You are on page 1of 3

ANSI - IEC Comparison

Filed under: Protection [Edit Tags]

ANSI IEC 60617 Description

21FL FLOC Fault locator

21G Z< Three-phase underimpedance protection, low-set stage

24 U/f> Overexcitation, low-set stage

24 U/f>> Overexcitation, high-set stage

25 SYNC Synchro-check/ voltage check, stage 1

25 SYNC Synchro-check/ voltage check, stage 2

27 3U< Three-phase undervoltage, low-set stage

27 3U<< Three-phase undervoltage, high-set stage

U1< U2>
27, 47, 59 Phase-sequence voltage protection, stage 1
U1>

U1< U2>
27, 47, 59 Phase-sequence voltage protection, stage 2
U1>

32 P Three-phase underpower or reverse power, stage 1

32 P Three-phase underpower or reverse power, stage 2

32 P Three-phase underpower or reverse power, stage 3

32P/32Q P>/Q> Three-phase directional overpower, stage 1

32P/32Q P>/Q> Three-phase directional overpower, stage 2

32P/32Q P>/Q> Three-phase directional overpower, stage 3

37 3I< Three-phase non-directional undercurrent, stage 1

37 3I< Three-phase non-directional undercurrent, stage 1

37 3I< Three-phase non-directional undercurrent, stage 2

40 X< Three-phase underexcitation protection, low-set stage

40 X<< Three-phase underexcitation protection, high-set stage

46 I2> Negative-phase sequence, low-set stage

46 I2>> Negative-phase sequence, high-set stage

46 I> Phase discontinuity

46R Phase reversal protection

Three-phase start-up supervision for motors (incl. I2t and speed


48, 14, 66 Ist, n<
device modes, and start-up counter)

49F 3Ith> Three-phase thermal protection for cables


Three-phase thermal protection for devices (motors, generators
49M/49G/49T
and transformers)

50N I0>>> Non-directional earth-fault, instantaneous stage

50N/51N I0>> Non-directional earth-fault, high-set stage

50P/51P 3I>>> Three-phase non-directional overcurrent, instantaneous stage

51 3I> Three-phase non-directional overcurrent, low-set stage

51C, 37C, 68C 3I> 3I< Three-phase overload protection for shunt capacitor banks

Non-directional earth-fault, low-set stage (or SEF=sensitive earth-


51N I0>/SEF
fault protection)

Three-phase current unbalance protection for H-bridge connected


51NC 3I>
shunt capacitor banks

51NC I> Current unbalance protection for shunt capacitor banks

51P-1 3I> Three-phase non-directional overcurrent, low-set stage

51V I(U)> Voltage-dependent overcurrent, low-set stage

51V I(U)>> Voltage-dependent overcurrent, high-set stage

551P-2 3I>> Three-phase non-directional overcurrent, high-set stage

59 3U> Three-phase overvoltage, low-set stage

59 3U>> Three-phase overvoltage, high-set stage

59N U0> Residual overvoltage, low-set stage

59N U0>> Residual overvoltage, High-set stage

59N U0>>> Residual overvoltage, instantaneous stage

60 FUSEF Fuse failure supervision

67-1 3I> Three-phase directional o/c, low-set stage

67-2 3I>> Three-phase directional o/c, high-set stage

67 3I>>> Three-phase directional o/c, instantaneous stage

67N I0>>> Directional earth-fault, instantaneous stage

67N I0>> Directional earth-fault, high-set stage

67N I0> Directional earth-fault, low-set stage

Directional earth-fault, low-set stage (or SEF=sensitive earth-fault


67N/51N I0> /SEF
protection)

Three-phase transformer inrush and motor start-up current


68 3I2f>
detector

79 01 Auto-reclosure

81U/81O f</f>, df/dt Underfrequency or overfrequency, stage 1 (incl. rate of change)

87G 3DI> Stabilized three-phase differential protection for generators


High-impedance or flux-balance based differential protection for
87G/87M 3DI>
generators and motors

87N I0>, REF High-impedance based restricted earth-fault

87T 3I>, 3I>> Stabilized three-phase differential protection for transformers

87TN I0> Stabilized restricted earth-fault, stage A

You might also like