ZXDU68 B201

DC Power System
Product Description

Version: V5.0R99M04

ZTE CORPORATION
No. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://support.zte.com.cn
E-mail: 800@zte.com.cn
LEGAL INFORMATION
Copyright 2015 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided as is, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit the ZTE technical support website http://support.zte.com.cn to inquire for related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.

Revision History

Revision No. Revision Date Revision Reason

R1.0 2015-09-14 First edition

Serial Number: SJ-20150914145904-001

Publishing Date: 2015-09-14 (R1.0)

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Contents
About This Manual ......................................................................................... I
Chapter 1 System Introduction and Features.......................................... 1-1
1.1 System Introduction............................................................................................ 1-1
1.2 System Features ................................................................................................ 1-1

Chapter 2 Configuration List ..................................................................... 2-1


Chapter 3 System Structure and Components........................................ 3-1
3.1 System Structure ............................................................................................... 3-1
3.2 PDU .................................................................................................................. 3-3
3.3 ZXD3000 Rectifier .............................................................................................. 3-5
3.4 Centralized Supervision Unit ............................................................................... 3-6
3.5 Signal Interface Unit ........................................................................................... 3-8
3.6 FBMU.............................................................................................................. 3-10

Chapter 4 ZXD3000 Rectifier Specifications ............................................ 4-1


4.1 Technical Specifications...................................................................................... 4-1
4.2 Input Features.................................................................................................... 4-3
4.3 Output Features ................................................................................................. 4-4
4.4 Power Decrease With High Temperature ............................................................. 4-5

Chapter 5 System Specifications.............................................................. 5-1


5.1 Environment Specifications ................................................................................. 5-1
5.2 Performance Specifications................................................................................. 5-1
5.3 Electrical specifications Specifications ................................................................. 5-2
5.4 Physical Specifications ....................................................................................... 5-4

Appendix A Alarm List .............................................................................. A-1


A.1 Monitoring Alarms .............................................................................................. A-1
A.2 AC Alarms......................................................................................................... A-4
A.3 SMR Alarms ...................................................................................................... A-9
A.4 DC Alarms....................................................................................................... A-10
A.5 Environment Alarms......................................................................................... A-14

Appendix B Electrical Connection Diagram ........................................... B-1


Glossary .......................................................................................................... I

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


This page intentionally left blank.

II

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


About This Manual
Purpose
This manual applies to the ZXDU68 B201 (V5.0R99M04) DC Power System(short for
ZXDU68 B201 system). The ZXDU68 B201 is a built-in DC power system and provides
power for 48 V communications equipment.
This manual describes the system structure, characteristics, and configuration.

Intended Audience
This manual is intended for:
l Planning engineers
l Maintenance engineers

What Is in This Manual


This manual contains the following chapters/appendices:

Chapter/Appendix Summary

Chapter 1. System Describes the system overview and features.


Introduction and Features

Chapter 2. Configuration List Describes the configuration list of the ZXDU68 B201 (V5.0R99M04)
system

Chapter 3. System Structure Describes the system structure, power supply chassis, ZXD3000
and Components (V5.0) rectifiers, Centralized Interface Unit (CSU), Signal Interface
Unit and FBMU.

Chapter 4. ZXD3000 Describes the ZXD3000 rectifier specifications, including technical


Rectifier Specifications specifications, input features, output features and the feature of power
decrease with high temperature.

Chapter 5. System Describes system environment specifications, performance


Specifications specifications, technical specifications, and physical specifications.

Appendix A, Alarm List Describes system alarm name, default Level / output Relay, alarm
generation conditions.

Appendix B, Electrical Provides the electrical connection diagram of the ZXDU68 B201
Connection Diagram (V5.0R99M04) system.

Related Documentation
The following documentation is related to this manual:
l ZXDT CSU500B (V1.01.00.00) Centralized Supervision Unit Operation Guide
l ZXDU68 B201 (V5.0R99M04) DC Power System Quick Installation Guide

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Conventions
This manual uses the following typographical conventions:

Typeface Meaning

Italics Variables in commands. It may also refer to other related manuals and documents.

Bold Menus, menu options, function names, input fields, option button names, check boxes,
drop-down lists, dialog box names, window names, parameters, and commands.

Danger: indicates an imminently hazardous situation. Failure to comply can result in


death or serious injury, equipment damage, or site breakdown.

Warning: indicates a potentially hazardous situation. Failure to comply can result in


serious injury, equipment damage, or interruption of major services.

Caution: indicates a potentially hazardous situation. Failure to comply can result in


moderate injury, equipment damage, or interruption of minor services.

Note: provides additional information about a certain topic.

II

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 1
System Introduction and
Features
Table of Contents
System Introduction....................................................................................................1-1
System Features ........................................................................................................1-1

1.1 System Introduction


The ZXDU68 B201 system is a built-in DC power system. It provides 48 V power for
communication equipment.
l Single-phase three-wire (L/N/PE) AC input, applicable to the 220 V electrical grid.
l The system can provide 48 V power for communication equipment.
l The system can be installed in a standard cabinet with 19-inch width.
l When fully configured, the power chassis is equipped with four ZXD3000 rectifiers
and can provide a maximum power output of 12 kW.

1.2 System Features


Efficient Rectifiers
l With 50% - 100% output power, the rectifier efficiency is 96%.
l With 30% - 50% output power, the rectifier efficiency is 94%.

Automatically Switching the Rectifiers to the Sleep Mode


The system switches one or more rectifiers to the sleep mode according to the load power.
The power of a rectifier in sleep mode is not larger than 4 W.

A Wide Range of Input Voltage


A wide range of input phase voltage (85 V to 295 V) makes the system suitable for areas
with unstable power sources and save energy consumption of the battery.

Managing Data in Batches


Users can set the parameters in batches, copy records and upgrade programs via a USB
flash drive.

1-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Professional Monitoring and Management


l The transmission speed is high via CAN bus.
l The monitoring unit supports energy saving management, intelligent battery
management, rectifier management, alarm management.
l The system can be remotely managed through a computer installed with a web
browser anywhere if Ethernet is available.
l Users can press the QUY button of a rectifier to query the data of the rectifier or control
it.

Flexible Monitoring Networking


The system provides input and output relays, RJ45 Ethernet interface, RS232 interface,
RS485 interface, and USB interface. The system supports multiple monitoring networking
modes via Telnet, Hypertext Transfer Protocol (HTTP), File Transfer Protocol (FTP), and
Simple Network Management Protocol (SNMP).

1-2

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 2
Configuration List
For the configuration list of the ZXDU68 B201 system, refer to Table 2-1.

Table 2-1 Configuration List of the ZXDU68 B201 System

Component Configuration

Product Model ZXDU68 B201(V5.0R99M04)

Rectifier Model ZXD3000(V5.0R03)

Quantity 4 sets (when fully configured)

Centralized Model CSU500B09


Supervision
Software version V1.01.00.00
Unit(CSU)

AC AC input mode One-phase(L/N)


distribution
AC input circuit breaker 180 A ACB
unit
AC auxiliary output 216 A ACBs

AC SPD Class C

DC Battery input circuit breakers l Four battery input branches


distribution l 4100 A ACBs
unit
DC load output l LLVD1+BLVD
l LLVD1: 2100 A ACBsr
l BLVD: 115 A+163 A ACBs

FBMU Two sets

Battery temperature sensor Four sets

Signal Interface Unit Provides multiple interfaces for supervision and


networking.

