Water Chillers

Water Chillers
S pecifications
Air Cooled

Air Cooled
Model UWA120JY1(130 ) UWA138JY1(150 ) UWA162JY1(180 ) UWA192JY1(200 ) UWA228JY1(240 ) UWA270JY1(300 )

kW 351.6 404.4 474.7 562.8 667.9 791.0


Cooling capacity *1 Btu/h 1,201,500 1,380,800 1,620,600 1,921,500 2,280,400 2,700,800
USRT 99.9 115.0 135.0 160.0 189.9 224.7
Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
UWA55J AY 1 UWA138J Y 1 UWA80J ATJ Chilled water flow rate 100-83-67-50-33-17-0 100-88-75-63-50-25-0 100-83-67-50-33-17-0
Type Semi-hermetic sealed reciprocating
Compressor
Motor output kW 30 3 37 3 45 3 37 4 45 4 37 6
Dry expansion shell
P rovides a s table s upply of chilled water even when the outdoor temperature is as Evaporator type Dry expansion shell and Hi-X tubes Dry expansion shell and corrugated tubes
and Hi-X tubes

high as 49 . Condenser type


Type
Cross fin coil (Waffle louver fins and Hi-X tubes)
Propeller
Drive Direct drive
Condenser
Wide Operating Range Wide Capacity Range fan Air flow rate
m3/min 2,580 3,000 3,720 4,000 4,960 6,000
cfm 91,100 105,900 131,400 141,300 175,200 211,900
Temperature range by model. UWA37J AY 1 109J AY 1 Motor output kW 0.9ea. 12 1.5ea. 12 0.9ea. 16 1.5ea. 16 0.9ea. 24
Refrigerant R-22
UWA37J AY 1 109J AY 1 5 to 52 UWA43J ATJ 122J ATJ Pipe connections water inlet/outlet 5B Flange (JIS16K)(125A)
UWA120J Y 1 270J Y 1 5 to 49 UWA120J Y 1 270J Y 1 Dimensions (H W D) mm 2,095 2,005 5,700 2,075 2,005 8,000 2,095 2,005 11,400
U W A27J AT J / 32J AT J , 70J AT J 122J AT J 15 to 49 C apacity can be controlled in multiple steps of between 3 and Weight kg 4,360 4,470 4,660 6,110 6,340 8,940
UWA43J ATJ 62J ATJ 5 to 49 7 for efficient energy use. Operation range 5 to 49
Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).
Full Lineup Includes Models with Two Independent Refrigerant Circuits *2 The following safety devices are equipped as standard. High pressure switch. Low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling
guard timer. Crankcase heater. 3-element overcurrent relay (Compressor, Fan motors). Freeze-up protection thermostat. Fusible plug. Safety valve (except for UWA120JY1).
Capacities Ranging from 79 791kW. UWA63 J AY 1 10 9J AY 1
*3 This product is manufactured in Japan.

UWA70J ATJ 122 J ATJ


UWA120J Y 1 270 J Y 1
Equipped with a Compact and A selector switch makes it possible to operate only one refrig-
Powerful Semi-hermetically Sealed erant circuit while the other is under repair.
Reciprocating Compressor.

For High Outdoor Temperature Use For High Outdoor Temperature Use
50Hz UWA37 109J AY 1 60Hz UWA27 122J ATJ
108.4 319.2kW clas s 79 370kW clas s
S pecifications S pecifications
UWA37JAY1 UWA47JAY1 UWA55JAY1 UWA63JAY1 UWA75JAY1 UWA80JAY1 UWA93JAY1 UWA109JAY1 UWA27JATJ UWA32JATJ UWA43JATJ UWA53JATJ UWA62JATJ UWA70JATJ UWA80JATJ UWA90JATJ UWA108JATJ UWA122JATJ
Model Model
(40 ) (50 ) (60 ) (70 ) (80 ) (90 ) (100 ) (120 ) (25 ) (30 ) (40 ) (50 ) (60 ) (70 ) (80 ) (90 ) (100 ) (120 )
kW 108.4 137.2 161.3 186.0 219.1 250.6 272.7 319.2 kW 79.0 94.3 125.0 162.0 185.0 212.0 253.0 274.0 324.0 370.0
Cooling capacity *1 Btu/h 369,800 468,200 550,400 634,900 747,600 855,100 930,500 1,089,200 Cooling capacity *1 Btu/h 269,800 320,600 426,600 553,500 632,100 722,200 865,000 936,400 1,107,000 1,262,000
USRT 30.8 39.0 45.8 52.9 62.3 71.2 77.5 90.7 USRT 22.4 26.7 35.5 46.1 52.6 60.0 72.0 78.0 92.2 105.0
Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system Power supply 3 phase, 60 Hz, 208/230 V, 3 wires system
Chilled water flow rate 282 358 420 485 571 653 711 832 Chilled water flow rate 206 245 326 423 483 552 661 715 845 964
kW 97.4 124.8 149.9 167.4 197.1 225.5 250.8 290.5 kW 71.0 82.0 111.0 145.0 171.0 191.0 219.0 248.0 285.0 335.0
Cooling capacity *2 Btu/h 332,500 425,800 511,500 571,400 672,600 769,400 855,900 991,200 Cooling capacity *2 Btu/h 242,000 280,900 378,900 494,000 584,100 653,100 746,400 845,200 972,200 1,145,000
USRT 27.7 35.4 42.6 47.6 56.0 64.1 71.3 82.6 USRT 20.1 23.4 31.5 41.0 48.6 54.2 62.1 70.4 81.0 95.3
Chilled water flow rate 279 325 391 436 514 588 654 757 Chilled water flow rate 185 215 289 377 466 497 570 645 742 873
Capacity steps % 100-66-33-0 100-75-50-25-0 100-83-66-50-33-0 100-88-75-63-50-25-0 Capacity steps % 100-50-0 100-66-33-0 100-75-50-25-0 100-83-66-50-33-0 100-88-75-63-50-25-0
Type Semi-hermetically sealed reciprocating Type Semi-hermetically sealed reciprocating
Compressor Compressor
Motor output kW 30 37 45 30 2 37 2 45 2 Motor output kW 22 30 37 45 26 2 30 2 37 2 45 2
Evaporator type Dry expansion shell and Hi-X tube Evaporator type Dry expansion shell and Hi-X tube
Condenser type Cross fin coil (Waffle louver fins and Hi-X tubes) Condenser type Cross fin coil (Waffle louver fins and Hi-X tubes)
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser Condenser
m /min 860
3
1,000 1,240 1,720 2,000 2,480 m3/min 580 480 1,160 1,400 1,920 2,320 2,800
fan Air flow rate fan Air flow rate
cfm 30,370 35,310 43,790 60,730 70,620 87,580 cfm 20,480 16,950 40,960 49,430 67,800 81,920 98,870
Motor output kW 0.9ea. 4 1.5ea. 4 0.9ea. 8 1.5ea. 8 Motor output kW 1.7ea. 2 1.0ea. 2 1.0ea. 4 1.7ea. 4 2.5ea. 4 1.0ea. 8 1.7ea. 8 2.5ea. 8
Refrigerant R-22 Refrigerant R-22
Pipe connections water 5B Flange Pipe connections water inlet/outlet FPT2 (50A) FPT2 1/2 (65A) FPT3 (80A) 4B Flange (JIS16K)(100A) 5B Flange (JIS16K)(125A)
FPT2 1/2 (65A) FPT3 (80A) 4B Flange (JIS16K)(100A)
inlet/outlet (JIS16K)(125A) 1,765 2,025 1,915 2,025 1,745 2,005
Dimensions (H W D) mm 1,890 2,005 2,000 1,915 2,005 4,000
Dimensions (H W D) mm 1,720 2,005 2,000 1,890 2,005 2,000 1,745 2,005 4,000 1,915 2,005 4,000 1,065 1,065 4,000
Weight kg 1,230 1,420 1,520 2,500 2,600 2,850 2,870 3,050 Weight kg 750 900 1,300 1,540 1,610 2,500 2,600 2,850 2,870 3,050
Operating weight kg 1,300 1,490 1,610 2,600 2,730 2,980 3,000 3,210 Operating weight kg 790 970 1,370 1,630 1,700 2,600 2,730 2,980 3,000 3,210
Operation range 5 to 52 Operation range 15 to 49 5 to 49 15 to 49
Notes: Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB). *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 35 DB(95 FDB).
*2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB). *2 Cooling capacity is based on the following conditions : Leaving chilled water temp.6.7 (44 F), entering chilled water temp.12.2 (54 F), and outdoor air temp. 46 DB(115 FDB).
*3 The following safety devices are equipped as standard. High/low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling guard timer. *3 The following safety devices are equipped as standard. High/low pressure switch. Oil pressure control switch. Compressor thermal protector. Recycling guard timer.
Crankcase heater. 3-element overcurrent relay for compressors and fan motors. Freeze-up prorection thermostat. Fusible plug. Safety valve(for UWA47, 55, 93, 109JAY1). Crankcase heater. 3-element overcurrent relay for compressors and fan motors. Freeze-up protection thermostat. Fusible plug. Safety valve(for UWA53, 62, 90, 108, 18
*4 This product is manufactured in Japan. 122JATJ).
17 *4 This product is manufactured in Japan.
Air Cooled Water Chillers - Heat PumpType
: UW Y P S eries
: UW Y S eries

