Professional Documents
Culture Documents
com/9-recommended-practices-for-grounding
During fault conditions, low impedance results in high fault current flow, causing overcurrent
protective devices to operate, clearing the fault quickly and safely. The grounding system also
allows transients such as lightning to be safely diverted to earth.
Bonding is the intentional joining of normally non-current-carrying metallic components to form an electrically
conductive path. This helps ensure that these metallic components are at the same potential, limiting potentially
dangerous voltage differences.
Careful consideration should be given to installing a grounding system that exceeds the minimum NEC
requirements for improved safety and power quality.
Bond all metal enclosures, raceways, boxes, and equipment grounding conductors into one electrically continuous
system. Consider the installation of an equipment grounding conductor of the wire type as a supplement to a
conduit-only equipment grounding conductor for especially sensitive equipment.
The minimum size the equipment grounding conductor for safety is provided in NEC 250.122, but a full-size
grounding conductor is recommended for power quality considerations.
Go back to Index ↑
As permitted by NEC 250.146(D) and NEC 408.40 Exception, consider installing an isolated grounding system to
provide a clean signal reference for the proper operation of sensitive electronic equipment.
Note that the NEC prefers the term isolated ground, while the IEEE prefers the term insulated
ground.
Go back to Index ↑
3. Branch-Circuit Grounding
Replace branch circuits that do not contain an equipment ground with branch circuits with an equipment ground.
Sensitive electronic equipment, such as computers and computer-controlled equipment, require the reference to
ground provided by an equipment grounding conductor for proper operation and for protection from static electricity
and power surges.
Failure to utilize an equipment grounding conductor may cause current flow through low-voltage control or
communication circuits, which are susceptible to malfunction and damage, or the earth.
Surge Protection Devices (SPDs) must have connection to an equipment grounding conductor.
Go back to Index ↑
4. Ground Resistance
Take reasonable measures to ensure that the resistance to ground is 25 ohms or less for typical loads. In many
industrial cases, particularly where electronic loads are present, there are requirements which need values as low
as 5 ohms or less many times as low as 1 ohm.
Go back to Index ↑
5. Ground Rods
Recommended practice is to
space multiple ground rods a
minimum of twice the length of the
rod apart. Install deep-driven or
chemically-enhanced ground rods
in mountainous or rocky terrain,
and where soil conditions are
poor. Detailed design of grounding
systems are beyond the scope of
this document.
Go back to Index ↑
6. Ground Ring
Go back to Index ↑
Earthing electrode
7. Grounding Electrode System The emergency generator connected to the ring-ground, and
additionally grounded to reinforcing rods in its concrete pad (photo
Bond all grounding electrodes that are present,
including metal underground water piping, structural
building steel, concrete-encased electrodes, pipe and rod
electrodes, plate electrodes, and the ground ring and all
underground metal piping systems that cross the ground
ring, to the grounding electrode system.
Go back to Index ↑
The use of surge protection devices is highly recommended. Consult IEEE Standard 1100 (The Emerald Book) for
design considerations. A surge protection system should only be connected to a high quality, low impedance, and
robust grounding electrode system.
Building lightning protection system (photo credit: Schneider Electric)
Generally, a surge protection device should not be installed downstream from an uninterruptible power supply
(UPS). Consult manufacturers’ guidelines.
Go back to Index ↑
Reference // Recommended Practices for Designing and Installing Copper Building Wire Systems – Copper
Development Association Inc.