PROJECT :
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
CLIENT :
CLIENT'S CONSULTANT:
CONTRACTOR:
Inabensa
P.O. Box - 148, P.C - 102, Al Khuwair, Muscat,
Sultanate of Oman
Tel: +968 24403750, Fax: +968 24692308
This document issued for the party which commissioned it and for specific purposes connected with captioned project
Document No.: SHEETS REVISION
only. It should not be relied upon by any other party and used for any other purpose. We accept no responsibility for the
consequences of this document being relied upon by any other party, or being used for any other purpose, or containing COM/102/2015/OHL/10005. 23 0
any error or omission in data supplied to us by other parties.
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 2
Page No. Rev. No. Date Page No. Rev. No. Date Page No. Rev. No. Date
1 0 04.05.2017
2 0 04.05.2017
3 0 04.05.2017
4 0 04.05.2017
5 0 04.05.2017
6 0 04.05.2017
7 0 04.05.2017
8 0 04.05.2017
9 0 04.05.2017
10 0 04.05.2017
11 0 04.05.2017
12 0 04.05.2017
13 0 04.05.2017
14 0 04.05.2017
15 0 04.05.2017
16 0 04.05.2017
17 0 04.05.2017
18 0 04.05.2017
19 0 04.05.2017
20 0 04.05.2017
21 0 04.05.2017
22 0 04.05.2017
23 0 04.05.2017
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 3
INDEX
1 DESIGN PARAMETERS 4 -5
FOUNDATION REACTION
5 14-15
8 References 21-23
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 4
1-DESIGN PARAMETERS
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 5
REFRERNCE DOCUMENT: 132/33kvV SAMAD GRID STATION ESTIMATION OF LOADS ON GANTRY AND SUPPORTS FOR OUTDOOR
EQUIPMENTS DOC.NO :SMD/102/2015/1010,REV B
Equipment
Support Structure
S1 (SA)
Height
2500
mm
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 6
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 7
1.0 MATERIAL
1.2 Bolts
b) Single Shear strength through Body for M16 =496 x area of bolt=496x201 =99.696 =100 KN.
1.3 Galvanizing ,
i) Galvanizing shall be as per BS 729, Zinc coating 915 gm/m (127 m)
2.1 Limiting value for effective slenderness ration KL/r for compression member shall be as following:
Refer to Tender Document ATLAS INTERNATIONAL ENGINEERING CONSULTANTS
Volume 3-Technical SPEC. for Overhead Transmission Line clause 7.2.10
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page :8
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 9
CASE
DESCRIPTION F.O.S
NO.
SUPPORT STRUCTURE
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 10
1133
286
464
Transverse Wind on Tower = 3000N/m
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page :11
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR "S1 SUPPORT STRUCTURE" DATE : 04.05.17
DOCUMENT NO. COM/102/2015/OHL/10005 REV.0 PAGE : 12
Compression portion:
Group Group Angle Angle Steel Max Usage Max Comp. Comp Comp. L/R Comp. Comp. Length Curve No.
Label Desc. Type Size Strength Usage Control Use Control Force Control Capacity Connect. Connect. Comp. No. Of
In Member Load Shear Bearing RLX RLY RLZ L/R KL/R Member Bolts
Comp. Case Capacity Capacity Comp.
(MPa) % % (kN (kN) (kN) (kN) (m)
M1 main leg SAE 75*75*6 355 0.76 Comp 0.76 2P -2.134 2. SC_T 288.664 792 282.24 2 2 1 39.65 39.65 0.452 1 4
M2 main leg SAE 75*75*6 355 0.98 Comp 0.98 3P -2.762 2. SC_T 288.664 792 282.24 2 2 1 39.65 39.65 0.452 1 4
M3 main leg SAE 75*75*6 355 1.69 Comp 1.69 4P -4.781 1. N_T 288.664 792 282.24 2 2 1 39.65 39.65 0.452 1 4
M4 main leg SAE 75*75*6 355 1.91 Comp 1.91 5P -5.38 1. N_T 288.664 792 282.24 2 2 1 39.65 39.65 0.452 1 4
M5 main leg SAE 75*75*6 355 3.33 Tens 3.25 6P -9.171 1. N_T 288.664 792 282.24 2 2 1 39.65 39.65 0.452 1 4
M6 main leg SAE 75*75*6 355 3.5 Tens 3.44 7P -9.663 1. N_T 280.997 792 282.24 7 7 1 46.05 46.05 0.15 1 4
FBR1 Front Brac SAE 45*45*5 275 1.81 Comp 1.81 9R -0.891 2. SC_T 84.002 99 49.2 1 1 1 62.36 91.18 0.542 3 1
FBR2 Front Brac SAE 45*45*5 275 2.47 Comp 2.47 10P -1.215 1. N_T 84.002 99 49.2 1 1 1 62.36 91.18 0.542 3 1
FBR3 Front Brac SAE 45*45*5 275 3.53 Comp 3.53 11R -1.737 1. N_T 84.002 99 49.2 1 1 1 62.36 91.18 0.542 3 1
FBR4 Front Brac SAE 45*45*5 275 4.78 Comp 4.78 12P -2.352 1. N_T 84.002 99 49.2 1 1 1 62.36 91.18 0.542 3 1
FBR5 Front Brac SAE 45*45*5 275 4.95 Comp 4.95 13R -2.434 1. N_T 84.002 99 49.2 1 1 1 62.36 91.18 0.542 3 1
HT0 Horz frm Tr SAE 75*75*6 275 6 Climb 0.43 14P -0.253 2. SC_T 199.309 99 59.04 1 1 1 20.41 70.2 0.3 3 1
IN Internal SAE 45*45*5 275 0 0 16P -0.018 1. N_T 108.644 99 49.2 0.5 0.5 0.5 24.38 48.29 0.424 2 1
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR "S1 SUPPORT STRUCTURE" DATE :04.05.17
DOCUMENT NO. COM/102/2015/OHL/10005 REV.0 PAGE : 13
Tension portion:
Group Group Angle Angle Steel Max Usage Max Tension Tension Tension Net Tension Tension
Label Desc. Type Size Strength Usage Control Use Control Force Control Section Connect. Connect.