Wide Operation Range Easy Installation


UWY P 40 480B Y 1 UWY 40 120AY 1 UWY P 40 480B Y 1 UWY 40 480AY 1
UWY P 40 120B Y B UWY 40 120AY B UWY P 40 120B Y B UWY 40 120AY B
A new defros ting s ys tem makes pos s ible heating operation The compact des ign of thes e units s ignificantly reduces the
even when the outdoor temperature is as low as -15 . s pace required for ins tallation.
Note: Measures to protect against drain water freezing are necessary in cold re- In the outdoor unit, component parts of a small size have been used wherever
gions where the highest temperature stays below 0 on several consecutive possible to reduced its size and correspondingly reduce how much space it re-
days. quires. Furthermore, replacing the 2-way refrigerant inlets with 4-way inlets has
reduced the amount of space the outdoor unit needs even further.
Outdoor Air Temperature R ange where C ooling P os s ible
C apacity
Models E mploying R -407C Models E mploying R -22 UWY P 125 750AY 3
5 30 -15 to 43 The horizontal linkup des ign increas es ins tallation flexibility.
40 480 -5 to 43 -5 to 43 This design ensures the installation does not protrude so far, making it possible

Air Cooled Water Chillers


Air Cooled Water Chillers

to install water chillers along a wall or under a roof overhang.


UWY P 750AY 3 UWY P 120B Y 1 UWY P 180B Y 1 Note: Water supply piping must be purchased separately.

- Heat Pump Type


- Heat Pump Type

(UWYP375AY3 750AY3)
Multiple Operating Modes
UWY P 40 160B Y 1 UWY 40 160AY 1
UWY P 40 120B Y B UWY 40 120AY B Reliability
Us ers can s elect the operating mode that bes t matches the
Applies to All Models Refrigerant
Model Lineup heat s ource application. Refrigerant
Outlet
S tainles s s teel heat ex- Inlet Water
Refrigerant Units series Model No.
Capacity (kW) page Capacity Control Mode changer plates prevent rus t, Outlet
6.7/7.5 11.2/12.5 17/19 22.4/25 33.5/37.5 45/50 56/63 67/75 106 132 160 212 265
The us er can s elect to give priority to either precis ion or reduced
thereby improving their du-
50/60Hz UWYPAY3 125 190 250 375 500 630 750 21
50Hz R-407C Standard Unit UWYPBY1 40 50 60 80 100 21, 22 power cons umption. rability and the s ys tem's
60Hz UWYPBYB 40 50 60 100 22 operational reliability.
50Hz UWYAY1 40 50 60 80 100 23 High-P rec is ion Mode L ow-P ower Mode Heat Exchanger with
R-22 Standard Unit Stainless Steel Plates
60Hz UWYAYB 40 50 60 80 100 24 C ontinues operation to levels This mode can be used to
as low as 12% of total ca- reduce power consumption if Applies to All Models
Capacity (kW)
Refrigerant Units series Model No. page pacity to provide s table wa- highly precise water tempera-
315 370 420 480 530 580 630 740 840 960 1060 1160 1260 Air heat exchangers employ fins with acrylic coating for
50Hz UWYPBY1 120 140 160 180 200 220 240 280 320 360 400 440 480 21, 22
ter temperature control even ture control is not necessary
R-407C Standard Unit
s uperior durability.
60Hz UWYPBYB 120 22 during low-load periods . during low- load periods . It
50Hz UWYAY1 120 140 160 180 200 220 240 280 320 360 400 440 480 23 shuts down the compressor UWY P 40 480B Y 1 UWY 40 480AY 1
R-22 Standard Unit
60Hz UWYAYB 120 24 when the load drops below UWY P 40 120B Y B UWY 40 120AY B
Note: Switching between the above modes is accomplished
40% . using a control on
the outdoor unit. Defros ting is performed under computer control as part of
continuous capacity control, res ulting in s table heating
New Refrigerant Low Power Consumption Demand Mode performance.
The system detects ice formation by constantly monitoring the outdoor tempera-
UWY P 125 750AY 3 UWY P 40 160B Y 1 UWY P 40 120B Y B C urrent Demand F unc tion ture, the pressures of the high- and low-pressure components, and the timers. In
UWY P 40 480B Y 1 UWY 40 120AY 1 UWY 40 120AY B addition, continuous capacity control allows smooth control of capacity even af-
UWY P 40 120B Y B The maximum current level of the compres s or can be s pecified
C ontinuous capacity control with a range from 10(12)% to ter a rise in the pressure of the high-pressure components. Remaining ice is
in order to control demand for power. S ince this function allows
E mploys the new refrigerant R -407C . 100% helps to reduce energy was tage during low-load melted a little at a time, and stable heating performance is maintained.
s etting of the upper limit current value, comfortable operation is
maintained while effectively controlling demand. In contras t to
conventional capacity control s tep limit s ys tems , maximum
Efficient and Reliable Compressors High Precision capacity is maintained at the des ired demand value.

