Professional Documents
Culture Documents
9. horizontal plastic tube shall be supported by stiff metal or wood backing with hangers for 38 mm
and smaller in diameter for its?
a. 1 m interval
b. 3 m interval
c. 1.2 m interval
d. entire length
9. Horizontal plastic tube sized 51 mm and larger in diameter shall be supported with space metal
hangers at approved spacing and
a. with backings
b. without backings
c. either a and b
d. none of the above
10. Tunnels shall have a clear height of______ above the pipe and shall be limited in length to
______the depth of a trench with a maximum length of _______. When pipe is driven, the drive pipe
shall be at least ________than the pipe to be laid.
a. 0.3 m, one half 2.4 m, one pipe size larger
b. 0.6 m, one half 2.4 m, one pipe size larger
c. 0.6 m, one half 2.4 m, two pipe size larger
d. 0.3 m, one half 2.4 m, two pipe size larger
11. Trenches of building drainage shall be backfilled in thin layers of ______m above the top of the
pipe with clean earth which not contain materials which can the damage the pipe
a. 0.3 m
b. 0.6 m
c. 0.4 m
d. around the pipe
13. Restaurant and other special use sinks may be made of approved type bonderized and
galvanized steel sheet of not less than
a. Gauge no. 16 (1.6 m thick)
b. Gauge no. 20 (0.8 m thick)
c. Gauge no. 12
d. Gauge no. 25
17. Continuous waste and fixture tailpiece that such connection where exposed or accessible may
be of seamless drawn brass not less than?
a. Gauge 16 B & S (1.6 m thick)
b. Gauge 20 B & S (0.8 m thick)
c. Gauge 12 B & S
d. none of the above
18. Each such tailpiece, continuous waste or overflows for sinks, dishwashers, laundry tubs,
bathtubs, urinal and similar fixtures shall not less than?
a. 32 mm O.D
b. 38 mm O.D.
c. 51 mm O.D
d. 31 mm O.D.
19. Continuous waste or tailpiece for lavatories, drinking fountain and similar small fixture shall not
be less than?
a. 38 mm O.D.
b. 32 mm O,.D
c. 51 mm O.D
d. 31 mm O.D
20. material should not be used for continuous waste and overflows tailpiece or trap for urinal?
a. copper and lead
b. copper and brass
c. plastic and lead
d. stainless and plastic
24. No water closet and bidet shall be set closer than from its center to any side of the wall or
obstruction?
a. 0.3 m
b. 0.6 m
c. 0.375 m
d. 0. 73 m
25. No water closet and bidet shall be set closer than from its center to center of a similar fixtures?
a. 0.6 m
b. 0.3 m
c. 0.375 m
d. 0.73 m
26. No urinal shall be set closer than from its center to any side of the wall or partition?
a. 0.3 m
b. 0.6 m
c. 0.375 m
d. 0. 73 m
26. No urinal shall be set closer than from its center to center of a similar fixtures?
a. 0.6 m
b. 0.3 m
c. 0.375 m
d. 0.73 m
28. Shower threshold or curb for special shower compartments for wheelchair used may be
a. Maintain
b. Eliminate
c. both a and b
d. none of the above
29. Showers threshold shall be sufficient width to accommodate a minimum of wide door
a. 550 mm
b. 500 mm
c. 600 mm
d. 559 mm
30. Minimum distance between the door or entry to the drain opening of shower shall be
a, 1.2 m
b. 1.5 m
c. 0.6 m
d. 1.8 m
31. All shower compartments, regardless in shape shall have a minimum finish interior area of
a. 0.8 sq. m
b. 0.6 sq. m
c. 762 mm diameter circle
d. 0.8 sq. m
33.Minimmum area and dimension of a shower compartments shall be maintain from a shower
