SH: 15 Drianage

163 Providing, laying and jointing glazed stoneware pipes class SP-1
with stiff mixture of cement mortar in the proportion of 1:1 (1
cement : 1 fine sand) including testing of joints etc. complete: 100 4 metre
mm diameter

164 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes
with collars jointed with stiff mixture of cement mortar in the
proportion of 1:2 (1 cement : 2 fine sand) including testing of joints 100 metre
etc. complete:
150 mm diameter
165 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes
with collars jointed with stiff mixture of cement mortar in the
proportion of 1:2 (1 cement : 2 fine sand) including testing of joints 75 metre
etc. complete:
300 mm diameter
166 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse
sand : 10 graded stone aggregate 40 mm nominal size) all-round
S.W. pipes including bed concrete as per standard design: 100 mm 4 metre
diameter S.W. pipe

167 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse


sand : 10 graded stone aggregate 40 mm nominal size) all-round
S.W. pipes including bed concrete as per standard design: 150 mm 100 metre
diameter S.W. pipe

168 Providing and fixing square-mouth S.W. gully trap class SP-1
complete with C.I. grating brick masonry chamber with water tight
C.I. cover with frame of 300x300 mm size (inside) the weight of 8 each
cover to be not less than 4.50 kg and frame to be not less than 2.70
kg as per standard design : 150 x 100 mm size P type With Fly ash
cement (non modular) bricks of class designation 7.5
169 Constructing brick masonry manhole in cement mortar 1:4 ( 1
cement : 4 coarse sand) with R.C.C. top slab with 1:2:4 mix (1
cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal 8 each
size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8
graded stone aggregate 40 mm nominal size), inside plastering 12
mm thick with cement mortar 1:3 (1 cement : 3 coarse sand)
170 Constructing brick masonry
finished with floating coat of manhole
neat cement in cement
and making mortar 1:4 ( in
channels 1
cement : 4 coarse sand) with R.C.C. top slab
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone with 1:2:4 mix (1
cement
aggregate : 220
coarse sand : 4 size)
mm nominal graded stonewith
finished aggregate
a floating20 mm coatnominal
of neat 6 each
size), foundation concrete 1:4:8
cement complete as per standard design:- mix (1 cement : 4 coarse sand : 8
graded
Inside sizestone aggregate
90x80 cm and 40 mm
45 cm nominal
deep size), inside
including C.I.plastering
cover with12
mm thick
framefor (light with
duty) cement mortar
455x610 -mm 1:3
internal (1 cement
dimensions, : 3 coarse
total sand)
weight of
171 Extra
finished depth
with for manholes
floating coat Size 90x80 cm- With making
Fly ash cement (non
cover
modular) and frame
bricks to be
of class notofless
neat
designation than
7.5
cement
38 kgand (weight of cover channels
23 kgin
cement concrete 1:2:4 (1 cement : 2 coarse
and weight of frame 15 kg): With Fly ash cement bricks(non sand : 4 graded stone
aggregate 20class
mm nominal size)7.5
finished with a floating coat of neat 1 metre
modular) of designation
cement complete as per standard design:-
Inside size 120x90 cm and 90 cm deep including C.I. cover with
172 frame
Extra for(medium
depth for duty) 500- mm
manholes Size internal
120x90 cm diameter,
With Fly total weight(non
ash cement of
cover and frame to be not less
modular) bricks of class designation 7.5 than 116 kg (weight of cover 58 kg
and weight of frame 58 kg) : With Fly ash cement (non modular) 1 metre
bricks of class designation 7.5

Sub Head 15 TOTAL:


SH: 16 Pile Work

173 Boring, providing and installing bored cast-in-situ reinforced


cement concrete piles of grade M-25 of specified diameter and
length below the pile cap, to carry a safe working load not less than 1188 metre
specified, excluding the cost of steel reinforcement but including
the cost of boring, with bentonite solution and temporary casing of
appropriate length for setting out and removal of same and the
174 Boring,
length ofproviding
the pile to and installing inbored
be embedded the pilecast-in-situ
cap etc. all reinforced
complete,
cement
including removal of excavated earth with all lifts anddiameter
concrete piles of grade M-25 of specified and
leads (Length
length below the pile cap, to carry a safe working load
of pile for payment shall be measured upto bottom of pile cap)- not less than 663 metre
specified,
500 mm dia excluding
piles the cost of steel reinforcement but including
the cost of boring, with bentonite solution and temporary casing of
appropriate length for setting out and removal of same and the
175 Vertical
length ofload testing
the pile to beof embedded
piles in accordance
in the pilewith IS 2911
cap etc. (Part IV)
all complete,
including installation
including removal of loadingearth
of excavated platform and
with all liftspreparation of pile
and leads (Length
head or construction of test cap and dismantling
of pile for payment shall be measured upto bottom of pile cap)- of test cap after 2 per test
test
750 mmetc. dia
complete
piles as per specification & the direction of Engineer-
in-Charge.- Single pile above 50 tonne and upto 100 tonne capacity
pile testing - Initial test
176 Vertical load testing of piles in accordance with IS 2911 (Part IV)
including installation of loading platform and preparation of pile
head or construction of test cap and dismantling of test cap after 6 per test
test etc. complete as per specification & the direction of Engineer-
in-Charge.- Single pile above 50 tonne and upto 100 tonne capacity
pile testing - Routine test
177 Integrity testing of Pile using Low Strain/ Sonic Integrity Test/ Sonic
Echo Test method in accordance with IS 14893 including surface
preparation of pile top by removing soil, mud, dust & chipping lean 91 per test
concrete lumps etc. and use of computerised equipment and high
skill trained personal for conducting the test & submission of
results, all complete as per direction of Engineer-in-charge.
Note:- The inclusion of the above item in the schedule of work shall
be judiciously decided by the technical sanctioning authority,
keeping in view the quality Sub Head
control, type16 TOTAL:
of soil strata & importance
of the project.

SH: 17 Aluminium Work

178 Providing and fixing aluminium work for doors, windows,


ventilators and partitions with extruded built up standard tubular
sections/ appropriate Z sections and other sections of approved 2400 kg
make conforming to IS: 733 and IS: 1285, fixing with dash fasteners
of required dia and size, including necessary filling up the gaps at
junctions, i.e. at top, bottom and sides with required EPDM rubber/
179 Providing
neoprene gasketand fixing aluminiumsections
etc. Aluminium work shall
for doors,be smooth, windows,rust
ventilators and partitions with extruded built up
free, straight, mitred and jointed mechanically wherever required standard tubular
sections/
including appropriate
cleat angle,Z Aluminium
sections andsnap otherbeading
sectionsfor of glazing
approved/ 600 kg
make conforming to IS: 733 and IS: 1285, fixing
paneling, C.P. brass / stainless steel screws, all complete with dash fasteners
as per
of required dia and size, including necessary filling
architectural drawings and the directions of Engineer-in-charge. up the gaps at
junctions, i.e.
(Glazing, panelingat top, bottom
andand and sides
dashsupplying with
fastenersvision required
to be paid panels EPDM rubber/
for separately)
180 Providing,
neoprene assembling
gasket sections glass (IGUs)rust in:
For fixed portion
aluminium/ UPVC -etc. Aluminium
Powder coatedventilators
windows, aluminium shall be smooth,
(minimum
and thickness
partitions etc.
free, straight,
of powder coating mitred and jointed
50 micron) mechanically wherever required
comprising
including cleat of hermetically-sealed
angle, Aluminium 6-12- snap 6 mm insulated
beading for glazing glass/ 435 sqm
(double
paneling,glazed)
C.P. brassvision panel units
/ stainless steelof screws,
size andallshape as required
complete as per
and specified,drawings
architectural comprising andof an
theouter heat strengthened
directions float glass
of Engineer-in-charge.
6mm thick,
(Glazing, of approved
paneling and colour
dash (Titanium
fasteners to be blue)
paid and
for shade with:
separately)
181 Providing
reflective and coating
soft fixing 12onmm thick# frameless
surface toughened glassshade,
door
For shutters
shutter ofHeat of doors,brand
approved windowsand &2 ventilators
of approved
manufacture,
colour and
including providing
an inner
and fixing tophinges/strengthned
pivotspivot clear
and making float glass
provision 6mm thick
forarrangement including
fixing of fittings
providing EPDM & bottom
gasket, & spring
perforated type fixing
aluminium and 39 sqm
wherevernecessary
making required including
holes etc. the
for cost
fixing EPDM spacers,
of required rubber
door /desiccants,
neoprene
fittings, all
sealant
gasket (Both
required primary and
(Fittings shall secondary sealant)
be paid for separately) etc. as
- Powder per
complete as
specifications, per direction of Engineer-in-charge
drawings and thickness
direction ofof powder (Door handle,
Engineer-in-Charge lock
coated
and aluminium
stopper etc.to be(minimum
paid separately). coating 50
complete.
micron)
The IGUs shall be assembled in the factory/ workshop of the glass
processor. For payment, only the actual area of glass on face # 1 of
the glass panels (excluding the areas of the grooves and weather
silicone sealant) provided and fixed in position, shall be measured
in sqm. (i) Coloured tinted float glass 6mm thick substrate with
reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat
182 Filling the gap in between aluminium frame & adjacent RCC /
Brick / Stone work by providing weather silicon sealant over backer
rod of approved quality as per architectural drawings and direction 270 metre
of Engineer-in-Charge complete. Upto 5 mm depth and 5 mm width

Sub Head 17 TOTAL:

SH: 18 Water Proofing

183 Providing and laying water proofing treatment to vertical and


horizontal surfaces of depressed portions of W.C., kitchen and the
like consisting of: 325 sqm
i) Ist course of applying cement slurry @ 4.4 Kg/ sqm mixed with
water proofing compound conforming to IS : 2645 in recommended
proportions including rounding off junction of vertical and
184 Providing and Placing in position suitable PVC water stops
horizontal surface
conforming
ii) IInd coursetoofIS:2012200 for construction/expansion
mm cement plaster 1:3 (1 cement : 3joints coarse
between two RCC members
sand) mixed with water proofing compound and fixed to thein reinforcement
recommended 280 metre
with
proportionbinding wirerounding
including beforeoffpouring
junctionconcrete
of verticaletc.
and complete.
horizontal
Serrated
surface. with central bulb(225 mm wide, 8-11 mm thick)
185 iii) IIIrd course
Providing andoflaying
applying blown or
integral residualbased
cement bitumen applied
water hot at
proofing
1.7 kg per sqm
treatment of area. preparation of surface as required for
including
iv) IVth course
treatment of 400balconies,
of roofs, micron thick PVC sheet.
terraces (Overlapsofatfollowing
etc consisting joints of 640 sqm
PVC sheet should
operations: be 100
a) Applying mm wide
a slurry coatand pasted
of neat to each
cement usingother
2.75with
kg/
bitumen
sqm of @cement
1.7 Kg/sqm).
admixed with water proofing compound
conforming to IS. 2645 and approved by Engineer-in-Charge over
the RCC slab including adjoining walls upto 300 mm height
including cleaning the surface before treatment. b) Laying brick
bats with mortar using broken Sub bricks/brick
Head 18 bats TOTAL:25 mm to 115 mm
size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand)
admixed with water proofing compound conforming to IS : 2645
and approved
C-1 : IEI AND by Engineer-in-Charge
FANS, STREET over 20 mm thick
LIGHTING AND layerPUMP
of SETS
cement mortar of mix 1:5 (1 cement : 5 coarse sand) admixed with
water proofing compound conforming to IS : 2645 and approved by Quantit
S.No Engineer-in-Charge to required Description
slope and treating similarly the Unit
adjoining walls upto 300 mm height including rounding of junctions y
of walls and slabs c) After two days of proper curing applying a
second coat of cement Sub-head
slurry using -2.75 I (Wiring)
kg/ sqm of cement
admixedfor
Wiring with water
light proofing
point/ compound
fan point/ exhaustconforming
fan point/ to call
IS : bell
2645
and
pointapproved
with 1.5by Engineer-in-Charge.
sq.mm FRLS PVC insulated d) Finishing
coppertheconductor
surface with
20 mmcore
single thickcable
jointless cement
in surface mortar ofmedium
/ recessed mix 1:4class
(1 cement
PVC : 4
coarse
conduit, sand)
withadmixed
modular with watermodular
switch, proofingplate,
compound
suitableconforming
GI box
1 to
andIS:earthing
2645 and theapproved
point with by 1.5
Engineer-in-Charge
sq.mm. FRLS PVC including
insulated laying
glass fibre cloth of approved quality in top layer of plaster and
copper conductor single core cable etc as required.
finally finishing the surface with trowel with neat cement slurry and
making pattern of 300x300 mm square 3 mm deep. e) The whole
terrace so finished shall be flooded with water for a minimum
period of two weeks for curing and for final test. All above
a) Group Cto be done in order and as directed and specified by the
operations 924 Point
Engineer-in-Charge:
Wiring for light/ power plug with 2 x 4 sq. mm FRLS PVC
With average
insulated copperthickness of 120
conductor mmcore
single and cable
minimum thickness at
in surface/
khurra
recessed as 65 mm class PVC conduit alongwith 1 No 4 sq. mm
medium
2 FRLS PVC insulated copper conductor single core cable for 1000 Metre
loop earthing as required.
Wiring for light/ power plug with 4 x 4 sq. mm FRLS PVC
insulated copper conductor single core cable in surface/
recessed medium class PVC conduit alongwith 2 Nos 4 sq.
3 mm FRLS PVC insulated copper conductor single core cable 700 Metre
for loop earthing as required.

