Professional Documents
Culture Documents
-=”
,, .
h:
*
.
r
-. .-
I.
-— . --
.C
.-
. ..
-. -.. ---
. .. . . . . ..—
.. --—. .. . . .—- --
.
. . ..
:--:1
.. .. . .. . . — _
.—.
Washington .
I
May 1937
‘-
.-
-----
/ =. .=. -..—_ . .. . .
I -;,-..-_-, . ..__.
-, ---
----- ----
“5\ .“L-..=
NATIONAL ADVISORY COMMITTEE FOR AERONAUTICS
-.
a TECHNICAL NOTE NO, 602
.—. — .
●
EEAT TRANSFER FRoh4 CYLINDERS HAVING CLOSELy sPAcxD FINS
By Arnold E. Biermann
SUMMARY ..
—.
The heat-transfer coefficients have been determined
for five stee~ cylinders having fins 1.22 inches wide and
the spacing between the fins ranging from 0.022.to 0.131
inch, The cylinders were tested with and without baffles
in a wind tunnel; they were also tested enclosed in jack-
. ets with the cooling air supplied by a blower.
. ...- *
A maximum beat transfer was reached at a fin space of ‘
74 (*WC
~
about 0.045 inch for the cylinders tested with each of the .*<L
three methods of cooling investigated. The rise in temper-
ature of the air ~assing between the fins slid the change . :1
in flow pattern were found to be important factors limit-
ing the heat transfer that may be obtained by decreasing ..
the fin space. — —
.+._ .. .
The use of %affles for directing the air around the.
cylinders with closely spaced fins nroved very effective
in increasing the over-all heat-tra~afor coefficient pro-
vided that the spacing was not appreciably less than that
for maximum heat transfer.
.-
IIITRODUCTIO)I
2
,4
N.A.C.A. Technical Note No. 1302
TEST APPMZATUS
\
I?ive steel cylinders having identical fins of recte.n-
.gular section and of 1.22-inch width and 0.035-inch thick-
Each fin was .
ness, but of varying pitch, were tested-
constructed integrally with that portion of the cylinder
wall which formed its base as shown in figure 1. The cyl-
inder:wall shoul~er of each fin was varied in width by
machining to give pitches of 0.166, 0.135, 0-111, 0=0831
and 0.057 inch and the adjacent shoulder surfaces were
sweated together during assembly to form an integral cyl-
inder. The-test portion of each cylinder was 4.66 inches .
in outside wall. diameter and 5 inches.in length-, The
steel use& TVaS S.A.E. 1050 forged stock, heat-treated to a
Brinell hardness of ajproxi.mately 200. . i
AS the fin width and thickness were the same for all
the cylinders of these tests, the fins will be designated
simply by the pitch of the fins, as 0.166, 0.136, ocll~~
0.083, and 0.057.
1
H,A,.C.A. Technical Note No. 602 3
b
The test cylinders were electrically heated and tested
with guard rings as described in reference 2. The assem-
. bled over-all lengt”h of the guard rl-ng’~-and the test “sec-
tion was in each case 10 inches. In all ‘test-s--theelec-
‘ trical heating elements and measuring instruments were es-
sentially the same as described in reference 2. The loca-
tions of the iron-constantan thermocou~les used-for rneas--
uring the surface temperatures are shown in figure 1. ~~he-
tyne of baffle used is shown in figure “20 The” ratio ‘of the
ex~t area to the are’a between the fins was apprbk~mat-ely
2. This proportion of areas as well as the baffle design
was found in prev”ious tes-&& (’reference “3) to give good re-
sults. The tunnel air speed was measured with a pitot
tube located ahead and to one side of the test cyIinder.
. TESTS
COMPUTATIONS
Surface heat-transfer
—.— coefficients.- The average sur-
face heat-transfer coefficient q was o%tained
..—_.“by div~d-
—
4 ?I.A.C.A. Technical Note No. 602
8
.ing..the heat input per hour by the product of the area of
the total cooling surface and the difference between the
average temperature of the cooling surface and the enter- .
t
ing-air tempe-ratur.e.
u=Q–-
S+tLa
[(2“ 1+2R%
W
--—
)
tanh awl + sb
1.
as derived in reference 2, where
f
N. A. C.A. Technical Note No. 602 5
8 tt
w?, w+ --, effective fin width.