drain outlet to a height of
a. 1.78 m
b. 1.76 m
c. 1.9 m
d. 2 m
34. Gutters and or gang shower room shall be spaced not more than?
a. 3.9 m
b. 5 m
c 4.9 m
d4m
35. In the absence of local regulation, shower occupancies shall be provide with individual
thermostatic mixing valve shall be adjusted to deliver the maximum hot water temperature of
a. 43.3 °c
b. 48.8 ˚ c
c. 60 °c
d 80 ° c
39. Minimum section of water test for the DWV shall be_____ and shall be filled with water for a______
before the inspection starts
a. 3 m head, 15 minutes
b. 4 m head, 15 minutes
c. 5 m head, 10 minutes
d. 3 m head, 10 minutes
40. Air test shall be made for DWV by attaching air compressor to a minimum uniform gauge
pressure of_______for the period of
a. 344.5 kpa or 254 mm height column mercury, 15 minutes
b. 34.5 kpa or 264 mm height column mercury, 15 minutes
c. 34.5 kpa or 254 mm height column mercury, 15 minutes
d. 34.5 kpa or 284 mm height column mercury, 15 minutes
41. Minimum water piping for hot and cold pressure test shall be test under a pressure of not less
than_______ for a period of
a. 1.5 time the working pressure, 15 psi
b. 1.5 times the design pressure, 15 minutes
c. not less than the working pressure, 15 minutes
d.1.5 times the working pressure, 15 minutes
42. Air may be substitute for a water piping test for hot and cold with a minimum of_______ for a
period of
a. 344.5 psi, 15 psi
b. 344.5 kpa, 15 minutes
c. 34.5 psi, 15 minutes
d. 34.5 psi, 15 psi
43. Minimum air gaps for water distribution for lavatories and other fixtures with effective opening
not greater than 13 mm in diameter when affected by the walls?
a. 38 mm
b 25 mm
c 19 mm
d 57 mm
44. Minimum air gaps for water distribution for sinks, laundry trays and other fixtures with
effective opening not greater than 19 mm in diameter when affected by the walls
a. 38 mm
b. 57 mm
c 25 mm
d. 51 mm
45 Over rim baths filler and other fixtures with effective opening not greater than 25 mm in
diameter when affective by the walls
a. 76 mm
b. 38 mm
c 57 mm
d. 51 mm
46 Over rim baths filler and other fixtures with effective opening not greater than 25 mm in
diameter when not affective by the walls
a. 76 mm
b. 38 mm
c 57 mm
d. 51 mm
47. Access and clearance for the backflow prevention assemblies shall require a minimum clearance
from a lowest portion of a assembly and the grade floor or platform.
a. 305 mm
b. 0.3 m
c. 0.6 m
d 1.5 m
48. Installation elevated more than 1.52 m above the floor grade of a backflow prevention
assemblies shall be provided with________capable of supporting a tester or maintenance person
a. temporary platform
b. permanent platform
c. removable platform
d. none of the above
49. Where potable water is discharge to the drainage system, it shall be means of an approved air
gap " with un obstructed atmospheric distance from the supply outlet and the top surface of the
drainage inlet, but in no case shall the gap be less than 25 mm
a. 2 pipe size diameter
b. 1 pipe size diameter
c. 1.5 size diameter
d. 25 mm
50. Backflow prevention for hot water over 43.3 ° c shall be a listed type assembly design to operate
at a temperature of_________without rendering any portion of the assembly inoperative.
a. 43.3 ° c or higher
b. 48.8 ° c or higher
c. 48.8 ° c or lower
.d 43.3 ° c or lower
51. Water closet and urinal flushometer valve shall be equipped with a listed
a. atmospheric vacuum breaker
b. ball cock
c. backflow prevention assembly
d. back water valve
52. Vacuum breaker shall be installed at the discharge side of the flushometer valve with the critical
level above the overflow rim of a water closet bowl or the highest part of a urinal
a. 25 mm
b. 152 mm
c 0.3 m
d. 0.6 mm
53. Water closet and urinal tanks shall be equipped with a listed?
a. float valve
b. ball cock
c. ball joint
d. both a & b
54. Ball cock shall be installed with the critical level at least_____above the full opening of the
overflow pipe
a. 152 mm
b. 38 mm
c. 25 mm
d. 0.3 m
55. Water closet flushometer tanks shall be protective against backflow by an approved device
a. back water valve
b. Reducing pressure
c. backflow prevention assembly
d. Air gap
56. Water supply inlet to receptors not protected by atmospheric vacuum breaker shall be
protected by approved
a. air break
b. air gap
c. reducing pressure
d. double check valve
57. Lawn sprinkler system shall be equipped with a listed and installed at discharge side of each of
the last shutoff valve.