Note:
Capacity configuration of DC output circuit breakers described in Table 2-1 is
recommended. The actual configuration is subject to the contract.

2-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

This page intentionally left blank.

2-2

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 3
System Structure and
Components
Table of Contents
System Structure .......................................................................................................3-1
PDU ...........................................................................................................................3-3
ZXD3000 Rectifier ......................................................................................................3-5
Centralized Supervision Unit ......................................................................................3-6
Signal Interface Unit ...................................................................................................3-8
FBMU.......................................................................................................................3-10

3.1 System Structure


The ZXDU68 B201 (V5.0R99M04) system consists two parts ZXDU68 B201 power
supply chassis and FBMU chassis.
For details of FMBU chassis, refer to 3.6 FBMU.

External view
The dimensions of the ZXDU68 B201 power supply chassis are 219.3 mm 442 mm
394 mm (Height Width Depth). For an external view of the ZXDU68 B201, see Figure
3-1.

3-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Figure 3-1 ZXDU68 B201 External View

Product Structure
The ZXDU68 B201 power supply chassis consists of power distribution units, rectifiers, a
signal processing board, and a monitoring unit.
For the product structure, see Figure 3-2.

Figure 3-2 ZXDU68 B201 Product Structure

1. PDU 3. SIU
2. Rectifier 4. CSU

For a description of the components, refer to Table 3-1.

3-2

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Structure and Components

Table 3-1 ZXDU68 B201 Component Descriptions

Serial Component Description


Number

1 PDU The PDU includes AC power distribution components and DC power


distribution components.
l AC power distribution components: AC input ACB,, AC output ACB,
AC input terminals, AC output terminals and AC SPD.
l DC power distribution components: battery input ACB, DC output ACB
and DC output terminals.
For details, refer to 3.2 PDU.

2 Rectifier A rectifier converts AC power to DC power for load and battery charging.
For a description of the rectifiers, refer to 3.3 ZXD3000 Rectifier.

3 SIU The signal processing board provides relay interfaces, battery temperature
detection interfaces, environment detection interfaces, and communication
interfaces. For details, refer to 3.5 Signal Interface Unit.

4 CSU The monitoring unit collects information, monitors alarms, and manages
the operation of the system. For details, refer to 3.4 Centralized
Supervision Unit.

3.2 PDU
AC Power Distribution Components
AC power distribution units are located in the left part of the PDU. Figure 3-3 shows the
layout of AC power distribution components.

Figure 3-3 AC Power Distribution Components

For a description of the AC power distribution components, refer to Table 3-2.

3-3

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Table 3-2 Descriptions of AC Power Distribution Components

Label Component Function

AC Input AC input terminals Connect to the live wire (L), neutral wire (N) and protection
Earth (PE) wire in AC input cables as the AC input interface.

AC input air circuit Connects or disconnects the total AC power supply.


breaker

AC Output AC output terminals Connect to the L/N cables of AC auxiliary output.

AC output air circuit Connect/disconnect the AC auxiliary output of the system.


breaker

AC SPD AC lightning arrester Provides surge protection for the AC input.

DC Power Distribution Components


DC power distribution units are located in the right part of the PDU. Figure 3-4 shows the
layout of DC power distribution components.

Figure 3-4 DC Power Distribution Components

For a description of the DC power distribution components, refer to Table 3-3.

Table 3-3 Descriptions of DC Power Distribution Components

Label Component Function

BATT Input Battery input terminals Connect BATT+ and BATT- cables of the battery
branches 1 and 2.

BLVD Load air circuit breaker l Connects DC output circuits.


l Control DC output to the LLVD and BLVD loads.
LLVD1

BATT1 ~ BATT4 Battery air circuit l Connects or disconnects battery circuits.


breaker l Connects to the negative output wire of a battery
pack as the battery input interface.

DC OUT DC OUT terminals Connects to the -48 V power cable for electrical load as
the DC output interface.

3-4

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Structure and Components

3.3 ZXD3000 Rectifier


Function
The ZXD3000 rectifiers convert AC to DC, power DC loads and charge the batteries.

External View
For the external view of the ZXD3000 rectifier, see Figure 3-5.

Figure 3-5 Rectifier External View

1. Indicators 2. Fan 3. QUY button

Buttons and Indicators


l Press and hold the QUY (query) button of a rectifier for 5 seconds and then the CSU
displays the rectifier's main information screen.
l The indicators display the operational status of the rectifier. For a description of the
indicators, refer to Table 3-4.

Table 3-4 Rectifier Operational Status

Indicator
Operational Status
Power Run Alarm Fault

Lit Lit - Not lit Operating with Stable


Voltage

Flashing Not lit - Not lit Sleep

Lit Flashing - Not lit Output Current Limit

Lit - Flashing - Communication Failure

Lit - Lit - Alarm

Lit Not lit - Lit Fault

"-" means that the status of the indicator is not relevant to the condition.

Interfaces
Input and output interfaces are laid at the back of the rectifier. For the interface layout of
the rectifier, see Figure 3-6. For a description of the pin definitions, refer to Table 3-5.

3-5

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

The interfaces complete the electrical and signal connections between the rectifier and the
ZXDU68 B201 power system.

Figure 3-6 Rectifier Interfaces

Table 3-5 Pin Definitions of Rectifier Interfaces

Interface Name Pin No. Signal Function


Definition

AC input 1-6 L Connects the AC input phase cable.


interfaces
7 - 12 N Connects the AC input neutral cable.

18 - 20 PE Connects the protection ground.

- 13 - Reserved

Phase detection 14 AA Locates the phase where an operating rectifier is.


interfaces
15 AB

CAN 16 CAN- A rectifier communicates with other devices


communication through the interfaces. For example, a rectifier
17 CAN+
detection transmits data to the CSU, and the CSU issues
interfaces commands to a rectifier.

DC output 21 - 28 OUTPUT+ Provide DC output power.


interfaces
29 - 36 OUTPUT-

Hot-plug pins 37, 38 Hot-plug pin (+) Prevent sparks when a rectifier is installed into
the ZXDU68 B201 system.
39, 40 Hot-plug pin (-)

3.4 Centralized Supervision Unit


The Centralized Supervision Unit (CSU) is the foreground monitoring unit of the system.
It monitors the AC distribution, DC distribution, rectifiers and batteries of the system.

Functions
l Gives an audible and visual alarm and provides the protection function when the
ZXDU68 B201 system is faulty.

3-6

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Structure and Components

l Collects the operational data and monitors the operations of the ZXDU68 B201
system.
l Performs advanced battery management with protection functions.
l Manages the rectifiers and automatically switches one or more rectifiers to the sleep
mode to save power.
l Transmits data to the background Supervision Center (SC) and receives commands
from the SC. In this way, the system can be monitored remotely.
l The CSU can be remotely managed through a computer installed with IE 7.0 (or
above) anywhere if Ethernet is available.
l Users can set the parameters in batches, copy records and upgrade programs via a
USB flash drive.

External View
For the external view of the CSU, see Figure 3-7.

Figure 3-7 CSU External View

1. RJ45 Ethernet interface 3. Indicators 5. Buttons


2. USB interface 4. LCDscreen

Interfaces
l USB interface
Supports USB flash drives but does not support SD card or other portable storage
devices, such as portable hard disks, MP3 or MP4.
Use a 2 GB (or below) USB flash drive with available capacity of greater than 32
MB.

l RJ45 Ethernet interface


The Ethernet interface rate is 10M/100M (adaptive).