2
. tt, fin-tip thickness, inches. *
PRECISION
s
IJeat-transfer coef~icients.- The maximum errors in the
values of the heat-transfer coefficients o~cuired-~t the
highest rates of the heat flow and are probably less than
+4 percent for U and *5 percent for q. These values in-
clude inaccuracies in measuring the heat input &nd suiiface
temperatures with all~~ance for small unaccotiritea heat iti”-
terchange through the ends of the cylinders. TnaccuFaEi es
.. occurring in the temperature meas”ureme~ts at high rates of
air flow were a chief source of error o~ing’fo the low t“6m-
perature differences obtaihed in this condition. The range
●
●
of average temperature &ifferenCes %etween the cylinder
wall and the entering air extended. from 40° 3’. to ~55° l?.
,— —. — -: ..
. Air smeetl. - The air-speed measurements are accurate
to within 1 percent for speeds a%o~e 4C) rniles’p6r-Kour,
-—... -
and within 3 percent belo~v this speed.
..-
Effect
——— of building
—— um
——— c~nders from separate fins.-
The practicability of using finely pitched finned cylin-
ders is partly determined by the difficulty In fi-~tifacture.
Integral steel cylinders having wide fins and a space be-
tween fins af less than 0.060 inch are very difficult to
machine. For this reason the fins for the present tests
were separately constructed and sweated together at the
shutting shoulders ,that make the cylinder wall. With only .—
radial -d circumferential heat flow, such as iS obtained
. wit’h the guard-ring method of testing> ther~ is little
heat exchange through tle-so-ldered, sufifacea--~d tests have
shown that the results obtained from cylinders cotistiucted,
in this manner are practically the same as for integral
●
cylinders. .— —.
✚✎ ✎
.
6 N.A.C.A. Technical Note No. 602
,
HEA’T-TRANSF3R COEFFICIENTS
.
The local surface heat-transfer coefficients q~ ar e
shown for the various cylinders in figures 4, 5, and 6.
These coefficients are slightly different from the true
coefficients owing to the cirqumi%~ential heat -flow caused
by the temperature gradient existing around the cylinder.
These coefficients,, however, give comparative values of
the heat-transfer distribution and %y this means it is
possible to compare the effectiveness of the various meth-
ods of directing the air over the cylinders.
●
1
N.A,C.A. Technical Note No. 602 7
“+
N.A.C.A. Technical Note No. 602
.
M&KILiUM VALUES OF THE HJ3AT-T!RANSKZR COEFFICIENT
.
A successive reduction in fin space is accompanied by
an increase in the coefficient U up &a maximum value,
as shfiwn by the curves in figure 10. These curves indi-
cate a maximum heat transf~~ with a fin space of approxi-
mately 00045 inch for all three methods of directing the
air over the cylinders and With all lut the lowest air
speeds, for which the space is somewhat larger. In these
curves the coefficient U is dependent on the fin dimen-
sions and on” the surface coefficient q. The fin-surface
area varies inversely as the fin thickness and fin space
and q is dependent almost entirely upon the character
and ‘velocity of the air f-low over the surfaces’. As the
number of fins per inch and the fin area are dependent
upon the fin thickness and fin width as well as the fin
space, it may be shown that the fin space at which the
curves in figure 10 reach maximum values will vary with
the fin thickness and width. The maximum values of U
for any desired fin thickness or fin width may be calcu-
lated from the theoretical equation and a curve Of q
against fin space. -. ...... . ,. . -,
.
lZffect of —-—chan~e in flow D ajtern.-
__ It is well known
that-a trangitj.on from t~b~l~t to laminar flow is accom-
panied by a decrease in the heat: transfer. The effect of .
a probable change in boundary-la”yer flow conditions may be
illustrated by the tests with blower cooling if the assump- .
ti.on is made that the heat transfer or the characteristic
flow over the surface of each fin of a cylinder having
fins spaced relatively far apart remain constant as the
fin Bpace is decreased. If this assumption is made, t-hen
the difference between the calculated U curve obtained
in this manner and..the experimental heat-transfer curve Of
U represents the effect of change in flow pattern. !l?his
effect is shown in figure II as the difference between
curves A and curves E or D, where curve B was de-
rived from tihe experimental data of the %lower tests based
on the difference between the cylinder temperatures and the
.