a. reducing pressure
b. double check valve
c. atmospheric vacuum breaker
d. air break
58. Backflow preventers shall not be located in any area containing fumes that are
a. toxic
b. poisonous
c. corrosive
d. all of the above
59. May be used for hot and cold water distribution system within a building
a. PVC pipe
b. DCI pipe
c. PB pipe
d. CPVC pipe
60. Cast iron fitting up to including 51 mm in size, when used in connection with potable water
piping shall be
a. steel
b. stainless
c. galvanized
d. all of the above
62. Water pipes and fittings with a lead content that exceed 8% shall be prohibited and not used in
a. DWV
b. storm drainage system
c. Gas piping
d. potable piping system
63. Valves up to and including 51 mm in sized shall be_______or other approved materials
a. brass or bronze
b. cast iron
c. both a and b
d. none of the above
68. Return bend vent pipe of a potable water storage tank shall be screened with a fined corrosion-
resistant screen with opening not less than or nor more than
a. 14-18 mess per 25 mm
b. 16-18 mess per 51 mm
c. 14-16 mess per 51 mm
b. 14-16 mess per 25 mm
70. If water pressure from the main will not provide a water pressure of at least 15 psi allowing
friction losses and pressure losses, what will be additional in the system to provide a 15 psi
a. booster pump
b. elevated tank
c. hydro-pneumatic pressure tank
d. either of the above
71. Excessive water pressure excess in 80 psi(551 kpa) shall be provide to reduce a pressure to the
required supply pressure.
a. Approved type relief valve
b. Approved type pressure regulator
c. By pass valve
d. Reduce pressure valve.
73. Water pipes and building sewer, and storm drainage constructed in clay material or not
approved material for used with in a building shall not be run or laid in the
a. same trench
b. same elevation
c. same Material
d. none of the above
74. Water pipes and building sewer, and storm drainage constructed on a clay material
laid or run in the same trench within a building shall have at least vertical clearance at all points of
a. 0.4 m from the bottom of water pipes to the top of storm drainage or building sewer
b. 0.5 m from the bottom of water pipes to the top of storm drainage or building sewer
c. 0.3 m from the bottom of water pipes to the top storm of drainage or building sewer
d 0.150 m from the bottom of water pipes to the top storm of drainage or building sewer
75. Water pipes and building sewer, and storm drainage constructed on a clay material laid or run
in the same trench within a building shall have at least horizontal clearance at all points of
a. 0.4 m from the side of water pipes to the side of storm drainage or building sewer
b. 0.5 m from the bottom of water pipes to the top of storm drainage or building sewer
c. 0.3 m from the side of water pipes to the side storm of drainage or building sewer
d 0.150 m from the side of water pipes to the side storm of drainage or building sewer
75. Water pipes crossing building sewer, and storm drainage within a building and constructed on a
clay material shall have at least vertical clearance at all points of
a. 0.4 m from the bottom of water pipes to the top of storm drainage or building sewer
b. 0.5 m from the bottom of water pipes to the top of storm drainage or building sewer
c. 0.3 m from the bottom of water pipes to the top storm of drainage or building sewer
d 0.150 m from the bottom of water pipes to the top storm of drainage or building sewer
76. Pipe shall have an outside protective coating of an approved material like bituminous coating
and fiberglass wrapping
a. plastic
b. Ferrous
c. PB
d. PE
78. Where joint are permitted on a copper tubing laid or run underground they shall be
a. soldered
b. brazed
c. Flux
d. flared
79. Pressure loss in a water line in such devices in a water supply system must be included in
a. water supply system
b. pressure loss calculation
c. the devices
d. all the above
80. No devices in a waterline supply system if the inlet/outlet is less than the and
a. diameter of water supply pipe, excessive pressure drop
b. Volume of the water supply pipe, excessive pressure drop
c. capacity of such devices, excessive pressure drop
d. none of the above.