Applies to All Models UWY P 40 160B Y 1 UWA40 160AY 1 UWY P 100 480B Y 1 UWY 100 480AY 1
UWY P 40 120B Y B UWA40 120AY B UWY P 100 120B Y B UWY 100 120AY B
To improve their operational reliability, 40 -- 480HP models
Duty cycling control equalizes the operating time of the
are equipped with s emi-hermetic s ingle s crew compres s ors . The outlet water temperature is precis ely controlled to within
0.5 UWY P 40 160B Y 1 UWY 40 160AY 1
(with a s table load) through the us e of electric expans ion UWY P 40 120B Y B UWY 40 480AY B
A choice of three control s ys tems is available.
R efrigerant inlet E xample of Outlet Water Temperature C ontrol
Outflow water temperature control
Water Temp. ( ) If outlet water temperature ris es above the upper limit s ignal,
the load s tarts to increas e in 10% increments Provides precise control of the water temperature.
10
Compressor count control
R efrigerant outlet 9 Controls the number of compressors operating depending on the load.
Upper Limit S ignal
8 Inflow water temperature control
Performs duty cycling control.
Value S et 7
S emi-hermetic s ingle
As the temperature As the temperature When changes in outlet
s crew compres s or falls below the upper falls below the s et water temperature
limit s ignal, the load value, the load become 1 or les s ,
increas e increments increas e increments the thermos tat is turned
are reduced to 5% . remain at 5% . off.

19 20
Air Cooled Water Chillers - Heat PumpType
Standard Unit Standard Unit
50/60Hz UWY P 125 750AY 3 50Hz UWY P 200 480B Y 1
11.2 / 12.5 67 / 75 kW clas s 530 1,260kW clas s
S pecifications S pecifications
UWYP125AY3 UWYP190AY3 UWYP250AY3 UWYP375AY3 UWYP500AY3 UWYP630AY3 UWYP750AY3 UWYP200BY1 UWYP220BY1 UWYP240BY1 UWYP280BY1 UWYP320BY1 UWYP360BY1 UWYP400BY1 UWYP440BY1 UWYP480BY1
Model Model
(5 ) (8 ) (10 ) (15 ) (20 ) (25 ) (30 ) (200 ) (220 ) (240 ) (280 ) (320 ) (360 ) (400 ) (440 ) (480 )
kW 11.2/12.5 17.0/19.0 22.4/25.0 33.5/37.5 45.0/50.0 56.0/63.0 67.0/75.0 kW 530 580 630 740 840 960 1,060 1,160 1,260
Cooling capacity *1
Btu/h 38,200/42,700 58,000/64,900 76,500/85,400 114,000/128,000 154,000/171,000 191,000/215,000 229,000/256,000 Cooling capacity Btu/h 1,809,000 1,979,000 2,150,000 2,525,000 2,867,000 3,276,000 3,617,000 3,959,000 4,300,000
(50/60 Hz)
USRT 3.19/3.55 4.83/5.40 6.37/7.11 9.53/10.7 12.8/14.2 15.9/17.9 19.1/21.3 USRT 151 165 179 210 239 273 301 330 358
Chilled water flow rate (50/60 Hz) /min 32/36 49/54 64/72 96/108 129/143 161/181 192/215 Chilled water flow rate /min 1,519 1,663 1,806 2,121 2,408 2,752 3,039 3,325 3,612
kW 13.2/15.0 20.0/22.4 25.0/28.0 37.5/42.5 50.0/56.0 63.0/71.0 75.0/85.0 kW 570 630 690 800 920 1,020 1,140 1,260 1,380
Heating capacity *2
Btu/h 45,100/51,200 68,300/76,500 85,400/95,600 128,000/145,000 171,000/191,000 215,000/242,000 256,000/290,000 Heating capacity Btu/h 1,945,000 2,150,000 2,355,000 2,730,000 3,140,000 3,481,000 3,890,000 4,300,000 4,710,000
(50/60 Hz)
USRT 3.75/4.27 5.69/6.37 7.11/7.96 10.7/12.1 14.2/15.9 17.9/20.2 21.3/24.2 USRT 162 179 196 228 262 290 324 358 392
Power supply 3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
Hot water flow rate (50/60 Hz) /min 38/43 57/64 72/80 108/122 143/161 181/204 215/244 Hot water flow rate /min 1,634 1,806 1,978 2,293 2,637 2,924 3,268 3,612 3,956
Capacity steps % 100-0 100-67-34-0 100-50-0 100-80-60-40-20-0 100-67-34-0 Capacity steps % 100~10-0
Type Hermetically sealed scroll type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 3.75 1 5.5 1 7.5 1 7.5+3.75 7.5 2 7.5 2+3.75 7.5 3 Motor output kW 45 2+60 45+60 2 60 3 (45+60) 2 (60 2) 2 (45 3) 2 (45 2+60) 2 (45+60 2) 2 (60 3) 2
Evaporator type Brazed plate heat exchanger Evaporator type Brazing Plate type
Air Cooled Water Chillers

