You are on page 1of 1

Dear Shiferaw Engdawork,

Thanks for your news about the 1600KVA&1000KVA.

Please find the attachment about the ISO certificate for quality of product line.

------------------------------------------------

Regarding the De-rating coefficient, please refer to the engine data sheet with the following
notes.

1)No Engine power decrease with below 40ºC environment temperature and 1500 meter altitude,

2)More than 40ºC and 1500m above sea level , decrease 0.5% per 1ºC , and decrease 4% per
300m;

As per the tender mentioned 1800m@28℃, the De-rating coefficient is less- on G1 (4.5%)
and on G2&G3 (4.5%).

After the de-rating, the output standby power can satisfy the requirement(1600KVA, 1000KVA).

------------------------------------------------

Hope that they will have the updated news again soon.

Best regards,

Bowen