You are on page 1of 7

FIRE RESISTANT

CABLES

MANAGEMENT
SYSTEMS MS ISO/IEC 17021 : 2011

LPS BS 6387 : 1994 Cert. No. 1122a

1.5MM2 -630MM2 1 CORE CU/MICA/XLEVA/LSHF (FRMI) IS LPCB APPROVED


01

FIRE RESISTANT CABLES


*1.5MM2 – 630MM2 1 CORE CU/MICA/XLEVA/LSHF (FRMI) IS LPCB APPROVED

1 Core CU/MICA/XLEVA/LSHF 600/1000V (FRMI) (OCC-F6C01)


LPS BS 6387 : 1994 Cert. No. 1122a

(MI) Nominal
cross-
Approx.
Overall
Approx.
Cable
Test Voltage Maximum
conductor
Current Current
rating based rating based
Volt drop for
3 phase
sectional Diameter Weight DC on enclosed on laid in air
area resistance in conduit at at 40°C
at 20°C 30°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)

1.5 5.7 49 3.5 12.1 19 21 27

2.5 6.1 61 3.5 7.41 26 29 16

4 6.9 83 3.5 4.61 35 37 10

6 7.4 105 3.5 3.08 45 46 6.8

10 8.2 149 3.5 1.83 63 62 4.0

16 9.1 209 3.5 1.15 85 94 2.5

600/1000 V FRMI NON-ARMOURED FIRE RESISTANT CABLES 25 10.8 314 3.5 0.727 111 126 1.65

Application 35 12.0 411 3.5 0.524 138 156 1.15


These cables offer enhanced circuit integrity over the same rated power cable. It is mainly used in installation where
vital circuits are required to continue to operate in the event of a fire. It is suited for use in public buildings like
shopping complex, hospitals, theatres, mass transit utilities, oil & gas plants, etc. 50 13.5 542 3.5 0.387 168 190 0.90

Specification 70 15.3 749 3.5 0.268 214 246 0.65


Mica fire barrier, cross-linked low smoke halogen free mineral insulated (XLEVA), low smoke halogen free outer sheathed
Non-Armoured FRMI cables meets the following cable specifications : 95 17.3 1006 3.5 0.193 259 300 0.50
BS 6387 Performance requirements for cables to maintain circuit integrity under fire conditions
IEC 60331 Fire resisting characteristics of electric cables 120 19.0 1253 3.5 0.153 299 350 0.42
IEC 60332-1 Flame retardant characteristics of electric cables
IEC 60332-3 Tests on electric cables under fire conditions Part 3 : Tests on bunched wires or cables
150 20.9 1531 3.5 0.124 328 405 0.37
IEC 60754 Test on gases evolved during combustion of materials from cables
IEC 61034 Measurement of smoke density of cables burning under defined conditions.
185 23.0 1903 3.5 0.0991 370 465 0.32
Construction
The conductor comprises of circular / compacted circular stranded plain annealed copper wires according to IEC 60228. 240 25.8 2461 3.5 0.0754 433 551 0.29

The insulation material consists of a layer of extruded cross-linkable low smoke halogen free mineral filled polyolefin 300 28.4 3052 3.5 0.0601 493 638 0.27
material (FRMI) as per IEC 60092/360, type HF90 with a temperature index of 300°C .
400 32.0 3875 3.5 0.0470 584 746 0.25
The core identification is by coloured insulation FRMI or bicolour lining throughout the core length.
500 35.5 4922 3.5 0.0366 666 852 0.24
For multicore cables, the cores may be laid up with the filler ( non-hygroscopic material ) and a layer of binder shall be
applied over the laid up cores.
630 39.7 6301 3.5 0.0283 764 973 0.23
The inner sheath shall consists of a layer of extruded low smoke halogen free mineral filled (LSHF) compound applied
over the FRMI insulation for single core cable and the binder around the laid up cores for multicore cables. 800 44.8 8025 3.5 0.0221 862 1105 0.22

The outer sheathing shall consist of a layer of extruded LSHF compound in accordance with IEC 60092-360. Special 1000 48.6 9969 3.5 0.0176 934 1228 0.20
outer sheathing material such as LSHF with termite or rodent protection and UV protection are available upon request.

* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
02
03
3 Core CU/MICA/XLEVA/LSHF 600/1000V (FRMI) 1 Core CU/MICA/LSHF/LSHF 600/1000V
Nominal Approx. Approx. Test Voltage Maximum Current Current rating Volt drop for Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop
cross- Overall Cable conductor rating based based on a 3 phase cross- Overall Cable bending Voltage conductor rating rating for 3
perforated based on based on phase
sectional Diameter Weight DC on clipped sectional Diameter Weight radius DC
cable tray
area resistance direct 25°C clipped free air circuit
/ free air at area resistance
at 20°C 30°C
direct trefoil at
at 20°C 25°C 30°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
(mm2) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
1.5 10.5 180 3.5 12.1 22 23 26.83
2.5 11.4 218 3.5 7.41 31 32 16.43 1.5 6.1 54 24 3.5 12.1 24 - 27
4 12.5 275 3.5 4.61 41 42 10.22
6 14.5 343 3.5 3.08 53 54 6.83 2.5 6.5 67 26 3.5 7.41 32 - 16
10 16.3 477 3.5 1.83 72 75 4.06
16 18.2 676 3.5 1.15 98 100 2.55 4 7.5 92 30 3.5 4.61 42 - 10
25 21.5 985 3.5 0.727 121 127 1.61
35 22.8 1296 3.5 0.524 150 158 1.17 6 8.0 116 32 3.5 3.08 55 - 6.8
50 26.3 1704 3.5 0.387 183 192 0.87
70 30.9 2364 3.5 0.268 234 246 0.61 10 8.8 160 35 3.5 1.83 75 - 4.0
95 35.6 3154 3.5 0.193 284 298 0.45
120 38.4 3962 3.5 0.153 328 346 0.36 16 9.7 221 39 3.5 1.15 101 - 2.5
150 45.2 5051 3.5 0.124 378 399 0.31
185 53.3 6394 3.5 0.0991 432 456 0.27 25 11.4 329 46 3.5 0.727 133 138 1.60
240 62.4 8362 3.5 0.0754 510 538 0.23
300 70.0 10531 3.5 0.0601 588 621 0.21
35 12.6 427 50 3.5 0.524 164 171 1.15
400 81.7 13450 3.5 0.0470 680 741 0.19
50 14.1 559 56 3.5 0.387 213 209 0.87
4 Core CU/MICA/XLEVA/ LSHF 600/1000V (FRMI)
70 15.9 768 64 3.5 0.268 273 270 0.61
Nominal Approx. Approx. Test Voltage Maximum Current Current rating Volt drop for
cross- Overall Cable conductor rating based based on a 3 phase 95 18.3 1045 73 3.5 0.193 333 330 0.45
sectional Diameter Weight DC on clipped
perforated
resistance cable tray
area at 20°C direct 25°C / free air at 120 19.6 1276 78 3.5 0.153 387 385 0.37
30°C
(mm2) (mm) (kg/km) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km) 150 21.8 1569 87 3.5 0.124 445 445 0.31
1.5 11.1 222 3.5 12.1 22 23 26.83
2.5 12.4 273 3.5 7.41 31 32 16.43 185 23.6 1931 94 3.5 0.0991 510 511 0.26
4 14.5 350 3.5 4.61 41 42 10.22
6 15.6 443 3.5 3.08 53 54 6.83 240 26.6 2505 160 3.5 0.0754 602 606 0.22
10 17.4 620 3.5 1.83 72 75 4.06
16 19.3 896 3.5 1.15 98 100 2.55 300 29.4 3115 177 3.5 0.0601 695 701 0.2
25 23.6 1315 3.5 0.727 121 127 1.61
35 26.0 1654 3.5 0.524 150 158 1.17 400 33.0 3944 198 3.5 0.0470 809 820 0.18
50 29.7 2208 3.5 0.387 183 192 0.87
70 34.0 3091 3.5 0.268 234 246 0.61 500 36.5 4998 219 3.5 0.0366 922 936 0.16
95 38.9 4148 3.5 0.193 284 298 0.45
120 42.2 5199 3.5 0.153 328 346 0.36 630 40.3 6347 242 3.5 0.0283 1054 1069 0.15
150 47.5 6598 3.5 0.124 378 399 0.31
185 55.8 8351 3.5 0.0991 432 456 0.27 800 44.8 8011 269 3.5 0.0221 1203 1214 0.15
240 66.4 10960 3.5 0.0754 510 538 0.23
300 72.8 13777 3.5 0.0601 588 621 0.21 1000 49.8 10004 299 3.5 0.0176 1349 1349 0.14
400 85.0 17607 3.5 0.0470 680 741 0.19

* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
04
05
3 Core CU/MICA/LSHF/LSHF 600/1000V 4 Core CU/MICA/LSHF/LSHF 600/1000V

Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop
rating rating based rating
cross- Overall Cable bending Voltage conductor rating for 3 cross- Overall Cable bending Voltage conductor for 3
based on a on enclosed based on a
based on phase in conduit phase
sectional Diameter Weight radius DC perforated sectional Diameter Weight radius DC perforated
clipped cable tray
on wall /
cable tray
area resistance area resistance ceiling or in
direct / free air at / free air at
trunking at
at 20°C 25°C 30°C at 20°C 30°C
25°C
2
(mm ) 2
(mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km) (mm ) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)

1.5 11.5 178 92 3.5 12.1 22 23 27 1.5 12.5 214 100 3.5 12.1 20 23 27

2.5 12.4 220 99 3.5 7.41 31 32 16 2.5 13.5 268 108 3.5 7.41 27 32 16

4 14.5 308 116 3.5 4.61 41 42 10 4 15.8 380 126 3.5 4.61 36 42 10

6 15.7 387 125 3.5 3.08 53 54 6.8 6 17.2 480 137 3.5 3.08 45 54 6.8

10 17.4 532 139 3.5 1.83 72 75 4.0 10 19.0 669 152 3.5 1.83 61 75 4.0

16 19.3 731 155 3.5 1.15 98 100 2.5 16 21.2 926 170 3.5 1.15 82 100 2.5

25 22.6 1068 180 3.5 0.727 121 127 1.65 25 24.8 1364 199 3.5 0.727 107 127 1.65

35 25.2 1400 202 3.5 0.524 150 158 1.15 35 27.8 1793 223 3.5 0.524 131 158 1.15

50 28.7 1852 229 3.5 0.387 183 192 0.87 50 31.7 2378 253 3.5 0.387 157 192 0.87

70 32.4 2523 260 3.5 0.268 234 246 0.60 70 36.1 3269 288 3.5 0.268 198 246 0.60

95 37.3 3423 299 3.5 0.193 284 298 0.45 95 41.5 4440 332 3.5 0.193 238 298 0.45

120 40.4 4189 323 3.5 0.153 328 346 0.37 120 44.9 5442 359 3.5 0.153 273 346 0.37

150 44.6 5133 356 3.5 0.124 378 399 0.30 150 49.6 6672 396 3.5 0.124 306 399 0.30

185 49.0 6344 392 3.5 0.0991 432 456 0.26 185 54.7 8280 438 3.5 0.0991 347 456 0.26

240 55.4 8233 443 3.5 0.0754 510 538 0.21 240 61.8 10746 495 3.5 0.0754 406 538 0.21

300 61.5 10244 492 3.5 0.0601 588 621 0.19 300 68.6 13371 549 3.5 0.0601 464 621 0.19

400 69.2 12991 554 3.5 0.0470 680 741 0.17 400 77.2 16955 618 3.5 0.0470 547 741 0.17

* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
06
07
1 Core CU/MICA/LSHF (or PVCFRT) 600/1000V

FIRE RESISTANT CABLES


Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop
rating based
cross Overall Cable bending Voltage conductor rating on
for 3
sectional Diameter Weight radius based enclosed in phase
DC
on clipped conduit on

(XLPE) area resistance


at 20°C
direct at
25°C
a wall / in
truncking at
30°C
2
(mm ) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)

