NOTES:

GENERAL
FOR THE LAPS ON ADJACENT SECTIONS OF WIRE FABRICS;
G1 ALL STRUCTURAL DRAWINGS AND ALL RELEVANT DOCUMENTS OF THE CONTRACT SHALL BE READ IN
CONJUNCTION WITH THE SPECIFICATIONS AND DRAWINGS OF OTHER TRADES WHICH FORM PART OF THE - END TO END LAPPING OF THE PIECES IN ONE FULL MESH = 450 mm
CONTRACT. ALL DISCREPANCIES SHALL BE REFERRED TO THE ENGINEER FOR DECISION BEFORE
- SIDE BY SIDE BY PLACING THE TWO SELVAGE WIRES = 900 mm
PROCEEDING WITH THE WORK.
G2 SHOP DRAWINGS SHOWING WATER STOP LAYOUT, INTERSECTION PIECES AND DETAILS, NO WELDING OF REINFORCEMENTS SHALL BE CARRIED OUT UNLESS AUTHORIZED BY AN ENGINEER.
SITE JOINTING METHOD, INSTALLATION PROCEDURES ETC., FOR WATER STOPS, C6 SIZES OF CONCRETE ELEMENTS DO NOT INCLUDE THICKNESS OF APPLIED FINISHES.
JOINT SEALING SYSTEM, ROOF WATER PROOF AND SLIP MEMBRANES SHALL BE
SUBMITTED FOR ENGINEER'S APPROVAL IN ACCORDANCE WITH THE CONTRACT. C7 BEAM WIDTHS ARE WRITTEN FIRST AND FOLLOWED BY BEAM DEPTH WHICH INCLUDE
SLAB THICKNESS.
G3 ALL DIMENSIONS ARE IN MILLIMETRES UNLESS STATED OTHERWISE.
ALL LEVELS ARE EXPRESSED IN METRES. C8 NO HOLES, CHASES OR EMBODIMENT OF PIPES OTHER THAN THOSE SHOWN ON THE
STRUCTURAL DRAWINGS SHALL BE MADE IN CONCRETE MEMBERS WITHOUT PRIOR APPROVAL
G4 ALLOWANCE SHALL BE MADE FOR THE USE OF KICKERS FOR COLUMNS AND WALLS. OF THE ENGINEER.

G5 ALL DIMENSIONS RELEVANT TO SETTING OUT SHALL BE VERIFIED BY THE CONTRACTOR C9 CONSTRUCTION JOINTS SHALL BE PROPERLY FORMED AND USED ONLY WHERE SHOWN
BEFORE CONSTRUCTION AND FABRICATION IS COMMENCED. THE STRUCTURAL DRAWINGS SHALL OR SPECIFICALLY APPROVED BY THE ENGINEER.
NOT BE SCALED BUT ONLY WRITTEN OR CALCULATED DIMENSIONS BE USED.
C10 REINFORCEMENT IS REPRESENTED BY THE FOLLOWING SYMBOLS:
G6 ALL WORKMANSHIP AND MATERIALS SHALL CONFORM TO THE SPECIFICATIONS.
ƒ =(460N/mm²)
T - DEFORMED HIGH YIELD BAR
G7 THE CONTRACTOR SHALL BE RESPONSIBLE FOR TAKING ALL NECESSARY PRECAUTIONS
TO AVOID FLOATATION OF PARTIALLY COMPLETED STRUCTURES. HE SHALL ENSURE THAT ƒ =( 250N/mm²)
R - PLAIN MILD STEEL BAR
NO PART OF THE STRUCTURE SHALL BE OVER STRESSED UNDER CONSTRUCTION ACTIVITIES. THE FOLLOWING ABBREVIATIONS ARE USED IN THIS SET OF DRAWINGS :

G8 THE CONTRACTOR TO VERIFY EQUIPMENT LOCATIONS AND SIZES TO SUIT VENDOR SUBMITTALS. T1 - TOP REINFORCEMENT CLOSEST TO TOP FACE OF THE CONCRETE.
CONCRETE nd
T2 - TOP REINFORCEMENT IN 2 LAYER FROM THE TOP FACE OF THE CONCRETE
C1 CEMENT USED IN THE WORKS SHALL BE ORDINARY PORTLAND CEMENT AS SPECIFIED IN
SPECIFICATION. B1 - TOP REINFORCEMENT CLOSEST TO BOTTOM FACE OF THE CONCRETE.
nd
C2 ALL REINFORCING STEEL BARS SHALL CONFORM TO BS 4449. B2 - TOP REINFORCEMENT IN 2 LAYER FROM THE BOTTOM FACE OF THE CONCRETE
C3 UNLESS SPECIFICALLY STATED OTHERWISE THE GRADE OF CONCRETE USED FOR STRUCTURAL PURPOSES B/W - BOTH WAYS
SHALL BE OF GRADE C35A AND THAT USED FOR BLINDING IS GRADE 15. FOR NORMAL REINFORCED
B/F - BOTH FACES
CONCRETE STRUCTURES. PIPELINE PROTECTION; BENCHING IN MANHOLES AND CHAMBERS USE C25.
C4 UNLESS INDIVIDUALLY SHOWN ON THE REINFORCEMENT DETAILS, THE NOMINAL COVER ALT - ALTERNATIVELY
TO THE REINFORCING BARS IN WATER RETAINING STRUCTURES (INCLUDING LINKS) SHALL BE AS FOLLOWS:
THE NUMBER FOLLOWING THE BAR SYMBOL IS THE NOMINAL BAR DIAMETER IN MILLIMETERS.