The Ethernet interface supports multiple monitoring networking modes through


Telnet, HTTP, FTP and SNMP.

3-7

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Indicators
The indicators display the operational status of the CSU and the system. For a description
of indicators, refer to Table 3-6.

Table 3-6 CSU Operational Status

Indicator
Operational Status
Power Run Alarm

Lit Flashing Not lit Operating Normally

Lit Flashing Flashing Alarm

Lit Lit or not lit - Faulty

"-" means that the status of the indicator is not relevant to the condition.

Buttons and LCD


The buttons and the LCD of the CSU enable the users to query operational data of the
system, set parameters, and control the operation of the system.
For a description of the functions of CSU buttons, refer to Table 3-7.

Table 3-7 Functions of Buttons

Button Function

l Scrolls pages up
l Moves to the previous item
l Increases numerical values

l Scrolls pages down


l Moves to the next item
l Decreases numerical values

Moves the cursor to the right

Moves the cursor to the left

Esc l Returns to the upper-level screen


l Cancels modifications

Ent l Displays the lower-level screen


l Saves modifications

<+> Enters the Language Set menu

<+Ent> Displays help information of the current menu

3.5 Signal Interface Unit


The Signal Interface Unit (SIU) is installed inside the SIU slot. The signal interfaces are
laid on the front panel of the SIU.

3-8

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Structure and Components

The interfaces include communication interfaces, battery temperature interfaces,


environment detection interfaces, input and output relay interfaces.
For the SIU interface layout and definitions of the ZXDU68 B201(V5.0R99M04) system,
see Figure 3-8and Figure 3-9.

Figure 3-8 Layout of SIU Interfaces

Figure 3-9 Definitions of the SIU Interfaces

For a description of the pin definitions, refer to Table 3-8.

Table 3-8 Pin Definitions of SIU Interfaces

Interface Description

Communication Interfaces

X1 RS485 The interface for RS485 communication

X8 RS232 The interface for RS232 communication

Environment Detection Interfaces

X2 BATT1.Temp Connects to temperature sensor of battery pack 1

X3 BATT2.Temp Connects to temperature sensor of battery pack 2

X4 Amb.Temp Connects to environment temperature sensor

X5 Flood Alarm Connects to flood detection sensor

3-9

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Interface Description

X6 Door Alarm Connects to the door magnet sensor

Input/Output Relay Interfaces

X7 In-relay 1, 2 l Users can customize these input relays for alarm


input.
l Alarm name, level and status of each input relay can
be modified in the CSU.

X9 Out-relay 1, 2 The output relays 1, 2 correspond to the software codes


A1, A2 in the CSU. Users can customize these output
relays for alarm output.

X10 BATT3.Temp, Connects to temperature sensor of battery pack 3.

X12 BATT4.Temp Connects to temperature sensor of battery pack 4.

3.6 FBMU
FBMU is a lithium iron battery management unit used to perform the elaborate
management of lithium iron batteries.

Function
FBMU is used to collect lithium iron battery data for real-time alarms and battery protection
to effective manage the lithium iron battery modules.
l Communication with supervision devices.
l Output of heating pad control signals.
l Collection of battery voltage and temperature detection signals.
l Collection of current detection signals.

External View
For the external view of the FBMU, see Figure 3-10. The dimensions of the FBMU are 41
mm 205 mm 129 mm (Height Width Depth).

3-10

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 3 System Structure and Components

Figure 3-10 FBMU External view

Interface Definitions
For the front overview of the interfaces on the FBMU board, see Figure 3-11.

Figure 3-11 Front overview of FBMU

For a description of the interfaces definitions, refer to Table 3-9.

Table 3-9 Description of the interfaces

Interface Interface Pin Interface and Signal Description Function


ID Name No.

RS485A RS485 com- 1 RS485 signal input terminal B Used to communicate with
munication supervision equipment.
2 RS485 signal input terminal A
interface

RS485B RS485 com- 1 RS485 signal input terminal B Used to communicate with
munication supervision equipment.
2 RS485 signal input terminal A
interface

PE/HC- Heating 1 Protective earth Used to output heating pad


/CO- pad control control signal and lead out
2 Normally-open terminal of the
interface battery load and PE cables.
circuit control relay of the heating
pad

3 Common terimnal of the circuit


control relay of the heating pad

4 Total load of batteries

3-11

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Interface Interface Pin Interface and Signal Description Function


ID Name No.

M1 ~ M4 interface of - - Used to introduce the


the batteries battery voltage and
temperature signal of
the batteries

CUR Current 1 Nagative terminal of the current Used to introduce the


detection splitter current detection signal
interface
2 Positive terminal of the current
splitter

For a description of the indicators , refer to Table 3-10.

Table 3-10 Description of the indicators

RUN (Green) ALM (Red) FBMU Operation Status Function

Not lit Lit Charging protection status Used to indicate an


visual alarm.
Lit Flashing (lit for 0.5 Charging alarm status
second and not lit for
1.5 second)

Lit Not lit Normal charging status

Not lit Flashing (lit for 0.5 Discharging protection


second and not lit for status
1.5 second)

Flashing (lit for 0.5 Flashing (lit for 0.5 Discharging alarm status
second and not lit for second and not lit for
1.5 second) 1.5 second)

Flashing (lit for 0.5 Not lit Normal discharging status


second and not lit for
1.5 second)

Flashing (lit for 0.5 Not lit Online non-float charging


second and not lit for status/this status is cleared
0.5 second) when the batteries are fully
charged.

Flashing (lit for 0.5 Flashing (lit for 0.5 Online non-float charging
second and not lit for second and not lit for alarm status
0.5 second) 0.5 second)

3-12

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 4
ZXD3000 Rectifier
Specifications
Table of Contents
Technical Specifications .............................................................................................4-1
Input Features ............................................................................................................4-3
Output Features .........................................................................................................4-4
Power Decrease With High Temperature ....................................................................4-5

4.1 Technical Specifications


For the technical specifications of the ZXD3000 (V5.0) rectifiers, refer to Table 4-1.

Table 4-1 Technical Specifications

Item Description

AC input Input mode Single-phase three-wire (L/N/PE)

Input voltage l Input voltage: 85 V to 295 V


l Rated input voltage: 100 V to 240 V

Maximum input current 18 A

Frequency l Frequency: 45 Hz to 66 Hz
l Rated frequency: 50 Hz/60 Hz

Input power factor 0.998 (when the input and output values are
rated)

DC output Maximum output power 3,000 W (when the input voltage is 176 V to 295 V
and the environment temperature is -40 C to 55
C)

Rated output voltage 53.5 V

Range of output voltage 42 V to 59.5 V


Adjusted through the monitoring unit of the power
system

Output current limit 5 A to 63.5 A


Set through the monitoring unit

Efficiency l Peak efficiency: 96%


l Efficiency with the rated load: 95%

4-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Item Description

Voltage stabilizing accuracy 0.6%

Output weighted noise 2 mV

Broad frequency noise l 50 mV (3.4 kHz to 150 kHz)


voltage l 20 mV (0.15 MHz to 30 MHz)

Discrete frequency noise l 5 mV (3.4 kHz to 150 kHz)


voltage l 3 mV (150 kHz to 200 kHz)
l 2 mV (200 kHz to 500 kHz)
l 1 mV (0.5 MHz to 30 MHz)

Peak-to-peak noise voltage 200 mV (bandwidth of 0 Hz to 20 MHz)

Inter-rectifier load sharing The number of the rectifiers that can be connected
in parallel is not less than 30; when the output
current of a single rectifier is 10% to 100% of the
rated value, the output current imbalance of the
rectifiers is not greater than 1.5 A.

Safety Dielectric strength l 2840 VDC voltage of the AC input terminals


protection to the chassis for one minute: no breakdown
or arc; the stable leakage current is less than
1 mA.
l 4242 VDC voltage of the AC input terminals
to the DC output terminals for one minute: no
breakdown or arc; the stable leakage current
is less than 1 mA.
l 707 VDC voltage of the DC output terminals
to the chassis for one minute: no breakdown
or arc; the stable leakage current is less than
1 mA.
l 707 VDC voltage of other interfaces to the
chassis for one minute: no breakdown or arc;
the stable leakage current is less than 1 mA.

Safety standard Compliant with IEC60950

Electromagnetic Compliant with EN55022 Class B and IEC61000


compatibility

Mean time between failures MTBF 2 105 h

Cooling mode l Forced cooling;


l The fan speed can be adjusted according to
the environment temperature and the working
status of the rectifier.

4-2

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 4 ZXD3000 Rectifier Specifications

Item Description

Environment requirement l Operating temperature: -40 C to 75 C


l Storage temperature: -40 C to 85 C
l Relative humidity: 95% (non-condensing)
l Air pressure: 80 kPa to 106 kPa

Dimensions 41.5 mm 132 mm 300 mm (HWD)

Weight 2 kg

4.2 Input Features


Overview
The ZXD3000 (V5.0) rectifier automatically adjusts its operational status according to the
AC input voltage.
The input features include the under-voltage protection, over-voltage protection, and power
limit.

Under-Voltage Protection
When the AC input voltage is lower than the under-voltage threshold, the rectifier
automatically shuts down and provides no output. Meanwhile, the alarm indicator is on.
After the AC input voltage reaches the under-voltage recovery threshold, the rectifier
automatically recovers.
The under-voltage recovery threshold = the AC input under-voltage threshold + the return
difference.
The AC input under-voltage threshold is (85 5) V and the return difference ranges from
8 V to 12 V.

Over-Voltage Protection
When the AC input voltage is higher than the over-voltage threshold, the rectifier
automatically shuts down and provides no output. Meanwhile, the alarm indicator is
on. After the AC input voltage falls to the over-voltage recovery threshold, the rectifier
automatically recovers.
The over-voltage recovery threshold = the AC input over-voltage threshold the return
difference.
The AC input over-voltage threshold is (295 5) V and the return difference ranges from
5 V to 10 V.

Power Limit
The rectifier limits its output power according to the input voltage.

4-3

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

See Figure 4-1 for the power limit feature of the rectifier when the following conditions are
met.
l Environment temperature: -25 C to 55 C
l Output voltage of the rectifier: 48 V to 59.5 V

Figure 4-1 Power Limit Feature

1. Under-voltage threshold 2. 55% power (110 V) 4. Over-voltage threshold


(855 V) 3. Maximum power (176 V) (2955 V)

For the relationship between the AC input voltage and the output power, refer to Table 4-2.

Table 4-2 Relationship Between AC Input Voltage and Output Power

AC Input Voltage Output Power (Percentage of the Maximum Output Power)

(85 5) V 0

(85 5) V to 110 V Linear power limit


Output power percentage: 40% to 55%

110 V to 176 V Linear power limit


Output power percentage: 55% to 100%

176 V to (295 5) V 100%

> (295 5) V 0

Maximum output power: 3000 W

4.3 Output Features


See Figure 4-2 for the output features of the ZXD3000 (V5.0) rectifier when the following
conditions are met.
l AC input voltage of the rectifier: 176 V to 295 V

4-4

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 4 ZXD3000 Rectifier Specifications

l Environment temperature: -25 C to +55 C

Figure 4-2 Output Features

As shown in Figure 4-2, the output features of the rectifier can be concluded as follows:

l When the output voltage ranges from 42 V to 48 V, the maximum output current is
constant.
l When the output voltage ranges from 48 V to 59.5 V, the maximum output power is
constant.
l When the output voltage is lower than 36 V, the rectifier restarts for protection.
When the environment temperature ranges from -25 C to +55 C and the input voltage
ranges from 85 V to 176 V, the rectifier still has the above output features. However,
because of the power limit feature, when the input voltage ranges from 85 V to 176 V, the
output power cannot reach the highest percentage (100%). Therefore, the input voltage
affects the maximum output power and maximum output current.

4.4 Power Decrease With High Temperature


The feature of power decrease with high temperature refers to that the output power of
the ZXD3000 (V5.0) rectifier decreases with the increase of the environment temperature
when the environment temperature reaches the over-temperature threshold.
For the feature of power decrease with high temperature, see Figure 4-3.

4-5

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Figure 4-3 Power Decrease With High Temperature

For a description of the feature, refer to Table 4-3.

Table 4-3 Power Decrease With High Temperature

Environment Temperature Output Power (Percentage of the Maximum Power)

-40 C to +55 C 100%

+55 C to 75 C Linear power limit


The output power decreases with the increase of the temperature
and is not less than 50% when the temperature is 75 C.

> 75 C 0% (the rectifier shuts down for protection against over-temperature)

Maximum output power: 3000 W

4-6

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 5
System Specifications
Table of Contents
Environment Specifications ........................................................................................5-1
Performance Specifications ........................................................................................5-1
Electrical specifications Specifications........................................................................5-2
Physical Specifications ...............................................................................................5-4

5.1 Environment Specifications


For a description of the environment specifications of the ZXDU68 B201 system, refer to
Table 5-1.

Table 5-1 Environment Specifications

Item Specifications

Operating temperature -10 C to +55 C

Storage temperature -40 C to +80 C

Operating relative humidity 90 (402 )

Storage relative humidity 95 (402 )

Altitude l 0 ~ 2000 m: 100% output power


l 2000 m ~ 3000 m: The power derating percentage is 1%
for each 100 m increase in altitude.

Other requirements l The cabinet should be stable and erect.


l No explosion hazard, no shake or jolt.
l Never install the equipment where there is a risk of liquid
or objects falling into the top of the equipment.
l No conductive dust or corrosive gas.
l No strong Electromagnetic Interference (EMI).

5.2 Performance Specifications


For the performance specifications of the ZXDU68 B201 DC power system, refer to Table
5-2.

5-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Table 5-2 Performance Specifications

Item Specification

Rated output power 12 kW (when fully configured with four ZXD3000 rectifiers)

System efficiency l Peak efficiency: 95.5%.


l Efficiency at rated load: 94.5%.

Power limitation based on


Refer to .
the input voltage

Power limitation based on


Refer to .
the temperature

Equipment noise 55 dB (A)

Network architecture for RS232 serial port mode, Ethernet mode, active-device transparent
monitoring transmission mode, relay mode

Mean time between failures MTBF3.2105 h

5.3 Electrical specifications Specifications


For the electrical specifications of theZXDU68 B201 DC power system, refer to Table 5-3
and Table 5-4

Table 5-3 AC Electrical Specifications

Item Specification

AC input AC input mode Single-phase three-wire (L/N/PE) with a rated phase voltage
features ranging from 220 V to 240 V

AC input voltage l Rated input voltage: 220 V - 240 V (phase voltage) / 380 V
- 415 V (line voltage)
l Phase voltage range: 85 V - 295 V

AC input frequency l Rated frequency: 50 Hz/60 Hz


l Frequency range: 45 Hz - 66 Hz

AC input power 0.998 (with rated load)


factor

AC surge l Standard class C SPD


protection l Imax = 40 kA (8/20 s)

Input Total THD 5% (with 30% - 100% rated power)


Harmonic
Distortion (THD)

5-2

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Chapter 5 System Specifications

Item Specification

Protection AC over-voltage If the input phase voltage is higher than the over-voltage
functions protection threshold, the system takes a protective action against
over-voltage

AC under-voltage If the input phase voltage is lower than the under-voltage


protection threshold, the system takes a protective action against
under-voltage

Input over-current The AC input circuit breaker (or AC input contactor) provides
protection the over-current protection function

Table 5-4 DC Electrical Specifications

Item Specification

DC output Rated output -53.5 V


features voltage

Output voltage -42 V to -58 V (adjustable in the CSU)


range

Rated output 12 kW (in full configuration with four ZXD3000 rectifiers)


power

DC surge Imax = 15 kA (8/20 s)


protection

DC voltage drop 0.5 V


inside the chassis

Regulated voltage 0.5%


precision

Weighted noise 2 mV
voltage

Peak-peak noise 150 mV (20 MHz bandwidth)


voltage

Load l Load Low Voltage Disconnect 1 (LLVD1)


disconnection l Battery Low Voltage Disconnect (BLVD)
modes l Battery High Temperature Disconnect (BHTD)
l Load Low Temperature Disconnect (LLTD)

5-3

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

Item Specification

Protection DC over-voltage If the DC output voltage is higher than the over-voltage


functions protection threshold, the system takes a protective action against
over-voltage

DC under-voltage If the DC output voltage is lower than the under-voltage


protection threshold, the system takes a protective action against
under-voltage

Battery under- l If the battery voltage is lower than the LLVD1 threshold,
voltage protection the system disconnects the LLVD1 loads.
l If the battery voltage is lower than the BLVD threshold, the
system disconnects the batteries.

Battery high- If the battery voltage is higher than the BHTD threshold, the
temperature system disconnects the batteries
protection

Load low- If the battery voltage is lower than the LLTD threshold, the
temperature system disconnects the loads
protection

5.4 Physical Specifications


For the physical specifications of the ZXDU68 B201 DC power system, refer toTable 5-5.

Table 5-5 Physical Specifications

Item Specification

Dimensions 219.3 mm 442 mm 394 mm (t W D)

Weight About 25 kg (excluding the rectifiers)

Installation mode Embedded in standard cabinet with 19-inch width

Maintenance mode Front-end maintenance

Cabling mode Bottom cabling

Protection degree IP20

5-4

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A
Alarm List
Table of Contents
Monitoring Alarms................................................................................................... A-1
AC Alarms .............................................................................................................. A-4
SMR Alarms ........................................................................................................... A-9
DC Alarms ............................................................................................................ A-10
Environment Alarms ............................................................................................. A-14

A.1 Monitoring Alarms


For a description of the monitoring alarms, refer to Table A-1.

Table A-1 Monitoring Alarm Description

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

1 Common Alarm Mask/Null If an alarm is generated in the


system, the corresponding output
relay action is triggered.

2 In-Relay-1# Mask/Null If In.Rly AppList-1# is set to Yes,


and input relay 1 detects equipment
malfunction, this alarm is generated.

3 In-Relay-2# Mask/Null If In.Rly AppList-2# is set to Yes,


and input relay 2 detects equipment
malfunction, this alarm is generated.

4 In-Relay-3# Mask/Null If In.Rly AppList-3# is set to Yes,


and input relay 3 detects equipment
malfunction, this alarm is generated.

5 In-Relay-4# Mask/Null If In.Rly AppList-4# is set to Yes,


and input relay 4 detects equipment
malfunction, this alarm is generated.

6 In-Relay-5# Mask/Null If In.Rly AppList-5# is set to Yes,


and input relay 5 detects equipment
malfunction, this alarm is generated.

A-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

7 In-Relay-6# Mask/Null If In.Rly AppList-6# is set to Yes,


and input relay 6 detects equipment
malfunction, this alarm is generated.

8 In-Relay-7# Mask/Null If In.Rly AppList-7# is set to Yes,


and input relay 7 detects equipment
malfunction, this alarm is generated.

9 In-Relay-8# Mask/Null If In.Rly AppList-8# is set to Yes,


and input relay 8 detects equipment
malfunction, this alarm is generated.

10 In-Relay-9# Mask/Null If In.Rly AppList-9# is set to Yes,


and input relay 9 detects equipment
malfunction, this alarm is generated.

11 In-Relay-10# Mask/Null If In.Rly AppList-10# is set to Yes,


and input relay 10 detects equipment
malfunction, this alarm is generated.

12 In-Relay-11# Mask/Null If In.Rly AppList-11# is set to Yes,


and input relay 11 detects equipment
malfunction, this alarm is generated.

13 In-Relay-12# Mask/Null If In.Rly AppList-12# is set to Yes,


and input relay 12 detects equipment
malfunction, this alarm is generated.

14 In-Relay-13# Mask/Null If In.Rly AppList-13# is set to Yes,


and input relay 13 detects equipment
malfunction, this alarm is generated.

15 In-Relay-14# Mask/Null If In.Rly AppList-14# is set to Yes,


and input relay 14 detects equipment
malfunction, this alarm is generated.

16 In-Relay-15# Mask/Null If In.Rly AppList-15# is set to Yes,


and input relay 15 detects equipment
malfunction, this alarm is generated.

17 In-Relay-16# Mask/Null If In.Rly AppList-16# is set to Yes,


and input relay 16 detects equipment
malfunction, this alarm is generated.

18 Batt.Test Fail Mask/A1 In a battery test, if the battery voltage


amounts to the test voltage, but the
battery capacity does not amount to
the test stop voltage, this alarm is
generated.

A-2

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

19 LLVD1 Loop Brk. Major/A1 When LLVD1 is performed, this alarm


is generated.

20 LLVD2 Loop Brk. Major/A1 When LLVD2 is performed, this alarm


is generated.

21 Batt.Det.Abr. Critical/A1 During the battery detection, if battery


terminal voltage is lower than the test
stop voltage, this alarm is generated.

22 BLVD Alarm Critical/A1 When BLVD is performed, this alarm


is generated.

23 LLTD Alarm Critical/A1 If the environment temperature is


lower than LLTD Env. Temp., and
the LLTD is performed, this alarm is
generated.

24 BHTD Alarm Critical/A1 If the battery temperature is higher


than BHTD Temp. and the BHTD is
performed, this alarm is generated.

25 All Alarm Blocked Critical/Null This alarm indicates that all real-time
alarms are not displayed. You can
set whether to display real-time
alarms in the CSU.

26 Batt. Equal Mask/Null This alarm indicates that the batteries


are in equalized charging.

27 BMU Comm.Fail Major/Null This alarm indicates that the


communication between the CSU
and BMU fails.

28 BLTD Alarm Critical/A1 If the battery temperature is lower


than BLTD Temp. and the BLTD is
performed, this alarm is generated.

29 Battery Testing Mask/Null This alarm indicates that the batteries


are in the testing status.

30 Sys.OverLoad Alm. Major/Null If the load current of the DC power


system (including battery charging
current) exceeds the system
overload current threshold, this alarm
is generated.

31 multi-SMR Alm. Major/Null If two or more SMRs are faulty, this


alarm is generated.

A-3

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

32 FBMU Comm.Fail Major/Null This alarm indicates that the


communication between the CSU
and FBMU fails.

33 DG.Start Alm. Mask/Null This alarm indicates that the CSU


has started the DG.

34 DG.Abnormal Alm. Major/A2 This alarm indicates that the CSU


has started the DG, but the DG does
not provide power to the DC power
system.

35 PV SPD Abr. Major/Null If the PV SPD is damaged or not


installed, this alarm is generated.

36 24V DC SPD Abr. Major/Null If the 24V DC SPD is damaged or not


installed, this alarm is generated.

37 PV.Comp.Missing Major/Null If the PV components are faulty or


not installed, this alarm is generated.

38 Sys. Expansion Major/Null If the system expansion is faulty, this


Alm. alarm is generated.

A.2 AC Alarms
For a description of the AC alarms, refer to Table A-2.

Table A-2 AC Alarm Description

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

1 AC Power Off Mask/Null If there is no AC input, this alarm is


generated.

2 AC Volt.High Major/Null If the AC input phase voltage is higher


than AC Volt.H.Thre., this alarm is
generated.

3 AC Volt.Low Major/Null If the AC input phase voltage is lower


than AC Volt.L.Thre., this alarm is
generated.

4 AC Phase Lack Major/Null If one phase or two phases are


missing for AC input, this alarm is
generated.

A-4

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

5 AC Curr.High Major/Null If the AC input phase current is higher


than the AC current high threshold,
this alarm is generated.

6 AC Volt.Imbala. Major/Null If the difference between AC input


phase voltages is greater than phase
voltage imbalance value, this alarm
is generated.

7 AC Out.SW Off Major/Null If the AC output circuit breaker is


broken, this alarm is generated.

8 AC In.Switch Off Major/Null If the AC input main circuit breaker is


broken, this alarm is generated.

9 AC SPD Abr. Major/Null If the AC surge protection device


(SPD) is damaged or not installed,
this alarm is generated.

10 DG.Out.UVP Major/Null If the DG output voltage is lower


than the low threshold of output AC
voltage, this alarm is generated.

11 DG.Out.OVP Major/Null If the DG output voltage is higher


than the high threshold of output AC
voltage, this alarm is generated.

12 DG.Over Curr. Major/Null If the DG output current is higher than


the output over current threshold, this
alarm is generated.

13 DG.Over Load Major/Null If the DG output power is higher than


the set power, this alarm is generated.

14 DG.Und.Freq. Major/Null If the DG output frequency is lower


than the low DG. frequency threshold,
this alarm is generated.

15 DG.Over Freq. Major/Null If the DG output frequency is


higher than the high DG. frequency
threshold, this alarm is generated.

16 DG.Und.Speed Major/Null If the DG speed is lower than the lower


threshold, this alarm is generated.

17 DG.Over Speed Major/Null If the DG speed is higher than


the upper threshold, this alarm is
generated.

A-5

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

18 DG.Low Oil Pres. Major/A2 If the DG oil pressure is lower than


the lower threshold, this alarm is
generated.

19 DG.Coolant OTP Major/Null If the DG water temperature is higher


than the upper threshold, this alarm
is generated.

20 DG.Oil OTP Major/Null If the DG oil temperature is higher


than the upper threshold, this alarm is
generated, this alarm is generated.

21 DG.Bat.UVP Major/Null If the DG battery voltage is lower


than the lower threshold, this alarm
is generated.

22 DG.Bat.OVP Major/Null If the DG battery voltage is higher


than the upper threshold, this alarm
is generated.

23 DG.Charge.Fail. Major/Null If the output of the AC charger is not


detected by the GCP, this alarm is
generated.

24 DG.Engine OTP Major/Null If the DG temperature is higher than


the upper threshold, this alarm is
generated.

25 DG.Engine UTP Major/Null Reserved. No alarm is available in


current version.

26 DG.Start Fail. Major/A2 If the DG failed to be started


through remote control, this alarm is
generated.

27 DG.Stop Fail. Major/A2 If the DG failed to be switched off


through remote control, this alarm is
generated.

28 DG.High Fl Lev. Major/Null If the oil level is higher than the upper
threshold set in the CSU, this alarm
is generated.

29 DG.Fail Load Major/A2 If the GCP sends DG output switch-on


signals, but the DG output switch
fails to be switched on, this alarm is
generated.

A-6

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

30 DG.Fail to Open Major/A2 If the GCP sends DG output switch-off


signals, but the DG output switch
fails to be switched off, this alarm is
generated.

31 Mns.GCB Fail Load Major/A2 If the GCP sends mains supply


output switch-on signals, but the
mains supply output switch fails to be
switched on, this alarm is generated.

32 Mns.GCB Fail Open Major/A2 If the GCP sends mains supply


output switch-off signals, but the
mains supply output switch fails to be
switched off, this alarm is generated.

33 Mns.High Freq. Major/Null If the mains output frequency is higher


than the upper threshold, this alarm
is generated.

34 Mns.Volt.Imba. Major/Null The difference between the


mains phase voltage and rated
phase voltage is greater than the
Mns.Volt.Imba. threshold, this alarm
is generated.

35 Mns.Ph.Seq.Err. Major/Null If the sequence of mains phases is


incorrect, this alarm is generated.

36 MLLS Comm.Fail Major/Null If the communication between the


CSU and the liquid level sensor fails,
this alarm is generated.

37 GCP Comm.Fail Major/Null If the communication between the


CSU and the GCP fails, this alarm is
generated.

38 DG.Fuel Leakage Major/Null If the fuel declining speed exceeds


the threshold, this alarm is generated.

39 ATS Comm.Fail Major/Null If the communication between the


CSU and the ATS control panel fails,
this alarm is generated.

40 ACEM Comm.Fail Major/Null If the communication between the


CSU and the electricity meter fails,
this alarm is generated.

A-7

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Level/Default Alarm Generation Conditions


Output Relay

41 GMU Comm.Fail Major/Null If the communication between the


CSU and the GMU fails, this alarm is
generated.

42 Mns.Failure Mask/Null If a mains failure occurs, this alarm is


generated.

43 Mns.Pha.Volt.High Major/Null If the mains voltage is higher than


the upper over-voltage threshold, this
alarm is generated.

44 Mns.Pha.Volt.Low Major/Null If the mains voltage is lower than the


lower under-voltage threshold, this
alarm is generated.

45 Mns.Pha.Curr.High Major/Null If the mains phase current is higher


than the upper Mns.Pha.Curr.High
threshold, this alarm is generated.

46 DG.Ph.Seq.Err. Major/Null If the phase sequence is incorrect,


this alarm is generated.

47 DG Maint.Not. Warning/Null If an interval between two


maintenances is greater than
the maintenance period, this alarm is
generated.

48 DG.Common Alm. Major/Null If an alarm occurs on the DG, this


alarm is generated.

49 DG.Low Fl.Lev. Major/Null If the oil level is lower than the


DG.Low Fl.Lev. threshold, this alarm
is generated.

50 DG Volt.Imbala. Major/Null If the ratio of the DG phase voltage


difference to the rated phase voltage
is greater than the DG.Volt.Imba.
threshold, this alarm is generated.

51 Mns.Low Freq. Major/Null If the mains frequency is lower than


the Mns.Low Freq. threshold, this
alarm is generated.

52 ATS Fault Major/Null If the ATS is faulty, this alarm is


generated.

A-8

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

A.3 SMR Alarms


For a description of the SMR alarms, refer to Table A-3.

Table A-3 SMR Alarm Description

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

1 SMR Fan Major/Null If the SMR fan is faulty, this alarm is generated.
Fault

2 SMR Major/Null If the temperature of the PFC heat radiator is higher


Ra.T.H.O. than the maximum radiator temperature, this alarm is
generated.

3 SMR Major/Null If the AC input voltage of the SMR is higher than the
In.V.H.O. maximum input voltage, this alarm is generated.

4 SMR Major/Null If the AC input voltage of the SMR is lower than the
In.V.L.O. minimum input voltage, this alarm is generated.

5 SMR Major/Null If the output voltage of the SMR is higher than the
Out.V.H.O. maximum output voltage, this alarm is generated.

6 SMR Major/Null If the output current of the SMR is higher than the
Out.C.H. maximum output current, this alarm is generated.

7 SMR Major/Null If the SMR PFC is faulty, this alarm is generated.


PFC.Fault

8 SMR Major/Null If the temperature of the SMR inlets is higher than


Inter.T.H. SMR Inter temperature high threshold, this alarm is
generated.

9 SMR Major/Null If the output fuse of the SMR breaks, this alarm is
Out.Fuse generated.

10 SMR Major/Null If the current difference is greater than the SMR current
Curr.Share share protection value, this alarm is generated.

11 SMR Input Major/Null If the power input of the SMR is interrupted, this alarm
Off is generated.

12 PFC Major/Null If the output voltage of PFC is higher than the threshold,
Out.V.H. this alarm is generated.

13 PFC Out.V.L. Major/Null If the output voltage of PFC is lower than the threshold,
this alarm is generated.

14 SMR Major/Null If errors occur when the SMR reads and writes the
EEPROM EEPROM, this alarm is generated.

15 SMR Major/Null If some error occurs to the communication of the Serial


In.Comm F. Communication Interface (SCI), this alarm is generated.

A-9

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

16 SMR Major/Null If the primary current of the transformer is higher than


Primy.C.H. the threshold, this alarm is generated.

17 PFC Input Major/Null Reserved alarm


C.H.

18 SMR Start Major/Null If the starting time of the SMR exceeds 5 minutes, this
Abr. alarm is generated.

19 SMR In.Fuse Major/Null If the input fuse of the SMR breaks, this alarm is
generated.

20 SMR Major/Null If the communication between the SMR and the


Comm.Fail CSU is interrupted because the SMR is removed or
there is some communication exception, this alarm is
generated.

21 SMR In.Freq. Major/Null If the input frequency of the SMR is too high or too low,
this alarm is generated.

22 SMR Major/Null If the output voltage of the SMR is lower than the
Out.V.L. threshold, this alarm is generated.

23 SMR Major/Null If the output power of the SMR exceeds the threshold,
Out.O.P. this alarm is generated.

24 SMR SN Major/Null If two or more than two SMR sequence numbers are
Clash the same, this alarm is generated.

25 SMR Pro.Err. Major/Null If the CSU does not support the CAN communication
protocol of the SMR, this alarm is generated.

26 SMR No Major/Null If the SMR that supports mix-use and the SMR that
Match does not support mix-use are used together in the
system, this alarm is generated.

27 SMR Major/Null If the temperature of the SMR inlet exceeds the


Ext.O.T. threshold, this alarm is generated.

28 Start. R.T.H. Major/Null .If the soft-starting resistor temperature is too high, this
alarm is generated.

A.4 DC Alarms
For a description of the DC alarms, refer to Table A-4.

A-10

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

Table A-4 DC Alarm Description

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

1 DC Volt.High Major/Null If the DC output voltage is higher than the DC voltage


high threshold, this alarm is generated.

2 DC Volt.Low Major/Null If the DC output voltage is lower than the DC voltage low
threshold, this alarm is generated.

3 DC SPD Abr. Major/Null If the DC SPD is faulty, this alarm is generated.

4 Batt.Volt.Low Major/Null If the voltage of a battery pack is lower than the battery
voltage low threshold, this alarm is generated.

5 Batt.Curr.Abr. Minor/Null If the rate of the detected battery current to the highest
detectable current is greater than the abnormal battery
current rate, this alarm is generated.

6 Batt.Temp.High Major/Null If the battery temperature is higher than the battery


temperature high threshold, this alarm is generated.

7 Batt.Temp.Low Major/Null If the battery temperature is lower than the battery


temperature low threshold, this alarm is generated.

8 Batt.Loop Brk. Critical/A1 If the battery loop is disconnected, this alarm is


generated.

9 Batt.Dischg. Mask/Null If the battery discharging current is higher than battery


discharging threshold, this alarm is generated.

10 Batt.T.Invalid Warning/Null If the system is configured with batteries, but the battery
temperature detection fails, or the battery temperature
sensor is not installed or the battery temperature is out of
the detection range, this alarm is generated.

11 LLVD1 Extend Major/A3 If the circuit breaker or fuse of the extended LLVD1 loop
Brk. breaks, this alarm is generated.

12 LLVD1 Loop Major/A3 If the circuit breaker or fuse of the LLVD1 loop breaks,
Brk. this alarm is generated.

13 LLVD2 Extend Major/A3 If the circuit breaker or fuse of the extended LLVD2 loop
Brk. breaks, this alarm is generated.

14 BLVD Extend Major/A3 If the fuse of the extended BLVD loop breaks, this alarm
Brk. is generated.

15 BLVD Loop Brk. Major/A3 If the fuse of the BLVD loop breaks, this alarm is
generated.

16 Cell Reverse Major/Null If a 2 V battery cell is reversely connected, this alarm


is generated.

A-11

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

17 Block Reverse Major/Null If a 12 V battery block is reversely connected, this alarm


is generated.

18 Cell Poor Major/Null If the difference between a 2 V battery cell voltage and
the average battery voltage is greater than Battery Cell
Voltage Differ Valve, this alarm is generated.

19 Block Poor Major/Null If the difference between a 12 V battery block voltage


and the average battery voltage is greater than Battery
Block Voltage Differ Valve, this alarm is generated.

20 DC.Loop.Brk. Critical/A3 If the load loop is broken, this alarm is generated.

21 Load Ext.Brk. Major/A3 If the extended load loop is broken, this alarm is
generated.

22 Batt.COCA_Li Critical/Null If the battery charging current exceeds the battery charge
over current alarm_Li value, this alarm is generated.

23 Batt.DOCA_Li Critical/Null If the battery discharging current exceeds the battery


discharge over current alarm_Li value, this alarm is
generated.

24 Cell DOTA_Li Critical/Null During battery discharging, if the battery cell temperature
is higher than the Cell Discharge Over Temperature
Protection_Li value, this alarm is generated.

25 Cell DUTA_Li Critical/Null During battery discharging, if the battery cell temperature
is lower than the Cell Discharge Under Temperature
Alarm_Li value, this alarm is generated.

26 Cell OVA_Li Critical/Null If the battery cell voltage is higher than the Cell Over
Voltage Alarm_Li value, this alarm is generated.

27 Cell UVA_Li Critical/Null If the battery cell voltage is lower than the Cell Under
Voltage Alarm_Li value, this alarm is generated.

28 Cell Poor_Li Critical/Null If the difference between the voltage of a single cell and
average cell voltage exceeds the Cell Poor_Li value, this
alarm is generated.

29 Batt.UVP_Li Critical/A1 If the battery pack voltage is lower than the Battery
Under Voltage Protection Threshold_Li value, this alarm
is generated.

30 Batt.DOCP_Li Critical/A1 If the battery discharging current exceeds the Battery


Discharge Over Current Protection_Li value and
the FBMU disconnects the discharging loop of the
corresponding battery pack, this alarm is generated.

A-12

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

31 Batt.COCP_Li Critical/A1 If the battery charging current exceeds the Battery


Charge Over Current Protection_Li value and the FBMU
disconcerts the charging loop of the corresponding
battery pack, this alarm is generated.

32 Cell DOTP_Li Critical/A1 During battery discharging, if the battery cell temperature
is higher than the Cell Discharge Over Temperature
Protection_Li value, this alarm is generated.

33 Cell DUTP_Li Critical/A1 During battery discharging, if the battery cell temperature
is lower than the Cell Discharge Under Temperature
Protection_Li value, this alarm is generated.

34 Cell OVP_Li Critical/A1 If the temperature of single battery cell is higher than
the Cell Over Voltage Protection_Li value, this alarm is
generated.

35 Cell UVP_Li Critical/A1 If the voltage of single battery cell is lower than the
Cell Under Voltage Protection_Li value, this alarm is
generated.

36 Cell TI_Li Critical/Null If the detected cell temperature exceeds the detection
range of the temperature sensor, this alarm is generated.

37 Batt.OVP_Li Critical/A1 If the voltage of a battery pack is higher than the


Battery Over Voltage Protection_Li value, this alarm is
generated.

38 Cell COTA_Li Critical/Null During battery charging, if the cell temperature is higher
than the Cell Charge Over Temperature Alarm_Li value,
this alarm is generated.

39 Cell CUTA_Li Critical/Null During battery charging, if the cell temperature is lower
than the Cell Charge Under Temperature Alarm_Li value,
this alarm is generated.

40 Cell COTP_Li Critical/A1 During battery charging, the cell temperature is higher
than the Cell COTP_Li value and the FBMU disconnects
the charging loop of the corresponding battery pack, this
alarm is generated.

41 Cell CUTP_Li Critical/A1 During battery charging, if the cell temperature is lower
than the Cell Charge Under Temperature Protection_Li
value and the FBMU disconnects the charging loop of
corresponding battery pack, this alarm is generated.

A-13

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

42 Chg.Over T._Li Critical/A1 If the battery charging duration exceeds the Battery
Charge Over Time Protecion_Li value and the FBMU
disconnets the charging loop of corresponding battery
pack, this alarm is generated.

43 Chg.Sw.Inv_Li Critical/Null This alarm is not available in current version.

44 Dch.Sw.Inv_Li Critical/Null This alarm is not available in current version.

45 Batt. CI_Li Critical/Null If the detected battery pack current exceeds the FBMU
current detection range, this alarm is generated.

46 Batt. VI_Li Critical/Null If the detected cell voltage exceeds the FBMU cell
voltage detection range, this alarm is generated.

47 Batt.UVA_Li Major/Null If the battery pack voltage is lower than the Battery
Under Voltage Alarm_Li value, this alarm is generated.

48 Batt.Low- Critical/Null If the battery pack SOC is lower than the Battery Low
SOC_Li SOC Alarm_Li value, this alarm is generated.

49 ZXD2430 Major/Null If the ZXD2430 is faulty, this alarm is generated.


Alarm

50 Inverter Alarm Major/Null If the inverter is faulty, this alarm is generated.

51 24V Load Brk. Major/A3 If 24V load loop is broken, this alarm is generated.

A.5 Environment Alarms


For a description of the environment alarms, refer to Table A-5.

Table A-5 Environment Alarm Description

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

1 Env.Temp. High Minor/A4 If the environment temperature is higher than


Env.Temp.H.Thre., this alarm is generated.

2 Env.Temp. Low Minor/A4 If the environment temperature is lower than


Env.Temp.L.Thre., this alarm is generated.

3 Env.Hum. High Minor/Null If the environment humidity is higher than


Env.Hum.H.Thre., this alarm is generated.

4 Env.Hum. Low Minor/Null If the environment humidity is lower than


Env.Hum.L.Thre., this alarm is generated.

A-14

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix A Alarm List

No. Alarm Name Default Alarm Generation Conditions


Level/Default
Output Relay

5 Door Alarm Major/Null If the status of the door sensor is abnormal, this
alarm is generated.

6 Access Control Mask/Null If the status of the door access control is abnormal,
this alarm is generated.

7 Smog Alarm Major/Null If the sensor detects smog, this alarm is generated.

8 Flood Alarm Major/Null If the sensor detects flood, this alarm is generated,
this alarm is generated.

9 Glass Brk.Alm. Minor/Null If the sensor detects broken glasses, this alarm is
generated.

10 Env.Temp.In- Mask/Null If the environment temperature sensor is damaged


valid or not installed, this alarm is generated.

11 Env.Hum.Invalid Mask/Null If the environment humidity sensor is damaged or


not installed, this alarm is generated.

12 T.Ctrl Unit Alm Minor/Null If the status of the temperature control unit is
abnormal, this alarm is generated.

13 Env.OTA_Li Minor/Null If lithium iron phosphate batteries are configured,


and the environment temperature is higher than
Env.OTA_Li., this alarm is generated.

14 Env.UTA_Li Minor/Null If lithium iron phosphate batteries are configured,


and the environment temperature is lower than
Env.UTA_Li., this alarm is generated.

A-15

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

This page intentionally left blank.

A-16

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


Appendix B
Electrical Connection
Diagram
For the electrical connection diagram of the ZXDU68 B201 system, see Figure B-1.

B-1

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description
Figure B-1 Electrical Connection Diagram of the ZXDU68 B201System B-2
SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential
Appendix B Electrical Connection Diagram

For the electrical connection diagram of the FBMU, seeFigure B-2 .

B-3

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description
Figure B-2 flectrical connection diagram of the FBMU B-4
SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential
Glossary
AC
- Alternating Current
-
ACB
- Air-conditioning Control Board
-
BHTD
- Battery High Temperature Disconnect
-
BLVD
- Battery Low Voltage Disconnect
-
CAN
- Controller Area Network
-

CSU
- Centralized Supervision Unit
-
DC
- Direct Current
-
EMI
- Electromagnetic Interference
-

FBMU
- FeLi Battery Management Unit
-
FTP
- File Transfer Protocol
-
HTTP
- Hypertext Transfer Protocol
-
IE
- Internet Explorer
-

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential


ZXDU68 B201 Product Description

LCD
- Liquid Crystal Display
-
LLTD
- Load Low Temperature Disconnect
-
LLVD
- Load Low Voltage Disconnect
-
MTBF
- Mean Time Between Failures
-
SC
- Supervision Center
-
SIU
- Signal Interface Unit
-
SNMP
- Simple Network Management Protocol
-

SPD
- Surge Protection Device
-
THD
- Total Harmonic Distortion
-
USB
- Universal Serial Bus
-

II

SJ-20150914145904-001|2015-09-14 (R1.0) ZTE Proprietary and Confidential