FOUNDATION CALCULATION SHEET

One-Stop Solution for Foundation

TITLE DESCRIPTION
PROJECT/JOB NO. IS456_SI
PROJECT/JOB NAME AFES VERIFICATION
CLIENT NAME AFES
SITE NAME AFES
DOCUMENT NO.
REFERENCE NO.
STRUCTURE NAME IS456
LOAD COMBINATION GROUP NAME
REV DATE DESCRIPTION PREP'D CHK'D APPR'D APPR'D

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 1

FOUNDATION LISTS
GROUP NAME : TNK1RING
No. Description No. Description No. Description
1 F9

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 2

CONTENTS

1. GENERAL
1.1 CODE & STANDARD
1.2 MATERIALS & UNIT WEIGHT
1.3 SUBSOIL CONDITION & SAFETY FACTORS
1.4 LOAD COMBINATION

2. DRAWING
2.1 LOCATION PLAN
2.2 DETAIL SKETCH

3. FOUNDATION DATA
3.1 FOOTING DATA
3.2 PIER DATA
3.3 SECTION DATA
3.4 LOAD CASE
3.5 LOAD COMBINATION

4. CHECK OF STABILITY
4.1 CHECK OF SLIDING
4.2 CHECK OF OVERTURNING MOMENT
4.3 CHECK OF CONTACT PRESSURE

5. DESIGN OF FOOTING
5.1 DESIGN MOMENT AND SHEAR FORCE
5.2 RING WALL DESIGN
5.3 REQUIRED REINFORCEMENT
5.4 ONE WAY SHEAR FORCE
5.5 TWO WAY SHEAR FORCE

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 3

1. GENERAL
1.1 CODE & STANDARD
Items Description
Design Code American Concrete Institute (ACI 318)
Horizontal Force for Wind INTERNATIONAL BUILDING CODE [IBC 2006]
Horizontal Force for Seismic API 650, APPENDIXE
Unit System Input : SI, Output : SI, Calculation Unit : IMPERIAL

1.2 MATERIALS & UNIT WEIGHT


Items Value
2
Concrete (fck : compressive strength) 28.000 N/mm
2
Lean Concrete (Lfck : compressive strength) 0.000 N/mm
2
Reinforcement (10M ~ 16M , yield strength) 420.000 N/mm
2
Reinforcement (19M ~ , yield strength) 420.000 N/mm
3
Rs (Soil unit weight) 20.000 kN/m
3
Rc (Concrete unit weight) 24.000 kN/m
2
Es (Steel Modulus of Elasticity) 200.000 kN/mm
2
Ec (Concrete Modulus of Elasticity) 25.100 kN/mm

- Soil Capacity
Items Value
Soil Name Unit-01
Footing List F9
2
Qa (Soil Bearing Capacity) 250 kN/m
Buoyancy Not Consider
WL (Water Label from the EL = 0) 0 mm
FD (Frost Depth from the EL = 0) 0 mm
Internal Friction Angle 30
Passive Soil Pressure Not Consider
2
Cu (Undrained cohesion) Clay , 0 kN/m

1.3 SUBSOIL CONDITION & SAFETY FACTORS


Items Description
Allowable Increase of Soil (Wind) 33.33 %
Allowable Increase of Soil (Seismic) 33.33 %
Allowable Increase of Soil (Test) 20 %
Safety factor against overturning for OVM1(FO1) 1.5
Safety factor against overturning for OVM2(FO2) 1.7
Safety factor against overturning for OVM3(FO3) 1.8
Safety factor against overturning for OVM4(FO4) 2.1

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 4

Safety factor against sliding for the SL1(FS1) 1.5


Safety factor against sliding for the SL2(FS2) 1.6
Safety factor against sliding for the SL3(FS3) 1.7
Safety factor against sliding for the SL4(FS4) 1.8
Friction factor (m) 0.35