Wiring for circuit/ submain wiring alongwith earth wire with


the following sizes of FRLS PVC insulated copper conductor,
4 single core cable in surface/ recessed medium class PVC
conduit etc. as required.

a) 2 x 1.5 sq.mm + 1 x 1.5 Sq.mm earth wire 700 Metre


b) 2 x 6 sq.mm + 1 x 6 Sq.mm earth wire 300 Metre
c) 4 x 6 sq.mm + 2 x 6 Sq.mm earth wire 500 Metre
Supplying and drawing following sizes of FRLS PVC insulated
copper conductor, single core cable in the existing surface/
5 recessed steel/ PVC conduit/ PVC trunking as required.

a) 6 x 1.5 sq.mm 400 Metre


b) 9 x 1.5 sq.mm 650 Metre
c) 3 x 4 sq.mm. 40 Metre
d) 6 x 4 sq.mm. 30 Metre
e) 9 x 4 sq.mm. 200 Metre
Supplying and fixing of following sizes of medium class PVC
conduit along with accessories in surface/ recess including
6 cutting the wall and making good the same in case of
recessed conduit etc. as required.

a) 20 mm 700 Metre
b) 25 mm 2000 Metre
c) 32 mm 200 Metre
Supplying and fixing of 100mm x 50mm size polycarbonate
cable management system (wall trunking) on surface/
ceiling with all accessories such as external, internal angles,
7 joint cover, internal coupler, flat cross, cable divider, cable 100 Metre
retainer and end cap complete as required.

Supplying and fixing suitable size GI box with modular plate


and cover in front on surface or in recess, including providing
and fixing 3 Nos. of 3 pin 5/6 amps modular socket outlets
8 and 3Nos.5/6 amps modular switch , connection etc. as 160 Each
required. (Computer Sockets)

Supplying and fixing suitable size GI box with modular plate


and cover in front on surface or in recess, including providing
and fixing 1 No. of 6 pin 15/16 amps modular socket outlet, 2
Nos. of 3 pin 5/6 amps modular socket outlets, 1 No. 15/16
9 amps modular switch and 2 Nos. 5A modular switch, 75 Each
connection etc. as required.(refer IEI & Fans Condition
No:35.4)
Supplying and fixing suitable size GI box with modular plate
and cover in front on surface or in recess, including providing
and fixing 2 Nos. of 5/6 amps modular switches and 2 Nos. of
10 3 pin 5/6amps modular socket outlets ,connection etc. as 30 Each
required.

Supplying and fixing suitable size GI box with modular plate


and cover in front on surface or in recess, including providing
and fixing 3 pin 5/6 amps modular socket outlet and 5/6
11 amps modular switch, connection etc. as required.(For CCTV) 3 Each

Supplying, installation, testing and commissioning of Passive


infrared (PIR) technology based occupancy sensor having
high performance, non regulating programmable type,
suitable for connected load upto 10 Amp, for mounting height
upto 2.8 mtr. And for 5m diameter coverage and along with
12 necessary fixing arrangement i/c. programming at site etc,. 12 Each
complete as required.

Supplying, installation, testing and commissioning of


13 electronic type call bell fixing on the wall etc., complete as 15 Each
required.
Supplying and fixing following modular switch/ socket on the
existing modular plate & switch box including connections
14 but excluding modular plate etc. as required.

a) 5/6 amp switch 115 Each


b) 3 pin 5/6 amp socket outlet 115 Each
Supplying and fixing stepped type electronic fan regulator on
the existing modular plate switch box including connections
15 but excluding modular plate etc. as required. 41 Each

Supplying and fixing following size/ modules, GI box along


with modular base & cover plate for modular switches in
16 recess etc as required. (For Telephone & Data point)

a) 1 or 2 Module (75mm x 75mm) 171 Each


Supplying and drawing following pair 0.5 mm dia FRLS PVC
insulated annealed copper conductor, unarmored telephone
17 cable in the existing surface/ recessed steel/ PVC conduit as
required.

a) 2 pair 600 Metre


Supplying and drawing of UTP 4 pair cat 6 LAN cable in the
18 existing surface/ recessed PVC/ Steel conduit as required. 1700 Metre

Supplying and fixing following modular switch/ socket on the


existing modular plate & switch box including connections
19 but excluding modular plate etc. as required.

a) Telephone socket outlet 43 Each


b) RJ 45 Socket - CAT-6 129 Each
Supplying and fixing of following pair crone box on surface,
20 i/c. fixing crone, termination of telephone wires etc. as
required.
a) 20 pair crone box 7 Each
Sub Head I TOTAL:
Sub-head - II (Fittings & Fans)
Supply, Installation, testing and commissioning of recess
mounted 600mm x 600mm LED light fitting having colour
temperature not less than 5700K, system lumen output not
less than 2850lm and system wattage not more than 40W,
CRI not less than 70 made of CRCA powder coated body with
high transmittance diffuser, buit in electronic driver
1 suspended from ceiling with chain link arrangement, 262 Each
including connections with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable in flexible metal conduit
and earthing etc. as required.

(Note: Gap between the RCC ceiling slab and false ceiling will
be 1.2m approx.)
Supply, Installation, testing and commissioning of recess
mounted circular LED Down lighter fitting with colour
temperature not less than 5700K, system lumen output not
less than 900lm and system wattage not more than 15W, CRI
not less than 70 made of die cast aluminium body with high
transmittance diffuser, buit in electronic driver suspended
2 from ceiling with chain link arrangement, including 54 Each
connections with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable in flexible metal conduit and
earthing etc. as required.

(Note: Gap between the RCC ceiling slab and false ceiling will
be 1.2m approx.)
Supply, Installation, testing and commissioning of recess
mounted square or rectangular LED Down lighter fitting
with- colour temperature not less than 5700K, system lumen
output not less than 850lm and system wattage not more
than 17W, CRI not less than 70 made of made of CRCA
powder coated body with high transmittance diffuser, built in
3 electronic driver suspended from ceiling with chain link 29 Each
arrangement, including connections with 1.5 sq.mm FRLS
PVC insulated copper conductor single core in flexible metal
conduit cable and earthing etc. as required.

(Note: Gap between the RCC ceiling slab and false ceiling will
be 1.2m approx.)
Supply, Installation, testing and commissioning of surface
mounted circular LED Down lighter fitting with colour
temperature not less than 5700K, system lumen output not
less than 800lm and system wattage not more than 15W, CRI
not less than 70 made of die cast aluminium body with high
transmittance diffuser, built in electronic driver, mounted
4 directly on wall/ ceiling, including connections with 1.5 103 Each
sq.mm FRLS PVC insulated copper conductor single core
cable and earthing etc. as required.

Supply, Installation, testing and commissioning of surface


mounted Suare of rectangle LED Down lighter fitting with
colour temperature not less than 5700K, system lumen
output not less than 900lm and system wattage not more
than 18W, CRI not less than 70 made of CRCA powder coated
body with high transmittance diffuser, buit in electronic
5 driver, mounted directly on wall/ ceilinig, including 87 Each
connections with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable and earthing etc. as required.

Supply, Installation, testing and commissioning of surface


mounted 1200mm long tube light LED fitting with colour
temperature not less than 5700K, system lumen output not
less than 3500lm and system wattage not more than 40W,
CRI not less than 70 made of CRCA powder coated body/ die
cast aluminium body/ galvanised steel body with high
6 transmittance diffuser, buit in electronic driver, mounted 78 Each
directly on wall/ ceilinig, including connections with 1.5
sq.mm FRLS PVC insulated copper conductor single core
cable and earthing etc. as required.

Supply, Installation, testing and commissioning of surface


mounted LED mirror lightfitting with colour temperature not
less than 5700K, system lumen output not less than 600lm
and system wattage not more than 8W, CRI not less than 70
made of CRCA powder coated body with high transmittance
diffuser, buit in electronic driver, mounted directly on wall/
7 ceilinig, including connections with 1.5 sq.mm FRLS PVC 7 Each
insulated copper conductor single core cable and earthing
etc. as required.
Supply, Installation, testing and commissioning of surface/
suspension mounted LED high bay light fitting with colour
temperature not less than 5700K, system lumen output not
less than 13800lm and system wattage not more than 150W,
CRI not less than 70, made of die cast aluminium body with
clear glass, heat sink, buit in electronic driver, mounted
8 directly on wall/ ceilinig, including connections with 1.5 8 Each
sq.mm FRLS PVC insulated copper conductor single core
cable and earthing etc. as required.

Supplying, installation, testing and commissioning of


electric ceiling fan 1400 mm SWEEP capacitor type with
double ball bearing complete with capacitor, 300mm down
rod, canopies, three number blades made of aluminium alloy,
9 but without speed regulator, suitable for operation on single 41 Each
phase AC, 230 Volts, 50Hz supply and Low voltage operation
etc. as required

Supply, Installation testing & commissioning of following


sweep exhaust fan with engineering plastic blades etc., in the
existing opening, including outer grill, making the hole to suit
10 the size of the above fan, making good the damage,
connections, earthing, testing & commissioning etc. but
without louver as required.

a) 305 mm sweep 28 Each


b) 225/230 mm sweep 7 Each
Sub Head II TOTAL:
Sub-head - III (Rising Main & MCBDBs)
Supplying, installation, testing and commissioning of floor
mounted indoor type cubicle panel of size not less than 1.20
m (H) x 1.30m (W) x 0.3m (D) made out of 2 mm thick CRCA
sheet for frame work and covers, compartmentalised, dust
and vermin proof, hinged doors with knobs 3 MM thick gland
plate i/c. cleaning and finishing with 7 tank process for
powder coating in approved shade, 100 amps capacity TPN
aluminium bus bars of high conductivity, DMC/ SMC bus bar
supports, PVC sleeves, bottom base channel of ISMC 75X40
( 7.14 Kg/m), G.I earth bar of size 25mm x 5 mm at the rear
for the entire width of the panel with 2 nos. earth studs
,connections, from busbar to switchgear and control wiring
with required size solid aluminium bus/ FR PVC insulated
1 copper conductor cable of suitable size, cable alley, cable
gland plates including providing and fixing the following
switchgear, as per attached specifications and confirming to
the CPWD general specifications part-I(Internal) , part-
II(External) part-IV (Sub station) as amended upto date
complete ., as required . ( Lighing Floor DB )

I) Incomer:
a) 63 A, 25KA breaking capacity ( Ics=100% Icu) 4 pole MCCB
with thermal magnetic release with over load, short circuit
protection, earth fault protection and suitable for
Communication Compatibility Port for BMS complete as
required - 1 No.