81. Union installed in water supply system shall be installed away from the regulating equipment
like water heater, conditioning tank and similar equipment within
a. 0.6 m
b. 0.3 m
c. 152 mm
d 1m
83. Support trap arm as close as possible to the trap, if the trap arm excess in
a. 0.6 m
b. 3 ft (1m)
c. 1.5 m
d. 1.8 m
83. No galvanized iron or galvanized steel shall be used underground and shall be kept at least___
above the ground.
a. 152 mm
b. 160 mm
c 0.3 m
d. 0.6 m
85. No vitrified clay pipe or fittings for building drain and sewer shall used
a. above the ground
b. below the ground
c. For high rise building
d. For medium rise buildings
86. Fittings on screw pipe joint shall be_____ to the full bore of the pipe
a. reamed
b. clean
c. welded
d. packed
87. How many fixture units shall be allow for a continuous flow in to a drainage system like sump
pump, ejector and air conditioning equipment for every 0.063 l/s(1gpm)
a. 6 fixture units
b. 2 fixture units
c. 4 fixture units
d. 1 fixture units
88. Changes and direction of drainage piping shall be made by the appropriate use of approve
fittings
a. 22. 5 ⁰ (1/6)
b. 45 ⁰ (1/8)
c. 60 ⁰ (1/6)
d. equivalent sweeps
e. all of the above
89. No fitting having more than one inlet at the same level shall be used unless the discharge of one
inlet cannot enter into the other?
a. inlet
b. outlet
c. pipe
d. fitting
90. Double sanitary tees may be used when the barrel of the fitting is at least two pipe sized larger
than the largest
a. outlet
b. inlet
c. fitting
d. pipe
93. Sixty (60) degree branches or offsets may be used only when installed in true
a. horizontal position
b. vertical position
c. perpendicular position
d. parallel position
94. Cleanout shall be provide at every length
a. 15 m
b. 20 m
c. 25 m
d. 10 m
95. Clean out may be omitted on a horizontal drain line less than 1.5 m in length except
a. urinal
b. sinks
c. both a & b
d. lavatory
96. Cleanout may be omitted on a short horizontal drainage pipe installed at a slope of?
a. 1/5
b. 1/4
c. 1/8
d. 1/6
99. Cleanout under floor piping shall have a vertical clearance from means of access not less than
a. 300 mm
b. 350 mm
c. 450 mm
d. 500 mm
100. Cleanout under floor piping shall have a horizontal clearance from the mean of access not less
than
a. 750 mm (30”)
b. 350 mm
c. 450 mm
d. 500 mm
101. No under floor cleanout in any residential occupancy shall be located from access door, trap
door, or crawl hole more than
a. 610 mm (24”)
b. 0.75 mm
c. 305 mm
d. 0.45 mm
102. Where it is impractical due to depth of street sewer or to adverse structural, a 102 mm
diameter pipe may have a slope not less than
a. 0.5 %
b. 1%
c. 2%
c. none of the above
103. Drainage piping serving fixture which have flood level rim located below the elevation of the
street sewer shall be protected from backflow by providing a
a. check valve
b. atmospheric vacuum breaker
c. backwater valve
d. Aspirator
104. Drainage piping serving fixture below the manhole invert of street sewer shall be discharge
directly to
a. Street sewer
b. watertight receptacle
c. watertight receptacle lifted by an approved pump
d. with backwater valve
105. Minimum pump discharge pipe from a sump having a water closet connected shall not be less
than
a. 76 mm
b. 102 mm
c. 50.8 mm
d. 152 mm
106. The vertical discharge pipe from a pump, ejector or other mechanical device to a horizontal
drain line shall be provided with a backwater valve or swing check valve and gate valve close to the
connection with the
a. Pump
b. Horizontal line
c. Suction pipe
d. Discharge pipe