Air Cooled Water Chillers


Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser
- Heat Pump Type

- Heat Pump Type


Fan Air flow rate m3/min 90/95 140/160 175/185 265/280 350/370 440/465 525/555 m3/min 3,010 3,440 3,870 4,300 5,160 6,020 6,880 7,740
Fans Air flow rate
(50/60 Hz) cfm 3,180/3,350 4,940/5,650 6,180/6,530 9,350/9,880 12,400/13,100 15,500/16,400 18,500/19,600 cfm 106,253 121,432 136,611 151,790 182,148 212,506 242,864 273,222
Motor output kW 0.20 0.22+0.14 0.22 2 0.22 2+0.20 0.22 4 0.22 4+0.20 0.22 6 Motor output kW 1.0 14 1.0 16 1.0 18 (1.0 10) 2 (1.0 12) 2 (1.0 14) 2 (1.0 16) 2 (1.0 18) 2
Refrigerant R-407C Refrigerant R-407C
1B Flange (JIS10K) 1B Flange (JIS10K) Pipe Water inlet/outlet 5B Flange (125A HG20593-97) 4B Flange (100A HG20593-97) 5B Flange (125A HG20593-97)
Pipe connections 1B Flange 1 1/2B Flange 1 1/2B Flange
1 1/2B Fiange(JIS10K)(40A) 2 (25A) 2+1 1/2B Flange (25A) 2+1 1/2B Flange connections Drain outlet RP1 1/4 Female screw (32A)
water inlet/outlet (JIS10K)(25A) 2 (JIS10K)(40A) 4 (JIS10K)(40A) 6
(JIS10K)(40A) 2 (JIS10K)(40A) 4 Dimensions (H W D) mm 2,456 7,050 2,000 2,456 7,500 2,000 2,456 7,950 2,000 (2,456 4,850 2,000) 2 (2,456 5,300 2,000) 2 (2,456 6,600 2,000) 2 (2,456 7,050 2,000) 2 (2,456 7,500 2,000) 2 (2,456 7,950 2,000) 2
Dimensions (H W D) mm 1,450 635 (839) 690 1,450 1,280 690 1,500 1,925 690 1,500 2,570 690 1,550 3,230 758 1,550 3,870 758 Weight kg 6,820 7,500 7,885 4,553 2 5,110 2 6,265 2 6,820 2 7,500 2 7,885 2
Weight kg 150 258 260 420 525 700 820 Operating weight kg 7,018 7,719 8,125 4,624 2 5,181 2 6,456 2 7,018 2 7,719 2 8,125 2
Operating weight kg 152 261 264 427 535 715 840 Operation range cooling -5 to 43, heating -20 to 21
Operation range -15 to 43 in cooling, -15 to 21 in heating Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
Notes:
*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
6 WB(43 FWB).
*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp. 40 (104 F), and outdoor air temp. 7 DB(44.5 FDB), and
*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
6 WB(43 FWB).
protector.
*3 The following safety devices are equipped as standard. High pressure switch. Reverse-phase protector. Fusible plug. Freeze up thermostat. Overcurrent relay for compressor
and fan motor. Overheat protection for discharge gas. fan thermal protector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
*4 This product is manufactured in Japan.

Standard Unit Standard Unit


50Hz UWY P 40 180B Y 1 60Hz UWY P 40 120B Y B
106 480kW clas s 118 355kW clas s
S pecifications S pecifications
UWYP40BY1 UWYP50BY1 UWYP60BY1 UWYP80BY1 UWYP100BY1 UWYP120BY1 UWYP140BY1 UWYP160BY1 UWYP180BY1 UWYP40BYB UWYP50BYB UWYP60BYB UWYP100BYB UWYP120BYB
Model Model
(40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (140 ) (160 ) (180 ) (40 ) (50 ) (60 ) (100 ) (120 )
kW106 132 160 210 265 315 370 420 480 kW 118 150 180 300 355
Cooling capacity 362,000
Btu/h 450,000 546,000 717,000 904,000 1,075,000 1,263,000 1,433,000 1,638,000 Cooling capacity Btu/h 403,000 512,000 614,000 1,024,000 1,212,000
30
USRT 38 46 60 75 90 105 119 137 USRT 34 43 51 85 101
Chilled water flow rate 304
/min 378 459 602 760 903 1,061 1,204 1,376 Chilled water flow rate /min 338 430 516 860 1,018
kW112 140 170 230 280 340 400 460 510 kW 132 170 200 335 400
Heating capacity 382,000
Btu/h 478,000 580,000 785,000 956,000 1,160,000 1,365,000 1,570,000 1,740,000 Heating capacity Btu/h 450,000 580,000 683,000 1,143,000 1,365,000
32
USRT 40 48 65 80 97 114 131 145 USRT 38 48 57 95 114
Power supply 3 phase,50 Hz 380/400/415 V, 4wires system Power supply 3 phase,60 Hz 400/440 V, 3 wires system
Hot water flow rate /min 321 401 487 659 803 975 1,147 1,319 1,462 Hot water flow rate /min 378 487 573 960 1,147
Capacity steps % 100~10-0 Capacity steps % 100~10-0
Type Semi-hermetic sealed single-screw type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 30 1 37 1 45 1 60 1 37 2 45 2 45+60 60 2 45 3 Motor output kW 30 1 37 1 45 1 37 2 45 2
Evaporator type Brazing Plate type Evaporator type Brazing Plate type
Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
Condenser Condenser
m3/min 780 860 1,290 1,600 1,720 2,150 2,580 m /min 810
3 1,010 2,020
Fans Air flow rate Fans Air flow rate
cfm 27,534 30,358 45,537 56,480 60,716 75,895 91,074 cfm 28,593 35,653 71,306
Motor output kW 0.5 4 1.0 4 1.0 6 1.0 8 1.0 10 1.0 12 Motor output kW 0.5 4 1.0 4 1.0 8
Refrigerant R-407C Refrigerant R-407C
5B Flange Pipe connections Water inlet/outlet 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
Pipe connections Water inlet/outlet 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
(125A HG20593-97) water inlet/outlet Drain outlet RP1 1/4 Female screw (32A)
water inlet/outlet
Drain outlet RP1 1/4 Female screw (32A) Dimensions (H W D) mm 2,456 2,200 2,000 2,456 4,400 2,000
Dimensions (H W D) mm 2,456 2,200 2,000 2,456 2,650 2,000 2,456 4,400 2,000 2,456 4,850 2,000 2,456 5,300 2,000 2,456 6,600 2,000 Weight kg 1,690 1,810 1,870 3,500 3,605
Weight kg 1,800 1,930 1,990 2,640 3,740 3,995 4,553 5,110 6,265 Operating weight kg 1,723 1,846 1,910 3,551 3,662
Operating weight kg 1,833 1,966 2,030 2,687 3,791 4,052 4,624 5,181 6,456 Operation range cooling -5 to 43, heating -20 to 21
Operation range cooling -5 to 43, heating -20 to 21 Notes:
Notes: *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and
*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and 6 WB(43 FWB).
6 WB(43 FWB). *3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase protector.
protector. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
21 Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. 22
*4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
Air Cooled Water Chillers - Heat PumpType
Standard Unit Standard Unit
50Hz UWY 40 180AY 1 60Hz UWY 40 120AY B
106 480kW clas s 118 355kW clas s
S pecifications S pecifications
UWY40AY1 UWY50AY1 UWY60AY1 UWY80AYAY1 UWY100AY1 UWY120AY1 UWY140AY1 UWY160AY1 UWY180AY1 UWY40AYB UWY50AYB UWY60AYB UWY100AYB UWY120AYB
Model Model
(40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (140 ) (160 ) (180 ) (40 ) (50 ) (60 ) (100 ) (120 )
kW 106 132 160 210 265 320 370 420 480 kW 118 150 180 300 355
Cooling capacity *1 Btu/h 362,000 450,000 546,000 717,000 904,000 1,092,000 1,263,000 1,433,000 1,638,000 Cooling capacity *1 Btu/h 403,000 512,000 614,000 1,024,000 1,212,000
USRT 30 38 46 60 75 91 105 119 137 USRT 34 43 51 85 101
Chilled water flow rate /min 304 378 459 602 760 917 1,061 1,204 1,376 Chilled water flow rate /min 338 430 516 860 1,018
kW 118 150 180 240 300 355 420 480 540 kW 132 170 200 335 400
Heating capacity *2 Btu/h 403,000 512,000 614,000 819,000 1,024,000 1,212,000 1,433,000 1,638,000 1,843,000 Heating capacity *2 Btu/h 450,000 580,000 683,000 1,143,000 1,365,000
USRT 34 43 51 68 85 101 119 137 154 USRT 38 48 57 95 114
Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system Power supply 3 phase, 60 Hz 400/440 V, 3 wires system
Hot water flow rate /min 338 430 516 688 860 1,018 1,204 1,376 1,548 Hot water flow rate /min 378 487 573 960 1,147
Capacity steps % 100~10-0 (continuous capacity control) Capacity steps % 100~10-0
Type Semi-hermetic sealed single-screw type Type Semi-hermetic sealed single-screw type
Compressor Compressor
Motor output kW 30 1 37 1 45 1 60 1 37 2 45 2 45+60 60 2 45 3 Motor output kW 30 1 37 1 45 1 37 2 45 2
Evaporator type Brazed plate type Evaporator type Blazing Plate type
Air Cooled Water Chillers

