You are on page 1of 12

Voltage Relay

MU350
Product Description
MU350 is 3-phase voltage relay that combines
various protections and starting delay.

Features
• Undervoltage
• Overvoltage
• Delay-on
• 2 voltage-free output contacts
• Voltage and frequency display
• 3-Phase
• Unbalance
• Phase loss
• Phase sequence
• With or without neutral connection
• Phase to phase or phase to neutral monitoring
• Programmable relay outputs
• ANSI Code : 27, 47, 59, 60

Technical Data
SETTING RANGES OUTPUT CONTACTS ENVIRONMENTAL CONDITIONS
Undervoltage : Off, 1% to 25% Rated voltage : 250 V AC Temperature : -5˚C to +55˚C
Time delay for undervoltage : 0.1s to 30s Contact rating : 5 A Humidity : 56 days at 93% RH and
Overvoltage : Off, 1% to 20% Expected electrical life : 100,000 operations at 40˚C non-condensing
Time delay for overvoltage : 0.1s to 30s rated current
Start time delay : 0s to 999s Expected mechanical life : 5 x 106 operations MECHANICAL
Unbalance : Off, 3% to 20% Mounting : Panel mounting
Time delay for unbalance : 0.5s to 30s Dimension (mm) : 96(w) x 96(h) x 90(d)
Phase loss : Fixed time <0.5s INDICATORS Approximate weight : 0.31 kg
Phase sequence : Fixed time <0.5s Auxiliary supply : Green indicator
Pickup indicator : Red indicator
Trip : 7-segment display and
AUXILIARY SUPPLY red LED indicators
MU350-415V : 380 V (-25%) to 415 V (+20%) AC
Supply frequency : 45 Hz to 65 Hz ACCURACY
Maximum power consumption: 3VA Protection thresholds : ± 3%
Time delay : 0 to 0.5s, ± 15% with
MU 350

minimum 40ms
MEASURING INPUT : 0.6s and above, < ± 3%
Line to line : 100 to 415 (+20%) VAC Measurements : ± 3%
Line to Neutral : 58 to 240 (+20%) VAC
Voltage Relay

Typical Application Diagrams Case Dimensions


96 mm
L-L 100-415V AC, L-N 58-240V AC
L1
L2

96 mm
L3
N Front
(OPTIONAL)
L1 L2 L3 N

R1 R2
90 mm
AUX 70 mm

NC NO COM NC NO COM
380-415V AC

Side

91.0 ± 0.5 mm

Ordering Information

91.0 ± 0.5 mm
Panel Cutout
MODEL DESCRIPTION
MU350-415V 3-Phase, auxiliary voltage 380 ~ 415 V AC, 45-65 Hz
MU 350
Voltage Relay
MU250
MU150
Product Description
MU150 and MU250 are voltage relays that
combine various protections and starting delay.
MU 150 MU150 is used for single-phase monitoring while
MU250 is used for 3-phase monitoring.

Features
• Microprocessor based numerical relay
• Undervoltage
• Overvoltage
• Delay-on
• 2 voltage-free output contacts
• Voltage and frequency display
• ANSI Code : 27, 47, 59, 60

MU 250 Features For MU 250 only


• 3-Phase
• Unbalance
• Phase loss
• Phase sequence
• With or without neutral connection
• Phase to phase or phase to neutral monitoring

Technical Data
SETTING RANGES POWER SUPPLY INPUT INDICATORS
Undervoltage : 1% to 25% Input voltage: Auxiliary supply : Green indicator
Time delay for undervoltage : 0.1s to 30s MU150-110V & MU250-110V Pickup indicator : Red indicator
Overvoltage : 1% to 20% : 100 V (-25%) to 120 V (+20%) AC Trip : 7-segment display and red
Time delay for overvoltage : 0.1s to 30s MU150-240V & MU250-220V LED indicators
Start time delay : 0s to 999s : 220 V (-25%) to 240 V (+20%) AC
MU250-415V ACCURACY
: 380 V (-25%) to 415 V (+20%) Protection thresholds : ± 3%
For MU250 only: Supply frequency : 45 Hz to 65 Hz Time delay : 0 to 0.5s, ± 15% with
Unbalance : 3% to 20% minimum 40ms
Time delay for unbalance : 0.1s to 30s : 0.6s and above, < ± 3%
Phase loss : Fixed time <0.1s Maximum power consumption: Measurements : ± 3%
MU 250 / 150