108. The invert elevation of the lowest inlet of the tank above starting level of the operation of the
pump into receiving tanks shall have a minimum distance of
a. 102 mm
b. 51 mm
c. 65 mm
d. 38 mm
109. Individual vent pipe size shall not be less than
a. 38 mm
b. 32 mm
c. 51 mm
d. 65 mm
110. Vent pipes size shall not be less than______ the diameter of the drain
a. two pipes size
b. one half
c. 1-1/2
d. 32 mm
111. Minimum air gap between the appurtenances outlet and the rim of the floor sink or receptor
a.25 mm
b.32 mm
c. 38 mm
d. 19 mm
112. Indirect waste pipe exceeding in length and but not less than, shall be directly trapped and
such trap need not be vented
a. 1 m to 3.5 m
b. 1.5 m to 3 m
c. 1.5 m to 4.6 m
d. 1 m to 4.6 m
113. Minimum size diameter of an indirect waste pipe
a. 13 mm
b. 10 mm
c. 19 mm
d. 25 mm
114. Sterile equipment and other similar equipment requiring water and waste and used for sterile
materials shall be drained through
a. an air gap
b. an air break
c. receiving tank
d. none of the above
115. When the condensate waste is discharge to an exposed fixture tailpiece and trap, such tailpiece
and trap may be
a. Plastic
b. Galvanized
c. brass
d. cast iron
118. Above temperature of water shall not be discharge under pressure directly into any part of a
drainage system.
a. 48.3 ° C
b. 43.3 ° C
c. 60 ° C
d. 70 ° C
120. No indirect waste receptor shall be installed on any other portion of a building not for
generally used by the occupants
a. cupboard
a. toilet room
b. closet
c. Storeroom
d. all of the above
121. Where clotheswashers are installed in the toilet and bathrooms areas, standpipes for
clotheswashers may
a. not installed in the same area
b. installed in the same area
c. is a code violation
d. None of the above
122. Every indirect waste receptor receiving discharge containing particles that clogs the receptor
drain shall have a readily removable
a. Wye strainer
b. Basket strainer
c. Beehive strainer
d. Filter
126. Fixtures that also serves as a wet vent for not to exceed
a. 2 fixtures
b. 4 fixture units
c. 2 fixture units
d. 4 fixtures
127. The vertical piping between any 2 fixtures or inlet level shall be considered as
a. Common vent
b. Dual vent
c. Wet vent
d. all of the above.
128. Clean out may not be required on a wet vented branch serving a single trap when the fixture
tailpiece or connection is not less than
a. 38 mm
b. 32 mm
c. 51 mm
d. 76 mm
129. Sacraruim waste of holy water, washwater at church services must be discharge to the
a. Sanitary drainage
b. Road drainage
c. ground
d. storm drainage
130. Vent piping may be omitted on a interceptor, when such interceptor acts as a
a. secondary settling tank
b. Primary settling tank
c. both a & b
d. none of the above
133. Unless prohibited by structural conditions, each vent shall rise vertically above the rim of a
fixture before offsetting horizontally to join the vent stack not less than
a. 100 mm
b. 152 mm
c. 25 mm
d. 1.5 m
135. Each vent pipe of VSTR shall extend its flashing and shall terminate vertically above the roof of
not less than
a. 0.3 m
b. 1.5 m
c. 152 mm
d. 3 m
135. Each vent pipe of VSTR shall extend its flashing and shall terminate vertically above the roof
with a horizontal clearance of any vertical surface nearby of not less than
a. 0.3 m
b. 1.5 m
c. 152 mm
d. 3 m
136. Minimum horizontal Clearance of a vent opening to a openable window, and door opening
shall not be less than
a. 0.9 m
b. 3 m
c. 1.5 m
d. 152 mm
137. Minimum clearance of a vent opening above a openable window, and door opening shall not
be less than
a. 0.9 m
b. 3 m
c. 1.5 m
d. 152 mm