II) Bus Bar Chamber:


4 Strip aluminium bus bars of 100 Amps capacity with heat
shrinkable coloured sleeves and i/c DMC/SMC bus bars
supports at required intervals complete for cross section, size
supports & their spacing etc.

III) Out goings:


a) 32A, 25 KA breaking capacity ( Ics= 100%Icu) 4 pole
MCCB with Thermal Magnetic Release and suitable for
Communication Compatibility Port for BMS- 3 Nos.
b). Load manager - 1no.
c). 100 / 5 amps CTs - 3 nos.
d) LED indication lamps holders ,back up protection HRC
fuses with base unit - 3 set 7 job
Supplying, installation, testing and commissioning of floor
mounted indoor type cubicle panel of size not less than 1.20
m (H) x 1.30m (W) x 0.3m (D) made out of 2 mm thick CRCA
sheet for frame work and covers, compartmentalised, dust
and vermin proof, hinged doors with knobs 3 MM thick gland
plate i/c. cleaning and finishing with 7 tank process for
powder coating in approved shade, 100 amps capacity TPN
aluminium bus bars of high conductivity, DMC/ SMC bus bar
supports, PVC sleeves, bottom base channel of ISMC 75X40
( 7.14 Kg/m), G.I earth bar of size 25mm x 5 mm at the rear
for the entire width of the panel with 2 nos. earth studs
,connections, from busbar to switchgear and control wiring
with required size solid aluminium bus/ FR PVC insulated
2 copper conductor cable of suitable size, cable alley, cable
gland plates including providing and fixing the following
switchgear, as per attached specifications and confirming to
the CPWD general specifications part-I(Internal) , part-
II(External) part-IV (Sub station) as amended upto date
complete ., as required . ( Power Floor DB )

I) Incomer:
a) 100 A, 25KA breaking capacity ( Ics=100% Icu) 4 pole
MCCB with thermal magnetic release with over load, short
circuit protection, earth fault protection and suitable for
Communication Compatibility Port for BMS complete as
required - 1 No.

II) Bus Bar Chamber:


4 Strip aluminium bus bars of 100 Amps capacity with heat
shrinkable coloured sleeves and i/c DMC/SMC bus bars
supports at required intervals complete for cross section, size
supports & their spacing etc.

III) Out goings:


a) 63A, 25 KA breaking capacity ( Ics= 100%Icu) 4 pole
MCCB with Thermal Magnetic Release and suitable for
Communication Compatibility Port for BMS- 3 Nos.
b). Load manager - 1no.
c). 100 / 5 amps CTs - 3 nos.
d) LED indication lamps holders ,back up protection HRC
fuses with base unit - 3 set 7 job
Supplying and fixing following ways, horizontal type three
pole and neutral, sheet steel, MCB distribution board, 415
Votls, on surface/ recess complete with tinned copper bus
bar, neutral bus bar, earth bar, din bar, interconnections,
3 powder painted including earthing etc. as required (but
without MCB/ RCCB/ Isolator) .

a) 6 way (4+18), Double door 15 Each


Supplying and fixing following ways, single pole and neutral,
sheet steel, MCB DB, 240 volts, on surface/ recess, complete
with tinned copper bus bar, neutral link, earth bar, din bar,
4 interconnections, powder painted including earthing etc. as
required. (But without MCB/ RCCB/ Isolator)

a) 2 + 12 way/ 14 way, Double door 6 Each


Supplying, installing on wall, testing and commissioning of
following capacity rising mains made of 1.6mm thick sheet
steel enclosure duly painted with powder coating, wall straps,
fully PVC insulated 4 Nos aluminium bus bars in convenient
sections and suitable for 415 volts, 3 phase, 4 wire, 50 Hz,
A.C. supply with extension joints, fire proof barriers,
5 expansion joints, thrust pads including jointing, and earthing
with 2 runs of galvanised iron strips etc. as required. (Rising
mains confirming to IS 8623,TEC 439)

a) 200 amps (S.C. rating for 1 sec - 15 KA) 52 Metre


b) 400 amps (S.C. rating for 1 sec - 25 KA) 26 Metre
Supplying, installing, testing and commissioning of following
capacity TPN tap off box made of 1.6mm thick sheet steel
enclosure duly painted with powder coating on existing
6 rising mains complete with TPN disconnector FSU and HRC
fuses,connections, earthing etc. as required.

a) 63 amps TPN 14 Each


b) 100 amps TPN 7 Each
Supplying, installing, testing and commissioning of following
capacity End Feed Unit made of 1.6mm thick sheet steel
enclosure duly painted with powder coating to existing rising
mains complete with TPN disconnector FSU and HRC
7 fuses,mounting stands, cable end box, brass compression
and,connections, earthing etc. as required.

a) 200 amps TPN ( End feed for RM) 2 Each


b) 400 amps TPN ( End feed for RM) 1 Each
Supplying and fixing 5 amps to 32 amps rating, 240/415
volts, "C" curve, miniature circuit breaker suitable for
inductive load of following poles in the existing MCB DB
8 complete with connections, testing and commissioning etc. as
required.

a) Single pole 342 Each


b) Single pole and Neutral 6 Each
Supplying and fixing 63 amps rating, 240/415 volts, "C"
curve, miniature circuit breaker suitable for inductive load of
following poles in the existing MCB DB complete with
9 connections, testing and commissioning etc. as required.

a) Triple pole and Neutral 15 Each


Supplying and fixing the following factory made cable end
10 box suitable for the mentioned existing MCCB DB / MCBDB
complete etc. as required.(Same make as DB)
a) Suitable for 6 way, Horizontal TP MCB DB 15 Each
b) Suitable for 12 way, SPN MCB DB 6 Each
Sub Head III TOTAL:
Sub-head -IV (L.T Cabling)
Supply of following sizes of XLPE insulated, PVC sheathed
1 aluminium conductor U.G armoured power cable of 1.1 KV
grade, ISI marked etc. as required.
a) 3½ X 35 sq. mm (for lifts) 80 Metre
b) 3½ X 120 sq. mm (for lighting rising main) 110 Metre
c) 3½ X 185 sq. mm (for power rising main) 50 Metre
Laying and fixing of one number PVC insulated and PVC
2 sheathed/ XLPE power cable of 1.1 KV grade of following size
on cable tray as required.
a) upto 35 sqmm (clamped with 1 mm thick saddle) 80 Metre
b) Above 95 sq. mm and upto 185 sq. mm (clamped with
25/40x3mm MS flat clamp) 160 Metre
Supplying and making end termination with brass
compression gland and aluminium lugs for following size of
3 PVC insulated and PVC sheathed/ XLPE aluminium conductor
cable of 1.1 KV grade as required.

a) 3½ x 35 sqmm (32 mm) 4 Each


b) 3½ X 120 sq. mm (45mm) 4 Each
c) 3½ X 185 sq. mm (57mm) 2 Each
Sub Head IV TOTAL:
Sub-head - V (Lightning Protection)
Providing and fixing G.I. tape 20 mm x 3 mm thick on parapet
1 or surface of wall for lightning conductor complete as 300 Metre
required. (For horizontal run)
Providing and fixing G.I. tape 20 mm x 3 mm thick on parapet
2 or surface of wall for lightning conductor complete as 120 Metre
required. (For vertical run)
Jointing copper/ G.I. tape (with another copper/ G I tape,
3 base of the finial or any other metallic object) by riveting/ 25 Each
sweating and soldering etc as required.
Providing and fixing testing joint, made of 20 mm x 3 mm
thick G.I. strip, 125 mm long, with 4 nos. of G.I. bolts, nuts,
4 chuck nuts and spring washers etc. complete as required. 5 Each

Providing and laying G.I. tape 32 mm x 6 mm from earth


5 electrode directly in ground as required. 25 Metre
Providing and fixing of lighting conductor finial made of 25
mm dia 300 mm long .G.i. tube, having single prong at top
6 with 85 mm dia 6mm thick G.I. base plate including holes etc. 1 Each
complete as required.

Sub Head V TOTAL:


Sub-head - VI (Earthing)
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick
including accessories, and providing masonry enclosure with
cover plate having locking arrangement and watering pipe of
1 2.7 metre long etc. with charcoal/ coke and salt as required. 3 Set
(For lightning arrestor)

Providing and fixing 25 mm x 5 mm G.I. strip on surface or in


2 recess for connections etc. as reqd. 100 Metre
Providing and fixing 6 SWG dia G.I. wire on surface or in
3 recess for loop earthing along with existing surface/ recessed 250 Metre
conduit/ submain wiring/ cable as required.

Sub Head VI TOTAL:


SUB HEAD VII STREET LIGHTING
1 Fabrication and Supplying of 65 mm dia (medium class) G I
pipe pole of following length with 12mm dia earth stud and
300mmx300mmx6mm M.S base Plate duly welded to the
bottom of the pole,drilling of hole including painting with
one coat of approved quality bituminuos paint to the pole
below ground and inside the cement concrete and painting
with one coat of approved primer and two coats of
aluminium paint to remaining portion of pipe complete as
required.

b) 6.0 Meters long 12 Each


2 Erection of metallic pole of following length in cement
concrete 1:3:6 ( 1 cement : 3 coarse sand : 6 graded stone
aggregate 40 mm nominal size ) foundation including
excavation and refilling etc as required.

a) Above 4.5 mtrs and upto 6.5 meter 12 Each


3 Supplying and fixing G.I pipe of 50 mm dia (nominal size ) 1.5
meters long along with pole for cable protection partially
buried, bent to required shape including painting with one
coat of zinc chromate primer and two coats of approved 12 Each
aluminium paint etc. as required.

4 Supply and fixing GI pipe bracket made of 32 mm dia.


Medium class G.I.Pipe of 1.00 metre length welded at
required angle to 80mm Dia medium class G.I. collar of 200
mm long with strenghtining MS plate of 10mm thick , cap on
top, and fixing the bracket to the existing street light pole
with 3 Nos bolts and nuts and painting one coat of approved 12 Each
primer and two coats of aluminium paint etc as required.

5 Supplying and fixing of loop in loop out thermo plastic cable


end box with locking arrangement including supplying and
fixing the following accessories connections, earthing,
Knockouts with PVC gland and making suitable dia hole on
the existing garden light poles by using welding machine for
drawing of UG cable complete as required.

a) 3 Way 16 A per way bakellite connector strip - 1 No.


b) 6 A MCB Single Pole 22 Each
6 Supply, Installation, testing and commissioning of LED Street
light fitting having colour temperature not less than 5700K,
system lumen output not less than 1650 lm and system
wattage not more than 25W, CRI not less than 70 made of
CRCA powder coated body with high transmittance diffuser, 12 Each
built in electronic driver etc. as required.

7 Supply, Installation, testing and commissioning of IP 66 LED


Flood light fitting with pressure die cast aluminium housing
having colour temperature not less than 5700K, system
lumen output not less than 7000 lm and system wattage not
more than 90 W, CRI not less than 70 with Toughened Glass, 10 Each
built in electronic driver etc. as required.