1.4 LOAD COMBINATION


Comb . ID Load Combination for stability
10 1.0 SW + 1.0 DL + 1.0 Empty + 1.0 Operation + 1.0 Test
20 1.0 SW + 1.0 DL + 1.0 WL + 1.0 Empty + 1.0 Operation + 1.0 Test
Comb . ID Load Combination for Reinforcement
100 1.4 SW + 1.4 DL
200 1.05 SW + 1.05 DL + 1.275 WL

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 5

2. DRAWING
2.1 LOCATION PLAN
2.2 DETAIL SKETCH

Copyright (c) GS E&C. All Rights Reserved


11/11/2017 Page 6

REFERENCE DWGS
NO. DWG NO. DWG TITLE

A01 A02 A03 A04 A05 A06 A07

20000 20000 20000


20000 20000 15000
NOTES
* OUTPUT UNIT : mm

27
14 16 34 28
02 2F2 36 12 18 33 29
F23 4F4 6F6 13 15 F10 32 30
F8 31 F12
20000

19
9 11 26 20
01 1F1 35 25 21
F22 3F3 7
5F5 8 10 24 22
F7 23 F11
AFES VERIFICATION PROJECT

17
F9
FOUNDATION LOCATION PLAN
IS456

SQUAD CHECK
Y PROCESS PIPING VESSELS STRUCT. ELEC. INST.

Z X SCALE JOB NO. MICROFILM NO.

AS SHOWN IS456_SI

Copyright (c) GS E&C. All Rights Reserved


11/11/2017 Page 7

OUTPUT UNIT : mm

Copyright (c) GS E&C. All Rights Reserved


11/11/2017 Page 8

REFERENCE DWGS
87000 NO. DWG NO. DWG TITLE
3000 81000 3000 CL FOOTING CL FOOTING
1150
700 83300 700
1150 TOP BOTTOM TOP BOTTOM

0Y0P.
00

50
@2

@T2
25M

25M
25M@200 25M@200

NOTES
* ANCHOR BOLT
FOUNDATION PLAN FOOTING REINF. PLAN REBAR ARRANGEMENT 1X12-M12 ANC. BOLTS (TYPE TYPE L)

* OUTPUT UNIT : mm
CL PED.
75 PROJ.
30 GROUT

84700
7000 700
38850 38850
75

TOG EL. + 500


10-25M
2000

16M 30
1500

AFES VERIFICATION PROJECT


100
500

LEAN CONC. 50 THK


CRUSHED STONE 100 THK PEDESTAL REBAR
SECTION FOUNDATION DETAIL FOR
F9

SQUAD CHECK
P.)
5M TY
2-2 50(

PROCESS PIPING VESSELS STRUCT. ELEC. INST.


0
70

16M@200
PEDESTAL REBAR ARRANGEMENT SCALE JOB NO. MICROFILM NO.

REV. DATE DESCRIPTION DRWNCHKDAPPDAPPDAPPD


AS SHOWN IS456_SI

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 9

3. FOUNDATION DATA
3.1 FOOTING DATA
Unit : mm Ft. Name F9
87000 Ft. Type TANK 1
3000 3000 Area 791.681 m
2

81000
Ft. Thickness 500.00 mm
3
Ft. Volume 395.841 m
Ft. Weight 9500.184 kN
Outer Soil Height 1500.00 mm
3
Soil Volume 1058.831 m
Soil Weight 21176.620 kN
Buoyancy Not Consider
Self Weight (except Pr.SW) 30676.800 kN

2000

1500

The Origin coordinate


500

The Center of gravity (0,0) mm

3.2 PIER DATA


Off X , Off Y is offset position from the Center of the footing
If Pier Shape is Circle or Circle wall, Pl is a Diameter. and Pw is a Inner Diameter
Area is pier concrete area
Weight is pier and inner soil weight in case circle wall except Tank1 Type(Circle Ring Footing Shape)
2
Unit( Length : mm , Weight : kN , Area : m )
Ft.Name Pr.Name Shape Pl Pw Ph Area Weight Off X Off Y
F9 17 CircleWall 84700.000 83300.000 2000.000 184.726 8866.829 0.000 0.000

