Depending on exactly what is needed, there are several bits of information available:-

Outputs C & D status can be read from page 190 registers 6 & 7

1. Page 190 Unnamed output status

This is implemented for 72xx/73xx modules and indicates to the PC software what the
current status of each output from the module is (both digital outputs and LEDs).

Registers
Register Name Minimum Maximum Scaling Units Bits/ Read/write
offset value value factor sign
0 Digital output A status (Fuel) 0 1 16 Read only
1 Digital output B status (Crank) 0 1 16 Read only
2 Digital output E status 0 1 16 Read only
3 Digital output F status 0 1 16 Read only
4 Digital output G status 0 1 16 Read only
5 Digital output H status 0 1 16 Read only
6 Digital output D status (Gen) 0 1 16 Read only
7 Digital output C status (Mains) 0 1 16 Read only

The actual configuration for the outputs (polarity and the controlling signal) can be determined
from page 180

2. Page 180 Unnamed output sources & polarities

This is implemented for 72xx/73xx modules and indicates to the PC software what each
module output has been configured to use as its source and polarity (both digital outputs
and LEDs).
Registers
Register Name Minimum Maximum Scaling Units Bits/ Read/write
offset value value factor sign
0 Digital output A source (Fuel) 0 65535 16 Read only
1 Digital output A polarity (Fuel) 0 1 16 Read only
2 Digital output B source (Crank) 0 65535 16 Read only
3 Digital output B polarity 0 1 16 Read only
(Crank)
4 Digital output E source 0 65535 16 Read only
5 Digital output E polarity 0 1 16 Read only
6 Digital output F source 0 65535 16 Read only
7 Digital output F polarity 0 1 16 Read only
8 Digital output G source 0 65535 16 Read only
9 Digital output G polarity 0 1 16 Read only
10 Digital output H source 0 65535 16 Read only
11 Digital output H polarity 0 1 16 Read only
12 Digital output D source 0 65535 16 Read only
(Generator)
13 Digital output D polarity 0 1 16 Read only
(Generator)
14 Digital output C source (Mains) 0 65535 16 Read only
15 Digital output C polarity 0 1 16 Read only
(Mains)

Regarding the digital inputs, their state is available from page 8 registers 129,130 & 131 with
input A corresponding to digital input 1 in the document but they are also available via page
160 & 170 (see below). For page 8, the customer should really be checking for a value of 2,3 or
4 to indicate an actual alarm condition.

3. Page 160 Unnamed input function

This is implemented for 72xx/73xx modules and indicates to the PC software what each
built-in digital input function is set as.

Registers
Register Name Minimum Maximum Scaling Units Bits/ Read/write
offset value value factor sign
0 Digital input A function 0 65535 16 Read only
1 Digital input B function 0 65535 16 Read only
2 Digital input C function 0 65535 16 Read only
3 Digital input D function 0 65535 16 Read only
4 Digital input E function 0 65535 16 Read only
5 Digital input F function 0 65535 16 Read only
6 Digital input G function 0 65535 16 Read only
7 Digital input H function 0 65535 16 Read only

4. Page 170 Unnamed input status


This is implemented for 72xx/73xx modules and indicates to the PC software what the
current status of each digital input to the module is (indicating both the actual input state
and the active/inactive indication from the module).

Registers
Register Name Minimum Maximum Scaling Units Bits/ Read/write
offset value value factor sign
0 Digital input A raw status 0 1 16 Read only
1 Digital input A processed status 0 1 16 Read only
2 Digital input B raw status 0 1 16 Read only
3 Digital input B processed status 0 1 16 Read only
4 Digital input C raw status 0 1 16 Read only
5 Digital input C processed status 0 1 16 Read only
6 Digital input D raw status 0 1 16 Read only
7 Digital input D processed status 0 1 16 Read only
8 Digital input E raw status 0 1 16 Read only
9 Digital input E processed status 0 1 16 Read only
10 Digital input F raw status 0 1 16 Read only
11 Digital input F processed status 0 1 16 Read only
12 Digital input G raw status 0 1 16 Read only
13 Digital input G processed status 0 1 16 Read only
14 Digital input H raw status 0 1 16 Read only
15 Digital input H processed status 0 1 16 Read only
16 Digital input I raw status 0 1 16 Read only
17 Digital input I processed status 0 1 16 Read only