Phase sequence : Fixed time <0.1s MU250 : 3VA


MU150 : 2.5VA
ENVIRONMENTAL CONDITIONS
Temperature : -5˚C to +55˚C
OUTPUT CONTACTS Humidity : 56 days at 93% RH and
Rated voltage : 250 V AC 40˚C non-condensing
Contact rating : 5 A
Expected electrical life : 100,000 operations at MECHANICAL
rated current Mounting : DIN rail
Expected mechanical life : 5 x 106 operations Dimension (mm) : 71(w) x 85(h) x 70(d)
Approximate weight : 0.4 kg
Voltage Relay

Typical Application Diagrams


MU250 MU150
L1 L
L2 N
L3
N
(OPTIONAL)
1 2 3 4 5 6 7

1 2 3 4 5 6 7 R1 R2

R1 R2
8 9 10 11 12 13 14
COM NO NC COM NO NC MU150
8 9 10 11 12 13 14
COM NO NC COM NO NC MU250

(Neutral connection is optional)

Case Dimensions Ordering Information


71 mm
MODEL DESCRIPTION
MU150-110V Single-Phase, 220/230/240 V AC,
20 mm
45-65 Hz power supply
45 mm

Front MU150-240V Single-Phase, 220/230/240 V AC,


45-65 Hz power supply

20 mm
MU250-110V 3-phase, 100/110/120 V AC
45-65 Hz power supply

MU250-220V 3-phase, 220/230/240 V AC


70 mm 45-65 Hz power supply

MU250-415V 3-Phase, 380/400/415 V AC,


45-65 Hz power supply
85 mm

Side

30 mm 20 mm 20 mm
MU 250 / 150
Voltage Relay
MU2300
Features
• Multifunction numerical voltage protection relay
• Low-set undervoltage stage (U<) with definite-
time or inverse-time characteristic
• High-set undervoltage stage (U<<) with definite-
time
• Low-set overvoltage stage (U>) with definite-time
or inverse-time characteristic
• High-set overvoltage stage (U>>) with definite-
time
• Negative sequence overvoltage protection (U2>)
with definite-time or inverse-time characteristic
• Neutral displacement / residual overvoltage
protection (U0>)with definite-time or inverse-time
characteristic
• Can be used in single-phase or three-phase
operation
Introduction • Multi-function isolated digital input with wide
input voltage range
The MU2300 is a microprocessor based numerical • Fault record and event code recording
relay for voltage protection functions in electrical
• Five programmable voltage-free output contacts
distribution network.
• Isolated RS485 Modbus - RTU communication
• ANSI Code : 27, 47, 59, 60

Technical Data
INPUTS OUTPUT CONTACTS NEGATIVE SEQUENCE OVER-VOLTAGE
Measuring input: 5 programmable contacts +1 IRF contact: ELEMENT
Rated voltage input : 57 ~ 130 V Rated voltage : 250 V AC / DC Negative sequence over-voltage setting, U2>
Rated frequency : 50 / 60 Hz Continuous carry :5A : 5 - 200 V
Make and carry for 0.2 s : 30 A Time multiplier, TMS : 0.5 - 100
Expected electrical life : 100,000 operations Negative sequence over-voltage definite time tU2>
Rated auxiliary voltage: at rated current : 0 - 600 s
Model MU2300-150D : 24 ~ 150 V DC Expected mechanical life : 5 x 106 operations
Model MU2300-240AD : 85 ~ 265 V AC RESIDUAL OVER-VOLTAGE ELEMENT
110 ~ 340 V DC UNDER-VOLTAGE ELEMENT Residual over-voltage setting, U0> : 0.5 - 130 V
Low set setting U< : 5 - 130 V Time multiplier, TMS : 0.5 - 100
Power consumption: High set setting U<< : 5 - 130 V Residual over-voltage definite time tU0>: 0 - 600 s
AC auxiliary voltage : 6 ~ 10 VA typical Time multiplier, TMS : 0.5 - 100
DC auxiliary voltage : 5 ~ 9 W typical Low set Definite time tU< : 0 - 600 s ENVIRONMENTAL CONDITIONS
High set Definite time tU<< : 0 - 600 s Temperature : -5˚C to +55˚C
MU 2300

