You are on page 1of 2

PITOT TUBE TRAVERSE, RECTANGULAR DUCT

Job. Job No.. Date


Location. System
Location of Duct. i SP

Duct Size Required CFM Required FPM


Duct Area Sq Ft Actual CFM ActualFPM
Actual CFM
Percent of Design: Required CFM initial
Final
Readings

ml
B

DUCT
D

Column =
1
Total
Totals of a l l
Columns

DUCT WIDTH
TOTAL ] ,
Divide recommended spacing into duct v A L L COLUMNS'- (
width for equal spacing between points ~y
of readings and write i n each space. / Total No.\
Split remainder i n half for spacing a t \f points,
) Average FPM
sides of duct and write i n . CONVERTING VP INTO FPM
VP FPM VP FPM VP FPM VP FPM VP FPM
3. To determine the a c t u a l average FPM,
total the FPM i n each column, add the .01
.02
400
566
.31
.32
2230
2260
.61
.62
3127
3153
.91
.92
3821
3842
1.21
1.22
4405
4423
columns together and divide by total .03
.04
693
801
.33
.34
2301
2335
.63
.64
3179
3204
.93
.94
3863
3884
1.23 4442
number of points i n traverse. .05 895 .35 2369 .65 3229 .95 3904
1.24
1.25
4460
4478

.06 981 36 2403 .66 3254 96 3924 1.26 4495


.07 1060 .37 2436 67 3279 .97 3945 1.27 4513
.08 1133 .38 2469 58 3303 98 3%5 1.28 4531
RECOMMENDED EQUAL SPACING BETWEEN .09
.10
1201
1266
,39 2501
2533
,69 3327
3351
.99 3985 1.29 4549
.40 ,70 1.00 4005 1.30 4566
POINTS OF READING .11 1328 .41 2563 .71 3375 101 4025 1.31 4583
.12 1387 .42 2595 .72 3398 4045
Width Range Spacing .13
.14
1444
1498
.43
.44
2626 73
.74
3422 1.02
1.03
1.04
4064
1.32
1.33
4601
4619
2656 3445 4084 1.34 4636
of Duct Inches in inches .15 1551 .45 2687 .75 3468 1.05 4103 1.35 4653

8-14 5 .16
.17
1602
1651
.46
.47
2716
2746
.76
.77
3491
3514
1.06
1.07
4123
4142
1.36
1.37
4671
4688
lS-24 6 .18
.19
1699
1746
.48
.49
2775
2804
.78
.79
3537
3560
1.08
1.09
4162
4181
1.38
1.39
4705
4722
25-36 7 .20 1791 ,50 2832 .80 3582 1.10 4200 1.40 4739

37-48 8 .21
22
1835
1879
,51
,52
2860
2888
.81
,32
3604
3625
1.11
1.12
4219
4238
1.41 4756
1.42 4773
.23 1921 .53 2916 ,83 3657 1.13 4257
49-60 9 .24 1962 ,54 2943 .84 3669 1.14 4276
1-43
1.44
4790
4806
2003
61-72 10 .25 55 2970 .85 3690 1.15 4295 1.45 4823
.26 2042 ,56 2997 .86 3709 1.16 4314
73-64 11 .27 2081 ,57 3024 .87 3729 1.17 4332
1.46 4840
4856
1,47
85-96 12
.28
.29
2119
2157
,58
,59
30 5C
3076
38
.89
3758
3779
1.18
1.19
4350
4368 1 484889
4873
30 2193 60 3102 .90 3800 1.20 4386 1,49 4905
1-50
Wpnrifis E n a i n e e r i n q and C o n t r a c t i n g Services 7/80 Form TAB 2 0 3
OUTLET AIR BALANCE REPORT
Project, Job No. Date

System

Instniments Used JTested by:.

OPEMING REQUIRED PRELIMINARY FINAL


ROOM
AREA SERVED
No. Model Size \ Vel CFM Vel CFM