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 10

3.3 SECTION DATA


Ft.Name / Sec.Name F9 / S1
87000 Unit : mm
3000 3000
81000

2
Direction All Direct Section Area 791.681 m
3
F.Volume 395.841 m F.Weight 9500.184 kN
3
S.Volume 1058.831 m S.Weight 21176.620 kN
Pier Wt 8866.829 kN Total Weight 39543.630 kN

3.4 LOAD CASE


Fz
Fy
Mz
Input the point loads in the global coordinate system direction. Positive directions of moments (shown in the sketch) are
My based on the right hand rule.
Fx
Mx

Index Load Case Name


1 SW
2 Empty
3 DL
4 Operation
5 Test
8 WL

Unit( kN , kN-m )
Ft.Name Pr.Name Load Case Fx Fy Fz Mx My
1 0.000 0.000 -8866.829 0.000 0.000
2 0.000 0.000 0.000 0.000 0.000
3 0.000 0.000 0.000 0.000 0.000
17
F9 4 0.000 0.000 0.000 0.000 0.000
5 0.000 0.000 0.000 0.000 0.000
8 1906.971 0.000 0.000 21630.430 0.000
Footing SW 0.000 0.000 -30676.800 0.000 0.000

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 11

3.5 LOAD COMBINATION


In Pier Top In Footing Bottom In Footing Bottom Center
without Self Weight with Pier Self Weight, with Pier & Footing Self Weight & Soil Weight,
But without Footing Self Weight, Case PileType
in centroid of Pile Group
Case NonPileType
in centroid of Footing

3.5.1 Load Combination in Pier Top (Without SW)


Unit( kN , kN-m )
Ft.Name Pr.Name L.Comb. SFx SFy SFz SMx SMy
10 0.000 0.000 0.000 0.000 0.000
20 1906.971 0.000 0.000 21630.430 0.000
F9 17
100 0.000 0.000 0.000 0.000 0.000
200 2431.388 0.000 0.000 27578.800 0.000

3.5.2 Load Combination in Footing Bottom (With Pier SW)


Unit( kN , kN-m )
Ft.Name Pr.Name L.Comb. SFx SFy SFz SMx SMy
10 0.000 0.000 -8866.829 0.000 0.000
20 1906.971 0.000 -8866.829 21630.430 4767.427
F9 17
100 0.000 0.000 -12413.560 0.000 0.000
200 2431.388 0.000 -9310.170 27578.800 6078.470

3.5.3 Load Combination in Footing Bottom Center (With Pier & Footing SW)
Load Combination of Elastic Condition
- C.G. of Load is coordinate from left bottom. Unit : mm Unit( kN , kN-m )
Ft.Name L.Comb. SFx SFy SFz SMx SMy C.G. of Loads
10 0.000 0.000 -39543.630 0.000 0.000 43500.0 , 43500.0
F9
20 1906.971 0.000 -39543.630 21630.430 4767.427 43500.0 , 43500.0

Load Combination of Ultimate Condition


- C.G. of Load is coordinate from left bottom. Unit : mm Unit( kN , kN-m )
Ft.Name Sec.Na L.Comb. SFx SFy SFz SMx SMy C.G. of Loads
100 0.000 0.000 -12413.560 0.000 0.000 43500.0 , 43500.0
F9 S1
200 2431.388 0.000 -9310.170 27578.800 6078.470 43500.0 , 43500.0

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 12

4. CHECK OF STABILITY
4.1 CHECK OF SLIDING
mSFz + P.F
Formula : > Fs => OK (Bi-Axial)
SFx + SFy
2 2

P.F = Passive Force (apply only in case checked passive force, mark by P ) Unit ( kN )
( mSFz + P.F ) / SFx + SFy
2 2
Ft.Name Dir. L.Comb. Fs(i) Result
SFx + SFy = 0 , Then N/A
2 2
10 1.6 OK
F9 Bi-Axial
20 0.35 186098.9 / 1906.97 = 34.16 1.6 OK