138. Minimum clearance of vents pipe above the roof or fire wall extended separately or combined,
of full required size shall not be less than
a. 3 m
b. 0.3 m
c. 152 mm
d. 0.9 m
139. Vent pipes for outdoor installation shall extend from any part of the roof that is used for other
purposes not of less than
a. 3 m
b. 152 mm
c. 0.9 m
d. 0. .3 m
141. Vent pipes for outdoor installation shall extend above any part of such roof that is used for
other purposes of not less than
a. 3 m
b. 152 mm
c. 0.9 m
d. 2.1 m
141. How many minimum floors requirement to provide a yoke vent at every fifth floor level
a. Fifth floor stories
b. Ten floor stories
c. Fifteen floor stories
d. 25 floor stories
142. Yoke vent connection with the vent stack shall have a minimum distance above the finish floor
level of not less than
a. 1 m
b. 1.5 m
c. 0.5 m
d. 1.2 m
144. Clean out may omitted on the trap arm when the in direction is not exceed
a. 45 ⁰
b 90 ⁰
c. 60 ⁰
d. 135 ⁰
145. For a trap arm 76 mm in size and larger, the change in direction not exceeding 22.5 ⁰ cleanout
is
a. required
b. not required
c. both a & b
d. none of the above
146. The develop length between the trap of a water closet or similar fixture measured from the top
of a closet ring(closet flange) to inner edge of vent shall not exceed
a. 1.5 m
b. 1.8 m
c. 1,2 m
d. 1.0 m
147. An exposed and readily accessible drawn brass tubing trap shall have a thickness of not less
than
a. Gauge 15
b. Gauge 17
c. Gauge 20
d. Gauge 18
148. Number of slip joint fitting approved may be used on the outlet side of the trap
a. one
b. two
c. three
d. four.
152. When such drain is subjected to reverse flow of sewage or liquid waste, floor drain shall be
equip with a
a. vacuum breaker
b. backwater valve
c. check valve
d. none of the above
153. Interceptor or clarifiers for sand and similar heavy solid shall have a water seal of not less than
a. 152 mm
b. 102 mm
c. 51 mm
d. 205 mm
154. Slaughter houses and packing establishment from which considerable amount of grease and
hair feather s are likely to be discharge into the plumbing system shall be connected grease
interceptor through
a. separator
b. screening device
c. a pit
d. clarifier
156. Auto wash rack and floor slab or slab used shall be protected from against storm and surface
water and shall be drain into directly in to
a. Storm drainage
b. sanitary drainage
c. Interceptor
d. Sump pit
157. Except when specially approved by the administrative, grease trap shall be installed for a
facility that has approved rate flow of not less than______ and more than_______
a. 1.3 L/s to 5 L/S
B. 1.3 L/s to 3.4 L/s (21gpm-54 gpm)
c. 1.3 L/S to 2.5 L/s
d. None of the above
158. Each plumbing fixture or piece of equipment connected to a grease trap shall be provided with
an approved type
a. volume control
b. back water valve
c. restricting device
d. material
159. Maximum number of separate fixture shall be connected to or discharge into any one grease
trap
a. 1
b. 2
c. 3
D.4
160. Each grease trap shall have an approved water sealed trap of not less than the diameter of its
outlet whichever is greater or
a. 51 mm
b. 102 mm
c. 152 mm
d. 76 mm
1. Rainwater conductor piping located on the exterior side of a low height building shall not be
less than
a. gauge 17 (1.1 mm thick)
b. gauge 20 (0.8 mm thick)
c. gauge 26
d. gauge 24
2. What is the net inlet area equivalent of the dome type- strainers to its outlet pipe drain
connected
a. Area of outlet pipe
b. 1.5 times of the drain pipe
c. 2 times of the drain pipe
d. 0.5 times of the drain pipe
3. What is the net inlet area equivalent of a flat type-strainers to its outlet pipe drain connected