8 Supplying, installation, testing and commissioning of 18 W


Bollard decorative luminaire in textured gray including
supplying and fixing of 18 W CFL lamp , Construction of
suitable CC foundation pillar of 300mm below ground &
200mm height above ground level for mounting the
luminaire, i/c fixing the luminaire with suitable bolt & nuts, 15 Each
connections, internal wiring etc., complete as required.
9 Supplying and drawing following size of FRLS PVC insulated
copper conductor, single core cable in the existing surface /
Steel tubular pole as required.
a).3x1.5 sq.mm 70 Metre
10 Supplying and making end termination with brass
compression gland and aluminium lugs for following size of
PVC insulated and PVC sheathed / XLPE aluminium
conductor cable of 1.1KV grade as required.

a) 4x10 sq.mm(25 mm) 25 set


11 Supplying of XLPE insulated PVC outer sheathed cable with
aluminium conductor armoured suitable for rated voltage 1.1
KV grade confiriming to IS : 7098 (Part- I ) 1988 as
ammended upto date of following sizes of cable. The cable
shall be ISI marked.

a) 4 x10 Sq.mm 460 Metre


12 Laying of one number PVC insulated and PVC sheathed /
XLPE power cable of 1.1 KV grade of following size in the
existing RCC / HUME / STONEWARE / METAL / DWC pipe as
required.

Upto 35 sq.mm 400 Metre


13 Supplying and Laying of 40mm dia HDPE pipe duly ISI
marked complete with necessary HDPE fitting for protection
of 1.1 kV grade underground cable directly in ground at a
depth of 50 cm including cutting the ground and making 350 Metre
good the same to original finish after laying the pipe
complete etc. as required.

a) 40mm outer dia,PN6,PE100


14 Supplying and laying of 25mm dia HDPE pipe duly ISI marked
below 0.5 mtr ground level including excavation the ground
and refilling and making original finish etc., complete as
required.

a) 25mm outer dia,PN6,PE100 120 Metre


15 Supplying and drawing 3 X 2.5 Sq.mm round/Flat copper
conductor unarmored cable in the existing GI/HDPE Pipe in
surface or recess including giving connections, testing and 130 Metre
commissioning etc.as required.

Sub Head VII TOTAL:


Sub head VIII- Pump Sets
Supplying, Installation, testing and Commissioning of open
well submersible pump set of 7.5HP/5.5KW capacity suitable
for operation on 3 phase,415 V, 50HZ, AC Supply and suitable
1 to discharge 385 LPM at an overall head of 42 mtrs i/c giving 2 Each
connections etc., complete as required.

Providing, laying and fixing following dia G.I. pipe (medium


2 class) with G.I. fittings like couplings, elbow, Tee and union
etc as required
a) 50mm Dia 12 Mtr
Supplying and fixing of following size Gun Metal Valves i/c
3 testing and commissioning etc., as req
a) 50mm Dia Gate Valve 1 Each
b) 50mm Dia NRV 2 Each
Supplying and fixing dust/vermin indoor Panel board of
suitable size made of 2mm thick MS Sheet wall/floor
mountable type complete with hinged door, locking
arrangement, all internally wiring with suitable size copper
4 cables and providing and fixing following acessories,
earthing, testing, commissioing etc., as required.

a) 100 Amps MCCB as incommer - 1No.


b) 63 A TP MCB - 2 Nos.
c) DOL starter - 2Nos
d) Single phase preventor with dry run protection:Model
VPGD 1 of minilac-2 Nos.
e) Load manager for monitoring and displaying Voltage,
Current , Power, Power factor etc., having accuracy class -1
with CT's
f) Indication lamps ON/OFF type with back up 5 A -MCB's - 1
Set.
g) 100 Amps 4strip bus bars - 1 set. 1 Job
Supplying and drawing 3 X 6 Sq.mm. flat submersible cable in
the existing G.I.Pipe/surface including giving connections
5 complete etc. as required.(For giving connections from P/sets 30 Mtrs
to Panel)

Sub Head VIII TOTAL:


S.No. Description Quantity Unit

Part-A ( SITC of Lifts )


Supply, Installation, Testing and Commissioning of 13
passengers (884 Kg) Machine room less, gear less lift having
contract speed of 1.5 m/s , serving different floors in the lift
1 shaft as per detailed specifications as follows and additional
conditions enclosed

Location of lift : I.T Services building for STPI at Vijayawada.

Type-machine room less & permanent magnet gearless motor

i) Speed : 1.5 mps


Floors served - Ground + 6 floors
iii) Travel : 25 Mtrs. Approximately
iv) Stops and opening : 7 nos.
v)Controller : A.C Variable Voltage & Variable Frequency.

vi) Automatic Rescue Device complete with dry maintenance


free batteries as required.
vii) Full length Infra red door protection system
viii) Operation: Micro processor based Duplex full collective
with / without attendant.
ix)Power: 415 V + 10% , 3 phase, 50 Hz, 4 wire system.
x) Type of doors:
a) Car: Power operated, center opening horizontal sliding
stainless steel scratch proof(moon rock finish/ Honeycomb
finish/ Linen finish.)
b) Landing :Power operated, center opening horizontal
sliding Stainless steel scratch proof (moon rock finish/
Honeycomb finish/ Linen finish.)
xi) S/S hand rail for entire width of panel of car and hand rail
900 mm above floor level to be fixed on 3 sides of the car

a) Voice announcement system in the car to announce the


position of the elevator in the hoist way as the car passes or
stops at a floor level served by the elevator. The system
should work duriing ARD operation also.

b) Braille buttons for visually challenged persons inside the


car and landings. 1 Job
Supply, Installation, Testing and Commissioning of 16
passengers cum goods lift Machine room less, gear less lift
having contract speed of 1.5 m/s , serving different floors in
2 the lift shaft as per detailed specifications as follows and
additional conditions enclosed

Location of lift : I.T Services building for STPI at Vijayawada.

Type- machine room less & permanent magnet gearless


motor
i) Speed : 1.5 mps
Floors served - Ground + 6 floors
iii) Travel : 25 Mtrs. Approximately
iv) Stops and opening : 7 nos.
v)Controller : A.C Variable Voltage & Variable Frequency.

vi) Automatic Rescue Device complete with dry maintenance


free batteries as required.
vii) Full length Infra red door protection system
viii) Operation: Micro processor based Duplex full collective
with / without attendant.
ix)Power: 415 V + 10% , 3 phase, 50 Hz, 4 wire system.
x) Type of doors:
a) Car: Power operated, center opening horizontal 4 panel
sliding stainless steel scratch proof(moon rock finish/
Honeycomb finish/ Linen finish.)
b) Landing :Power operated, center opening horizontal 4
panel sliding Stainless steel scratch proof (moon rock finish/
Honeycomb finish/ Linen finish.)
xi) S/S hand rail for entire width of panel of car and hand rail
900 mm above floor level to be fixed on 3 sides of the car
a) Voice announcement system in the car to announce the
position of the elevator in the hoist way as the car passes or
stops at a floor level served by the elevator. The system
should work duriing ARD operation also.

b) Braille buttons for visually challenged persons inside the


car and landings. 1 Job
Note:- Lifts 1 & 2 as above are to be connected in duplex
mode
Sub Head (Part-A) TOTAL:
Part-B ( Comprehensive Maintenance )
Comprehensive Maintenance of 1 No. 13 passenger lift above
which include routine, preventive & breakdown maintenance
for a period of five years including repair/ replacement of
worn out items with minimum down time and warranty &
1 guarantee of repaired/ replaced items after completion of
one year guarantee period.

a) First year 1 Per Year


b) Second year 1 Per Year
c) Third year 1 Per Year
d) Fourth year 1 Per Year
e) Fifth year 1 Per Year
Comprehensive Maintenance of 1 No. 16 passenger cum
goods lift above which include routine, preventive &
breakdown maintenance for a period of five years including
repair/ replacement of worn out items with minimum down
time and warranty & guarantee of repaired/ replaced items
after completion of one year guarantee period.

a) First year 1 Per Year


b) Second year 1 Per Year
c) Third year 1 Per Year
d) Fourth year 1 Per Year
e) Fifth year 1 Per Year
Sub Head (Part-B) TOTAL:
Total of LIFTS

C-4 FIRE FIGHTING SYSTEM (Wet riser and sprinkler system)


S.No. Description Quantity Unit
SUBHEAD I: PUMPSET , CONTROL PANEL & CABLES
Electric Fire Pump
Supply and Installation, Testing and Commissioning of
1 electric motor driven main fire pump set suitable for
automatic operation comprising of:
a) 1 no. horizontal split casing centrifugal type multistage fire
pump of capacity 2280 liters per minute at 70 meter head
conforming to IS:1520 giving a pressure of 3.5 Kgf / sq cm at
the highest and farthest outlet from the pump with pump
casing of cast iron to grade FG 200, IS:210-1978, and parts
like impeller, shaft sleeve, wearing ring etc. of noncorrosive
metal like bronze, brass or gun metal and shaft of stainless
steel with mechanical seal. The pump shall be capable of
giving a discharge of not less than 150 percent of the rated
discharge at a head of not less than 65 percent of the rated
head. The shut off head shall be within 120 % of the rated
head.

b) 1 no. squirrel cage induction motor conforming to IS: 325-


1978 with class 'F' insulation, totally enclosed fan cooled
type, enclosure conforming to IP55 protection clause of IS
4691, synchronous speed of 1500 rpm, continous duty having
a horse power rating necessary to drive the above pump at
150 %of its rated discharge with atleast 65 % rated head
designed for operation on 415 V, 50 Hz, 3 phase, AC supply.

c) common bed plate fabricated with MS channel / cast iron


type for assembling the pump and the motor, flexible
coupling between the pump and the motor with coupling
guard for protection.

d) With following pump valves & accessories.


SUCTION END: One number 150 mm dia strainer, one lot of
150 mm dia GI heavy class double flange, suction piping and
suitable taper pipe connection as per manufacturer's design
or as per standard requirement at site.

DELIVERY END: One number pressure gauge of suitable


range with dial of size 150 mm & necessary cocks, one
number 125 mm non return valve, one number Tee piece for
delivery branch, one number 125 mm test valve with pipe
with suitable taper pipe connection, one number 125 mm dia
sluice valve and 200 mm dia header of required length
connecting delivery of other pumps also as required.

e) Making cement concrete foundation suitable for the above


pump set including vibration isolation pads as necessary,
foundation bolts, brackets,clamp fixtures, grouting etc. in
accordance with the manufacturer's design and as per
standard requirements at site.

f) Interconnecting cable work for controls from control panel


and controls 2 Set
( one each for wet riser and Sprinkler system)
Diesel Fire Pump
Supply, Installation, Testing and Commissioning of standby
2 fire pump set operated by diesel engine suitable for
automatic operation comprising of:
a) 1 no. horizontal split casing centrifugal type multistage fire
pump of capacity 2280 litres per minute at 70 metre head
conforming to IS:1520 giving a pressure of 3.5 Kgf / sq cm at
the highest and farthest outlet from the pump with pump
casing of cast iron to grade FG 200, IS:210-1978, and parts
like impeller, shaft sleeve, wearing ring etc. of noncorrosive
metal like bronze, brass or gun metal and shaft of stainless
steel with mechanical seal. The pump shall be capable of
giving a discharge of not less than 150 percent of the rated
discharge at a head of not less than 65 percent of the rated
head. The shut off head shall be within 120 % of the rated
head.

b) 1 no. Diesel Engine conforming to BS 649/IS1601/IS


10002 all amended up-to-date complete with auto starting
mechanism with a speed of 1500 rpm cold starting type,
multi cylinder, vertical four stroke cycle, water cooled
developing suitable BHP at operating speed specified to drive
the fire pump capable of driving continuous nonstop
operation for 8 hours and at least 3000 hours of operation
before major haul, having 10 % over load capacity for one
hour in any period of 12 hours continuous run, capacity to
accept full load within 15seconds from the receipt of signal to
start and complete with following accessories.