Air Cooled Water Chillers


Condenser type Cross fin coil Condenser type Cross fin coil
Type Propeller Type Propeller
Drive Direct drive Drive Direct drive
- Heat Pump Type

- Heat Pump Type


Condenser Condenser
m3/min 700 710 840 940 1,420 1,680 1,780 1,880 2,520 m3/min 800 810 940 1,620 1,880
fan Air flow rate fan Air flow rate
cfm 24,710 25,063 29,652 33,182 50,126 59,304 62,834 66,364 88,956 cfm 28,240 28,593 33,182 57,186 66,364
Motor output kW 0.5 4 0.8 4 1.2 4 0.8 8 1.2 8 1.2 12 Motor output kW 0.5 4 0.8 4 1.2 4 0.8 8 1.2 8
Refrigerant R-22 Refrigerant R-22
Pipe connections water inlet/outlet 3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97) 5B Flange (125A HG20593-97) Pipe connections
3B Flange (80A HG20593-97) 4B Flange (100A HG20593-97)
2,460 6,600 water inlet/outlet
Dimensions (H W D) mm 2,395 2,200 2,000 2,395 4,400 2,000
2,000 Dimensions (H W D) mm 2,395 2,200 2,000 2,395 4,400 2,000
Weight kg 1,700 1,800 1,950 2,020 3,600 3,900 4,020 4,040 6,205 Weight kg 1,700 1,800 1,950 3,600 3,900
Operating weight kg 1,717 1,820 1,973 2,052 3,636 3,942 4,084 4,104 6,270 Operating weight kg 1,717 1,820 1,973 3,636 3,942
Operation range cooling -5 to 43, heating -20 to 21 Operation range cooling -5 to 43, heating -20 to 21
Notes: Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB).
*2 Heatinging capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and *2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and
6 WB(43 FWB). 6 WB(43 FWB).
*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase *3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector. protector.
Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve.
*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil (charged before delivery). *4 The unit is equipped with standard water filter. *5 The limited length of wire represents its max. length when the pressure is lower than 2%. *6 This product is manufactured in China.
*6 This product is manufactured in China.

Option L is t
Standard Unit UWYP40BY1 UWYP80BY1 UWYP100BY1 UWYP180BY1 UWYP280BY1 UWYP360BY1
50Hz UWY 200 480AY 1 Model
UWYP50BY1
UWYP60BY1
UWYP40BYB
UWYP120BY1
UWYP140BY1
UWYP160BY1
UWYP200BY1
UWYP220BY1
UWYP320BY1 UWYP400BY1
UWYP440BY1
UWYP50BYB UWYP100BYB UWYP240BY1 UWYP480BY1
530 1,260kW clas s UWYP60BYB UWYP120BYB
Remote controller BRC307D503
S pecifications Chilling water supply interrupting relay GWEL-UWYP40B GWEL-UWYP100B GWEL-UWYP180B GWEL-UWYP280B GWEL-UWYP360B
Water high pressure (1.6 MPa) upgrader GWP-UWYP40B GWP-UWYP80B GWP-UWYP100B GWP-UWYP180B GWP-UWYP280B GWP-UWYP360B
UWY200AY1 UWY220AY1 UWY240AY1 UWY280AY1 UWY320AY1 UWY360AY1 UWY400AY1 UWY420AY1 UWY480AY1
Model IPU DAM602A5
(200 ) (220 ) (240 ) (280 ) (320 ) (360 ) (400 ) (420 ) (480 )
Dio unit DEC102A
kW 530 580 630 740 840 960 1,060 1,160 1,260
D Air unit DAM101A
Cooling capacity *1 Btu/h 1,809,000 1,979,000 2,150,000 2,525,000 2,867,000 3,276,000 3,617,000 3,959,000 4,300,000
Interface for use in LONWORKS DMS504B51
USRT 151 165 179 210 239 273 301 330 358
Interface for use in BACnet DMS502A51
Chilled water flow rate /min 1,519 1,663 1,806 2,121 2,408 2,752 3,039 3,325 3,612
Central remote controller DCS302CA61
kW 600 660 720 840 960 1,080 1,200 1,320 1,440
Unified ON/OFF controller DCS301BA61
Heating capacity *2 Btu/h 2,048,000 2,252,000 2,457,000 2,867,000 3,276,000 3,686,000 4,095,000 4,505,000 4,914,000
Schedule timer DST301BA61
USRT 171 188 205 239 273 307 341 375 410
Power supply 3 phase, 50 Hz 380/400/415 V, 4 wires system
Hot water flow rate /min 1,720 1,892 2,064 2,408 2,752 3,096 3,440 3,784 4,128 Model UWYP125AY3 UWYP190AY3 UWYP250AY3 UWYP375AY3 UWYP500AY3 UWYP630AY3 UWYP750AY3
Capacity steps % 100~10-0 (continuous capacity control) Remote controller *1 BRC307C50
Type Semi-hermetic sealed single-screw type Communication I/F P.C. board BRP66B3
Compressor
Motor output kW 45 2+60 45+60 2 60 3 (45+60) 2 (60 2) 2 (45 3) 2 (45 2+60) 2 (45+60 2) 2 (60 3) 2 Communication I/F P.C. B storage box BPR66A97 BPR66A100
Evaporator type Blazing plate type Transmission wire BER66A5 BER66A7
Condenser type Cross fin coil Notes:
Type Propeller *1 Communication I/F P.C. board, Communication I/F P.C. B storage box and Transmission waire are also required.
Drive Direct drive
Condenser
m3/min 2,620 2,720 2,820 3,560 3,760 5,040 5,240 5,440 5,640 UWYP40AY1 UWYP80AY1 UWYP100AY1 UWYP180AY1 UWYP280AY1 UWYP380AY1
fan Air flow rate
cfm 92,486 96,016 99,546 125,668 132,728 177,912 184,972 192,032 199,092 Model
UWYP50AY1 UWYP120AY1 UWYP200AY1 UWYP320AY1 UWYP400AY1
Motor output kW 1.2 12 (1.2 8) 2 (1.2 12) 2 UWYP60AY1 UWYP140AY1 UWYP220AY1 UWYP440AY1
Refrigerant R-22 UWYP160AY1 UWYP240AY1 UWYP480AY1
Pipe connections Water inlet/outlet 5B Flange (125A HG20593-97) 4B Flange (100A HG20593-97) 5B Flange (125A HG20593-97) Remote controller BRC307D503
Chilling water supply interrupting relay GWEL-UWYP40B GWEL-UWYP100B GWEL-UWYP180B GWEL-UWYP280B GWEL-UWYP360B
Dimensions (H W D) mm (2,460 6,600 2,000) 2 (2,395 4,400 2,000) 2 (2,460 6,600 2,000) 2 Water high pressure (1.6 MPa) upgrader GWP-UWYP40B GWP-UWYP80B GWP-UWYP100B GWP-UWYP180B GWP-UWYP280B GWP-UWYP360B
Weight kg 6,260 6,295 6,350 4,020 2 4,040 2 6,205 2 6,260 2 6,295 2 6,350 2 IPU DAM602A5
Operating weight kg 6,337 6,382 6,450 4,084 2 4,104 2 6,270 2 6,337 2 6,382 2 6,450 2 Dio unit DEC102A
Operation range cooling -5 to 43, heating -20 to 21 D Air unit DAM101A
Notes: Interface for use in LONWORKS DMS504B51
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), and outdoor air temp. 35 DB(95 FDB). Interface for use in BACnet DMS502A51
*2 Heating capacity is based on the following conditions : Leaving hot water temp.45 (113 F), entering hot water temp.40 (104 F), and outdoor air temp. 7 DB(44.5 FDB),and Central remote controller DCS302CA61
6 WB(43 FWB).
Unified ON/OFF controller DCS301BA61
*3 The following safety devices are equipped as standard. High pressure protector. Low pressure protector. Compressor thermal protector. Fusible plug. Reverse-phase
protector. Schedule timer DST301BA61
23 Overheat protection of discharge gas. Overcurrent relay(compressor). Freeze-up protection thermostat. Overcurrent relay(fan). Safety valve. 24
*4 Standard for the max. chilled water pressure is 0.7MPa, but1.6MPa is available if required. *5 Installation/operating weight includes the weight of refrigerant and refrigerant oil(charged before delivery).
Water Cooled Water Chillers
: UWP S eries
: UWD S eries ZUW S eries
Year Round Cooling Operation Efficient Performance
Applies to All Models P erformance characteris tics under partial load are efficient.
P rovides a s table s upply of chilled water throughout the
100
Since the heat exchanger employs water, operation of the unit is not affected by
changes in the outdoor temperature. A stable water temperature is maintained

Power consumption ratio (%)


year round.

2
compressors
Wide Water Temperature Control Range
Range
UWP 90AY 3 900AY 3 50
The water temperature s etting can be s et to any value
between 4 and 25 . 1 compressor
is operating

Simple Operation and Control Increased characteristic


under partial load
UWD1320DY 1 4000DY 1
A s ingle built-in control box s implifies operation and control. 0 25 50 100

All controls and indicators are centralized in a single control box, making it possi- Cooling capacity ratio (%)
ble to control the system using fewer personnel. Installation is simplified by inte-
gration of the control box with the main unit.
UWP 900AY 3 UWD1320DY 1 ZUW175AY 1
Reliability
Well Appointed
All models are fitted with a pres s ure gauge as s tandard.
Water Chillers

Water Chillers
Water Cooled

Water Cooled
Model Lineup
Capacity (kW)
Refrigerant Units series Model No. page
8/9 13.2/15 20/22.4 26.5/30 40/45 53/60 67/75 80/90 118 150 180 236 300 355
50/60Hz R-407C Standard Unit UWPAY3 90 150 224 300 450 600 750 900 27
50Hz R-134a Standard Unit UWDDY1 1320 1700 2000 2650 3350 4000 27 Easy Installation
Capacity UWP 90AY 3 900AY 3
Refrigerant Units series Model No. page
100RT 120RT 150RT 175RT 200RT 240RT 280RT 300RT 350RT 400RT The 10 HP model has a footprint meas uring only 0.32
50Hz ZUWAY1 100 120 150 175 200 240 280 300 350 400 28 s quare meters .
Standard Unit
60Hz ZUWAYB 120 150 175 200 240 280 28
R-134a 8 to 30 HP models have a modular design that enables units with different capaci-
50Hz ZUWAY1Z 100 120 150 175 200 240 280 300 350 400 29
Brine Cooling Unit ties to be used together in a single system and simplifies increasing system ca-
60Hz ZUWAYBZ 120 150 175 200 240 300 29
pacity later on 3 5 HP models have a similar configuration and are designed
for compactness.
Maintenance
New Refrigerant Efficient and Reliable Compressors UWD1320DY 1 4000DY 1
The s tarter panel is built into the control panel, s implifying UWP 90AY 3 900AY 3
UWP 90 900AY 3 Applies to All Models The double-pipe heat exchanger and an individual error
UWD1320 40000DY 1 indication function help reduce the manpower required for
To improve their operational reliability, 5 -- 30HP models
ZUW100 400AY (1)(B ) employ s croll compres s ors , while 40 -- 120HP models are The new double-pipe heat exchanger design reduces clogging, significantly in-
creasing resistance to dirty cooling water.
ZUW100 400AY (1)(B ) Z equipped with s emi-hermetic s ingle s crew compres s ors .
E mploys the new refrigerants R -407C and R -134a.