Humidity : 56 days at 93% RH and


Binary Input: OVER-VOLTAGE ELEMENT 40˚C non-condensing
External binary input : 85 ~ 265 V AC/DC Low set setting U> : 5 - 200 V MECHANICAL
High set setting U>> : 5 - 260 V Mounting : Panel mounting
Time multiplier, TMS : 0.5 - 100 Dimension (mm) : 142(w) x 165(h) x 198(d)
COMMUNICATION Low set definite time tU> : 0 - 600 s Enclosure protection : IP54 at the panel
RS485 Modbus - RTU High set definite time tU>> : 0 - 600 s Approximate weight : 2.7 kg
Voltage Relay

Undervoltage Characteristic Overvoltage Characteristic Case Dimensions


100
142 mm

100
Operating time (sec)

Operating time (sec)


10

165 mm
1
Front
10
10 TMS=8 TMS=10
TMS= TMS=8
5 TMS=5
TMS=
TMS=3
TMS=
3 0.1
TMS=1

1
TMS=
1 0.01
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 0 2 4 6 8 10 12 14 16 18 20
Applied voltage/relay setting voltage Applied voltage/relay setting voltage 198 mm

34 mm

Typical Application Diagrams


A A

136 mm
Side
B B
C C
2 34 Trip Contact 2 34 Trip Contact
36 R1 36 R1
3 35 3 35

5 38 5 38
37 R2 37 R2
6 6
40 40
8 39 R3 8 39 R3
129 1 mm
9 42 9 42
41 R4 41 R4
11 11
27 27
12 26 R5 12 26 R5
139 1 mm
28 Internal 28 Internal Panel Cutout
13 30 Relay 30 Relay
External
Digital 29 Failure 13 29 Failure
Input 14 22 External 22
Termination Resistor Digital 14 Termination Resistor
32 23 N- Input 23 N-
A Uaux 33 A 32
24 P+ Uaux 24 P+
33
25 Communication 25 Communication
31 Cable Shield 31 Cable Shield

C B C B
Phase rotation Phase rotation

3Vp-p + Vresidual connection 2Vp-p + Vresidual connection

A
B
A
B Ordering Information
C C
2 34 Trip Contact 2 34 Trip Contact

3
36 R1
35 3
36 R1
35 MODEL DESCRIPTION
5 38 5 38
MU2300-150D For 50 / 60 Hz system, auxiliary
37 R2 37 R2
6 6
voltage 24 ~ 150 V DC
40 40
8 39 R3 8 39 R3

9 42 9 42
MU2300-240AD For 50 / 60 Hz system, auxiliary
41 R4 41 R4
11 11 voltage 85 ~ 265 V AC or
27
26 R5
27
26 R5
110~340 V DC
12 12
MU 2300

28 Internal 28 Internal
13 30 Relay 30 Relay
External
Digital 29 Failure 13 29 Failure
External
Input 14 22 Digital 14 22
Termination Resistor Termination Resistor
Input
32 23 N- 23 N-
A Uaux 33 A 32
24 P+ Uaux 24 P+
33
25 Communication 25 Communication
31 Cable Shield 31 Cable Shield

C B C B
Phase rotation Phase rotation

3Vp-n + Vresidual connection 3Vp-n connection


3 - Phase Voltage Relay
MX210
Features
• Numerical voltage protection relay
• Undervoltage
• Overvoltage
• Phase loss
• Phase sequence
• 3-Phase/Single-phase
• ANSI Code: 27, 47, 59

Product Description
MX210 is voltage relay that combines
overvoltage, undervoltage, phase loss,
phase sequence and delay start functions.

MX210 can be programmed by user to


set nominal voltage as well as set into 3-
phase or Single-phase mode.