1. Dynamically balanced fly wheel.


2. Flexible coupling with coupling guard.
3. Radiator with hoses, fan, water pump, drive arrangement
and guard.
4. Corrosion resistor.
5. Air cleaner (oil bath type/dry type)
6. Fuel service tank, support, semi rotary hand pump and fuel
oil filter with necessary pipe work.
7. Pump for lubricating oil and lubricating oil filter.
8. Electric starting system comprising of necessary batteries
of required capacity, 24 volt(2 x 12 volt), starter motor etc. as
per specifications.
9. Residential type exhaust silencer with necessary pipe work
extended upto 1 m outside pump house duly insulated with
50 mm thick glass wool with 1.0 mm thick aluminium sheet
cladding.

10. Governor.
11. Instrument panel housing all the gauges including
tachometer and starting switch with key for manual starting
etc.
12. Necessary safety controls.
13. Engine shut down mechanism.
14. Suitable anti vibration mounting.
15. Stop solenoid for auto stop in the event of fault with audio
indication.
c) common bedplate fabricated with MS channel/ cast iron
type for assembling the pump and the engine, flexible
coupling between the pump and the engine with coupling
guard for protection.

d) necessary controls such as pressure switch, float switches,


level indicator (UG sump) etc.
e) Interconnecting cable work for controls from control panel
and controls/batteries etc. including battery leads.

f) With following pump valves & accessories.


SUCTION END: One number 150 mm dia strainer, one lot of
150 mm dia GI heavy class double flange, suction piping and
suitable taper pipe connection as per manufacturer's design
or as per standard requirement at site.

DELIVERY END: One number pressure gauge of suitable


range with dial of size 150 mm &necessary cocks, one
number 125 mm non return valve, one number Tee piece for
delivery branch, one number 125 mm test valve with pipe
with suitable taper pipe connection, one number 125 mm dia
sluice valve, pipe fittings and connection with the header as
required.

g) Making cement concrete foundation suitable for the above


pump set including vibration isolation pads as necessary,
foundation bolts, brackets, clamp fixtures, grouting etc. in
accordance with the manufacturer's design and as per 1 Set
standard requirements at site.

Pressurisation Pump
Supply, Installation, Testing and Commissioning of electric
3 motor driven automatic pressurization pump consisting of
the following:
a) 1 no. horizontal / vertical end suction multistage/single
stage pressurization pump conforming to IS:325 having 200
liters per minute at a head of 70 meter , pump casing of cast
iron FG200 IS: 210-1978, parts like impeller, shaft sleeve
wearing ring etc. of noncorrosive metal like bronze, brass or
gun metal and shaft of stainless steel and mechanical seal.

b) 1 no. squirrel cage induction motor conforming to IS: 325-


1978 with class 'F' insulation, totally enclosed fan cooled
type, enclosure conforming to protection class IP 55 of IS
4691 - 1968, synchronous speed of 1500 rpm, continuous
duty designed for operation on 415 V, 50 Hz, 3 phase, AC
supply.
c) common bedplate fabricated with MS channel/ cast iron
type for assembling the pump and the motor, flexible
coupling between the pump and the motor with coupling
guard for protection.

d) With following pump valves & accessories.


SUCTION END: One number 50 mm dia sluice valve/gun
metal foot valve & strainer one lot of 50 mm dia GI heavy
class double flange suction piping and suitable taper pipe
connection.

DELIVERY END: One number pressure gauge of suitable


range with dial of size 150 mm &necessary cocks, one
number non return valve, one number Tee piece for delivery
branch, one number 32 mm test valve with pipe with suitable
taper pipe connection, one number 32 mm dia sluice valve.

e) controls such as pressure switches/limit switch etc.


f) Necessary interconnecting cable work both power and
control circuits from control panel to controls / motor as per
specifications.
g) Making cement concrete foundation suitable for the above
pump set including vibration isolation pads as necessary,
foundation bolts, brackets, clamp fixtures, grouting etc. in
accordance with the manufacturer's design and as per 2 Set
standard requirements at site.

Self Priming Pump


Supply, Installation, Testing and Commissioning of
submersible pump of 60 litres per minute discharge of water
at head of 10m complete with base plate and all accessories
suitable for operation on 415V 3 phase, 50 Hz AC supply
complete with starter for automatic operation including
4 water level sensing device, interconnection with submersible 1 Each
cable, including supply installation of 2500ltrs capacity M.S
Priming Tank as per additional conditions etc., as required.

FIRE CONTROL PANEL


Fabrication, Supplying. installation, Testing & Commissioning
of electrical control panel of cubical construction, floor
5 mounted type, fabricated out of 2mm. thick CRCA sheet

compartmentalised with hinged lockable doors, dust and


vermin proof, powder coated of approved shade after tank
treatment, cable alley, inter-connection, having switch gears
and accessories mounting and internal wiring, earth in all
respect, suitable for operation on 415 V, 3 phase, 50 HZ. AC
supply with enclosure protection class IP 42 as required.

A. COMMON PANEL IN THE FIRE PUMP HOUSE


I) Incomer:-
Incomer
a. 320 A, 50 KA breaking capacity (Ics= 100% Icu) 4 pole
MCCB with Micro processor release, rotary handle and
spreader links, suitable for operation on 415 V, 50 Hz - 1 no

b. Voltmeter with selector switches and HRC fuses (0 - 500


volts) - 1 set
c. Ammeter with selector switch and CTs (0 - 500 A) - 1 set

d. LED Type Phase indication lamps with HRC fuses - 3 sets.

e. Bus bar chamber with aluminium bus bars of 400 A


capacity - 1 set
Outgoing
Fire pump and sprinkler pump
a)160 A 4 pole MCCB 35 kA (Ics= 100% Icu) with Thermal
magnetic release, rotary handle and spreader links, suitable
for operation on 415 V, 50 Hz AC supply- 3 Nos. (for fire pump
and sprinkler pump i/c one spare)

b. Voltmeter with selector switch and HRC fuses (0 - 500


volts) - 3 set
c. Ammeter with selector switch and CTs (0 - 500 A) - 3 set

d. 3 Nos. LED Type Phase indication lamps with HRC fuses - 3


sets.
e. suitable HP fully automatic star/ delta starter with over
load protection, current sensing type single phasing
preventer complete with all accessories and internal wiring
required for automatic operation- 2 Nos.(for main fire pump
and 1spare)

f. Selector switch for local/ remote, auto/ manual/off


operation ON/ OFF indication lamps etc., - 3 Set
b. Jockey pump
a)63 A 4 pole MCCB 25 kA (Ics= 100% Icu) with Thermal
magnetic release, spreader links, suitable for operation on
415 V, 50 Hz - 2Nos.
b. Voltmeter with selector switch and HRC fuses (0 - 500
volts) - 2 set
c. Ammeter with selector switch and CTs (0 - 500 A) - 2 set

d. 3 Nos. LED Type Phase indication lamps with HRC fuses - 2


sets.
f. Selector switch for local/ remote, auto/ manual/off
operation ON/ OFF indication lamps etc., - 2 Set
g. Suitable HP fully automatic star/ delta starter with over
load protection, current sensing type single phasing
preventer complete with all accessories and internal wiring
required for automatic operation, selector switch for lock/
remote, auto/ manual/ OFF operation - 2 sets

D. PRIMING PUMP CONTROL


a. 40 A, 25 KA breaking capacity (Ics= 100% Icu) 4 pole MCCB
with Micro processor release, rotary handle and spreader
links, suitable for operation on 415 V, 50 Hz - 1 no

b. Voltmeter with selector switch and HRC fuses (0 - 500


volts) - 1 set
c. Ammeter with selector switch and CTs (0 - 500 A) - 1 set

d. 3 Nos. LED Type Phase indication lamps with HRC fuses - 1


set.
e. suitable HP D.O.L starter with over load protection, current
sensing type single phasing preventer complete with all
accessories and internal wiring required for automatic
operation - 1 set.

f. Selector switch for local/ remote, auto/ manual/off


operation ON/ OFF indication lamps etc., - 1 set
E. Diesel Engine Control
Control for Diesel Engine comprising:-
(i) Auto/Manual selector switch & 3 attempt starting device,
timers and relays as required, push buttons, start/stop in
manual mode.
(ii) Indication lamp for High/ Low Lub.oil pressure, High
Water Temp.and Engine ON indication.
(iii) Battery charger suitable for 12 V/ 24 V DC with boost
and tickle selector switch, 0--30 V DC voltmeter, 0-20A DC
Ammeter.
(iv)All standard relays and accessories for automatic
operation of diesel engine.
F. SYSTEM CONTROLLER
Designing, Supply, Installation, Testing and Commissioning of
system controller to control operation of Main Electric Fire
Pump, Diesel Pump. Pressurisation Pump, Terrace Pump in
sequence as per specification consisting of relays, timers,
sensors, annunciation window for fault indication, complete
as per specification including necessary 1 SET
arrangement/Provisions to connect Building Management
System as required.

INDICATION PANEL IN FIRE CONTROL ROOM


Fabrication, Supply, Installation, Testing & Commissioning of
wall mounted remote indication panel for fire fighting system
fabricated from not less than 1.6 mm. thick CRCA sheet,
powder coated of approved shade, complete internal wiring,
indicating lamps, relays, accessories, numbering, lettering
6 complete in all respectS and consisting of the following as
required.

(a) ON/OFF indication of Main Electrical Fire Pump,


Pressurisation Pump, Terrace Pump
(b) Audio/Visual indication of operation of Main
Electric/Diesel Fire Pump and Terrace Pump with reset push
button.
(c) Pressure indication in Fire Fighting System (pressure
transducer to be installed under separate item). 1 job

LT POWER CABLES
Supplying of XLPE insulated, PVC sheathed aluminium
conductor armoured U.G power cable of 1.1KV grade on
7 surface/ in the existing cable tray suitably clamped as per the
following size.

(a) 3 1/2 X 120 sq.mm (incoming cable) 60 mtr.


(b) 3 X 70 sq.mm( fire pump and sprinkler pump) 30 mtr.
(c) 3 X 25 sq.mm(for jockey pump) 30 mtr.
Supplying and laying control wiring with multi core copper
stranded conductor of following sizes PVC insulated, PVC
sheathed armoured underground cable between various
sensors and system controller/starter etc.in pump house &
8 outside on surface/existing cable tray complete with
connections at both end with glands ete., as required.

(a) 8 x 2.5 sq.mm. 30 mtr.


(b) 6 x 2.5 sq.mm. 30 mtr.
Supplying and making end termination with brass
compression gland & Al.lugs for following sizes of PVC
9 insulated, PVC sheathed/ XLPE Al.conductor cables of 1.1 KV
grade as required.

(a) 3½ X 120 sq. mm (45mm) 2 set


(b) 3 X 70 sq. mm (35mm) 4 set
(c) 3 X 25 sq. mm (25mm) 2 set
Supplying and installing following size of perforated pre-
painted M.S. cable trays with perforation not more than
17.5%, in convenient sections, joined with connectors,
10 suspended from the ceiling with M.S. suspenders including
bolts & nuts, painting suspenders etc as required.

(a) 300 mm width X 50 mm depth X 1.6 mm thickness 30 mtr.


