You are on page 1of 1

GTP OF 33KV 1250A OUTDOOR ISOLATOR

Sl. No. Description Technical Particulars


1. Make To be filled by manufacturer
2. Mode No. To be filled by manufacturer
3. Main switch Double end break centre post rotating
gang type
4. Service Outdoor
5. Applicable Standards IS : 9921/IEC-129/IEC-62271-102
6. Pole 3-pole gang operated
7. Rated Nominal voltage 33kV
8. Maximum Voltage 36kV
9. Rated Frequency 50Hz
10. System earthing Solidly Earthed
11. Temp rise Over Above Ambient As per IEC
12. Insulation level impulse withstand voltage
a) Across isolating distance 195kV Peak
b) To earth and between poles 170kV Peak
13. One min. Power frequency withstand voltage
a) Across isolating distance 80kV Peak
b) To earth and between poles 70kV Peak
14. Rated current 1250A
15. Short time current for 3 Sec 31.5kA for 3 Sec
16. Operating mechanism Motorised
17. Aux voltage
a) AC voltage 240V
b) DC voltage 220V
18. Safe duration for overload
a) 150% of rated voltage 5 Minute
b) 120% of rated voltage 30 Minute
19. Min. Creepage distance 900mm
20. Mounting structure On GI structure
21. Control Manual/Remote
22. Closing & Opening time of isolator Less than 12 Sec
23. Weight of isolator operating box To be filled by manufacturer
24. Weight of isolator Earth switch operating box To be filled by manufacturer
25. Isolator capable of safety breaking following
duty of current
Inductive 0.7A at 0.15 PF
Capacitive 0.7A at 0.15 PF

You might also like