average air temperature and curve D was calculated from
the experimental q from the blower tests, also based on
the average air-temperature difference. Curve A was .
calculated by the use of a constant obtain.ed from
curve B for a fin space of 0.131 in~h. The cu”rves show
that , with the air speed given, a change in the flow Pat-
tern starts gradually ~i.th a fin space of between 0.065
and 00070 inch and increases to what may ‘be fully devel-
N.A.C.A. Technical Note No. 602
.
oped laminar flow with some fin space less than that for
maximum heat transfer, That such a change in flow also
.
occurs in the wind-tunnel tests is indicated by the curves
in figures 5, 6, and 7 in the comparison between the re-
sults obtained with the 0.057-inch pitch cyli”nder and the”
cylinders having larger pitches. The. tugnel te~ts were,
however, unlike the blower tests in that the decrease in .
heat transfer was caused by the combined effect of chfige
in air-flow characteristics and a reducticn in air velocity
between fins, whereas in the blower tests the average ve-
locity between fins was held constant.
Effect of air-temperature
——= rise.- In the blower tests
it was possible to measure and to calculate the air-
temperature rise. From these data the effect of air-
temperature rise on U is shown in figure 11 as the dif- .-
ference between U based on the average air temperature
difference arourid the cylinder (curve B) and U based on
the inlet-air temperature difference (curve G). The
curves show that the fin space at which U is a maximum
is practically unaffected by an increase in the temperature
of the air. Furthermore, the decrease in U caused by
air-temperature rise is shown to become greater as the fin
space is decreased. Since the amount of air-temperature
rise is directly proportional to the length of any one
flow path between fins, it is evident that in the applica-
tion of closely sPaced fins there is a definite advantage
in making the flow paths aS short as is practical. {
In ad-
dition, short flow paths offer less. res~stance to flow and
therefore should permit cooling with lower pressure heads.. / . .
10 I?.A.C.A. T~chnical No&e No. 602’
. .
CONCLUSIONS --
.
For the cylinders tested it may be concluded that:
REFERENCES
‘z
t, Schey, Oscar If., and Rollin, Vern G. : The Effect of
Baffles on the Temperature Distribution and Heat-
Transfer Coefficients of Finned Cylinders. T.R. .
No. 511, N.A.C.Am, 1934.
.
. —
.
‘J
mall
thloknem -
-
.
v
~’” “a’~ ‘
fi~. a.-SUPOof Wflos
tith mspeet to
and laation
oylinder.
riguro 3.- Jaoket for tasts in whioh m bImm was used
to drw tQecooling air over the qlinders.
4
. Figs. 4a,b
M.A.O.A. ‘Tecbdcal Mote Hi. 602 ,.
.24 I I
#~ 0-
.20 >
c~
.16
.12
,)
.06
4’
\
.04
5
2
g (m)FIn pit oh, O.lea
a o
ok .28
g.
la
. \
:. Air epeed,
m.p.h.
. 1% .24
g
(a
. -
s
+.
.20
m“
. 1—
&
.I_6
0
.1a
44
.
“04i%RTF
0
I I
60
I I I
40
[
60
1
60 100 1=
Position around oylAnder from frent, degreee
I
140
I
I I
160
1
160
Tigure 4a,b.- Va.riatlon of q with p06itiOn .szound the oylltier when tested ui~hout bafflem
in the wind tkel.
—
d.
M.A.C.A. TechnicalHote No. 602 Figs. 40,d,e
Air epeed,
.ao -
I
<L
. 1s
\
< ) >
77
\ \
.la
0\ .
\
1I
~ _ M \
\
I 40
.08 I I-=L I NI
~ . ~ -
.04 - — —
I 1 I I I I
4 I I I I 1“ 1“’-b4\l
! 1 I
) I I I 1 1 1 I
[
(d) Fin pltoh, 0.083
I I I I
11~
I I I I I I
1
I I I [
o
I I
I
I ,
.04 ~
.
~1 I 1..1 I
.I k
. .
._ 7’
.
If. A.C. A. Techoioal Note Ho. 602 TtE9. ~,b, c
●SU
.