4.2 CHECK OF OVERTURNING MOMENT


Formula : (SMry / SMoy or SMrx / SMox) > OVM(i) => OK Unit ( kN-m )
Ft.Name Dir. L.Comb. SMry / SMoy = OVM or SMrx / SMox = OVM OVM(i) Result
10 SMo = 0 , Then N/A 1.7 OK
X
20 1720148 / 4767.43 = 360.81 1.7 OK
F9
10 SMo = 0 , Then N/A 1.7 OK
Y
20 -1720148 / -21630.43 = 79.52 1.7 OK

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 13

4.3 CHECK OF CONTACT PRESSURE


4.3.1 Contact Pressure Formula
from API 650 (Tank_1)
* Total vertical pressure loads at bottom of footing by vertical loading
P1 = [( Empty Wt. - Steel Bottom Wt.) + FDN.Wt. + ( Test or Operation Wt. - Empty Wt. ) A2 / A3 ] / A1
* Total vertical pressure loads at bottom of footing by overturning moment loading
1.273 SMx + SMy
2 2

P2 = 2 (Bi-Axial)
Dp Fwid
P3 = [ ( Test or Operation Wt. - Empty Wt. )
+ Steel Bottom Wt. ] / A3 + gs1 h1 + gs2 h2
(Checking of pressure inside the ring wall under the soil)

Qmax = Max ( P1 + P2 , P3 )
Steel Bottom Wt. = Dp p / 4 Bthk W tu SW Load Factor
2

3
W tu = Steel Unit Weight (76.98 kN/m )
A1 = ( D - d ) p / 4
2 2

A2 = ( Dp - d ) p / 4
2 2

A3 = Dp p / 4
2

Dp = Outer Diameter of Equipment Bottom


D = Outer Diameter of Footing
d = inner Diameter of Footing
Fwid = D/2 - d/2
Bthk = Thickness of Eq't Bottom Plate

4.3.2 Input Data


2 4 4
Ft.Name Af (m ) Fl (m ) Fw (m ) Ix (m ) Iy (m )
F9 791.681 87.000 87.000 699153.6000 699153.6000

4.3.3 Pressure Check


- Qa = Soil bearing capacity
- Uc = Uplift Allowable capacity Unit( kN , kN/m )
2

Ft.Name L.Comb. Empty Wt Oper Wt Test Wt St B Wt FDN Wt


10 20421.950 949835.300 1.092 #x 10#o6#p 21331.220 39543.630
F9
20 20421.950 949835.300 1.092 #x 10#o6#p 21331.220 39543.630

SFz SMx +SMy


2 2
Ft.Name L.Comb. P1 P2 P3 Qmax Qa Result
10 -39543.630 0.00 131.158 0.000 177.248 177.248 250.000 OK
F9
20 -39543.630 21630.43 131.158 1.301 177.248 177.248 250.000 OK

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 14

5. DESIGN OF FOOTING
5.1 DESIGN MOMENT AND SHEAR FORCE
Footing design is in accordance with unltimate strength method at footing bottom.
Calculated total pier load as
SQ = SFz - Self Weight Factor (Soil Weight + Footing Weight)
Ft.Name : Footing Name , Sec.Name : Strip Name for Footing Reinforcement Design
Dir. : Direction , L.Comb. : Load Combination Index , Sl or Sw : Strip X or Y width

5.1.1 Data Unit( mm , kN , kN-m )


Ft.Name Sec.Na Dir. L.Comb. Fl or Fw Sl or Sw SFz SM SQ
100 87000.00 87000.00 12413.560 0.00 12413.560
S1 Long
200 87000.00 87000.00 9310.170 6078.47 9310.170
F9
100 87000.00 87000.00 12413.560 0.00 12413.560
S1 Ridial
200 87000.00 87000.00 9310.170 6078.47 9310.170

5.1.2 Design Parameters


Yield Strength - 10M ~ 16M : fy1 , 19M ~ : fy2
f_cl : Clear Cover for edge of footing reinforcement
f_clt : Clear Cover for top of footing reinforcement
f_clb : Clear Cover for bottom of footing reinforcement
Loc. : Location of Critical Point from left side of footing

2
Unit(N/mm ,mm)
f(Flexure) f(Shear) fck fy1 fy2 f_cl f_clt f_clb
0.9 0.8 28.00 420.00 420.00 50.0 50.0 80.0

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 15

5.2 RING WALL DESIGN


5.2.1 Ring Wall Formula
Definitions,
W : Weight of tank shell plus the tributary weight
of a cone roof per feet of circumference (kN/m)
N : Thickness of tank shell plate
BPT : Bottom Plate Thickness
D : Tank diameter
f : Angle of internal friction of soil
H : Height of tank (Height of liquid)
h : Height of ring wall
h1,h2 : Filling material height of ring wall
gs1,gs2 : Unit weight of soil under tank (kN/m )
3

gs1 h1 + gs2 h2
gs =
h1 + h2
3
q = Unit weight of tank fluid (kN/m )
gc = Unit weight of concrete (kN/m )
3

F = Radial outward force on ringwall


T = Axial tension in ring
Ko = Rest Earth Pressure Coefficient

Minimum required thickness of ringwall


The center-to-center diameter of ring wall is equal to the nominal tank diameter.
The tank diameter is 4572mm or more
If above assumptions are not applicable, an alternate foundation type shall be used.
EmptyLoad - Bottom Plate Weight
W= (kN/m)
p tank diameter
3
Bottom Plate Weight = 76.98(kN/m ) Bottom Plate Thickness Bottom Plate Area
2 W
t.cal =
q H - 2 h (gc - gs)
t.min = Minimum wall thickness = 12 in
t.used = User input wall thickness (mm)

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
T
of Project No. : IS456_SI
q
a
Foundation Client : AFES Page 16
n

h1
H Horizontal reinforcement of ringwall
gPu
k s1 2

Pu1 = ko ( h1 + h2 ) q H Pu2 = 1/2 ko gs1 h1


2 Pu1 F

h2
Pu3 = ko gs1 h1 * h2 Pu4 = 1/2 ko gs2 h2
2
Pu3 Pu4 gs2
F = Pu1 + Pu2 + Pu3 + Pu4
T = 1/2 F D , the F(horizontal force) causes a hoop tension in the ring wall
T
Req'd As = Load Factor , f = 0.9
f fy
t
Req'd As must not be less than that required for temperature
& shrinkage reinforcement.
fac : Shrinkage And Temperature Factor T
Reinforcement is more than 60000 psi and 10M ~ 16M..............fac = 0.002

D
else case......................................................................................fac = 0.0025 F
As.Min = factors (By Design Code) ringwall cross section area
Req'd As = Required steel area to resist entire axial tension T

Vertical reinforcement of ringwall


Mu = Load Factor ( Pu1 1/2 ( h1 + h2 ) + Pu2 (1/3 h1 + h2 ) + Pu3 1/2 h2 + Pu4 1/3 h2 )
200 3 fck
Selected As = Max ( fac b h , r.req b d , Min ( 1.333 r.req b d , Max ( bd, bd)))
fy fy
fac : Shrinkage And Temperature Factor
Reinforcement is more than 60000 psi and 10M ~ 16M..............fac = 0.0012
else case......................................................................................fac = 0.0015
Mu 0.85 fck 2Rn
Rn =
fbd
2 , f = 0.9 , r.req =
fy ( 1- 1-
0.85fck )
Asmax = 0.75 rb b d
fck 0.003 Es
rb = 0.85 b1
fy 0.003 Es + fy
If Selected As < Using As < Asmax , then OK!!
When Fdn type is block, Selected As = fac b h

5.2.2 Check of Minimum required Thickness & Reinforcement of ringwall


Footing Name : F9 GroupType : Tank_1
Input Data
2 2 3
Dia (mm ) h (mm ) Hor. Bar Ver. Bar Hor. fy (N/mm ) Ver. fy (N/mm ) rc (kN/m ) Ko Load F.
87000.00 500.00 25M @ 200 mm 16M @ 200 mm 420.00 420.00 24.00 0.500 1.4

Input Equipment Data


gs1 (kN/m ) gs2 (kN/m )
3 3 3
Dia (mm ) H (mm ) N (mm ) BPT (mm ) h1 (m ) h2 (m ) q (kN/m )
84000.01 20000.00 20.00 50.00 0.200 0.300 10.79 11.77 9.81

Result of Thickness
W (kN/m ) t.Cal (mm ) t.Min (mm ) t.Used (mm ) Result
30.79 422.87 304.80 700.00 OK

Result of Hooptension
2 2 2
F (kN/m ) T (kN ) Tu (kN ) As.req (mm ) As.Min (mm ) As.Used (mm ) Result
49.730 2088.641 2924.097 7735.708 3500.000 10799.230 OK

Result of Vertical Reinforcement


2 2 2
b(mm) d(mm) F(kN) Mu(kN-m) As.Used (mm ) As.Selected (mm ) As.Max (mm ) Result
1.00 2.11 196.83 68.81 306.42 382.91 4158.23 NG

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 17

5.3 REQUIRED REINFORCEMENT


5.3.1 Reinforcement Formula
- Shrinkage And Temperature Reinforcement ---- ACI CODE 7.12.2
As As1 = fac b h , fac = following
Area of shrinkage and temperature reinforcement shall provide at least the following ratio
of reinforcement area to gross concrete area, but not less than 0.0014
(a) Slabs where Grade 40 or 50 deformed bars are used ........................................................................0.0020
(b) Slabs where Grade 60 deformed bars or welded wire reinforcement are used....................................0.0018
(c) Slabs where reinforcement with yield stress exceeding 60,000 psi measured at a yield
0.0018 60,000
strain of 0.35 percent is used .......................................................................................................
fy
- Required Reinforcement by Analysis
As As2 = r.req b d
- At every section of flexural members where tensile reinforcement is required
3 fck 200
As (As5 = bw d) (As4 = b d) ---- ACI Eq (10-3)
fy fy
- The requirements of Eq (10-3) need not be applied, if every section As provided is
at least one -third greater then that required by analysis ---- ACI CODE 10.5.3
As3 = 1.333 r.req b d
Asmax = 0.75 rb b d
fck 0.003 Es
rb = 0.85 b 1
fy 0.003 Es + fy
Selected As = Max ( As1 , As2 , Min ( As3 , Max ( As4 , As5 ) ) )
If Selected As < Using As < Asmax , then OK!!

Note : The reinforcement is calculated bases on the maximum moment under the foundation in each direction.
But, the 'ISO' , 'OCT' , 'HEX' , 'COMB' , 'TANK1' foundations are calaulated as face pier
Where,
Mu 0.85 fck 2Rn
Rn =
fbd
2 , f = 0.9 , r.req =
fy
1- 1- (
0.85fck )

Mutop = 0
Mubottom = 0

L = Max( L1 , L2 )
Mutop = 0
2
WL
Mubottom =
2

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 18

5.3.2 Check of Footing Reinforcement


Footing Name : F9 GroupType : Tank_1
- Longitudinal direction

Sec.Nam L.Comb. Using Bar (mm) qmax (kN/m )


2
Width b (m) d (mm) As (mm )
2

200 top 2 - 25M @ 200 52.899 0.305 437.500 981.748


S1
200 botom 2 - 25M @ 200 52.899 0.305 407.500 981.748

Sec.Nam L.Comb. As1(mm )