Technical Data
POWER SUPPLY INPUT SETTING RANGES INDICATORS
3-Phase System Undervoltage : 78% - 98% Power supply ON : Green indicator
Phase-to-phase voltage : 380 V (-25%) to 415 V Overvoltage : 102% - 122% Output ON : Green indicator
(+20%) AC Delay time : 0.1 - 10s Undervoltage : Red indicator
Normal voltage : 380, 400, 415 Vpp, 220, Overvoltage : Red indicator
Single Phase 230, 240, Vpn Phase error : Red indicator
Phase-to-neutral voltage : 220 V (-25%) to 240 V 3-phase / Single-phase
(+20%) AC
Frequency range : 45 to 65 Hz ENVIRONMENTAL CONDITIONS
Max. power consumption : 3 VA maximum ACCURACY Temperature : -5˚C to +55˚C
Protection thresholds : ± 3% Humidity : 56 days at 93% RH and
Hysteresis : 1% 40˚C non-condensing
OUTPUT CONTACTS Delay time : 0-0.5s, ± 15%,
Rated voltage : 250 V AC 40ms minimum MECHANICAL
Contact rating : 5 A : 0.5s and above, ± 3% Mounting : DIN rail
Expected electrical life : 100,000 operations at Measurements : ± 3% Dimension (mm) : 71(w) x 85(h) x 70(d)
rated current Approximate weight : 0.3 kg
Expected mechanical life : 5 x 106 operations
MX 210
3 - Phase Voltage Relay

Wiring Diagram
Single-Phase System 3-Phase System

L L1
N L2

L3

N
1 2 3 4 5 6 7

R1
1 2 3 4 5 6 7
8 9 10 11 12 13 14
R1

8 9 10 11 12 13 14

Operations Diagram
i ) Over Voltage Function ii ) Under Voltage Function

R
Over Voltage Limit Y
Hysteresis B
R Hysteresis
Y Under Voltage Limit
B
Relay T
Relay T
ON
ON
>U LED ON
<U LED ON

Case Dimensions Ordering Information

71 mm 70 mm MODEL DESCRIPTION
MX210 - 415V 3-Phase 380-415V AC
20 mm Single-Phase 220-240V AC
45-65Hz
45 mm

85 mm

Front Side

20 mm

30 mm 20 mm 20 mm
MX 210
Voltage Relay
MX 160A
MX200A
MK180A
Under Voltage Relay

MX 180A

MK160A
Over Voltage Relay

MX 200A
Under & Over Voltage Relay

Features
• Electronic monitoring relay
• Voltage monitoring for single
3-phase system
• Phase failure monitoring
• Adjustable voltage limit
• Adjustable delay time
• Indicators for voltage fault
• Indicators for power and output ON
• ANSI Code : 27, 47, 59

Product Description
MX160A, MX180A & MX200A are single
or 3-phase monitoring relays. The relays
are designed for application where it
required to maintain the voltage within
set limits. A built-in adjustable time delay
prevents nuisance tripping.

Technical Data
POWER SUPPLY INPUT SETTING RANGES INDICATORS
3-Phase System Lower voltage limit * : 78% - 98% Power supply ON : Green indicator
Phase-to-phase voltage : 380 V AC ± 20% Upper voltage limit ** : 102% - 122% Output ON : Red indicator
MX 200A / 180A / 160A

400 V AC ± 20% Delay time, T : 0.1 - 10s Under voltage limit (U<) * : Red indicator
415 V AC ± 20% Over voltage limit (U>) ** : Red indicator