use as an parking decks and sun decks and other similar occupied areas
a. 1.5 times of the drain pipe
b. 2 times of the drain pipe
c. Equal to the drain pipe
d. ½ of the drain pipe
4. Rate of rainfall intensity used around Metro Manila
a. 102 mm/hr
b. 104 mm/hr
c. 100 mm/hr
d. 112 mm/hr
1. Public sewer may be considered as not being available, when such public sewer from the
proposed building is more than
a. 61 m
b. 71 m
c. 51 m
d. 30 m
2. Building sewer pipe size shall not be smaller than the building drain or not less than
a. 102 mm
b. 152 mm
c. 200 mm
d. 250 mm
3. When approve by the Administrative authority, when it is impractical, due to the depth of the
street sewer, to obtain a slope of 2%, a 102 mm and 152 diameter mm may have a slope of not
less than
a. 1%
b. 0.5%
c. 2%
d. 0.3 %
4. When approve by the Administrative authority, when it is impractical, due to the depth of the
street sewer, to obtain a slope of 2%, a 203 mm diameter may have a slope of not less than
e. 1%
f. 0.5%
g. 2%
h. 0.3 %
5. Water pipes joints shall be installed away from a sewer pipes in both direction of not less than
a. 3 m
b. 0.3 m
c. 1.8 m
d. 0.6 m
6. Every abandoned house/building sewer, or part thereof, shall be plugged or cap in an approved
manner within 1.5 m of the
a. Building line
b. Property line
c. Side walk
d. Curb
7. Every abandoned cesspool, septic tank or seepage pit, which no more waste or soil pipeline or
connected shall have the sewage removed and completely
a. Demolished
b. Filled with aggregates
c. Abandoned
d. None of the answers
8. From the time of connecting the sewer service line to the public sewer, a permittee shall fill all
abandoned facilities as required by the Administrative Authority within
a. 35 days
b. 30 days
c. 120 days
d. 45 days
9. Minimum horizontal distance required from a building sewer to property line adjoining private
property
a. 1.5 m
b. 0.6 m
c. Clear
d. 0.3 m
10. Minimum horizontal distance required from a building sewer to onsite domestic water service
line and public water main
a. 0.6 m
b. 3 m
c. 0.3 m
d. 1.5 m
11. If a drainage piping materials approved for used within a building, a 15. 2 m required distance
from building sewer to domestic water supply wells may be reduced to not less than
a. 10 m
b. 7.6 m
c. 3 m
d. 13 m
1. Joint for Cast iron pipe and fittings for bell and spigot or hubless shall be made with
a. Caulked joints
b. Compression joints
c. Screwed joints
d. Either a & b
2. Joints for cast iron pipe and fittings for a hubless shall be made
a. Caulked joints
b. Mechanical joints(Shielded couplings)
c. Screwed joints
d. None of the above
3. Mechanical joints for a cast iron hubless pipe and fittings shall be made with
a. Mechanical joint coupling type
b. Shielded coupling type
c. Expansion joint
d. None of the above
4. Copper pipe joint to cast iron pipe or tubing shall be made with a listed
a. Compression type joint
b. Brass ferrule
c. Caulked joint
d. All of the above
8. Threaded pipe joints to copper pipe shall be made by the use of a listed
a. Brass adapter
b. Dielectric fitting
c. Either a & b
d. Mechanical joints
11. Lead pipe or fittings joints to cast iron pipe shall be made by means of
a. Caulking ferrule
b. Soldering nipple
c. Mechanical joints
d. Both a & b
12. Solders and fluxes prohibited in piping system used to convey potable water with a lead
content exceeds to
a. 0..02
b. 0.0002
c. 0.002
d. 0.01
13. Hubless cast iron pipe and solvent cement plastic pipe joints shall comply with appropriate
installation standard of
a. ASTM