(b) 150 mm width X 50 mm depth X 1.6 mm thickness 10 mtr.
(c) 100 mm width X 50 mm depth X 1.6 mm thickness 10 mtr.
Sub Head I TOTAL:
SH II : HYDRANTS AND PIPES
Internal Hydrants
Providing and fixing internal hydrants comprising double
headed double outlet gun metal landing valves conforming to
type -B of IS: 5290-1977 with separate valves one on each of
the two heads, cap and chain arrangement of one head of the
outlet with an instantaneous pattern female coupling suitable
for connecting to hose pipe and adaptor on the other head for
1 first aid hose reel connection, GI Tee tapping from the 7 each
wetriser, distant piece and any other accesories as required.
( G+6 floors )

Yard Hydrants
Providing and fixing external (yard) hydrants"STAND POST"
type conforming to IS: 908-1975and comprising of stand post
for single outlet of cast iron, cast in one piece, conforming to
grade 20 of IS: 210-1970, internal dia at the top shall be
80mm, outlet being angled towards ground
withinstantaneous spring lock type gun metal female
2 coupling of 63 mm dia for connecting to hose pipe,single 11 each
headed Brass/Gun metal valve conforming totype- A of IS:
5290 1977, CI tee taping fromunderground mains, duck foot
bend, flange riser and any other accessories as required.

Hose Pipes
Providing and installation of 63 mm dia. 15 m long rubber
lined woven jacketed hose pipe, type -A (REINFORCED
RUBBER LINED) of IS: 636 -1988 complete with necessary
3 instantaneous spring lock type coupling at the ends to match 36 each
with landing valve / hose pipe / branch pipe complete as
required.

First Aid Hose Reel


Providing and installing first aid hose reel wall mounting
type equipment comprising of, hose reel, hose guide,
swinging type fixing bracket, 20mm dia 40 Mtr long high
pressure hose tubing conforming to IS: 1532 - 1969, 20 mm
4 size nozzle and globe valve, stop cock duly conforming to 7 each
IS:884 - 1969.( for internal hydrants)

Sluice Valves for Hydrants & Risers


Supplying and fixing, testing & commissioning of double
flanged sluice valve of rating PN 1.6 with non rising spindle,
bronze/gun metal seat, ISI marked complete with nuts, bolts,
5 washers, gaskets, conforming to IS 780 of following sizes as
required.(11 Nos. for Yard hydrants 2 Nos. main raisers and 3
Nos. FBC)

a. 100mm 16 each
Non-return valves
Providing, Installation, testing and commissioning of dual
plate non-retum valve of following sizes confirming to IS:
6 5312 complete with rubber gasket, GI bolts, nuts, washers
ete.as required.
a. 100mm 3 each
Butterfly valves
Supplying, installation, testing and commissioning of cast
iron butteryfly valves of following dia with standard lever
operated type including SS 304 disc., conforming to PN 1.6 of
7 IS: 13095, with required flanges, nuts & bolts complete as
required

a. 150mm 11 each
b. 100mm 12 each
c. 80mm 1 each
Fire Brigade Inlet for Sump
Providing and fixing one set of "SIAMESE" fire brigade inlet
with 4 way 63 mm dia instantaneous male inlet gun metal
8 couplings complete with plugs and chains, necessary 1 each
reducers, Tees, bends etc. as reqd.( for sump)

Fire Brigade Inlet for risers


Providing and fixing one set of "SIAMESE" fire brigade inlet
with 2 way 63 mm dia instantaneous male inlet gun metal
couplings complete with plugs and chains, necessary
9 reducers, Tees, bends etc. as reqd.( for main risers) 2 each

Cabinet for Fire Brigade Inlet


Providing weather proof cabinet of suitable size but not less
than 0.8 m high x 1.5 m wide x 0.6 m deep , fabricated out of
2.0 mm thick sheet steel ,having lockable centre opening
glazed doors ,painted red and stove enameled , and fixing on
10 masonary steel frame structure as required for 3 each
accommodating item no. (12) and ( 13) above.

Cabinet for Yard Hydrants


Providing and mounting standard hose cabinets, weather
proof, painted red and stove enamelled, fabricated out of 2.0
mm thick sheet steel having lockable centre opening glazed
doors, of suitable size but not less than 1.2 m high x 0.6 m
wide x0.45 m deep so as to accommodate the following
including mounting to the yard hydrants etc. complete as
11 required. 1) complete yard hydrant unit- 1no. 2) 63 mm dia 11 each
15 m long hose pipe - 2 nos. 3)63 mm dia branch pipe - 1 no.
(for external hydrants)

Air Vessel
Providing and fixing air vessel of continuous welded
construction and galvanized to IS: 4736 - 1968 fabricated of
at least 10 mm thick MS plate, with dished ends and
supporting legs, 450 mm dia. 2 m high complete with
necessary air release valve, safety valve, pressure gauge,
12 flange connection to the wetriser piping and air release valve 2 each
with necessary piping to meet the functional requirements of
the system.

Hydraulic Siren
Providing and fixing hydraulic siren, turtrine type with
associated plumbing with heavy class GI pipe with
13 accessories fittings and isolating valve etc. to indicate the 1 each
flow of water in the wetriser system.

Branch Pipe
Providing and fixing 63 mm dia branch pipe of copper/gun
metal/ alu. alloy complete with male instantaneous spring
lock type coupling (for connection to the hose pipe ) on one
end and external threading on the other end , 20 mm dia.
(internal) nozzle of copper/gun metal having screw thread
and hexagonal head at the inlet end to facilitate screwing of
14 nozzle on to the branch pipe both conforming to IS:903 - 25 Each
1985( for internal hydrants 14 Nos. and yard Hydrants 11
Nos.)

MS Pipe With Pipe Coating


Providing laying, testing & commissioning of 'C' class heavy
duty MS Pipe conforming to IS 1239/3589 i/c fittings like
elbows, tees. flanges tapers, nuts bolts, gaskets etc. in ground
including excavation and providing cement concrete blocks
as supports, anticorrosive treatment with coal tar sphalt tape
15 as per IS | 10221, refilling the trench etc. of following sizes 300 mtr
complete as required.

a. 150 mm dia "C" class


GI Pipe For Risers
Providing, laying, testing and commissioning of following size
heavy class GI pipe with ISI mark conforming to IS: 1239 with
necessary fittings and accessories like Tees. elbows, flanges,
tapers, bolts and nuts, gaskets etc., fixing the pipe on
wall/ceiling with suitable clamps/brackets and painting with
16 2 or more coats of synthetic enamel paint of required shade 25 mtr
etc complete as required.

a. 150mm dia "C" class


b. 125 mm dia "C" class 25 mtr
c. 100 mm dia "C" class 80 mtr
Masonry Enclosure
Providing masonry enclosures 90 cm x 40 cm x100 cm
(inside) for sluice valve with 22 cm thick brick work in
cement mortar with manhole and cover of size 60 cm x 60 cm
17 and RCC top slab with 1:2:4 i/c masonry work, excavation, 15 each
plastering etc. as required.

Providing, fixing, testing and commissioning of 15 mm dia.


Quartzoid bulb type sprinkler with temperature rating at
1 68°C made out of forged brass and in nickel chrome finish. 1142 each
(Quick response sprinklers)

a. Pendent /upright spray, ceiling or flush type.


Providing & fixing testing & commissioning of control valve
of Cast iron body and brass/bronze working parts comprising
of water motor alarm, bronze seat clapper, and clappier arm.
hvdraulically driven mechanical gong Bell to sound
continuous alarm when the Wet riser/ sprinkler activates,
pressure gauges, emeraency releases, strainer, pressure
2 switch, cock valve complete with drain valve and bypass test 1 each
control box, ball valves, MS pipe of required size, flanges,
orifice plate, gasket etc. of size 150 mm dia as required.

Providing, laying, testing & commissioning of 'C' class


medium duty G.I. Pipe conforming to IS 1239 including
fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets
etc., fixing the pipe on the wall/ceiling with suitable clamps
3 and painting with two or more coats of synthetic enamel
paint of required shade complete as required.

a. 100 mm dia 120 mtr


b. 80 mm dia 300 Mtr.
c. 65 mm dia 250 Mtr.
d. 50 mm dia 200 Mtr.
e. 40 mm dia 100 Mtr.
f. 32 mm dia 50 Mtr.
g. 25 mm dia 150 Mtr.
Butterfly valves
Providing and fixing cast iron butteryfly valves of following
dia with standard lever operated type including SS 304 disc.,
conforming to PN 1.6 of BS: 5155, with required flanges, nuts
4 & bolts complete as required 2 Each

a. 100mm 7 Each
b. 65mm 2 Each
c. 50mm 3 Each
Providing, fixing, testing and commissioning of Gunmetal
5 screwed Valves CI -1 (ISI Marked) (IS :778)of following sizes .
( for drain pipe)
a. 50 mm 7 each
Providing, fixing, testing and commissioning of vane type
6 water flow detector capable of detecting flow in automatic 7 each
sprinkler system as required.
Providing and fixing M.S. cabinet fabricated from1.6mm thick
M.S. sheet with full front glass door and locking arrangement
with suitable shelves with holes suitable for storage capacity
of 20 spare sprinklers and one spanner properly fixed in the
shelves and cabinet painted fire red with stove enameled of
7 approved shade with size 900 mm x 300 mm x 100mm high 4 each
etc. as required.

Sub Head II TOTAL:


SUB HEAD III: EARTHING
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm
thick including accessories, and providing masonry enclosure
with cover plate having locking arrangement and atering
1 pipe of 2.7 metre long etc. with charcoal/ coke and salt as 4 set
required

Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia


G.I. pipe from earth electrode including connection with G.I.
2 nut, bolt, spring, washer excavation and re-filling etc. as 40 metre
required.

Providing and fixing 25 mm X 5 mm G.I. strip on surface or in


3 recess for connections etc. as required. 30 metre

Sub Head III TOTAL:


Total of Fire Fighting System ‘C4’
C5: PROVIDING FIRE ALARM SYSTEM
S.No. Description Quantity Unit
Supply, installation, testing and commissioning of UL/EN
listed intelligent Addressable Fire Alarm control panel with
loop cards with a minimum of 250 detectors/ devices per
loop capacity, PC connectivity and battery backup etc.,
enclosed in dust and vermin proof sheet steel cubical wall
mounting type complete with all accessories and the loop
module shall be encapsulated and shall be hot pluggable. The
control panel shall be capable of identifying the open circuit /
short circuit / earth faults and shall provide fire / fault
warning audio visual alarm facility with main control panel
along with a built in buzzer unit i/c locking arrangement,
connections, earthing the panel etc. as required. The panel
1 shall have LCD Colour touch screen display for system status.
The panel shall work on 240 V AC power supply, automatic
battery charger, SMF batteries sufficient for 48 hours in
standby and 30 minutes in alarm and complete as per
specification. All necessary software for functioning of the
panel shall be built in / installed and commissioned.

Eight loop Fire Alarm Control panel 1 each


Supply of Intelligent Addressable Photo electric type smoke
detectors with twist lockable removal base and dual ray
2 technology with inbuilt Fault Isolator Modules including
connection complete etc, as required.

a) Smoke detectors above False ceiling 199 each


b) Smoke detectors below False ceiling 199 each
Supply of Intelligent addressable Rate of rise cum fixed heat
detector with standard base and dual ray technology with
3 inbuilt Fault Isolator Modules complete as per specification. 5 each
Supplying, installation, testing, commissioning of addressable
4 manual Call Box made of polycarbonate with break glass 14 each
complete etc, as required.
Supply, installation, testing and commissioning of
5 addressable control relay module complete as per 14 each
specification.
Supply, installation, testing and commissioning of
6 addressable monitor module complete as per specification. 7 each

Supply, installation, testing and commissioning of


Addressable Fire alarm loop sounders of Low intensity dual
tone electronic hooter with sound output of 90-100dB at 1
7 mtr suitable for indoor application and operative on 24V DC 14 each
supply complete as reqd.

