Product Catalog

2013
2 DV Power Products Catalog
Optimum Energy Products Ltd.
About DV Power Western Canadian Distributor
1-877-766-5412

Reliable test devices


for reliable electric
power systems
The company with the headquarters in Stockholm, Sweden
was founded in 2000 by the group of engineers with an extensive
experience in the power electronics technology area.

Under the trade mark "DV Power" the company develops,


manufactures and markets the new generation of the test and
measurement equipment for the electric power industry.

Our products are

PORTABLE - Up to two or three times lighter than similar devices from our competitors.
PRACTICAL - Can use lighter/thinner cables.
USER-FRIENDLY - Completely automated sage in test processes.
EFFICIENT - Modern switch techniques, power electronics, sophisticated design.
ACCURATE - Typical accuracy of our products is 0,1 %.
ROBUST - Our devices are built in metal or plastic cases. The rigid design makes our products ideal
for use in high voltage substations and industrial environments.
COMPLIANT - IEC and other applicable international standards, CE approved.

Circuit Breaker Test Equipment SALES


Micro Ohmmeters page 4-5 The price list and additional information on
RMO series
delivery terms can be received from the DV Power
Coil Analyzers page 6 area/country distributor or directly via the e-mail:
SAT series sales@dv-power.com.
Coil Testers & Breaker Suppliers page 6-7
POB series DV Power has a rising presence on the World
Circuit Breaker Analyzers and Timers page 7-9 Market, with over 50 representatives and
CAT series distributors worldwide. DV Power products can
be found and are in use in more than 70 countries.
Transformer/Motor Test Equipment
Winding Ohmmeters & Tap Changer Analyzer page 10 WARRANTY
RMO-T series
Tap-Changer & Winding Analyzer TWA30D page 11-12 DV Power provides a three year warranty on all its
Three-Phase Transformer Turns Ratio Tester page 13 products. That is a guarantee to our customers that
TRT series they will receive the highest quality instrumentation
available.
Three-Phase Transformer Demagnetizer page 14
DEM60C
TECHNICAL SUPPORT
Motor & Generator Winding Ohmmeters page 14
RMO-M series Our technical support is always available to help
Accessories & Sof tware page 15 you. You may call at +46 70 0925 000
or e-mail to support@dv-power.com.
We will always respond within 24 hours.

www.dv-power.com 3
Circuit Breaker
LOREM IPSUM Test Equipment
\ IPSUM LOREM

RMO-A Series High DC Current Micro Ohmeters

The High DC Current Micro Ohmmeters RMO-A series instruments are designed to provide safer, faster and easier
resistance measurements of:

High, middle and low voltage Microohmmeter RMO600A Optional Accessories


circuit breakers
Disconnecting switches Lightweight - only 8 kg Test Shunt 100
High-current busbar joints Powerful 5 A - 600 A DC Transport case
Cable splices True DC (ripple free) current Thermal printer (built in)
Welding joints Measuring range 0,1 - 999,9 m
Max. resolution 0,1
DV-Win software

RMO-A Series

RMO100A
RMO200A
RMO300A
RMO400A
RMO500A
RMO600A
RMO60E (Earthing)

RMO-G Series Microohmmeter With Both Sides Grounded Feature

The High DC Current Micro Ohmmeters RMO-G series instruments are mounted in plastic housings and have an
additional Both Sides Grounded feature as an extension to its versatile list of measurement possibilities.

Microohmmeter RMO600G Optional Accessories

Lightweight - only 9,5 kg Thermal printer (built in)


Powerful 5 A - 600 A DC Test Shunt 100
True DC (ripple free) current Both sides grounded unit
Measuring range 0,1 - 999,9 m (Current clamp)
Max. resolution 0,1 Remote control
Single/Continuous/CC Mode Cable plastic case
DV-Win software

RMO-G Series

RMO100G
RMO200G
RMO300G
RMO400G
RMO500G
RMO600G
RMO800G

4 DV Power Products Catalog


Circuit Breaker Test Equipment

During the HV circuit breaker contact resistance measurement, an efcient way of insuring
protection from the induced voltages is to ground the tested circuit breaker on both sides.
RMO-G series instruments have the possibility to perform measurements with both sides of
a test device grounded. This will ensure the safety of the operators and protect the instrument
as well. The gure on the right, presents the connection diagram of the instrument to the high
voltage circuit breaker with both sides grounded.

In order to remotely perform the measurements, the RMO-G


devices are provided with the RMO Remote Control Unit. In
addition, it enables multiple measurements to be performed with
the same test current. This signicantly speeds up the entire test
procedure.

RMO-D Series Microohmmeter With Demagnetization Feature

The High DC Current Micro Ohmmeters RMO-D series instruments are the most advanced version of RMO-G series
instruments. The additional feature is the ability to perform fully automatic demagnetization of a current transformer core
after the measurement. Demagnetizing a magnetic core of a current transformer requires alternating current to be applied
with a decreasing magnitude down to zero. Using the proprietary solution design the RMO-D series instruments provide the
appropriate magnitudes and alternates by internally changing the polarity of a controlled DC current.

RMO-D Series Microohmmeter RMO600D Optional Accessories

RMO200D Lightweight - only 11 kg Both sides grounded unit


RMO500D Powerful 5 A - 600 A DC (Current clamp)
RMO600D True DC (ripple free) current Remote control
Measuring range 0,1 - 999,9m Thermal printer (built in)
Max. resolution 0,1 Test Shunt 100
Single/Continuous/CC Mode Cable plastic case
Demagnetization of a CT core
on the dead tank CB
DV-Win software

Technical specication RMO Series

Mains power supply 90 V 264 V AC, 50 / 60 Hz


Typical accuracy (0,1 % rdg + 0,1 % FS)
Measuring range Resolution
0,1 - 999,9 0,1
1000 - 9999 1
10,00 m - 99,99 m 10
100,0 m - 999,9 m 0,1 m

www.dv-power.com 5
Circuit Breaker
LOREM IPSUM Test Equipment
\ IPSUM LOREM

SAT Series Circuit Breaker Coil Analyzer

The Coil Analyzer SAT series instruments are ideal for testing circuit breakers, where
substation battery is not connected or available. These devices are compatible with
breaker analyzers from different vendors and eliminate use of station batteries during
testing. An additionally provided feature on these types of the DV Power instruments is
a signicant reduction of testing time when using our CAT and SAT devices together.

Technical specication SAT Series

Power Output
Coils output DC voltage 10 V DC - 300 V DC
Coils output AC voltage 10 V AC - 250 V AC
Motor output DC voltage 10 V DC - 250 V DC
Coil resistance measurement
Measuring range Resolution
0,5 - 99,9 0,1 Highlights
100 - 999 1
Minimum trip voltage - Lightweight only 9,20 kg
fully automatic test Coil current measurement
Start voltage 10 V - 299 V DC; 10 V - 249 V AC Coil resistance measurement
Minimum trip voltage test
Stop voltage 11 V - 300 V DC; 11 V - 250 V AC
of the circuit breaker's coils
Step voltage 1 V - 20 V DC; 1 V - 20 V AC Undervoltage release test
Typical accuracy (0,25 % rdg + 0,25 % FS) Supplying spring-charging motors
Providing a power supply for
Operating temperature -10 C + 50 C
breaker analyzers from different vendors

POB series AC / DC Power Supply for Circuit Breaker Testing

The Coil Tester & Breaker Supply POB series instruments are the variable voltage power supply units ideal for testing circuit
breakers, where substation battery is not connected or available. They are intended for operating breaker coils, and spring-
charging motors as a part of commissioning and maintenance testing. These devices are compatible with breaker analyzers
from different vendors and eliminate use of station batteries during testing.

Highlights Main Features

Lightweight only 9,20 kg Powerful up to 40 A


Minimum trip voltage test of the True DC (ripple free) voltage
circuit breaker's coils DC Voltage from 10 V to 300 V
Supplying spring-charging motors AC Voltage from 10 V to 250 V
Providing a power supply at test with
breaker analyzers from different vendors

Load Voltage Current Max Load Interval


110 V DC 30 A 20 sec
24 A 60 sec
12 A continuous
220 V DC 15 A 20 sec
12 A 60 sec
8A continuous

6 DV Power Products Catalog


Circuit Breaker Test Equipment

Max DC Current Max AC current Output DC Voltage Output AC Voltage


POB30AD 30 A 12 A 10 V 300 V 10 V 250 V
POB40AD 40 A 15 A 10 V 300 V 10 V 250 V
POB40ADL 40 A 15 A 1 V 50 V 1 V 40 V
POB50ADL 50 A 15 A 1 V 50 V 1 V 40 V

Max DC Current Output DC Voltage


POB30D 30 A 10 V 300 V
POB40D 40 A 10 V 300 V
POB40DL 40 A 1 V 50 V
POB50DL 50 A 1 V 50 V

CAT series - Circuit Breaker Analyzers & Timers

Circuit Breaker Analyzer & Timer CAT series are standalone or PC controlled digital instruments for a condition assessment of
circuit breakers. A simultaneous measurement of up to 12 main contacts (4 breaks per a phase) including pre-insertion resistors
and 6 auxiliary contacts. CAT series instruments record graphs of both, the open and close coil currents and displacements
of the HV and MV circuit breaker moving parts. The main contact channels can also measure the resistance value of the pre-
insertion resistors (if present in the circuit breaker).

Circuit Breaker Analyzer & Timer CAT64

Simple & easy to operate CAT Series


Timing and motion measurement
CAT03 CAT61 CAT125
6 timing channels (3x2) for main and resistive contacts
CAT31 CAT64 CAT126
3 timing channels for auxiliary inputs
CAT34 CAT65 CAT126D
Resistance measurement of pre-insertion resistors
CAT66
4 Analog Inputs + 1 Transducer Input
CAT66D
Supports both digital and analog transducers
Detailed analysis of test results using DV-Win software

www.dv-power.com 7
Circuit Breaker Test Equipment
Two CAT Device Series
The rst series of CAT instruments was designed to meet requirements of an easy to use circuit breaker analyzer & timer
with an attractive price. Their primary intention was timing and motion measurement of HV and MV circuit breakers.
Series 1 CAT03 CAT31 CAT34 CAT61 CAT64
Main contacts and 3 3 3 6 6
preinsertion
resistors contacts
timing channels
Auxiliary contacts NO 3 3 3 3
timing channels

Coil control NO YES YES YES YES


Coil current NO 2 2 2 2
measurement
channels
External trigger 2 2 2 2 2
channels
Analog input NO NO 2 NO 2
channels
Transducer input NO NO 1 NO 1
channels
Thermal printer Optional Optional Optional Optional Optional
(built-in)
First trip test NO YES YES YES YES
The second series of CAT instruments utilizes the latest enhancements for safe and fast testing, with unique technical
capabilities for additional diagnostics of circuit breakers. Sophisticated design ensures efcient and reliable operations in
high-voltage substations and industrial environments.
Series 2 CAT65 CAT66 CAT66D CAT125 CAT126 CAT126D
Main contacts and 6 6 6 12 12 12
preinsertion
resistors contacts
timing channels
Auxiliary contacts 6 6 6 6 6 6
timing channels
Coil control YES YES YES YES YES YES
Coil current 4 4 4 4 4 4
measurement
channels
Analog input 4 4 4 4 4 4
channels
Transducer input 3 3 3 3 3 3
channels
Thermal printer Optional Optional Optional Optional Optional Optional
(built-in)
First trip test YES YES YES YES YES YES
Both Sides YES YES YES YES YES YES
Grounded
Micro ohmmeter NO YES YES NO YES YES
Dynamic resistance NO 500 A 200 A NO 500 A 200 A
measurement
Demagnetization NO NO YES NO NO YES
of CT
8 DV Power Products Catalog
Circuit Breaker
LOREM IPSUM Test Equipment
\ IPSUM LOREM

BSG (Both Sides Grounded)

BSG feature enables safe and fast testing in high voltage substations,
without removing the safety ground connections on both sides of the
circuit breaker. No additional modules or remote boxes are required.
Each main contacts timing channel is able to detect main contacts state
in a case when both terminals are grounded.

First Trip Test

A First trip analysis is important to determine a condition of the coil


operating mechanism. A circuit breaker spends most of its lifetime
conducting a current without any operation. Once the protective relay
detects a problem, the circuit breaker, that was idle for maybe a year or
longer, has to operate as fast as possible. However, if the circuit breaker
has not been operated for a long time, the latch friction may increase.
Information about the latch friction can be obtained from the coil current
waveform recorded during the First trip test.

Static Resistance Measurement

The built-in micro ohmmeter generates a true DC ripple free current with an
automatically regulated test ramps. The resistance measurement is using
the well known .elvins four points method. The DC current is generated
through the closed circuit breaker contacts. The voltage drop is measured
between the terminals of the circuit breakers. The resistance is calculated
using the Ohms law R U/I.

DRM (Dynamic Resistance Measurement)

The built-in micro ohmmeter can also be used for the DRM. The DRM test is performed by injecting a current through the
breaker contact and simultaneously monitoring the voltage drop across the breaker contact as well as the current ow during
the operation of the breaker. Resistance curve as a function of contact travel can be used to reveal failures in relation to the
arcing contact condition. The test current should be at least 100 A to provide a higher voltage drop to allow easier detection
of the arcing contact. The DRM test requires the circuit breaker analyzer with a high resolution measurement.

Demagnetization of a Current Transformer Core after DC Contact Resistance Measurement

After a DC current test of a circuit breaker or bus-bars, the magnetic core of associated current transformers may be magnetized
(remanent magnetism). To eliminate this source of potential problems, demagnetization should be performed. Following the
apparatus resistance measurements, there is a possibility to start the demagnetization process using this instrument. The
whole demagnetization process is performed automaticaly and does not require modication of any connections.

www.dv-power.com 9
Transformer Test Equipment

RMO-TW, TD and TT Series Tap Changer Analyzers & Winding Ohmmeters

The Winding Ohmmeters RMO-TT, -TD and -TW series are designed for the winding resistance measurement of inductive test
objects (transformers/generators/motors) and for the on-load tap changer analysis of power transformers. Typical application
areas of RMO-TT, -TD and -TW are high-voltage substations and industrial environments.

Transformers
Measuring the winding resistance is an
Generators/motors
important part of commissioning,
Electrical machines
maintaining and production of:
High-current busbar joints
Cable splices

RMO-TW series RMO-TD series RMO-TT series Optional Accessories

RMO10TW RMO25TD RMO60TT Transport case


RMO20TW RMO40TD RMO100TT Thermal printer (built-in)
RMO30TW RMO60TD Test shunt 150 A / 150 mV
RMO50TW RMO100TD

All the RMO-TT, -TD and -TW instruments have a resistance measurement accuracy of up to 0,1%. This enables a very
reliable determination of the transformer condition. The open circuit voltage of up to 60 V enables a very short transformer
charging time. The instruments generate a true DC ripple-free current.

The DV-Win software (included in the purchase price) provides additional analysis options, such as creation of test reports,
static and dynamic resistance graphs, measurement of the tap changer transition times, the result download, as well as many
other features. A Heat Run resistance/temperature extrapolation can also be performed using the software for the RMO-TT
instruments.

The instruments from the RMO-TT and RMO-TD series also have the automatic demagnetization feature. The process
is completely safe, fully automated and very fast. This enables the user to avoid problems such as high inrush currents at
the start-up of power transformers, incorrect operation of protective relays, erroneous diagnostics or inaccurate electrical
measurement on a transformer.
Tap Changer Analyzer & Winding Ohmmeter Tap Changer Analyzer & Winding Ohmmeter RMO60TD
RMO60TT
Two resistance measurement channels
Three resistance measurements channels Test current 5 mA 60 A DC
Test current 5 mA 60 A DC On-load tap changer dynamic resistance measurement
Three temperature measurement channels Rapid automatic demagnetization
Automatic resistance/temperature measurement Tap changer motor current monitoring channel
for the Heat Run test Measuring range 0,1 2 k
On-load tap changer dynamic resistance measurement Automatic discharge process
Rapid automatic demagnetization Built-in tap changer control unit
AC Current monitoring channel for USB ash drive feature
tap changer motor current measurement
Measuring range 0,1 2 k
Automatic discharge process
Built-in tap changer control unit
USB ash drive feature
Winding Ohmmeter RMO50TW

Two resistance measurement channels


Test current 5 mA 50 A DC
On-load tap changer veri cation
Measuring range 0,1 - 2 k
Automatic discharge circuit
Lightweight only 7,5 kg

10 DV Power Products Catalog


Transformer Test Equipment

TWA30D Tap Changer and Winding Analyzer

Tap-Changer & Winding Analyzer TWA30D is a one-of-a-kind diagnostic solution for power transformer testing. Using this
device, the transformer testing is safer, signicantly faster, and more convenient. The TWA30D instrument is designed
for simultaneous three-phase tap changer analysis and six-winding resistance measurement of both the primary and the
secondary transformer windings.

The measurement is obtained very quickly by saturating all three legs of the magnetic core at the same time. Once all 6-8
bushings are connected and the transformer conguration selected, the instrument adjusts the test procedure automatically.
The TWA30D generates a true DC ripple-free current. The injection of current and the discharge of energy from the magnetic
circuit are both automatically regulated.

Simultaneous three-phase OLTC dynamic resistance


measurement and analysis, 3 x 10 A per phase
Rapid core saturation for fast secondary winding test
Total test current 10 mA - 36 A DC
Resistance measurement range 0,1 - 2 k
All 6 windings measured in one test
Extremely quick measurement, the cable setup is
performed only once
Typical measurement accuracy of 0,1%
Automatic discharge process
Rapid automatic demagnetization
Using two sets of four cables, all bushings of HV and LV sides are AC current monitoring channel for tap changer motor
connected at once. The connection to the transformer is made with current measurement
two-contact clamps providing for four-wire Kelvin test method. Built-in tap changer control unit

Three-Phase Tap Changer Analysis

Dynamic resistance graphs are recorded for all three phases simultaneously, so the synchronization is veried using the
cursors provided in the DV-Win software. All three phase traces are plotted on the same graph. In addition, the tap changer
motor current is recorded, and displayed on the same graph. The measurement is completed quickly even on the largest
power transformers. Each vector group has a special measurement algorithm which is optimized for the fast stabilization of
test results.

Interchangeable Cables with the TRT63 Three - Phase Transformer Turns Ratio Testers

The test cables used for the measurement are completely compatible with the DV Power TRT instruments. This enables the
user to measure, with a single connection of the test leads:

Transformer turns ratio


Excitation current
Phase angle
Winding resistance in all tap positions
Dynamic resistance in all on-load tap changer transitions
On-load tap changer motor current
On-load tap changer transition time in all transitions
On-load tap changer transition ripples in all transitions
Transformer vector group

Automatic Three-Phase Demagnetization

The TWA30D instrument can perform three-phase demagnetization after the DC


test is nished. The process is completely safe, fully automated and very fast. This enables the user to avoid problems such
as high inrush currents at the start-up of power transformers, incorrect operation of protective relays, erroneous
diagnostics or inaccurate electrical measurement on a transformer.

www.dv-power.com 11
Transformer Test Equipment

On-Load Tap Changer Analysis with DV Power Instruments

Due to their unique capabilities, the TWA30D and RMO-T series instruments are the best on-load tap changer analyzers in
the market today. A tap changer analysis can be performed either by the stand-alone instruments, or in a combination with the
DV-Win software. When used together with the DV-Win software, they enable the measurement of:

Static resistance in all tap positions


Dynamic resistance in all tap transitions
On-load tap changer (OLTC) transition times in all tap transitions
OLTC transition ripples in all tap transitions
OLTC motor current

The TWA30D instruments enable simultaneous OLTC testing of all three phases in a
single pass through the tap positions. In this manner, the total OLTC testing time is greatly
shortened, by two thirds in comparison with the classic methods. This test procedure also
enables observing the synchronization problems between the different phases.

The static resistance measurement provides winding resistance values on all tap positions
for each of the three phases. There is no need to discharge the transformer between the
measurements in different tap positions. The DV-Win software enables creating the static
resistance graph from the results of the resistance measurement in different positions,
as well as the automatic recalculation of the measured values to a reference temperature
value. The shape of the static resistance graph depends on the winding regulation mode.

The dynamic resistance measurement (DRM) feature enables measuring and recording of the test current at high sampling
rate during the tap change transition. The variation of the current represents the change of the resistance in the circuit during
the change of the tap positions. Tap changer verication can be performed in the DV-Win software or on the stand-alone
TWA30D or RMO-T instruments. The stand-alone instruments detect any open circuits during the tap changer operation.

The dynamic resistance measurement graph is unique, and above all, powerful tool that provides condition assessment of
an OLTC regarding the mechanism itself and its contact wear. It is recorded by the DV-Win software. The innovative graph
analysis tools enable the detection of:

High resistance contacts in the tap selector


Loose contacts in the tap selector
Burned, loose contacts in the diverter switch
Broken resistors in the diverter switch
Abnormal arcing
Misaligned contacts
Contact bounce
Mechanical and motor problems
Phase synchronization problems

The AC current monitoring channel enables monitoring and recording the OLTC mechanical-drive motor current during the
tap changer operation. The motor-current waveform is also printed on the same DV-Win-generated graph, and can help in
detecting OLTC mechanical problems.

The OLTC transition times, as well as the percentage of a current drop during transitions (known as the transition ripples), are
recorded numerically. The DV-Win software records these values
in the Test Report together with the static winding resistance
values. It is possible to save the Test Report in various formats,
such as PDF, XLS, DOC, etc.

12 DV Power Products Catalog


Transformer Test Equipment

TRT Series Three-Phase Transformer Turns Ratio Testers

The TRT is a true three-phase, fully automatic test set, specially designed for a turns ratio, a phase shift and an excitation
current measurement of power, distribution and instrument transformers. The TRT determines the transformer turns
ratio by accurately measuring the voltages across the unloaded transformer windings. Following these measurements it
displays the ratio of these voltages.

All the TRT devices are equipped with a tap changer control unit which allows changing tap positions remotely. USB Flash
Drive feature enables saving all the test results to a USB memory stick. DV Power provides 112 mm built-in thermal printer
as an option.

Main Features

Ratio range 0,8 50 000


Test voltages 1 V to 250 V AC
Measurement of turns ratio
Measurement of phase shift
Measurement of excitation current
Vector group detection
Built-in thermal printer

Setting up the TRT is as simple as connecting it to de-energized


transformer and entering the transformer conguration using the
device front panel keyboard. Once the parameters are selected, the
test of the three-phase transformer is performed in one of the two
ways:

SINGLE-PHASE Three single-phase voltages are applied to the


three transformer primary windings, and all three phases are measured consecutively (phase by phase). All connections
and short circuit procedures at the primary and secondary voltage terminals are automatic, done internally before each
measurement, depending on the selected vector group.

TRUE THREE-PHASE A true three-phase excitation voltage is applied to the three transformer primary windings.
Three induced phase voltages are measured at the same time. In such a way it is possible to detect the phase angle and
measure the turns ratio of any transformer type, including phase shifting transformers, where other three-phase turns
ratio testers cannot.

The TRT63 series is upgraded to use the same cable set as the Tap Changer & Winding Analyzer TWA30D, which
enables a one-time cable setup. This makes TRT63 and TWA30D one combined measurement system.
Test voltage TRT03A TRT03B TRT03C
Single phase 8/40/100 V AC 10/40/100 V AC 8/40/80 V AC

TRT30A TRT30B TRT30C


Single-phase 8/40/100 V AC 10/40/100 V AC 8/40/80 V AC

True three-phase 3x(8/40/100)3 V AC 3x(10/40/100)3 V AC 3x(8/40/80)3 V AC

TRT33A TRT33B TRT33C


Single-phase 1/8 /40/100 V AC 1/10/40 /100 V AC 1/8/40/80 V AC

True three-phase 3x(1/8/40/100)3 V AC 3x(1/10/40/100)3 V AC 3x(1/8/40/80)3 V AC

TRT63A TRT63B TRT63C


Single-phase 1/8/40/100/250 V AC 1/10/40/100/250 V AC 1/8/40/80/250 V AC

True three-phase 3x(1/8/40/100/250)3 V AC 3x(1/10/40/100/250)3 V AC 3x(1/8/40/80/250)3 V AC

www.dv-power.com 13
Transformer
LOREM IPSUMTest Equipment
\ IPSUM LOREM

DEM60C - Three-Phase Transformer Demagnetizers

The Three-Phase Transformer Demagnetizer DEM60C is lightweight instrument


designed for single and three-phase transformer core demagnetization. The
demagnetization process with DEM60C instrument is completely safe, fully
automated and very fast. The instrument generates an alternating current
applied with decreasing magnitude down to zero. This option is implemented by
internally changing the polarity of a controlled DC current.

Main features:

Lightweight - only 13,1 kg


Demagnetization currents 5 mA - 60 A DC
Demagnetization process graph
Fully automatic demagnetization
Automatic discharging circuit
DV-Win PC software

This powerful instrument generates a true DC ripple-free current of up to 60 A.


High output currents enable an effective demagnetization even in case when
there is no data of condition of the transformer core or previous tests.

The new DEM60C instrument replaces the model DEM60, with an additional
feature of displaying and monitoring the demagnetization process in real time.

Supported by the DV-Win software, DEM60C enables current waveforms and


values to be displayed during the demagnetization progress on the DV-Win
generated graph. The graphical display of demagnetizing current in real time
allows monitoring the transformer core demagnetization process.

The generated graph can be saved on a computer. This option provides easy
after-the-test analysis of the demagnetization process, in terms of current
waveforms and values for each step, along with duration of the complete
process.

Generator/Motor Test Equipment

RMO50M & RMO100M - Winding Ohmmeter

The Winding Ohmmeters RMO50M and RMO100M are designed for winding resistance mea-
surement of motors and generators. Built-in discharging circuit is designed for energy dis-
charge of motors and generators. Using DV-Win software a test can be performed from a PC
and the results can be obtained directly at a PC.

Main Features

Lightweight - only 8 kg
Test current 10 mA 100 A DC
Measuring range 0,1 - 600
Extremely quick measurement
Mechanical protection IP43

14 DV Power Products Catalog


Accessories and Software

Accessories - a Selection

Current cables 2 x 10 m 10 mm2 and Sense cables 2 x 10 m with TTA clamps Shunts
Sense cables 2 x 10 m with TTA clamps

Digital rotary transducer Universal transducer Current clamp 30/300A


with 5 m connection cable mounting kit with cable set 5 m

Transport Bags and cases

DV-Win Software
Features

Full control of all DV Power instruments from a PC.


Downloading the test results from the instrument.
Acquisition and analysis of the test results
The test results can be viewed, edited, saved,
printed and exported.
Viewing and overlaying several graphs, for an easy
test result comparison.
Selecting the measurement points and intervals
using the two cursors.
Zoom and pan graph feature.
Specic test sequence setup.
Customized conguration of the test result graphs.
Creation of the predened test plans for an
easy and quick eld testing.

www.dv-power.com 15
DISTRIBUTORS WORLDWIDE

IBEKO Power AB

Postal Address

Box 1346
181 25 Liding
Sweden

Delivery Address

Stockholmsvgen 18
181 33 Liding
Sweden

E-mail DISTRIBUTED BY Optimum Energy Products Ltd.


Western Canadian Distributor
sales@dv-power.com 1-877-766-5412
support@dv-power.com

Phone numbers

Local support (Scandinavian): +46 8 731 78 24


International support: +46 70 0925 000
Fax: +46 8 731 77 99

DV Power Products Catalog