Job Name NPCIL Summer Conditions

Enthalpy
BTU/lb of
Project MAPS 1&2 CONDITIONS DB TEMP ⁰F RH % dry air
MCR AND CER 1&2
Space used for OUTSIDE 95 70 50
Area in Sq ft 11700 INSIDE 72 50 27
Height 16.4 DIFFERENCE 23
F/c ht. 16.4
Occupancy 20
air change cfm (design
manual) 1590
Ventillation cfm 2900

SOLAR & TRANS GAIN EXCEPT WALLS & ROOF Room Sensible Heat Room Latent heat
Area in sq sensible heat Latent
Orientation U factor ft Heat gain BTU/hr Area in sq ft heat
Wall (N) 0.37 785 23 6680.35 785 0
Wall (E) 0.37 4167 32 49337.28 4167 0
Wall (W) -Solar gain 0.37 4167 39 60129 4167 0
Wall (S) 0.37 785 23 6680.35 785 0
ROOF 0.17 11700 23 45747 11700 0
FLOOR 0.2 11700 23 53820 11700 0
INTERNAL HEAT Room Sensible Heat Room Latent heat
sensible heat Latent
Source Factor BTU/HR BTU/hr heat
People 20 persons 1.0 269 5380 249 4980
230 LEDs
Lighting load (12W) 1.0 41 9430 0 0
Appliances 32 PCs 1.0 1025 32800 0 0
4 pedestal
fans 1.0 615 4305
Electrical loads 38KVA 1.0 175284 0 0
48V DC 1.0 29582 0 0
Centrifugal fans 7.5HP 3nos 19100 57300 0 0
INFILTRATION & VENTILATION Room Sensible Heat Room Latent heat
sensible +
Enthalpy Latent
Dry air Btu/lbs of dry heat
Vent Cfm Tem. Diff Lbs/hr air BTU/hr
2900 23 Outside 12177 50 608873
room 13903 27 375396 233477
SUB TOTAL 774932
SAFETY FACTORS 12.5% 96867
EFFECTIVE ROOM
HEAT 871800 72.65 TR
SELECTED APPARATUS DEW POINT
61F