Supply, installation, testing and commissioning of glow LED


type Response Indicator lamp suitable for connecting
8 respective heat/ smoke detector complete etc, as required. 199 each

Supply Installation, Testing & Commissioning of Active type


9 repeater panel connected from the main fire panel complete 1 each
as required.
Supply, installation, testing and commissioning of Intelligent
10 Addressable Beam Detectors with base including connections 2 each
complete as required.
Supplying and fixing of following sizes of steel conduit along
with accessories in surface / recess including painting in case
of surface conduit, or cutting the wall and making good the
11 same in case of recessed conduit as required.

12 a) 20 mm 3500 Metre
Supplying and drawing following sizes of FRLS PVC insulated
copper conductor, single core cable in the existing surface /
13 recessed steel / PVC conduit as required.

a) 2 x 1.5 sq.mm. 4000 Metre


b) 4 x 1.5 sq.mm. 500 Metre
Total of C5 FIRE ALARM
C6: SUB STATION EQUIPMENT
S.No. Description Quantity Unit
Sub Head : I ( HT Equipment & Transformer )
Supplying, installation, testing and commissioning of Outdoor
type Three Panel Ring Main Unit (RMU - 2 LBS & 1 VCB)
Floor Mounted, Metal Clad, Sectionalised & Non Extensible
Type totally enclosed in SF6 in 2.5 mm thickness stainless
steel Tank of Non Ferrite, Non magnetic Grade, with 2 Nos.
630 Amp Fixed Manual load break switches and 1 No. Fixed
Manual type Vacuum Circuit Breaker, as per IEC: 62271-200
with upto date amendments thereon and additional
specifications, etc with 11KV, 630 Amps, 350 MVA, 50 Hz AC
and fitted with Manually Operated Spring Charging
Mechanism, Series Trip Coil, Closing Coil, automatic safety
shutters and push button single break trip free mechanism,
featured with mechanical ON/OFF indicator with hand trip
1 device etc, provision for sealing arrangement, complete with
self contained, fully interlocked, rack in and rack out
mechanism, copper bus bars of 630 Amps capacity and
equipped with the following accessories including
connections, suitable provision for 11 KV end termination
with heat shrinkable termination kit for 3 Core x 240 sq.mm
XLPE HT cable including foundation, fastening, etc as reqd.
The RMU shall be type tested for 20KA for 1 Sec Internal arc
as per IEC: 62271-200.

Current Transformer
Single phase CT ratio:- 50-100/1A, accuracy class 5P10,
burden 2.5VA - 3Nos
Bus Bars:
3 phase, 11 KV, 630Amps Copper Main Bus bars- 1 Set
Fault passage Indicator (FPI) - 1 No. for each Incoming LBS
Module
Provision for receiving Incoming & Outgoing Cable though
Side/rear/front through Bottom Entry - 1 No.
All as above 1 Set
Supplying, installation, testing & commissioning of indoor
type floor mounted metal clad, 11KV, VCB panel with 3Nos.
VCBs (1No. Incomer & 2Nos. Outgoing) totally enclosed &
fully interlocked, horizontal drawout, horizontal/vertical
isolation type breaker as per IS: 13118, as amended up to
date and additional specifications, having capacities
mentioned below, single break, trip free mechanism,
manually charged and auto/manually closing breaker,
suitable for use on 11KV, 3 Phase, 50 Hz A.C. supply with
short circuit fault level of 350 MVA, complete with self
contained, fully interlocked, rack in and rack out mechanism,
air insulated but encapsulated copper bus bars of 630 Amps
capacity, breaker featured with mechanical ON/OFF indicator
2 with hand trip device, spring release coil, shunt trip coil and
auxiliary switch of 4 NO + 4NC and equipped with following
switchgears and accessories i/c connections suitable for 3
core x 240Sq.mm, XLPE 11 KV cable (cable entry from
bottom) end termination with heat shrinkable jointing
material etc. as required. (Note: Cost of end termination not
included in this item)

A Incoming - 630 Amp. VCB with following- 1No.


a) 11 KV /110 Volts P.T. class 0.5 accuracy and 100 VA burden
with 1No. voltmeter (0-15KV), digital type, selector switch
for voltmeter and protection MCB for HT metering up to
12KV on incomer 1No.

b) (0-200 A) dual scale Ammeter, digital type, selector


switches for ammeters- 1No..
c) Microprocessor based numerical relay with O/L, E/F and
S/C protection with communication facility and Modbus
Protocol- 1No.
d) Dual core, dual ratio 3 CTs 300/150/5/5 VA burden and
accuracy Class - 0.5 for metering and class 5P10 for
protection- 1 Set.
e) Power pack with 220 Volt AC input & 24Volt DC continuous
output suitable for closing/tripping/indication of 3 Nos. of
HT panel boards with 2Nos.12 Volts each maintenance free
batteries 100AH ( suitable) each , charging unit, capacitor
bank for emergency delivering for trip system complete with
suitable capacity of Ammeter & Voltmeter i/c connections
with 2.5 Sq.mm FRLS insulated copper conductor cable etc. as
required- 1 Set.

B Outgoing: 630A VCB with the following- 2 Nos.


a) (0-100A) Ammeters, dual scale digital type & selector
switches for Ammeters- 2Nos.
b) Microprocessor based numerical relays with O/L, E/F &
S/C protections with communication facility and Modbus
Protocol- 2Nos.
c) Dual core, dual ratio 3 CTs 100/50/5/5A of 15VA burden
and accuracy Class-1.0 for protection- 1 Set. 1 Set
SITC of Cast Resin Dry Type 750KVA 11/0.433 KV, 3 Phase,
50Hz, Dyn 11 vector group, copper wound, class "F"
insulation associated with winding temperature
indicator/controller actuated by means of resistance
temperature detector emended in LV windings, indoor type
Transformer with Approximately 5% impedance, tapping for
off load operation on HV side in steps of +/-2.5%, +/-5%,
-7.5%, having cable end boxes on HV side suitable for 3 core x
240Sq.mm. XLPE cable of 11KV grade and 1200Amp. bus
trunking arrangement on LV side with neutral brought out
separately including supplying and laying of copper
conductor multicore control cable from transformer to HT
breaker for safety tripping, suitably mounted on M.S. Channel
3 with all accessories and confirming to IS: 211171:1985 & as 2 Job
per specification attached complete in all respects as
required at site. ( The transformer shall be equipped with
communication facility and Modbus Protocol to monitor
winding temperature indication through BMS). The
Maximum allowable losses of the transformer shall be as per
ECBC- 2009 code.

Total of Sub Head I


Sub Head : II ( MV Panels )
(NON ESSENTIAL PANEL)
Supplying, installation, testing and commissioning of floor
standing indoor type extendable cubical LT Non-Essential
panel (as per general arrangement drawing approved by
engineer-in-charge) suitable for operation on 415V, 3 Phase,
4 Wire, 50 Hz, AC supply system, fabricated in totally
enclosed compartmentalized flush finish design from CRCA
sheet steel of 2mm thick for frame work and covers, 3mm
thick for gland plates in split sections, including cleaning and
finishing complete with 7 tank process for powder coating in
approved shade, provision for incoming & outgoing
termination from bottom at rear side of the panel with cable
chamber, busbar chamber having horizontal and vertical TPN
bus bars of 1600 Amp capacity aluminium Alloy bus bars of
1 high conductivity and DMC/ SMC bus bar supports, having
short circuit withstand capacity of 31 MVA for 1 Sec., suitable
ventilation, bottom base frame with MS channel (ISMC 100
designation) of section not less than 100mm X 50mm X 5 mm
thick and fabrication of the panel shall be done in
transportable sections, entire width of the panel shall have a
common Copper earth bar of size 2 Nos x 25mm x
5mm at the rear with 2 Nos. earth stud, connection and
interconnections from main bus bar to switch gears with
required size of Al. bus bars and control wiring with
1.5sq.mm. FRLS PVC insulated copper conductor single core
cable, cable alleys, detachable cable gland plates including
providing and fixing the following MCCB/ Switchgears
/metering accessories etc complete as required.

The cubical panel shall generally confirm to CPWD General


Specification for Electrical works, Part-I Internal 2013, Part II
External 1994 and Part IV substation equipment 2013 as
ammended upto date.

The size of the Panel shall be not less than 5200 mm (Width)
x 2100 mm (Height) x 800 mm (Depth)
A. Incomings
1250 Amps, four pole, horizontal electrical drawout type
(EDO) Air Circuit Breaker (ACB) of fault breaking capacity
50kA (Icu = Ics = Icw for 1 sec) with Communication
Compatibility Port for BMS, manually operated, fitted with
interlocked door, automatic safety shutters, mechanical
ON/OFF, LED indicating lamps and service/test/isolated
(i) position indicators and frame earthing contact, conforming to
IS/IEC 60947-2 & IEC 60947-2 as amended up-to-date
complete with following accessories for ACB. - 2 Nos

Independent manual spring closing mechanism -2 Nos


Microprocessor release for over current, earth fault & short
circuit protection alongwith inbuilt LCD display for fault
indication, menu setting and trip history information
facilities, nuetral protection - 2 sets.

Communication module ( Modbus Module ) and power


supply module- 1 set.
3 Nos. Phase indication LED lamps with 6 Amp backup MCB,
breaker ON / OFF, LED indicating lamps with 6 Amp backup
MCB, test terminal block set, circuits as per- standard
practice, as required. - 2 sets.

Shunt trip coil 220V A.C. 2 Nos


Digital type Load Manager with RS 485 Port - 2 Sets
APFC Relay sensing CTs- 2 sets.
Bus Coupler:
1250 Amps, four pole, horizontal Electrical drawout type
(EDO), Air Circuit Breaker (ACB) of fault breaking capacity
50kA (Icu = Ics = Icw for 1 sec) with Communication
Compatibility Port for BMS, manually operated, fitted with
interlocked door, automatic safety shutters, mechanical
ON/OFF, LED indicating lamps and service /test /isolated
(ii) position indicators and frame earthing contact, conforming to
IS/IEC 60947-2 & IEC 60947-2 as amended up-to-date
complete with following accessories for ACB. - 1 No.

Independent manual spring closing mechanism -1 No.


Communication module ( Modbus Module ) and power
supply module- 1 set.
Breaker ON / OFF LED indicating lamps with 6 Amp backup
MCB test terminal block set, circuits as per- standard practice
etc., as required. -1 set
Interlocking
Electrical interlocking alongwith required control wiring and
accessories & Mechanical interlocking with Bowden type
Mechanical interlock for EDO Breakers so as to ensure that
only one supply is available at a time on each section of bus
(iii) and to eliminate any possibility of accidentally approaching
two supplies at one bus section/parallel operation of two
transformers-1Set.

Bus Bars:
Horizontal and vertical TPN aluminium bus bars of 1600
Amps capacity with heat shrinkable coloured sleeves and i/c
DMC/SMC bus bars supports at required intervals complete
(iv) suitable for withstanding fault level of 31 MVA for 1 Sec. - 1
Set

(The operation logic shall be that any one of the Transformer


Incomer will be ON & 2nd Transformer will be Standby)

Out going:
800 Amps, four pole, horizontal electrical drawout type
(EDO), Air Circuit Breaker (ACB) of fault breaking capacity
50kA (Icu = Ics = Icw for 1 sec), with Communication
Compatibility Port for BMS, manually operated, fitted with
interlocked door, automatic safety shutters, mechanical
ON/OFF, LED indicating lamps and service/test/isolated
(i) position indicators and frame earthing contact, conforming
toIS/IEC 60947-2 & IEC 60947-2 as amended up-to-date
complete with following accessories for ACB - 3 Nos.

