A B C 1 C2 C3 depends on the following factors:
2000
Current value
1000
20
Impedance of the human body
10
0,1 0,2 0,5 1 2 5 10 20 50 100 200 5001000 2000
When a current in excess of 30 mA flows
500010000 mA
Current flowing through the body Is
through part of the human body, the
person is in danger if this current is not
1 Unperceived 3 Reversible effects : muscular contraction
interrupted in a relatively short time.
2 Perceived 4 Possible irreversible effects
Risks for persons
Danger for human life
electrocution (cont.)
Direct contact:
Contact of persons or animals with live conductors
(phase or neutral) or with live pieces of equipment
Indirect contact:
Contact of persons or animals with exposed
conductive parts which become accidentally live
following an insulation fault.
Risks for equipment
Danger for equipment
fire
The danger of fire is all the greater the higher the fault
current. It increases in relation to the degree of fire
or explosion hazard in the premises.
Risks for availability of
Electrical power
Danger for availability of electrical power
power cuts
Damage to installations.
Earthing arrangement
Where should a residual current device be
installed?
According to the installations earthing
arrangement, a residual current device
(RCD) is necessary:
Earthing arrangement
Device TT IT TN
RCD ( ) ( )
PIM
Circuit-breaker
Earthing arrangement
TT earthing arrangement
TT earthed neutral
Definition
The neutral point of the LV
transformer is directly connected
to an earth electrode
Consequences
Tripping each group of
equipment must occur on the first
fault
Consequences
The appearance of the first insulation fault does not present a
danger for persons
Consequences
Protection is provided by the circuit-breaker
An accurate calculation of loop impedance is required in order
to guarantee tripping on an insulation fault
A residual current device makes calculation unnecessary, in
particular when changes to the installation are made.
Multi 9 earth leakage
protection The principle of Multi 9 earth leakage protection
instantaneous
selective
Discrimination
A A A A
A m m m m
0
A fault downstream from RCD
m 0 0 0 0
30 10 30 50 30
Current-based discrimination
sensitity band Il
instantaneous
(horizontal)
Total discrimination
(vertical)
Partial discrimination
0,030 0,100 0,300 0,500 3000 current
In
Multi 9 earth leakage
protection
Choice criteria
continuity of supply (cont.)
Total discrimination
A
1000 mA In the event of a fault, only the faulty circuit is
S types de-energized
Partial discrimination
All these devices benefit from a high level of immunity to transient currents
Multi 9 earth leakage
protection Multi 9 switchgear
RCCB - ID residual current circuit-breaker
Pole: 2P or 4P
Rating: 16 to 125 A
Sensitivity: 10 mA to 500 mA
Instantaneous, selective, time delay
C120
C60
OF SD OF + SD MN MN s MNX ID
MX + OF OF.S
MX MSU