ELEMENT CLEAR COVER 10 T 12 _ 01 _ 200


EG.

a) FOUNDATION BOTTOMS CAST AGAINST A


75 mm
LAYER OF BLINDING CONCRETE
NUMBER HIGH YIELD BAR BAR BAR
b) FORMED SURFACE IN CONTACT WITH SOIL OR 50 mm
EXPOSED TO THE WEATHER OR WATER OF BARS DEFORMED BAR DIAMETER MARK SPACING

c) COLUMNS, BEAMS AND WALLS 40 mm


C11 CONCRETE PROTECTION SHALL BE AS SPECIFIED IN SPECIFICATION.

d) TOP AND BOTTOM STEEL OF INTERIOR SLABS 25 mm C12 ALL JOINT SEALANT SHALL BE A TWO PART CHEMICALLY CURING POLYSULPHIDE SEALANT COMPLYING

e) TOP STEEL IN RESERVOIR SLABS 50 mm WITH BS 4254.

C13 JOINT FILLER SHALL BE NON ABSORBENT, SEMI RIGID, CROSS LINKED CLOSE CELL AND HEAT
f) BOTTOM STEEL IN RESERVOIR SLABS 50 mm
LAMINATED POLYETHYLENE FILLER BOARD IN ACCORDANCE WITH BS 6920.
g) COLUMNS AND BEAMS IN RESERVOIR INTERIOR 50 mm
C14 SLIP MEMBRANE SHALL BE OF PRE FORMED LOW FRICTION BEARING STRIP TO FORM A THIN THIN
SLIDING JOINT OF MINIMUM BEARING CAPACITY OF 0.7 N/mm2.
h) INTERIOR FACE OF WALLS IN RESERVOIR 50 mm
C15 RESERVOIR ROOF WATER PROOF SHEET MEMBRANE SHALL BE BITU-THENE 1200 HC. THE WATER PROOFING
MEMBRANE SHALL COMPRISE OF A DURABLE NON-ABSORBENT ELECTROMETRIC SHEET MEMBRANE.
C5 SPLICES IN REINFORCEMENT SHALL BE MADE ONLY IN THE POSITIONS SHOWN BLINDING CONCRETE
OR AS OTHERWISE APPROVED BY THE ENGINEER. THE FOLLOWING LAP LENGTHS B1 A LAYER OF BLINDING OF 75 mm SHALL BE PLACED ON THE UNDERSIDE OF ALL FOUNDATION AND GROUND
SHALL BE USED UNLESS SHOWN OTHERWISE ON THE DRAWINGS. SLABS ORDERED BY THE ENGINEER.

UNLESS OTHERWISE SPECIFIED, LAP LENGTH OF BARS SHALL BE AT LEAST


42 TIMES THE DIAMETER OF THE BAR AND THE LAPS SHALL BE POSITIONED
IN A STAGGERED PATTERN.

CLIENT NATIONAL WATER SUPPLY AND DRAINAGE BOARD REV DESCRIPTION DATE SIGN DESIGNED GI APPROVED IN PRINCIPLE SUBJECT TO THE REV NO DATE
WILGAMUWA HEENGAGA WATER SUPPLY PROJECT CONDITION THAT THE DESIGN & BUILD 0 2017-12-06
GALLE ROAD, RATHMALANA, SRI LANKA. -1 1st SUBMISSION 2017-05-12 DRAWN Kaushi CONTRACTOR IS RESPONSIBLE FOR THE
DESIGN DRAWING TITLE -0 2nd SUBMISSION 2017-07-27 CHECKED AHDS CONFORMITY OF THE DESIGN WITH FUNCTIONALSHEET
& SIZE SCALE
YUNICA ENGINEERS & CONSULTANT STRUCTURAL REQUIREMENTS. A3
NO:157/2, MUIBUN TOWERS DHARMAPALA MAWATHA ,COLOMBO - 07 0 CONSTRUCTION ISSUE 2017-12-06 NOT TO SCALE
NATIONAL WATER SUPPLY AND DRAINAGE BOARD

CONTRACTOR DRG NO
CML-MTD CONSTRUCTION LTD
NO:155, DHARMAPALA MAWATHA,COLOMBO - 07
STRUCTURAL GENERAL DETAILS ...................................................... .............................................. NWS&DB/CP/WIL/700/SD/01
CONTRACT NO PROJECT MANAGER PROJECT DIRECTOR
P&P/D&B/LBF/WILGAMUWA/2014 CML - MTD CONSTRUCTION NWS&DB