Independent manual spring closing mechanism 1 No


Microprocessor release for over current, earth fault & short
circuit protection alongwith inbuilt LCD display for fault
indication, menu setting and trip history information
facilities - 1 set.
Communication module ( Modbus Module ) and power
supply module- 1 set.
3 Nos. Phase indication LED lamps with 6Amp back up MCB
breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

Shunt trip coil 220V A.C. - 1 No


Digital Voltmeter with selector switch -1Set
Digital Ammeter with suitable CT ' S & Selector switch - 1 Set

630 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),


50kA breaking capacity (Ics=100% Icu) with Microprocessor
release, horizontal, mechanical drawout type (MDO), suitable
for Communication Compatibility Port for BMS with Inbuilt
RS485 Port to communicate on MODBUS Protocol for remote
Status & Control of MCCB, having adjustment for over load,
(ii) short circuit, protection suitable for operation on 415V, 50Hz,
3 phase, AC supply confirms to IS/IEC : 60947-2 & IEC
60947-2 alongwith spreader links -1 No. ( for capacitor
bank )

3 Nos. Phase indication LED lamps with 6Amp back up MCB


breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

400 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),


50kA breaking capacity (Ics=100% Icu) with Microprocessor
release, horizontal, mechanical drawout type (MDO), suitable
for Communication Compatibility Port for BMS with Inbuilt
RS485 Port to communicate on MODBUS Protocol for remote
Status & Control of MCCB, having adjustment for over load,
(iii) short circuit, protection suitable for operation on 415V, 50Hz,
3 phase, AC supply confirms to IS/IEC : 60947-2 & IEC
60947-2 alongwith spreader links -2 Nos

3 Nos. Phase indication LED lamps with 6Amp back up MCB


breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

Danger plate and lettering of the Panel for display of


(iv) incoming and outgoing switchgear etc., as required. 1 Job
(ESSENTIAL PANEL)
Supplying, installation, testing and commissioning of Floor
standing indoor type extendable cubical LT Essential panel
(as per general arrangement drawing approved by engineer-
in-charge) suitable for operation on 415V, 3 Phase, 4 Wire, 50
Hz, AC supply system, fabricated in totally enclosed
compartmentalized flush finish design from CRCA sheet steel
of 2mm thick for frame work and covers, 3mm thick for gland
plates in split sections, including cleaning and finishing
complete with 7 tank process for powder coating in approved
shade, provision for incoming & outgoing termination from
bottom at rear side of the panel with cable chamber, busbar
chamber having horizontal and vertical TPN bus bars of
1000 Amp capacity aluminium Alloy bus bars of high
2 conductivity and DMC/ SMC bus bar supports, having short
circuit withstand capacity of 31 MVA for 1 Sec., suitable
ventilation, bottom base frame with MS channel (ISMC 100
designation) of section not less than 100mm X 50mm X 5 mm
thick and fabrication of the panel shall be done in
transportable sections, entire width of the panel shall have a
common 2 runs of G I earth bar of size 50mm x 5mm

at the rear with 2 Nos. earth stud, connection and


interconnections from main bus bar to switch gears with
required size of Al. bus bars and control wiring with
1.5sq.mm. FRLS PVC insulated copper conductor single core
cable, cable alleys, detachable cable gland plates including
providing and fixing the following MCCB/ Switchgears
/metering accessories etc complete as required.

The cubical panel shall generally confirm to CPWD General


Specification for Electrical works, Part-I Internal 2013, Part II
External 1994 and Part IV substation equipment 2013 as
ammended upto date.

The size of the Panel shall be not less than 2500 mm


(Width) x 2100 mm (Height) x 800 mm (Depth)
A.Incomings
800 Amps, four pole, horizontal electrical drawout type
(EDO), Air Circuit Breaker (ACB) of fault breaking capacity
50kA (Icu = Ics = Icw for 1 sec), with Communication
Compatibility Port for BMS, manually operated, fitted with
interlocked door, automatic safety shutters, mechanical
ON/OFF, LED indicating lamps and service/test/isolated
(i) position indicators and frame earthing contact, conforming to
IS/IEC 60947-2 & IEC 60947-2 as amended up-to-date
complete with following accessories for ACB. - 1 No.

Independent manual spring closing mechanism -1 Nos


Microprocessor release for over current, earth fault & short
circuit protection alongwith inbuilt LCD display for fault
indication, menu setting and trip history information
facilities, nuetral protection - 1 set.

Communication module ( Modbus Module ) and power


supply module- 1 set.
3 Nos. Phase indication LED lamps with 6 Amp backup MCB ,
breaker ON / OFF’LED indicating lamps with 6 Amp backup
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 sets.

Shunt trip coil 220V A.C. 1 Nos


Digital type Load Manager with RS 485 Port - 1 Set
Bus Bars:
Horizontal and vertical TPN aluminium bus bars of
1000Amps capacity with heat shrinkable coloured sleeves
and i/c DMC/SMC bus bars supports at required intervals
(ii) complete suitable for withstanding fault level of 31 MVA for 1
Sec. - 1 Set

B) Logic Circuit compartment:-


Logic to be built up in such a way that in normal course DG
supply connected to this panel feeds essential power supply
and in case of any of the two DG sets connected to DATA
CENTRE PANEL fail to start, this panel Incomer Breaker to
TRIP & DG set power to be feed to DATA CENTRE PANEL only.

C) Out going:
630 Amps, four pole, horizontal electrical drawout type
(EDO), Air Circuit Breaker (ACB) of fault breaking capacity
50kA (Icu = Ics = Icw for 1 sec), with Communication
Compatibility Port for BMS, manually operated, fitted with
interlocked door, automatic safety shutters, mechanical
ON/OFF, LED indicating lamps and service/ test/ isolated
(i) position indicators and frame earthing contact, conforming to
IS/IEC 60947-2 & IEC 60947-2 as amended up-to-date
complete with following accessories for ACB. - 1 No.

Independent manual spring closing mechanism 1 No


Microprocessor release for over current, earth fault & short
circuit protection alongwith inbuilt LCD display for fault
indication, menu setting and trip history information
facilities - 1 set

Communication module ( Modbus Module ) and power


supply module- 1 set.
3 Nos. Phase indication LED lamps with 6Amp back up MCB
breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.
200 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),
35kA breaking capacity (Ics=100% Icu) with Thermal
magnetic release, suitable for Communication Compatibility
Port for BMS with Inbuilt RS485 Port to communicate on
MODBUS Protocol for remote Status & Control of MCCB,
having adjustment for over load, short circuit, protection
(ii) suitable for operation on 415V, 50Hz, 3 phase, AC supply
confirms to IS/IEC : 60947-2 & IEC 60947-2 alongwith
extended rotary operating handle and spreader links -4 Nos

160 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),


25kA breaking capacity (Ics=100% Icu) with Thermal
magnetic release, suitable for Communication Compatibility
Port for BMS with Inbuilt RS485 Port to communicate on
MODBUS Protocol for remote Status & Control of MCCB,
having adjustment for over load, short circuit, protection
(iii) suitable for operation on 415V, 50Hz, 3 phase, AC supply
confirms to IS/IEC : 60947-2 & IEC 60947-2 alongwith
extended rotary operating handle and spreader links -2 Nos

100 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),


25kA breaking capacity (Ics=100% Icu) with Thermal
magnetic release, suitable for Communication Compatibility
Port for BMS with Inbuilt RS485 Port to communicate on
MODBUS Protocol for remote Status & Control of MCCB,
having adjustment for over load, short circuit, protection
(iv) suitable for operation on 415V, 50Hz, 3 phase, AC supply
confirms to IS/IEC : 60947-2 & IEC 60947-2 alongwith
extended rotary operating handle and spreader links -2 Nos

63 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),


25kA breaking capacity (Ics=100% Icu) with Thermal
magnetic release, suitable for Communication Compatibility
Port for BMS with Inbuilt RS485 Port to communicate on
MODBUS Protocol for remote Status & Control of MCCB,
having adjustment for over load, short circuit, protection
(v) suitable for operation on 415V, 50Hz, 3 phase, AC supply
confirms to IS/IEC : 60947-2 & IEC 60947-2 alongwith
extended rotary operating handle and spreader links -2 Nos

Danger plate and lettering of the Panel for display of


(vi) incoming and outgoing switchgear etc., as required. 1 Job

APFC panel
Supplying, installation, testing and commissioning of Floor
standing indoor type cubical indoor type 300KVAr APFC
panel suitable for 415 Volts, 3 Phase,4 wire 50 Hz AC supply
system fabricated in compartmentalized design from CRCA
sheet steel of 2 mm thick for frame work and covers, 3mm
thick for gland plates i/c cleaning & finishing complete with
7-tank process, powder coating in approved shade, hinged
openable doors with panel lock, having 800 amps capacity
extensible type 4 strip TPN Aluminium bus bars of high
conductivity, DMC/SMC bus bar supports, with short circuit
with stand capacity of 31MVA for 1 sec. including supplying
and fixing following switch gear etc., including drilling holes,
3 welding, providing detachable gland plate/ knock outs,
connection, interconnections from bus bar to switch gears
with required size of Al. bus bars/ FRLS PVC insulated copper
conductor single core cable, earthing etc. as required.

The cubicle board shall be provided with bottom base MS


channel (ISMC 100 designation) of size not less than 100 x 50
mm x 5 mm thick fabrication shall be done in transportable
sections, including painting the base channel with primer &
finish paint. Entire panel shall have a common G I earth bar of
size 25 mm x 5 mm at the rear with 2 nos earth studs, solid
connections from main bus bar to switch gears

The cubical panel shall generally confirm to CPWD General


Specification for Electrical works, Part-I Internal 2013, Part II
External 1994 and Part IV substation equipment 2013 as
ammended upto date.

The size of the Panel shall be not less than 2000 mm


(Width) x 1300 mm (Height) x 500 mm (Depth)
INCOMING:
400 Amps. 4 pole, Moulded Case Circuit Breaker (MCCB),
50kA breaking capacity (Ics=100% Icu) with Microprocessor
release, horizontal, mechanical drawout type (MDO), suitable
for Communication Compatibility Port for BMS with Inbuilt
RS485 Port to communicate on MODBUS Protocol for remote
Status & Control of MCCB, having adjustment for over load,
short circuit, protection suitable for operation on 415V, 50Hz,
3 phase, AC supply confirming to IS/IEC : 60947-2 & IEC
60947-2 alongwith spreader links -1 No.

OUTGOING:
a) 160 Amps TP, 25 kA Short circuit current Capacity ( Ics=
100% Icu ) MCCB - 1 Nos
b) 125 Amps TP, 25kA Short circuit current Capacity ( Ics=
100% Icu ) MCCB's - 1 Nos
c) 100 Amps TP, 25kA Short circuit current Capacity ( Ics=
100% Icu ) MCCB's - 7 Nos
d) Capacitor switching Power contactor of following capacity
suitable for 3-phase, 415 volts, AC supply for switching on
and off each of the below rated capacitor bank in conjunction
with APFC relay/ Manual operation along with necessary
auxiliary contacts including making connections,
interconnections etc. complete as required.

i) Capacitor duty contactor suitable for 30KVAR Capacitor - 7


Nos.
ii) Capacitor duty contactor suitable for 40 KVAR Capacitor -1
No.
iii) Capacitor duty contactor suitable for 50 KVAR Capacitor
-1 No.
e) