O246 REF543R EXERCISE 7

Exercise 2

1. Configuring SPA-ZC 400

In this exercise you will select a connectivity package for REF 543 and then
configure SPA-ZC 400 with the help of the connectivity package and the SPA-
ZC 40x Communication Engineering Tool. You will also change the IP
address of SPA-ZC 400.

2.1 REF 543 connectivity package

Start the Connectivity Package Manager by double-clicking the


shortcut on the desktop of your pc.

Select the correct connectivity package 2.1 for REF543R.

2.2 New project with CET for SPA-ZC 400

Start Communication Engineering Tool (CET) for SPA-ZC 40x by


double-clicking the shortcut on the desktop of your PC.
O246 REF543R EXERCISE 7

Create a new project by selecting File / Open/Manage Projects…

Press New Project and fill in the following project information. Press
Create and Open Project.

2.3 Adding SPA-ZC 400 and REF543R

Add SPA-ZC 400 to your project by right clicking with the mouse and
navigating to New / IEC61850 / SPA-ZC40x_v2x. The Object
Properties window can be accessed from View / Object Properties. It
is also advisable to open the output window that will display messages
related to possible errors.
O246 REF543R EXERCISE 7

Add REF543R by right clicking on top of the SPA-ZC 400 with the
mouse and navigating to New / Feeder IEDs / REF541,543,545.

Set the REF properties in the Object Properties window according to


your relay type (ordering number). The relay used in this exercise is
REF543KM129CABA.

2.4 Importing REF configuration

You should import the REF configuration .AR-file to your project by


right clicking with the mouse on top of REF541,543,545 and by
selecting Import.

Select the correct file from your hard drive (C:\O246_Materials) and
press Open.
O246 REF543R EXERCISE 7

Those function blocks that do not contain information relevant to the


IEC 61850 data model are excluded from the tree structure.

Press OK.

The configuration is then imported in CET in IEC 61850 format.

Select LD1 and set the SPA address of REF543R to 7.


Also change Baud Rate to 38400 Bits / s.

2.5 Downloading the configuration to SPA-ZC 400

SPA-ZC 400 is delivered with a default IP address (192.168.2.10)


which has to be changed if you have several SPA-ZC 400 devices in
O246 REF543R EXERCISE 7

your project. Every SPA-ZC 400 in the same system needs a unique IP
address.

The IP address can be checked by using IP Query Tool:

Select SPAZC40x on the tree hierarchy and define a new IP address in


the Object Properties window. The IP address should be changed from
192.168.2.10 to 192.168.2.11. The gateway (this was the IP address
for the pc) can be left as the default 192.168.2.1.

Define also the SNTP Server 1 by entering the IP address of your


computer.

Set the Time Zone Correction in minutes (120).


O246 REF543R EXERCISE 7

Select SPA-ZC 400 in the tree hierarchy and right click with the mouse.
Select CID Export.

Check that Target IP address in the CID Export window is


192.168.2.10. This is the current IP address of SPA-ZC 400. The IP
address will be changed to 192.168.2.11 when you press Write and
download the configuration to SPA-ZC 400.
O246 REF543R EXERCISE 7

Press Write.

Press Yes to accept the change of IP address.

Save the .CID configuration file on your computer by assigning it a file


name and pressing Save.

After downloading the new configuration, open Internet Explorer and


write the IP address of the SPA-ZC 400 in the address field as shown
below. Click on the SPA Unit. The status should show OK, if the
configuration is downloaded successfully.
O246 REF543R EXERCISE 7