You are on page 1of 6

DPX-EXP-TPX 7.

5-10
SSB-121-11

BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 08/18/08
(803) 817-5600 or (803) 817-5750 (fax) for further information.

Instrument Air Duplex Expandable to Triplex Single Point Connection (SPC) Base Mount Systems
(7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) System Design Isolation System
The Expandable Instrument Air System shall be of a single Each compressor and motor assembly shall be fully isolated
point connection base mounted design consisting of two from the main compressor module base by means of a four
compressor modules with dryers, and a single control module point, heavy duty, spring isolation system for a minimum of
with control panel, air receiver, filtration system and oil/water 95% isolation efficiency. Where required by local or state
condensate separator. Each module has a maximum base regulation, optional seismically restrained isolators can be
width of 34.50" (88 cm), and be fully compliant with the latest provided at an additional cost.
edition of NFPA 99. The modules shall be assembled as one
unit with single point connections for air discharge, electrical Control Module with Air Receiver/Filter/Regulator
and condensate drain. Piping provisions shall be provided for System
the future expansion module. The control module shall include a NEMA 12, U.L. labeled
Compressor/Dryer Module (Compressor, Drive, Motor, control system, duplexed final line filters, regulators, oil
Piping, Dryer) indicators, and a condensate oil/water separator and dew point
The compressor shall be a high pressure "oil-lubricated" monitor and an air sampling port. All of the above shall be
continuous duty rated type. The design shall be two staged, factory piped and wired in accordance with NFPA 99 and
air-cooled, reciprocating type with corrosion resistant reed include valving to allow complete air receiver bypass. The
type valves with stainless steel reeds. Both oil scrapper ring vertical air receiver shall be ASME Coded, National Board
and piston rings shall be made from long lasting special cast Certified, galvanized, rated for a minimum 250 PSIG design
iron and designed for continuous duty operation. The pressure and includes a liquid level gauge glass, safety relief
crankshaft shall be constructed of forged steel and fully valve, manual drain valve, and automatic solenoid drain valve.
supported on both ends by heavy duty ball bearings and seals. Control System
The crankcase shall be constructed of gray cast iron. The triplex control system shall be supplied with all the
Maximum heat dissipation shall be achieved through cast iron necessary internal wiring and components for the future
cylinders with external cooling vanes. Cylinder sleeves are not expansion module. The control system shall include an HMI
required. Both low and high pressure pistons are made from touch screen control, automatic lead/lag sequencing with
cast aluminum with chrome-moly piston pins. Second stage circuit breaker disconnects for each motor with external
cylinder head shall be equipped with a wired shutdown switch operators, full voltage motor starters, overload protection, 24V
for high discharge air temperature. The connecting rod shall control circuit and hand-off-auto selector switch for each
be of a one-piece design. The compressor shall be v-belt compressor. Automatic alternation of all compressors based
driven through a combination flywheel/sheave and steel motor on first-on/first-off principle with provisions for simultaneous
sheave with tapered bushing and protected by an OSHA operation if required. Automatic activation of reserve unit, if
approved totally enclosed belt guard. A sliding motor required, will activate an audible alarm as well as a visual
mounting base that is fully adjustable through twin adjusting alarm on the HMI. The HMI displays service due, run hours
screws shall achieve belt tensioning. The motor shall be a for each compressor, system status, operating pressure, dew
NEMA rated, open drip proof, 1800 RPM, with 1.15 service point and high discharge air temperature shutdown. A
factor suitable for 208 or 230/460V electrical service. Each complete alarm and service history is available on the HMI.
compressor shall have its own inlet air filter mounted on the
first stage compressor heads. Discharge air from the first Dew Point Transmitter
stage compressor cylinder passes through an air-cooled The control module shall incorporate a dew point transmitter
intercooler prior to entering the second stage. The second that is mounted, pre-piped, wired to the control panel and
stage discharge air then passes through an air-cooled displayed on the HMI touch screen. The transmitter probe
aftercooler designed for a maximum approach temperature of shall be 316L SS with sintered stainless steel filter and thin
12° F complete with moisture separator and zero loss film polymer sensor. The system accuracy shall be ± 2° C.
automatic drain valve prior to entering the dryer. The Dew point alarm shall be factory set at -22° F (-30° C) per
compressor discharge line shall include a flex connector, NFPA 99 with remote alarm contacts in the control panel.
safety relief valve, isolation valve, and check valve. The
discharge air piping shall be of ASTM B-819 copper tubing,
brass, and/or stainless steel. The discharge flex connector shall
be braided 304 stainless steel, brass, or bronze. Each
compressor has its own dedicated dryer. Each dryer is
individually sized for peak calculated demand and capable of
producing a -40° F (-40° C) pressure dew point. Dryer purge
only occurs when its respective compressor is running.
Upstream of the dryer will be a separator with a zero loss
drain valve followed by a 0.01 micron coalescing filter. Both
filters shall have element change indicators.

BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-121-11
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 08/18/08
(803) 817-5600 or (803) 817-5750 (fax) for further information.

AIR DISCHARGE
(WITH SHUT-OFF VALVE) AIR INTAKE FUTURE EXPANSION
3/4" NPT (7.5Hp) FILTER MODULE
1" NPT (10Hp)

FUTURE EXPANSION
MODULE

"C"
"B"

"A2" "A3" "A3" 10 HP W/200 GAL TANK SHOWN


"A1"

MODEL NO. HP RECEIVER (GAL.) A1 A2 A3 B C WEIGHT


HPA-7D-D200-T 7.5 200 3549*
138.0 34.5 34.5 67.0 84.5
HPA-10D-D200-T 10 200 3849*

NOTE: UNIT SHIPPED ASSEMBLED AS SHOWN. BASEFRAMES CAN BE UNBOLTED


FOR PASSAGE THROUGH A STANDARD DOORWAY.
(* TOTAL WEIGHT WITH EXPANSION MODULE)
(Ref. DIA 24-858X-SSB)

Instrument Air System Specifications1 (Expanded System Data)

Complete System Capacity2 System FLA


System3 Receiver4 Noise5
System HP
BTU/HR (Gallons) Level
Model No. 200 psig 208V 230V 460V
HPA-7D-D200-T 7½ 33 34,124 200* 79 69 60 30
HPA-10D-D200-T 10 48 46,028 200* 82 90 78 39

Notes: 1 Normal operating conditions at a maximum ambient of 105 °F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities (reserve compressor on standby) and are shown in Inlet Cubic
Feet per Minute (ICFM). System losses subtracted from pump capacity.
3 All system BTU/HR is shown with reserve compressor on standby.
4 * Indicates standard receiver
5 All noise levels are shown in dB(A) and reflect two pumps running.

BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600 Fax: (803) 817-5750
TPX-EXP-QPX 7.5-10
SSB-121-12

BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 08/18/08
(803) 817-5600 or (803) 817-5750 (fax) for further information.

Instrument Air Triplex Expandable to Quadruplex Single Point Connection (SPC) Base Mount
Systems
(7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) System Design Isolation System
The Expandable Instrument Air System shall be of a single Each compressor and motor assembly shall be fully isolated
point connection base mounted design consisting of three from the main compressor module base by means of a four
compressor modules with dryers, and a single control module point, heavy duty, spring isolation system for a minimum of
with control panel, air receiver, filtration system and oil/water 95% isolation efficiency. Where required by local or state
condensate separator. Each module has a maximum base regulation, optional seismically restrained isolators can be
width of 34.50" (88 cm), and be fully compliant with the latest provided at an additional cost.
edition of NFPA 99. The modules shall be assembled as one
unit with single point connections for air discharge, electrical Control Module with Air Receiver/Filter/Regulator
and condensate drain. Piping provisions shall be provided for System
the future expansion module The control module shall include a NEMA 12, U.L. labeled
Compressor/Dryer Module (Compressor, Drive, Motor, control system, duplexed final line filters, regulators, oil
Piping, Dryer) indicators, and a condensate oil/water separator and dew point
The compressor shall be a high pressure "oil-lubricated" monitor and an air sampling port. All of the above shall be
continuous duty rated type. The design shall be two staged, factory piped and wired in accordance with NFPA 99 and
air-cooled, reciprocating type with corrosion resistant reed include valving to allow complete air receiver bypass. The
type valves with stainless steel reeds. Both oil scrapper ring vertical air receiver shall be ASME Coded, National Board
and piston rings shall be made from long lasting special cast Certified, galvanized, rated for a minimum 250 PSIG design
iron and designed for continuous duty operation. The pressure and includes a liquid level gauge glass, safety relief
crankshaft shall be constructed of forged steel and fully valve, manual drain valve, and automatic solenoid drain valve.
supported on both ends by heavy duty ball bearings and seals. Control System
The crankcase shall be constructed of gray cast iron. The quadruplex control system shall be supplied with all the
Maximum heat dissipation shall be achieved through cast iron necessary internal wiring and components for the future
cylinders with external cooling vanes. Cylinder sleeves are not expansion module. The control system shall include an HMI
required. Both low and high pressure pistons are made from touch screen control, automatic lead/lag sequencing with
cast aluminum with chrome-moly piston pins. Second stage circuit breaker disconnects for each motor with external
cylinder head shall be equipped with a wired shutdown switch operators, full voltage motor starters, overload protection, 24V
for high discharge air temperature. The connecting rod shall control circuit and hand-off-auto selector switch for each
be of a one-piece design. The compressor shall be v-belt compressor. Automatic alternation of all compressors based
driven through a combination flywheel/sheave and steel motor on first-on/first-off principle with provisions for simultaneous
sheave with tapered bushing and protected by an OSHA operation if required. Automatic activation of reserve unit, if
approved totally enclosed belt guard. A sliding motor required, will activate an audible alarms as well as a visual
mounting base that is fully adjustable through twin adjusting alarm on the HMI. The HMI displays service due, run hours
screws shall achieve belt tensioning. The motor shall be a for each compressor, system status, operating pressure, dew
NEMA rated, open drip proof, 1800 RPM, with 1.15 service point and high discharge air temperature shutdown. A
factor suitable for 208 or 230/460V electrical service. Each complete alarm and service history is available on the HMI.
compressor shall have its own inlet air filter mounted on the
first stage compressor heads. Discharge air from the first
stage compressor cylinder passes through an air-cooled Dew Point Transmitter
intercooler prior to entering the second stage. The second The control module shall incorporate a dew point transmitter
stage discharge air then passes through an air-cooled that is mounted, pre-piped, wired to the control panel and
aftercooler designed for a maximum approach temperature of displayed on the HMI touch screen. The transmitter probe
12° F complete with moisture separator and zero loss shall be 316L SS with sintered stainless steel filter and thin
automatic drain valve prior to entering the dryer. The film polymer sensor. The system accuracy shall be ± 2° C.
compressor discharge line shall include a flex connector, Dew point alarm shall be factory set at -22° F (-30° C) per
safety relief valve, isolation valve, and check valve. The NFPA 99 with remote alarm contacts in the control panel.
discharge air piping shall be of ASTM B-819 copper tubing,
brass, and/or stainless steel. The discharge flex connector shall
be braided 304 stainless steel, brass, or bronze. Each
compressor has its own dedicated dryer. Each dryer is
individually sized for peak calculated demand and capable of
producing a -40° F (-40° C) pressure dew point. Dryer purge
only occurs when its respective compressor is running.
Upstream of the dryer will be a separator with a zero loss
drain valve followed by a 0.01 micron coalescing filter. Both
filters shall have element change indicators.

BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-121-12
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 08/18/08
(803) 817-5600 or (803) 817-5750 (fax) for further information.

AIR DISCHARGE
(WITH SHUT-OFF VALVE) AIR INTAKE FUTURE EXPANSION
1" NPT (7.5-10Hp) FILTER MODULE

FUTURE EXPANSION
MODULE

"C"
"B"

"A2" "A3" "A3" "A3"


10 HP W/200 GAL TANK SHOWN
"A1"

MODEL NO. HP RECEIVER (GAL.) A1 A2 A3 B C WEIGHT


HPA-7T-D200-Q 7.5 200 4397*
172.5 34.5 34.5 67.0 84.5
HPA-10T-D200-Q 10 200 4797*

NOTE: UNIT SHIPPED ASSEMBLED AS SHOWN. BASEFRAMES CAN BE UNBOLTED


FOR PASSAGE THROUGH A STANDARD DOORWAY.
(* TOTAL WEIGHT WITH EXPANSION MODULE)
(Ref. DIA 24-860X-SSB)

Instrument Air System Specifications1 (Expanded System Data)

Complete System System Capacity2 System3 Receiver4 Noise5 System FLA


HP
Model No. BTU/HR (Gallons) Level
200 psig 208V 230V 460V
HPA-7T-D200-Q 7½ 49.5 51,186 200* 81 92 80 40
HPA-10T-D200-Q 10 72 69,042 200* 84 119 104 52

Notes: 1 Normal operating conditions at a maximum ambient of 105 °F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities (reserve compressor on standby) and are shown in Inlet Cubic Feet per
Minute (ICFM). System losses subtracted from pump capacity.
3 All system BTU/HR is shown with reserve compressor on standby.
4 * Indicates standard receiver
5 All noise levels are shown in dB(A) and reflect three pumps running.

BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600 Fax: (803) 817-5750
EXPANSION MODULE
7.5-10 BASE MOUNT
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-121-13
Modifications made to meet current CSA Standards may result in changes to Page 1 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 08/18/08
(803) 817-5600 or (803) 817-5750 (fax) for further information.

Instrument Air Simplex Expansion Module Single Point Connection (SPC) Base Mount Systems
(7½ - 10 HP)
SPECIFICATION
SPC (Single Point Connection) Expansion Module Design Isolation System
The Instrument Air Expansion Module shall be of a single Each compressor and motor assembly shall be fully isolated
point connection base mounted design consisting of one from the main compressor module base by means of a four
compressor modules with dryers. The module has a maximum point, heavy duty, spring isolation system for a minimum of
base width of 34.50" (88 cm), and be fully compliant with the 95% isolation efficiency. Where required by local or state
latest edition of NFPA 99. The modules shall be assembled regulation, optional seismically restrained isolators can be
with single point connections for air discharge, electrical and provided at an additional cost.
condensate drain.
Compressor/Dryer Module (Compressor, Drive, Motor,
Piping, Dryer)
The compressor shall be a high pressure "oil-lubricated"
continuous duty rated type. The design shall be two staged,
air-cooled, reciprocating type with corrosion resistant reed
type valves with stainless steel reeds. Both oil scrapper ring
and piston rings shall be made from long lasting special cast
iron and designed for continuous duty operation. The
crankshaft shall be constructed of forged steel and fully
supported on both ends by heavy duty ball bearings and seals.
The crankcase shall be constructed of gray cast iron.
Maximum heat dissipation shall be achieved through cast iron
cylinders with external cooling vanes. Cylinder sleeves are not
required. Both low and high pressure pistons are made from
cast aluminum with chrome-moly piston pins. Second stage
cylinder head shall be equipped with a wired shutdown switch
for high discharge air temperature. The connecting rod shall
be of a one-piece design. The compressor shall be v-belt
driven through a combination flywheel/sheave and steel motor
sheave with tapered bushing and protected by an OSHA
approved totally enclosed belt guard. A sliding motor
mounting base that is fully adjustable through twin adjusting
screws shall achieve belt tensioning. The motor shall be a
NEMA rated, open drip proof, 1800 RPM, with 1.15 service
factor suitable for 208 or 230/460V electrical service. Each
compressor shall have its own inlet air filter mounted on the
first stage compressor heads. Discharge air from the first
stage compressor cylinder passes through an air-cooled
intercooler prior to entering the second stage. The second
stage discharge air then passes through an air-cooled
aftercooler designed for a maximum approach temperature of
12° F complete with moisture separator and zero loss
automatic drain valve prior to entering the dryer. The
compressor discharge line shall include a flex connector,
safety relief valve, isolation valve, and check valve. The
discharge air piping shall be of ASTM B-819 copper tubing,
brass, and/or stainless steel. The discharge flex connector shall
be braided 304 stainless steel, brass, or bronze. Each
compressor has its own dedicated dryer. Each dryer is
individually sized for peak calculated demand and capable of
producing a -40° F (-40° C) pressure dew point. Dryer purge
only occurs when the compressor is running. Upstream of the
dryer will be a separator with a zero loss drain valve followed
by a 0.01 micron coalescing filter. Both filters shall have
element change indicators.

BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600 Fax: (803) 817-5750
This product has been designed to meet U.S. NFPA 99, latest edition.
SSB-121-13
Modifications made to meet current CSA Standards may result in changes to Page 2 of 2
the product's weight and physical dimensions. Please contact BeaconMedæs at 08/18/08
(803) 817-5600 or (803) 817-5750 (fax) for further information.

AIR INTAKE
FILTER
AIR DISCHARGE
3/4" NPT

"B"

"C"

10 HP MODULE SHOWN

"A"

MODEL NO. HP A B C WEIGHT


HPA-7X-D-Y 7.5 38.6 798
34.5 67.0
HPA-10X-D-Y 10 39.2 898

NOTE: UNIT SHIPPED ASSEMBLED AS SHOWN.


(Ref. DIA 24-863X-SSB)

Instrument Air System Specifications1 (Expanded System Data)

Complete System Capacity2 Motor FLA


System Noise3
System HP
BTU/HR Level
Model No. 200 psig 208V 230V 460V
HPA-7X-D-Y 7½ 16.5 17,062 76 22.4 19.5 9.79
HPA-10X-D-Y 10 24 23,014 79 29.2 25.4 12.7
Notes: 1 Normal operating condition at a maximum ambient of 105 °F. Consult factory for higher ambient conditions.
2 All capacities are shown as NFPA system capacities and are shown in Inlet Cubic Feet per Minute (ICFM). System
losses subtracted from pump capacity.
3 All noise levels are shown in dB(A) and reflect one pump running.

BeaconMedæs Š 1800 Overview Drive Rock Hill, SC 29730 Š Phone: (803) 817-5600 Fax: (803) 817-5750