Sensor and Event Report For DFIU3300793

ago 22, 2013 to ago 23, 2013

System Configuration at the Time of Interrogation:

Interrogated On ago 23, 2013


Extracted By DataLine Rev 2.1.0

Controller Software: 5354


Controller Serial #: 04623671

Bill of Lading #:
Origin: Origin Date:
Destination: Discharge Date:
Comment:

Probe Calibration Readings: USDA1 0.0 USDA2 0.0 USDA3 0.0 Cargo 0.0

Temperature Units: Fahrenheit


_______________________________________________________

ago 22, 2013


Setpoint: 56.98, O2: OFF, CO2: OFF, Container: DFIU3300793, Serial : 04623671

2 Sensors Logged at 60 minute interval.


Sensor Format Resolution
Supply Average Low
Return Average Low

Time SupAir RetAir


01:00 63.95 64.40
02:00 65.75 65.30
03:00 67.10 66.65
04:00 68.45 67.55
05:00 69.35 68.45
06:00 69.80 69.35
07:00 70.25 70.25
08:00 70.70 70.70
09:00 71.60 71.60
10:00 72.05 72.05
15:00 68.90 73.40
16:00 33.53 41.90
17:00 23.00 26.60
18:00 42.80 42.80

Time Event Data


14:50 Power On (Battery Present)
14:50 Power Down (Battery Present)
14:50 Operating Mode Changed to Power Off
14:50 Power On (Battery Present)
14:51 Operating Mode Changed to Cool Max
14:52 Setpoint Changed By Keypad to 19.99
15:55 Operating Mode Changed to Cool Reduced
16:43 AUTO3 Pre-Trip Initiated By Keypad
16:43 Operating Mode Changed to Pretrip
16:43 P0-0: RMU Detection status: Not Present
16:44 P1-0 Heaters On Test: Passed- A: 5.49, B: 5.46, C: 5.47
P1-1 Heaters Off Test: Passed- A: 5.49, B: 5.46, C: 5.47
P1-2 Remote Heater Test: Not Run- A: 0.00, B: 0.00, Voltage: 0.0
16:44 P2-0 Condenser On Test: Passed- A: 1.12, B: 0.00, C: 1.12, WPS: On
P2-1 Condenser Off Test: Passed- A: 1.10, B: 0.00, C: 1.10
16:46 P3-0 Low Evap On Test: Passed- A: 0.83, B: 1.49, C: 0.83
P3-1 Low Evap Off Test: Passed- A: 0.83, B: 1.49, C: 0.83
16:48 P4-0 High Evap On Test: Passed- A: 1.77, B: 3.12, C: 1.77, Ratio: 1.76
P4-1 High Evap Off Test: Passed- A: 1.79, B: 3.12, C: 1.79
P4-2 Remote Evap Fans On Test: Not Run
16:51 P5 Probe Test: P5-0: Passed, P5-1: Passed, P5-2: Passed
STS: 31.14, RTS: 29.03, SRS: 31.14, RRS: 29.10
P5-3 Evap Fan Dir Test: Not Run
P5 Remote Probe Test: P5-4: Not Run, P5-5: Not Run, P5-6: Not Run
P5-7: Not Run
P5-8: Not Run
P5-9: Not Run
P5 Humidity Sensor Test: P5-10: Not Run, P5-11: Not Run, P5-12: Not Run
16:57 P6-0 Discharge Thermistor Test: Pass
P6-1 Suction Temperature Sensor Test: Pass
P6-2 Discharge Pressure Sensor Test: Pass
P6-3 Suction Pressure Sensor Test: Pass
P6-4 Compressor Current Draw Test: Pass- Comp Current 0: 0.01, Comp Current
1: 7.84
Amb: 93.09, Board Temp: 106.68, RTS: 29.82
P6-5 ESMV Test: Pass
Suction Pressure 0: 2.42, Suction Pressure 1: 17.89
P6-6 Economizer Valve Test: Pass- Suction Pressure 0: 1.05, Suction Pressure
1: 5.36
P6-7 Unloader Valve Test: Pass- Suction Pressure 0: -5.00, Suction Pressure
1: 2.90
P6-8 TXV Boost/Bypass Circuit Test: Not Run
P6-9 LIV Test: Not Run
P6-10 EVXV Test: Not Run
17:01 P7-0 HPS Closed Test: Passed- Amb: 90.82, Pressure: 335.37
P7-1 HPS Open Test: Passed- Amb: 91.04, Pressure: 238.12
18:10 P8-0 Perishable Heat Test: Passed- STS: 59.47, Time: 35 min
P8-1 Perishable Pulldown Test: Passed- STS: 32.00, Time: 17 min
P8-2 Perishable Control Test: Passed- SRS: 31.82
_______________________________________________________

ago 22, 2013


Setpoint: 20.01, O2: OFF, CO2: OFF, Container: DFIU3300793, Serial : 04623671

Time SupAir RetAir


19:00 38.30 41.00
20:00 53.15 57.65
21:00 59.00 62.15
22:00 63.50 64.85
23:00 67.10 67.55
24:00 70.25 70.25

Time Event Data


18:10 Pre-Trip Test Termination
P0-0: Not Present
P1-0: Passed P1-1: Passed
P2-0: Passed P2-1: Passed
P3-0: Passed P3-1: Passed
P4-0: Passed P4-1: Passed
P5-0: Passed P5-1: Passed P5-2: Passed P5-3: Not Run P5-4: Not Run
P5-5: Not Run P5-6: Not Run P5-7: Not Run P5-8: Not Run
P5-9: Not Run P5-10: Not Run P5-11: Not Run P5-12: Not Run
P6-0: Passed P6-1: Passed P6-2: Passed P6-3: Passed P6-4: Passed
P6-5: Passed P6-6: Passed P6-7: Passed P6-8: Not Run
P6-9: Not Run P6-10: Not Run
P7-0: Passed P7-1: Passed
P8-0: Passed P8-1: Passed P8-2: Passed

19:17 Power Down (Battery Present)


19:17 Power On (Battery Present)
19:18 Setpoint Changed By Keypad to 57.00
19:19 Operating Mode Changed to Power Off
19:19 Power Down (Battery Present)
19:19 Operating Mode Changed to Power Off
_______________________________________________________

ago 23, 2013


Setpoint: 56.98, O2: OFF, CO2: OFF, Container: DFIU3300793, Serial : 04623671

Time SupAir RetAir


01:00 72.05 71.15
02:00 72.95 71.60
03:00 73.40 72.05
04:00 73.85 72.50
05:00 74.30 72.95
06:00 74.30 72.95
07:00 74.30 73.40
08:00 74.30 73.40
09:00 74.30 73.85
10:00 74.30 73.85
11:00 74.30 73.85
12:00 74.30 74.30
13:00 74.30 74.30
14:00 74.75 74.30
15:00 75.20 75.20

Time Event Data


15:39 Power On (Battery Present)
15:39 Operating Mode Changed to Cool Max
15:41 Data Retrieval
_______________________________________________________