2
As2(mm )
2
As3(mm )
2
As4(mm )
2
As5(mm )
2
Asmax(mm )
2

200 top 135.098 - - 437.817 418.508 2833.688


S1
200 bottom 135.098 - - 407.795 389.810 2639.377

Sec.Nam L.Comb. Using As(mm )


2
Select As(mm )
2
Result
200 top 981.748 135.098 OK
S1
200 bottom 981.748 135.098 OK

- Radial direction

Sec.Nam L.Comb. Using Bar (mm) qmax (kN/m )


2
Width b (m) d (mm) As (mm )
2

200 top 2 - 25M @ 200 52.899 0.305 412.500 981.748


S1
200 botom 2 - 25M @ 200 52.899 0.305 382.500 981.748

Sec.Nam L.Comb. Mu (kN-m) Rn r.Req


200 top - - -
S1
200 bottom 10.662 0.266 0.0006

Sec.Nam L.Comb. As1(mm )


2
As2(mm )
2
As3(mm )
2
As4(mm )
2
As5(mm )
2
Asmax(mm )
2

200 top 135.098 - - 412.799 394.593 2671.763


S1
200 bottom 135.098 74.156 98.850 382.777 365.895 2477.452

Sec.Nam L.Comb. Using As(mm )


2
Select As(mm )
2
Result
200 top 981.748 135.098 OK
S1
200 bottom 981.748 135.098 OK

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 19

5.4 ONE WAY SHEAR FORCE


5.4.1 One-Way Shear Formula
ACI 318-05 CODE 11.3.1.1
- For members subject to shear and flexure only.
- f Vc = 0.8 2 fck B'w d (eq 11-3)
- Vu <= f Vc , then OK!!

Vu = 0

L = Max( L1 , L2 )
L' = L - d
Vu = WL

5.4.2 Check of One-Way Shear


Footing Name : F9 GroupType : Tank_1 PileType : False

87000 Unit : mm
3000 3000
81000

- Radial direction One-Way Shear


Sec.Nam L.Comb. Loc. (mm) d (mm) Bw (mm) fVc (kN) Vu (kN) Result
100 - 382.5 304.8 81.961 4.713 OK
S1
200 - 382.5 304.8 81.961 3.649 OK

Copyright (c) GS E&C. All Rights Reserved


11/11/2017

Project Na. : AFES VERIFICATION


Calculation Sheet
of Project No. : IS456_SI

Foundation Client : AFES Page 20

5.5 TWO WAY SHEAR FORCE


5.5.1 Two-Way Shear Formula
Vu = SFz Shade Ratio
(a) f Vc1 = 0.8 2 (1 + 2/b c) fck bo d (eq 11-33) <- Vc1
(b) f Vc2 = 0.8 2 (1 + as d / 2 bo) fck bo d (eq 11-34) <- Vc2
(c) f Vc3 = 0.8 4 fck bo d (eq 11-35) <- Vc3
f Vc = Min(f Vc1 , f Vc2 , f Vc3) ACI 318-05 CODE 11.12.2.1
Vu f Vc , then OK
where
b = ratio of long side to short side of the column, concentrated load or reaction area
as = 40 for interior colimns
= 30 for edge columns
= 20 for corner columns
bo = perimeter of critical section
Footing Area - Punching Area
Shade Ratio =
Footing Area

5.5.2 Check of Two-WayShear

2.923 108 mm
2
Ft.Name F9 Punching Area
87000
3000 3000 Pr.Name 17 Ratio Shade 0.631
81000
Shape CircleWall f Vc1 453593.200 kN

L.Comb. 100 f Vc2 153532.500 kN

Pl 84700 mm f Vc3 302395.400 kN

Pw 84700 mm f Vc 153532.500 kN
17
bo / d 527787.6 / 407.5 mm Vu 7830.886 kN

bc / as 1 / 40 Result OK