I163 can not be used. Although there is no such warning during the writing of a program, a warning message will
appear after the program is downloaded to a PLC.
6. Frequency measurement card triggered interruption:
I180: When the PLC sets up the frequency measurement card in mode 1 (pulse cycle measurement) and mode 3
(pulse number counting) by M1019 and D1034, I180 will be supported as well.
The types and functions of special auxiliary relays (special M) and special data registers (special D) are listed in the
table below. Please be noted that some devices of the same No. may bear different meanings in different series
MPUs. Special M and special D marked with “*” will be further illustrated in the 2.11. Columns marked with “R” refers
to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains unchanged and “#” refers to the system
will set it up according to the status of the PLC.
ES SA Off STOP RUN
Special EH2 EH3
Function EX SX Attribute Latched Default
M SV SV2
SS SC On RUN STOP
M1000* Monitoring normally open contact (A) Off On Off R NO Off
M1001* Monitoring normally closed contact (B) On Off On R NO On
M1002* Enabling positive pulses (On when RUN) Off On Off R NO Off
M1003* Enabling negative pulses (Off when RUN) On Off On R NO On
M1004* On when syntax errors occur Off Off - R NO Off
Password of data backup memory card and
M1005* Off - - R NO Off
password of MPU do not match
Data backup memory card has not been
M1006* Off - - R NO Off
initialized
Data do not exist in the program area of data
M1007* Off - - R NO Off
backup memory card
M1008* Scanning watchdog timer (WDT) On Off Off - R NO Off
Insufficient 24V DC supply, LV signal has been
M1009 Off - - R NO Off
occurred.
ES/SA: PLSY Y0 mode selection, continuous
output when On
M1010 Off - - R/W NO Off
EH2/SV/EH3/SV2: Pulse output when
reaching END instruction
M1011* 10ms clock pulse, 5ms On/5ms Off Off - - R NO Off
M1012* 100ms clock pulse, 50ms On / 50ms Off Off - - R NO Off
M1013* 1s clock pulse, 0.5s On / 0.5s Off Off - - R NO Off
M1014* 1min clock pulse, 30s On / 30s Off Off - - R NO Off
M1015* Enabling high-speed counter Off - - R/W NO Off
M1016* Displaying real time clock in A.D. Off - - R/W NO Off
M1017* 30 seconds correction on real time clock Off - - R/W NO Off
M1018 Flag for radian/degree, On: for degree Off - - R/W NO Off
M1019 Enabling frequency measurement card Off Off - R NO Off
M1020 Zero flag Off - - R NO Off
M1021 Borrow flag Off - - R NO Off
M1022 Carry flag Off - - R NO Off
PLSY Y1 mode selection, continuous output
M1023 Off - - R/W NO Off
when On
M1024 Requesting COM1 monitoring Off - - R NO Off
M1025* There is incorrect request for communication. Off - - R NO Off
M1026 Enabling RAMP module Off - - R/W NO Off
M1027 Number of PR outputs Off - - R/W NO Off
10ms time switching flag.
M1028 Off: time base of T64 ~ T126 = 100ms Off - - R/W NO Off
On: time base of T64 ~ T126 = 10ms