b. ANSI
c. IAPMO
d. UL
14. Stainless steel pipes joint by the use of welding shall be either
a. Fusion or resistance weld
b. Brazed joint, soldered joint
c. Compression joint, threaded joint
d. Flux joint, soldered joint
15. Plastic pipe joint to other type of plastic material or other type of piping material shall be made
with approved listed
a. Adapter fittings
b. Die electric fitting
c. Expansion joints
d. Wiped joints
16. CPVC Plastic pipe and fittings joint shall be made with
a. Threaded joints
b. Solvent joint
c. Mechanical joints
d. All of the above
18. Closet rings or closet flange for water closet or similar fixtures shall be approximately
a. 12 inches
b. 7 inches in diameter
c. 6 inches
d. 3 inches
19. Closet screw, bolts washers and similar fasteners shall be or other listed equally corrosion-
resistant materials
a. Copper and brass
b. Galvanized steel
c. Steel
d. Black iron
1. Average consumption of a flush valve, flush tank operated water closet shall not to exceed to
a. 1.6 gal/flush
b. 15 gpm
c. 15 gal/flush
d. 8 gpm
5. Water consumption for sink faucet shall have a maximum flow rate of not more than (Except
for clinical sink, service sink and laundry sinks)
a. 2.5 gmp at 60 psi
b. 2.2 gpm at 60 psi
c. 2.4 gpm at 60 psi
d. 2.1 gpm at 60 psi
CHAPTER 14. QUALITY AND WEIGHTS OF MATERIALS
1. Copper tube for a water supply piping shall a weight of not less than
a. Type K
b. b.. Type L
c. Type M
d. all of the above
2. Type M copper tubing may be used for water piping when piping above ground inside or atop
of a building or underground outside provided with outside protective coating
a. True
b. False
c. Maybe
d. all of the above
3. All hard drawn copper tubing shall be marked by means of a continuous and indelibly colored
stripe of width at least
a. 7. 5 mm
b. 6.4 mm
c. 8. 5 mm
d. 5.5 mm
11. Each such closet rings or closet flanged shall have a diameter of approximately
a. 178 mm(7” )
b. 152 mm (6” )
c. 200 mm (8” )
d. 76 mm (3” )
12. Caulked-on closet rings shall have a thickness of not less than
a. 6.4 mm (1/4” )
b. 19 mm (3/4” )
c. 25 mm (1” )
d. 32 mm (1-1/4” )
13. Caulked-on closet rings shall have a depth of not less than
a. 51 mm
b. 76 mm
c. 38 mm
d. 32 mm
14. Sizes 102 mm or larger in diameter, when used in a drainage work shall be
a. Cast brass bodies
b. Cat iron bodies
c. Aluminum
d. Steel
18. Plumbing material standard for porcelain enameled formed steel plumbing fixtures
a. ANSI/FS
b. ASTM
c. UL
d. IAPMO
19. Plumbing materials standard for Cast iron and bronze gate valves
a. ASTM
b. FS
c. UL
d. ANSI
1. If the highest group of fixtures contains flushometer valves, the pressure for this group should
not be less than
a. 103 kpa (15 psi)
b. 55.1 kpa (8 psi)
c. 275 kpa (40 psi)
d. 413 kpa(60 psi
2. If the highest group of fixtures contains flush tanks, the pressure for this group
a. 103 kpa (15 psi)
b. 55.1 kpa (8 psi)
c. 275 kpa (40 psi)
d. 413 kpa(60 psi
3. Formula in static head = 9.79 kpa/m (height from the meter to the last group of fixture)
1. Where permitted by the rules and regulation of DENR, building sewer may be connected to a
a. Private sewage disposal system
b. Storm drainage system
c. Private sanitary drainage system
d. All of the above
3. All concrete septic tank shall be protected from corrosion by coating with an approved
a. wrapping
b. elastomeric paint
c. bituminous coating
d. none of the above
4. Bituminous coating shall extend to at least________ below the water line and shall cover all the
internal area above the point
a. 228. 6 mm
b. 101. 6 mm
c. 50.8 mm
d. 304.8 mm
REGULATORY REQUIREMENTS