1.5 3.8 27 15 3.5 12.1 23 19 27

2.5 4.2 37 17 3.5 7.41 32 26 16

4 5.1 57 20 3.5 4.61 42 35 10

6 5.7 78 23 3.5 3.08 55 45 6.8

10 6.6 118 26 3.5 1.83 75 63 4.0

1 Core CU/MICA/XLPE/LSHF (or PVCFRT) 600/1000V


Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop
cross Overall Cable bending Voltage conductor rating rating for 3
600/1000 V XLPE NON-ARMOURED FIRE RESISTANT CABLES sectional Diameter Weight radius DC based on based on phase
clipped free air
area resistance
Application direct trefoil at
These cables offer enhanced circuit integrity over the same rated power cable. It is mainly used in installation where at 20°C 25°C 30°C
vital circuits are required to continue to operate in the event of a fire. (mm2) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
It is suited for use in public buildings like shopping complex, hospitals, theatres, mass transit utilities, etc. 1.5 6.0 49 24 3.5 12.1 23 23 27
2.5 6.4 61 26 3.5 7.41 32 32 16
Specification
4 6.9 79 28 3.5 4.61 42 41 10
Mica fire barrier, XLPE insulated, low smoke halogen free outer sheathed Non-Armoured cables meets the following
cable specifications : 6 7.5 101 30 3.5 3.08 55 50 6.8
BS 6387 Performance requirements for cables to maintain circuit integrity under fire conditions 10 8.4 144 34 3.5 1.83 75 68 4.0
IEC 60331 Fire resisting characteristics of electric cables
16 9.6 203 37 3.5 1.15 101 103 2.5
IEC 60332-1 Flame retardant characteristics of electric cables
IEC 60332-3 Tests on electric cables under fire conditions Part 3 : Tests on bunched wires or cables 25 10.7 299 43 3.5 0.727 133 138 1.65
35 12.0 399 48 3.5 0.524 164 171 1.15
Construction 50 13.3 520 53 3.5 0.387 213 209 0.90
The conductor comprises of circular / compacted circular stranded plain annealed copper wires according to IEC
70 15.4 728 62 3.5 0.268 273 270 0.65
60228.
95 17.1 974 68 3.5 0.193 333 330 0.50
The core identification is by coloured XLPE insulation or bicolour lining throughout the core length. 120 18.9 1215 76 3.5 0.153 387 385 0.42
150 20.7 1483 83 3.5 0.124 445 445 0.37
For multicore cable, the cores may be laid up with the filler ( non-hygroscopic material ) and a layer of binder shall be
applied over the laid up cores. 185 22.9 1844 92 3.5 0.0991 510 511 0.32
240 25.7 2389 154 3.5 0.0754 602 606 0.29
The inner sheath shall consists of a layer of extruded low smoke halogen free mineral filled (LSHF) compound applied 300 28.1 2955 169 3.5 0.0601 695 701 0.27
over the XLPE insulation for single core cables and the binder around the laid up cores for multicore cables.
400 31.7 3755 190 3.5 0.0470 809 820 0.25
The outer sheathing shall consist of a layer of extruded LSHF or Flame Retardant PVC (PVCfrt) compound. Special outer 500 35.1 4778 211 3.5 0.0366 922 936 0.24
sheathing material such as LSHF or PVCfrt with termite or rodent protection and UV protection are available upon 630 39.6 6146 238 3.5 0.0283 1054 1069 0.23
request.
800 44.5 7814 267 3.5 0.0221 1203 1214 0.22
1000 49.3 9745 296 3.5 0.0176 1349 1349 0.20

* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
08
09
2 Core CU/MICA/XLPE/LSHF (or PVCFRT) 600/1000V 4 Core CU/MICA/XLPE/LSHF (or PVCFRT) 600/1000V

Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop
rating based rating rating
cross Overall Cable bending Voltage conductor on enclosed for single cross Overall Cable bending Voltage conductor rating for 3
based on a based on a
in conduit based on phase
sectional Diameter Weight radius DC perforated phase a.c sectional Diameter Weight radius DC perforated
on wall /
cable tray clipped cable tray
area resistance ceiling or in area resistance
/ free air at direct / free air at
trunking at
at 20°C 30°C at 20°C 25°C 30°C
25°C
(mm2) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km (mm2) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
1.5 10.9 141 66 3.5 12.1 22 26 31 1.5 12.4 231 74 3.5 12.1 22 23 27
2.5 11.8 169 71 3.5 7.41 31 36 19
4 12.8 211 77 3.5 4.61 41 49 12 2.5 13.4 282 80 3.5 7.41 31 32 16
6 14.0 261 84 3.5 3.08 52 63 7.9 4 14.7 356 118 3.5 4.61 41 42 10
10 15.8 357 95 3.5 1.83 70 86 4.7
16 17.5 468 105 3.5 1.15 93 115 2.9 6 16.1 448 129 3.5 3.08 53 54 6.8
25 16.8 644 101 3.5 0.727 121 149 1.90 10 18.4 627 147 3.5 1.83 72 75 4.0
35 18.5 840 148 3.5 0.524 149 185 1.35
50 21.1 1096 168 3.5 0.387 179 225 1.00 16 20.4 810 122 3.5 1.15 98 100 2.5
70 23.9 1511 191 3.5 0.268 225 289 0.69 25 21.5 1184 129 3.5 0.727 121 127 1.65
95 26.4 2020 211 3.5 0.193 270 352 0.52
120 29.3 2516 234 3.5 0.153 311 410 0.42 35 23.9 1577 191 3.5 0.524 150 158 1.15
150 32.7 3088 261 3.5 0.124 341 473 0.35 50 27.4 2075 219 3.5 0.387 183 192 0.87
185 36.2 3846 290 3.5 0.0991 392 542 0.29
240 40.5 4995 324 3.5 0.0754 468 641 0.24 70 31.7 2920 254 3.5 0.268 234 246 0.60
300 44.5 6193 356 3.5 0.0601 543 741 0.21 95 35.6 3945 284 3.5 0.193 284 298 0.45
400 50.7 7892 406 3.5 0.0470 638 865 0.19
120 39.4 4917 315 3.5 0.153 328 346 0.37

