You are on page 1of 3

Customer: RS

Project: GST
No. Document: 001
Date: 17/09/2017

CALCULATION ACCORDING TO EN 13384-1, CHIMNEY WITH NEGATIVE


PRESSURE
HEATING APPLIANCE DATA

Fuel: Natural gas


Appliance type: Over pressured boiler
Condensation: NO
Working conditions: Modulating
Nominal Minimum
Heat output: kW 750 250
Efficiency: % 90 90
Flue gas temperature: ºC 180 120
Minimum draught: Pa 0 0
Mass flow: g/s 348.92 116.31

ENVIRONMENT DATA

Altitude: m 50
Maximum ambient
ºC 15
temperature:
Minimum temperature at the
ºC 0
chimney outlet:
Inside
Installation
building
Wind velocity pressure: NO

CONNECTING FLUE PIPE DATA

Total length (m): 1


Route:
Total height (m): 1
Chimney system: Dinak SW

CHIMNEY DATA

Total length (m): 5


Route: 5 m in the boiler room
Total height (m): 5
Chimney system: Dinak SW
Connection: 90º Tee: 1
Chimney outlet: Open terminal
Elements total zeta
1.2
value:

Calculation according to EN 13384-1 Page 1 of 3


Customer: RS
Project: GST
No. Document: 001
Date: 17/09/2017
COMBUSTION AIR SUPPLY DATA

Boiler room ventilation: Ventilated


Pressure losses (Pa): 0

CALCULATIONS AND CHECKINGS

PRESSURE REQUIREMENTS
Flow safety coefficient SE 1.2
Nominal Minimum
+ Thermal draught in the connection point: PH 19.91 14.02 Pa
- Chimney pressure losses: PR 15.25 1.53 Pa
- Wind velocity pressure: PL 0 0 Pa
Available draught in the connection point: PZ 4.66 12.49 Pa

+ Minimum draught of the heating appliance: PW 0 0 Pa


+ Connecting flue pipe pressure losses: PFV -3.6 -2.96 Pa
+ Combustion air supply pressure losses: PB 0 0 Pa
Required draught in the connection point: PZe -3.6 -2.96 Pa

Fulfills
First pressure requirement: PZ ≥ PZe requireme
nts
At nominal heat output: 4.66 > -3.6 YES
At minimum heat output: 12.49 > -2.96 YES
Fulfills
Second pressure requirement: PZ ≥ PB requireme
nts
At nominal heat output: 4.66 > 0 YES
At minimum heat output: 12.49 > 0 YES
Draught in the installation: PZ - PZe
At nominal heat output: 8.26 Pa
At minimum heat output: 15.45 Pa

Calculation according to EN 13384-1 Page 2 of 3


Customer: RS
Project: GST
No. Document: 001
Date: 17/09/2017
TEMPERATURE REQUIREMENTS Nominal Minimum
Inner wall temperature at chimney outlet: Tiob 104.1 41.2 ºC
Inner wall limit temperature: Tg 0 0 ºC

Fulfills
First temperature requirement: Tiob ≥ Tg requireme
nts
At nominal heat output: 104.1 > 0 YES
At minimum heat output: 41.2 > 0 YES

SIZING

CONNECTING FLUE PIPE


Chimney system: Dinak SW
Inner diameter: mm 350
Outer diameter: mm ---
Designation according to EN 1856-1: T600 N1 W V2 G

Nom Min
Average flue gas velocity: m/s 4.9 1.4
Average flue gas temperature: ºC 178 118
Average outer wall temperature: ºC 127 62

CHIMNEY
Chimney system: Dinak SW
Inner diameter: mm 350
Outer diameter: mm ---
Designation according to EN 1856-1: T600 N1 W V2 G
Nom Min
Average flue gas velocity: m/s 4.8 1.4
Average flue gas temperature: ºC 168 108
Average outer wall temperature: ºC 113 53

CHIMNEY OUTLET
Nom
Flue gas velocity: m/s 4.7
Flue gas temperature: ºC 161
Outer wall temperature: ºC 110

Calculation according to EN 13384-1 Page 3 of 3