R efrigerant inlet

R efrigerant outlet

S emi-hermetic s ingle
s crew compres s or

25 26
Water Cooled Water Chillers
Standard Unit Standard Unit
50/60Hz UWP 90 900AY 3 50Hz ZUW100 400AY 1
8 / 9 80 / 90kW clas s 367 1,450kW clas s
S pecifications S pecifications
UWP90AY3 UWP150AY3 UWP224AY3 UWP300AY3 UWP450AY3 UWP600AY3 UWP750AY3 UWP900AY3 ZUW100AY1 ZUW120AY1 ZUW150AY1 ZUW175AY1 ZUW200AY1 ZUW240AY1 ZUW280AY1 ZUW300AY1 ZUW350AY1 ZUW400AY1
Model Model
(3 ) (5 ) (8 ) (10 ) (15 ) (20 ) (25 ) (30 ) (100RT) (120RT) (150RT) (175 RT) (200RT) (240RT) (280RT) (300RT) (350RT) (400RT)
kW 8.0/9.0 13.2/15.0 20.0/22.4 26.5/30.0 40.0/45.0 67.0/75.0 80.0/90.0 kW 367 454 508 631 710 857 1,000 1,114 1,260 1,450
53.0/60.0
Cooling capacity *1 Cooling capacity Btu/h 1,252,132 1,548,959 1,733,196 2,152,848 2,422,381 2,923,916 3,411,804 3,800,750 4,298,874 4,947,117
Btu/h 27,300/30,700 45,100/51,200 68,300/76,500 90,500/102,000 137,000/154,000 181,000/205,000 229,000/256,000 273,000/307,000
(50/60 Hz) USRT 104 129 144 179 202 244 284 317 358 412
USRT 2.28/2.56 3.75/4.27 5.69/6.37 7.54/8.53 11.4/12.8 15.1/17.1 19.1/21.3 22.8/25.6
Power supply 3 phase, 50 Hz 380/400/415 V, 60 Hz 400/440 V, 3 wires system Power supply 3 phase, 50 HZ 380/400/415 V, 3 wires system
Chilled water flow rate Chilled water flow rate /min 1,052 1,301 1,456 1,809 2,035 2,457 2,867 3,193 3,612 4,157
/min 23/26 38/43 57/64 76/86 115/129 152/172 192/215 229/258 Condenser water flow rate /min 1,253 1,545 1,727 2,153 2,400 2,930 3,407 3,773 4,235 4,883
(50/60 Hz)
Capacity steps % 100-0 100-50-0 100-60-0 100-67-0 Type single screw compress
Type Hermetically sealed scroll type Compressor Motor output kW 37 2 45 2 60 2 75 2 90 2 90+110 110 2 130 2
Compressor Capacity control % 100 25-0 continuous capacity control 100 10-0 continuous capacity control
Motor output kW 3.0 1 3.75 1 5.5 1 7.5 1 5.5 2 7.5 2 7.5+5.5 2 7.5 3
Evaporator type Brazed plate heat exchanger Evaporator type shell and tube flooded type
Condenser type Double pipe condenser Condenser type shell and tube type
Refrigerant R-407C Refrigerant R-134a
Condenser water inlet/outlet FPT1 (25A) FPT1 1/2 (40A) FPT1 1/2 2 (40A) FPT1 1/2 3 (40A) Condenser water inlet/outlet 5B Flange (125A) 6B Flange (150A) 8B Flange (200A)
Pipe Pipe Chilled water inlet/outlet 5B Flange (125A) 6B Flange (150A) 8B Flange (200A)
Chilled water inlet/outlet FPT1 (25A) FPT1 1/2 (40A) FPT1 1/2 2 (40A) FPT1 1/2 3 (40A)
connections connections Chilled water drain outlet NPT1 1/2 1 NPT1 1/2 1, NPT1 1/4 2
Drain outlet FPT3/4 (20A)
Dimensions (H W D) mm 1,280 405 690 1,280 405 790 1,280 808 790 1,280 1,211 790 Condenser water drain outlet NPT1 1/2 1 NPT1 1/2 1, NPT1 1/4 2
Weight kg 100 110 150 160 305 325 465 485 Dimensions (H W D) mm 1,765 1,160 3,530 1,765 1,210 3,680 1,830 1,320 3,960 2,000 1,400 4,000 2,060 1,470 4,550 2,270 1,830 4,250
Operating weight kg 102 112 154 165 313 478 500 Weight (Approx.) kg 3,500 3,650 3,750 3,900 4,750 5,250 6,650 6,750 8,300 8,450
335
Operating weight (Approx.) kg 3,700 3,850 4,000 4,150 5,050 5,600 7,100 7,200 8,900 9,150
Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering Notes:
condenser water temp. 30 (86 F). *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
*2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Reverse-phase protector. condenser water temp. 30 (86 F).
Discharge gas overheat protector. Fusible plug. Safety valve. *2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Compressor thermal
*3 This product is manufactured in Japan. protector. Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve.
*3 This product is manufactured in China.
Water Chillers

Water Chillers
Water Cooled

Water Cooled
Standard Unit Standard Unit
50Hz UWD1320 4000DY 1 60Hz ZUW120 300AY B
118 355kW clas s 441 1,040kW clas s
S pecifications S pecifications
UWD1320DY1 UWD1700DY1 UWD2000DY1 UWD2650DY1 UWD3350DY1 UWD4000DY1 ZUW120AYB ZUW150AYB ZUW175AYB ZUW200AYB ZUW240AYB ZUW300AYB
Model Model
(40 ) (50 ) (60 ) (80 ) (100 ) (120 ) (120RT) (150RT) (175RT) (200RT) (240RT) (300RT)
kW 118 150 180 236 300 355 kW 441 542 606 759 848 1,040
Cooling capacity *1 Btu/h 403,000 512,000 615,000 806,000 1,020,000 1,210,000 Cooling capacity Btu/h 1,504,606 1,849,198 2,067,554 2,589,560 2,893,211 3,548,277
USRT 33.6 42.7 51.2 67.1 85.3 101 USRT 125 154 172 216 241 296
Power supply 3 phase, 50 Hz 380/400/415 V, 3 wires system Power supply 3 phase, 60 Hz 400/440 V, 3 wires system
Chilled water flow rate /min 1,264 1,553 1,737 2,175 2,430 2,981
Chilled water flow rate /min 338 430 516 677 860 1,018
Condenser water flow rate /min 1,517 1,864 2,085 2,609 2,903 3,584
Type single screw compress
Condenser water flow rate /min 420 534 640 837 1,068 1,263
Compressor Motor output kW 37 2 45 2 60 2 75 2 90 2
Type Semi-hermetic sealed single screw type Capacity control % 100 25-0 continuous capacity control
Compressor Motor output kW 30 1 37 1 45 1 30 2 37 2 45 2 Evaporator type shell and tube flooded type
Capacity control % 100-70-40-0 100-70-40-20-0 Condenser type shell and tube type
Evaporator type Shell and Hi-X tube type Refrigerant R-134a
Condenser type Shell and cross fin tube type Condenser water inlet/outlet 5B Flange (125A) 6B Flange (150A) 8B Flange (200A)
Refrigerant R-134a Pipe Chilled water inlet/outlet 5B Flange (125A) 6B Flange (150A)
Condenser water inlet/outlet FPT3 (80A) FPT4 (100A) FPT3 (80A) FPT4 (100A) connections Chilled water drain outlet FPT1/2
Pipe Chilled water inlet/outlet FPT3 (80A) 4B Flange (JIS10K)(100A) 5B Flange (JIS10K)(125A) Condenser water drain outlet FPT1/2 4,450
connections Chilled water drain outlet FPT3/4 FPT1 Dimensions (H W D) mm 1,765 1,160 3,400 4,700 1,830 1,320 3,600 2,000 1,400 3,960 2,060 1,680 4,000
Condenser water drain outlet FPT1/4 Weight (Approx.) kg 3,800 4,150 5,100 5,850 6,350
Dimensions (H W D) mm 1,600 2,320 759 1,702 2,600 759 1,623 3,330 994 1,745 3,338 1,050 Operating weight (Approx.) kg 4,000 4,400 5,400 6,200 6,800
Weight (Approx.) kg 1,100 1,250 1,280 1,800 2,200 2,300 Notes:
Operating weight (Approx.) kg 1,220 1,390 1,420 1,980 2,420 2,520 *1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp. 30 (86 F).
Notes: *2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Compressor thermal
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.7 (44.5 F), entering chilled water temp.12 (53.6 F), leaving condenser water temp. 35 (95 F), entering protector.
condenser water temp. 30 (86 F). Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve.
*2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Compressor thermal
protector. Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve(for UWD2000DY1,UWD4000DY1).
*3 This product is manufactured in Japan.