3 Core CU/MICA/XLPE/LSHF (or PVCFRT) 600/1000V 150 44.2 6060 354 3.5 0.124 378 399 0.30

185 49.0 7552 392 3.5 0.0991 432 456 0.26


Nominal Approx. Approx. Minimum Test Maximum Current Current Volt drop
rating based rating
cross Overall Cable bending Voltage conductor on enclosed
for 3 240 54.8 9811 439 3.5 0.0754 510 538 0.21
based on a
in conduit phase
sectional Diameter Weight radius DC perforated 300 60.5 12206 484 3.5 0.0601 588 621 0.19
on wall /
area resistance ceiling or in
cable tray
trunking at / free air at 400 69.2 15582 553 3.5 0.0470 680 741 0.17
at 20°C 30°C
25°C
(mm2) (mm) (kg/km) (mm) (kV/5min) (Ω/km) (Amp) (Amp) (V/A/km)
1.5 11.5 171 69 3.5 12.1 20 23 26.83
2.5 12.4 210 74 3.5 7.41 27 32 16.42
4 13.6 266 81 3.5 4.61 36 42 10.22 1. Current ratings are based on the following conditions:
6 14.8 336 89 3.5 3.08 45 54 6.83 Ambient air temperature 30°C
Ground temperature 25°C
10 16.8 473 101 3.5 1.83 61 75 4.06
Soil thermal resistivity 1.2°C m/w
16 18.6 636 112 3.5 1.15 82 100 2.55
Depth of laying 0.5m
25 19.2 914 115 3.5 0.727 107 127 1.61 Load Factor 100%
35 21.3 1209 170 3.5 0.524 131 158 1.17 Number of circuit 1
50 24.3 1586 195 3.5 0.387 157 192 0.87
70 27.7 2202 222 3.5 0.268 198 246 0.61 2. Ratings factors for other temperature :
95 31.3 2988 250 3.5 0.193 238 298 0.45 Cables in ambient temperature 25°C 30°C 35°C 40°C 45°C
120 34.7 3723 277 3.5 0.153 273 346 0.37 Factor 1.02 1.00 0.96 0.91 0.87
150 38.7 4571 309 3.5 0.124 306 399 0.31
185 42.8 5696 343 3.5 0.0991 347 456 0.26
3. Other Low Voltage Fire Resistance & Medium Voltage Flame Retardant Cables are available upon request
240 48.0 7400 384 3.5 0.0754 406 538 0.21
300 53.0 9208 424 3.5 0.0601 464 621 0.19
400 60.3 11730 483 3.5 0.0470 547 741 0.17

* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
* The content of this catalogue is provided for information only and is to the best of our knowledge correct at the time of printing. The company makes no representations or warranties about the accuracy, reliability, completeness or timeless
of the information in this catalogue. The company in its sole discretion may revise the contained herein at any time without prior notice. Users should independently evaluate the suitability of each product for the desired application.
10
Sales & Marketing Office:
Lot 2008, Level 20, Tower 2, Faber Towers, Jalan Desa Bahagia,
Taman Desa, 58100 Kuala Lumpur, Malaysia.
Tel: +603-7989 1700 Fax: +603-7989 1701 Email: exim@olympic-cable.com.my

Factory (Malaysia):
Olympic Cable Company Sdn Bhd (Co. No. 7644-M )
Lot PT 2126-2131, Jalan PK1, Taman Perindustrian Krubong,
75250 Melaka, Malaysia
Tel: 606-337 3088 / 90 Fax: 606-337 3099 Email: mar@olympic-cable.com.my

Factory (Vietnam):
OVI Cables (Vietnam) Co., LTD
Lot E-4A1-CN & Lot E-4B1-CN, My Phuoc 2 Industrial Park, Ben Cat District,
Binh Duong Province, Vietnam.
Tel: (84) (0650) 553 683/84 Fax: (84) (0650) 553 685

MANAGEMENT
SYSTEMS MS ISO/IEC 17021 : 2011

LPS BS 6387 : 1994 Cert. No. 1122a

v.0416

You might also like