Single Phase HYSTERESIS


Phase-to-neutral voltage : 220 V AC ± 20% ≤1% of rms - value ENVIRONMENTAL CONDITIONS
230 V AC ± 20% Temperature : -5˚C to +55˚C
240 V AC ± 20% Humidity : 56 days at 93% RH and
Frequency range : 45 to 65 Hz OUTPUT CONTACTS 40˚C non-condensing
Max. power consumption : 3 VA Rated voltage : 250 V AC
Contact rating : 5 A MECHANICAL
Input Connections Expected electrical life : 100,000 operations at Mounting : Circular 11-pin plug-in
For 3-phase model : Phase L1, L2, L3 to rated current socket
pin 5, 6, & 7 Expected mechanical life : 5 x 106 operations Dimension (mm) : 35(w) x 80(h) x 72.5(d)
Neutral to pin 11 Approximate weight : 0.3 kg
For single-phase model : Phase L to pin 5, 6 &
7***
Neutral to pin 11 * Applicable to MX160A and MX200A only
** Applicable to MX180A and MX200A only
*** For single phase connection, short pin 5,6 & 7
Voltage Relay

Wiring Diagram
Single-Phase System 3-Phase System
L L3
N L2
L1
N

5 6 7
4 8 5 6 7
3 9 4 8
2 10 3 9
1 11 2 10
1 11

Operations Diagram
i ) Over Voltage Function** ii ) Under Voltage Function*

R
Over Voltage Limit Y
Hysteresis B
R Hysteresis
Y Under Voltage Limit
B
Relay T
Relay T
ON
ON
>U LED ON
<U LED ON

Case Dimensions Ordering Information

FUNCTION
Under Over Supply
MODEL Voltage Voltage Voltage
Monitoring Monitoring V AC
MX160A - 380 YES NO 380
MX 200A / 180A / 160A

MX160A - 400 YES NO 400

80 mm MX160A - 415 YES NO 415

MX180A - 380 NO YES 380


MX180A - 400 NO YES 400
72.5 mm
MX180A - 415 NO YES 415
35 mm

MX200A - 380 YES YES 380


MX200A - 400 YES YES 400
MX200A - 415 YES YES 415
Voltage Relay
MX100
MX 50
Phase Failure monitoring

MX 100
Phase Sequence &
Phase Failure monitoring MK50
Features
• Electronic monitoring relay
• Phase sequence monitoring*
• Phase failure monitoring
• Plug-in type module
• Indicators for power and alarm status
• ANSI Code : 47

Product Description
This phase sequence and phase failure
relay is designed for application where the
3-phase supply needs to be continuously
monitored for proper sequencing and
phase loss. Commonly used to protect a
3-phase motor.

Technical Data
POWER SUPPLY INPUT INDICATORS
Phase-to-phase voltage : 230 V AC ±20% Power supply ON : Green indicator
: 400 V AC ±20% Output ON : Red indicator
Frequency range : 45 to 65 Hz
Max power consumption : 3 VA
Input connections : Phase L1 to pin 5 ENVIRONMENTAL CONDITIONS
Phase L2 to pin 6 Temperature : -5˚C to +55˚C
Phase L3 to pin 7 Humidity : 56 days at 93% RH and
Neutral (optional) to 40˚C non-condensing
pin 11

OUTPUT CONTACTS MECHANICAL


Rated voltage : 250 V AC Mounting : Circular 11-pin plug-in
MX 100 / 50

Contact rating : 5 A socket


Expected electrical life : 100,000 operations at Dimension (mm) : 35(w) x 80(h) x 72.5(d)
rated current Approximate weight : 0.3 kg
Expected mechanical life : 5 x 106 operations
Voltage Relay

Wiring Diagram
Example 1 Example 2

L3 L3
L2 3~ L2 3~
L1 L1
N

6 5 6 7
5 7
4 8 4 8
3 9 3 9
2 10 2 10
1 11 1 11

Function Table
Condition Pin 5 Pin 6 Pin 7 Relay Remark
1 L1 L2 L3 ON System healthy
2 Loss L2 L3 OFF Phase failure
3 L1 Loss L3 OFF Phase failure
4 L1 L2 Loss OFF Phase failure
5 L2 L1 L3 OFF Sequence fault*
6 L3 L2 L1 OFF Sequence fault* * Applicable to MX100 model only

Case Dimensions Ordering Information

MODEL DESCRIPTION
MX100 - 230 Auxiliary voltage 184~276 V AC
MX100 - 400 Auxiliary voltage 320~480 V AC
MX50 - 230 Auxiliary voltage 184~276 V AC
MX50 - 400 Auxiliary voltage 320~480 V AC
80 mm