Length Tension
In Member Load Capacity Shear Bearing No. of Bolts Tens. No. of Holes Hole Diameter
member
TENS. Case Capacity Capacity
(MPa) % % (kN (kN) (kN) (kN)
M1 main leg SAE 75*75*6 355 0.76 Comp 0.65 2XY 1.536 2. SC_T 236.075 792 282.24 0.452 4 2 1.75
M2 main leg SAE 75*75*6 355 0.98 Comp 0.86 3XY 2.035 2. SC_T 236.075 792 282.24 0.452 4 2 1.75
M3 main leg SAE 75*75*6 355 1.69 Comp 1.61 4XY 3.803 1. N_T 236.075 792 282.24 0.452 4 2 1.75
M4 main leg SAE 75*75*6 355 1.91 Comp 1.82 5XY 4.306 1. N_T 236.075 792 282.24 0.452 4 2 1.75
M5 main leg SAE 75*75*6 355 3.33 Tens 3.33 6XY 7.857 1. N_T 236.075 792 282.24 0.452 4 2 1.75
M6 main leg SAE 75*75*6 355 3.5 Tens 3.5 7XY 8.251 1. N_T 236.075 792 282.24 0.15 4 2 1.75
FBR1 Front Brac SAE 45*45*5 275 1.81 Comp 1.48 9P 0.73 2. SC_T 84.769 99 49.2 0.542 1 1 1.75
FBR2 Front Brac SAE 45*45*5 275 2.47 Comp 1.5 10R 0.737 1. N_T 84.769 99 49.2 0.542 1 1 1.75
FBR3 Front Brac SAE 45*45*5 275 3.53 Comp 2.4 11P 1.179 1. N_T 84.769 99 49.2 0.542 1 1 1.75
FBR4 Front Brac SAE 45*45*5 275 4.78 Comp 3.78 12R 1.859 1. N_T 84.769 99 49.2 0.542 1 1 1.75
FBR5 Front Brac SAE 45*45*5 275 4.95 Comp 4.25 13P 2.092 1. N_T 84.769 99 49.2 0.542 1 1 1.75
HT0 Horz frm Tr SAE 75*75*6 275 6 Climb 0.34 14YR 0.201 1. N_T 190.575 99 59.04 0.3 1 1 1.75
IN Internal SAE 45*45*5 275 0 0 16P 0 84.769 99 49.2 0.424 1 1 1.75
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page :14
5 - FOUNDATION REACTIONS
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 15
Max. Joint Support Reaction (KN) OF SA SUPPORT STRUCTURE SURGE ARRESTER (S1)
Case Force
Compression 1-N.T 10
Uplift 1-N.T 9
Max. Joint Support Reaction Per Base (KN) OF SA SUPPORT STRUCTURE SURGE ARRESTER (S1)
Case Force
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page :16
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 17
8. Design of Base Plate & Anchor Bolts for Surge Arrester Support Structure For (S1)
Stringing Action
Max. Compression Force =C (KN) 10
Material Properties
For Determination of Anchor Bolts size, Refer to ASCE STANDARD ANSI/ASCE 10-97 Design of Latticed Steel Transmission Structures page 22 clause 7.4.2
S.F. = 1
AS = ( 40 + 17.1 ) / 1
AS = 57.11
= PI/4 * (d - 0.974/n) 2
For Smooth Bar Anchor Bolts Refer to ASCE STANDARD ANSI/ASCE 10-97 Design of Latticed Steel Transmission Structures page 23 clause 7.5.2.1
S.F. = 1.5
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page :18
SECTION ( 1-1)
C/ 1 * e =
C/ 1 * 8 = 80 KN.mm
WL = U * 1000 / SS * L * 0.707
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page : 19
7 - Design Drawing
Page No. 20
CLIENT'S CONSULTANT:
CONTRACTOR:
Inabensa
P.O. Box - 148, P.C - 102, Al Khuwair, Muscat,
Sultanate of Oman
Tel: +968 24403750, Fax: +968 24692308
TOWER SUPPLIER :
MAXIMUM JOINT SUPPORT REACTION
(KN)
Document No.:
RES.MOMENT 2-SC.T 4 COM/102/2015/OHL/10005
0 Sheet 1 of 1
Oman Electrical Transmission Co.S.A.O.C
Construction of new 132/33kv Grid Substation at Samad and Sinaw
With Associated 132kv Overhead transmission Lines
DOCUMENT TITLE DETAILED DESIGN CALCULATION FOR SA Support Structures Surge Arrester (S1) 04.05.2017
DOCUMENT NO. COM/102/2015/OHL/10005. REV.0 Page :21
8 - References