Installation Instruction
ESD-7521-6/17
Raychem
Joint for Single-Core
Polymeric Insulated
Cables
36 kV with
Aluminium Wire Armour
Type: MXAW
Refer to the kit label and the title of the installation instructions.
Components or working steps may have been modified since you last installed this product.
General Instructions
Use a propane (preferred) or butane gas torch.
Adjust the torch to obtain a soft blue flame with a yellow tip.
Keep the torch aimed in the shrink direction to preheat the material.
Clean and degrease all parts that will come into contact with adhesive.
Tubing should be cut smoothly with a sharp knife leaving no jagged edges.
Ensure that the tubing is shrunk smoothly all around before continuing along the cable.
Tubing should be smooth and wrinkle free with inner components clearly defined.
The Information contained in these installation instructions is for use only by installers trained to make electrical power
installations and is intended to describe the correct method of installation for this product. However, TE Connectivity
has no control over the field conditions which influence product installation. It is the user’s responsibility to determine
the suitability of the installation method in the user’s field conditions. TE Connectivity’s only obligations are those in TE
Connectivity’s standard Conditions of Sale for this product and in no case will TE Connectivity be liable for any other
incidental, indirect or consequential damages arising from the use or misuse of the products.
Raychem, TE, TE Connectivity and TE connectivity (logo) are trademarks.
© 2017 TE Connectivity. All Rights Reserved.
ESD-7521-6/17 Page 2/9
Cable Overlap
Overlap the cables to be jointed according to dimensions as Reference line
given in the drawing.
500
Cable 1
Mark the reference line as shown in drawing.
Cable 2
100
Al-wire armour
Oversheath
Cable 1 Cable 2
350 350
Reference line
Core screen
Tape shield
Inner sheath
40 20 20 40
250 250
Cut the cores at the reference line. Remove the inner sheath to dimension as given in the drawing.
Place a wire binder temporarily over the tape shield 40 mm away from the inner sheath cut.
Remove the tape shield against the wire binder.
Thoroughly remove the core screen to the dimension given in drawing, so that the insulation surface is
free from all traces of conductive material.
Note: Do not nick the insulation!
Core screen
Wire shield
Inner sheath
Al-wire armour
Reference line
Oversheath
40 40
230 230
Remove the inner sheath to dimension as given in the drawing. Bend back the shield wires onto the oversheath.
Cover the sharp wire ends with plastic tape. Cut the cores at the reference line.
Thoroughly remove the core screen to the dimension given in drawing, so that the insulation surface is
free from all traces of conductive material.
Note: Do not nick the insulation!
80 80
Completion of Joint
Slide the screened insulation sleeve, the inner sleeve and
the outer sealing sleeve over the cable end where the
2
armour wires are still covered.
The plastic bag of the tubing set can be used as an
additional protection by placing it under the tubing set.
1. Stress control sleeve (black)
2. Screened insulation sleeve (black/red) 4 3 2 1
3. Inner sealing sleeve (black)
4. Outer sleeve (black)
Note: If the tubings cant all be nested together as shown,
position them behind each other, so that they can be
installed in the sequence 1 - 2 - 3 - 4.
Do not park any tubings on the other cable side.
Insert shells
Remove the printed release paper from the void filling tape
(yellow). Apply the tape with a 50 % overlap stretching it to 8
about half of its original width.
Fill up the connector area continuing onto the insulation for
not more than 10 mm. Use the filler to achieve a smooth
transition from the connector onto the insulation. 10
Note: Do not use too much void filler, max. 2 mm over the
connector
Pull the stress control sleeve (black) from the inside of the
tubing set and position it centrally over the connector. Start 9
shrinking in the centre working towards the ends. The tubing
should be fully shrunk and wrinkle free.
30 30
50
Copper mesh
50
Centre the inner sealing sleeve (black) over the joint area.
Start shrinking in the centre, working towards the ends. 12
This sleeve is to seal on to the cable inner sheath.