.16
.12
. ..
.Oa
.04
. ..
oh
+
*
Id .12
0“
. C6
.94
.08
.
. .04
I I
. ~ /78 I
t *
I 1
0 30 40 84
Poeltion exouml oyllnder from fron$, degreem
Figure 5a,b, o.- Variationof q with position around the oylixxlerwhen teeted with bafflee
in the wind tuknel.
4? .
H.A.C.A, Tecbnioal Mote Ho. 602
. , , x
I I I I 1
1
I I I
1 1 1 I
1
.12 I -1=% 1 I I 1-
.04
.- ..
0
t!:!
(b) Fin’
m
pitoh, 0.138
40
:iiiiiiliiiiiij
%0 80 100 lao 140 160 w)
Position arouncl oylirdle.r
from front, degrees
rigue s-a, b.-Variation of qz with position around the oyllmer when tested in a #aoket with
blower oooling.
. .
& - ““
--
“A .
.
.*
..
i.
.IL.. ““
‘+.
i?. A.O. A. Teohnloal. Note 10. 602 ITfjs. 60, d,e
.,.
.
, —-
. .-
.-
4= “~t I I I -w 16.861 I
I ! 1 ! , , , -1
(d) Fd pit~h, O !083
o I 1
. la / ~ \ I I I I I I
/ ?aight valocity,
Vnpg, lb./eeo ./nq.ft.
t / \
\ 13.8
HIL-!’-4-I \
.o*u4=LH=b . — . — - . — — — — —-
\ 10.4
\
. I i I I I — a a“I
*“. -,
~
I
.041 ~
~ _ I
1 .9?
13, ~
—1 I T I ,
I
(e) Fin Pitoh, 0.067 .37
1 I 1
I
I
.-
. . . . . ●
!
!i
a
6
!
i
-1
16
+
< la
m
P’
OE
04
,,,
I
* . . . . .
8.5
!-a
2.s
ii
8,1
1.9
!!
a
ii
t%
i
1,?
?
1.6 ~
1.3;
D’
1.1
.9
.7
a 4 10 la M
Vfi, 61b./eea./:ftft.
(f) Fin pltoh, 0.0S3 (blcmer ooolei)
I
* . . . ● .
.10 .x) .W .40 ..01 .Oa .0s .04 .OE ,0s ,10
EPY Wmeom fins, s ,icab
(b)
?iEIH 8a, b.- Hf4ut of BWOM be’tmea fim on tho valua of q for ti-tunnal tatio.
:,
I
N.A.C.A. Technical Note ~o. 602 / Fig. 9
———
Yo
.2
(d
— — --—With bafflea
F-J .
El
2 -—. ——— .—.—. -
0 1 23 4 5 6 ‘7,8 9’10”11
Yioightvelocity thro-aghfins, Vmpg ,lb./sec./sftft.
8,
a.
1.
1.
M
!!
H I I /’l i i [%itir.mei,m.p.h,l [ i I
*1.4,h
I / I I I L I w I 1“ , I I I I Ill If I I
* 1 I
l/11. 1111’Niml 1111
Y I I I W ‘i- 1 I I I I II
&
I B /l,J-~l~JwMl!~,
I
i’”alwt I I I I l?wl~l’kl I I
/1 /1 1 I I I I I 1 x I I x I I If
/1/1 I I -L- I
. al , , 1 , 1 ,, I I I I I I I I I I I I I I I I
.Ois .036” .Osa .078 J-al! .Us .1= .016 .Ea .Ga5 ,07s o .ia .C4 .m .9s . lD ,18
S e bhmn finmm,irnh
(0) h- d? -mu, an bfflu [b’
) R UT Bt=a% -h (o) B1OWI OWI1%
(
3“0
‘Tl”’ ~
3 ~
-’
.. — -. A, Constant q
\! B, Based on averege air temp-
I
._~.._ — .- .erature.
C, Based on inlet-air ternper-
28,;+ A---~, ature.
,
.— —1----- — D, Similar to B but calculated
from equation.
2.6~
space for blower cooling at a
weight velocity of 9 lb./sec./s(
.
!
..
—- —.
t
—,——
I I i _.[
● 02 .04 .06 .08 .10 .12
Space between fins, s ,inch