27 28
Water Cooled Water Chillers
Brine Cooling Unit Option L is t
50Hz ZUW100 400AY 1Z Model ZUW100AY1 ZUW120AY1 ZUW150AY1 ZUW175AY1 ZUW200AY1
IPU DAM602A5
190 715kW clas s Dio unit DEC102A
D Air unit DAM101A
S pecifications Interface for use in LONWORKS DMS504B51
Interface for use in BACnet DMS502A51
ZUW100AY1Z ZUW120AY1Z ZUW150AY1Z ZUW175AY1Z ZUW200AY1Z ZUW240AY1Z ZUW280AY1Z ZUW300AY1Z ZUW350AY1Z ZUW400AY1Z
Model Central remote controller DCS302CA61
(100RT) (120RT) (150RT) (175RT) (200RT) (240RT) (280RT) (300RT) (350RT) (400RT)
kW 190 243 272 338 382 459 534 599 628 715 Unified ON/OFF controller DCS301BA61
Btu/h 648,243 829,069 928,011 1,153,190 1,303,309 1,566,018 1,821,904 2,043,671 2,142,613 2,439,440 Schedule timer DST301BA61
Cooling capacity
USRT 54 69 77 96 109 131 152 170 179 203 Upgrader adaptor GD3-ZUW100A
Power supply 3 phase, 50Hz 380/400/415V, 3 wires system
Chilled water flow rate /min 545 697 780 969 1,095 1,316 1,531 1,717 1,800 2,050
Condenser water flow rate /min 730 920 1,032 1,287 1,458 1,758 2,049 2,282 2,379 2,723 Model ZUW240AY1 ZUW280AY1 ZUW300AY1 ZUW350AY1 ZUW400AY1
Type single screw compress
Compressor Motor output kW 37 2 45 2 60 2 75 2 90 2 90+110 110 2 130 2 IPU DAM602A5
Capacity control % 100 25-0 continuous capacity control 100 10-0 continuous capacity control Dio unit DEC102A
Evaporator type shell and tube flooded type D Air unit DAM101A
Condenser type shell and tube type Interface for use in LONWORKS DMS504B51
Refrigerant R-134a Interface for use in BACnet DMS502A51
Condenser water inlet/outlet 5B Flange (125A) 6B Flange (150A) 8B Flange (200A) Central remote controller DCS302CA61
Pipe Chilled water inlet/outlet 5B Flange (125A) 6B Flange (150A) 8B Flange (200A) Unified ON/OFF controller DCS301BA61
connections Chilled water drain outlet NPT1 1/2 1 NPT1 1/2 1, NPT1 1/4 Schedule timer DST301BA61
Condenser water drain outlet NPT1 1/2 1 NPT1 1/2 1, NPT1 1/4 Upgrader adaptor GD3-ZUW100A
Dimensions (H W D) mm 1,765 1,160 3,400 1,765 1,210 3,680 1,830 1,320 3,960 2,000 1,400 4,000 2,060 1,470 4,550 2,270 1,830 4,250
Weight (Approx.) kg 3,500 3,650 3,750 3,900 4,750 5,250 6,650 6,750 8,300 8,450
Operating weight (Approx.) kg 3,700 3,850 4,000 4,150 5,050 5,600 7,100 7,200 8,900 9,150
Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp. 30 (86 F).
*2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Compressor thermal
protector.
Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve.
Water Chillers

Water Chillers
Water Cooled

Water Cooled
Brine Cooling Unit
60Hz ZUW120 300AY B Z
233 555kW clas s
S pecifications
ZUW120AYBZ ZUW150AYBZ ZUW175AYBZ ZUW200AYBZ ZUW240AYBZ ZUW300AYBZ
Model
(120RT) (150RT) (175RT) (200RT) (240RT) (300RT)
kW 233 290 320 400 460 555
Cooling capacity Btu/h 794,951 989,423 1,091,778 1,364,722 1,569,430 1,893,552
USRT 66 82 91 114 131 158
Power supply 3 phase, 60Hz 400/440 V, 3 wires system
Chilled water flow rate /min 1,242 1,546 1,706 2,132 2,452 2,958
Condenser water flow rate /min 909 1,118 1,238 1,542 1,783 2,159
Type single screw compress
Compressor Motor output kW 37 2 45 2 60 2 75 2 90 2
Capacity control % 100 25-0 continuous capacity control
Evaporator type shell and tube flooded type
Condenser type shell and tube type
Refrigerant R-134a
Condenser water inlet/outlet 5B Flange (125A) 6B Flange (150A) 8B Flange (200A)
Pipe Chilled water inlet/outlet 5B Flange (125A) 6B Flange (150A)
connections Chilled water drain outlet FPT1/2
Condenser water drain outlet FPT1/2
Dimensions (H W D) mm 1,765 1,160 3,400 1,830 1,320 3,600 2,000 1,400 3,960 2,060 1,680 4,000
Weight (Approx.) kg 3,800 4,150 4,450 5,100 5,850 6,350
Operating weight (Approx.) kg 4,000 4,400 4,700 5,400 6,200 6,800
Notes:
*1 Cooling capacity is based on the following conditions : Leaving chilled water temp.-5 (23.0 F), entering chilled water temp.-2 (28.4 F), leaving condenser water temp. 35 (95 F), entering
condenser water temp. 30 (86 F).
*2 The following safety devices are equipped as standard. High/low pressure switch. Freeze-up protection thermostat. Overcurrent relay for compressors. Compressor thermal
protector.
Reverse-phase protector. Discharge gas overheat protector. Fusible plug. Safety valve.

29 30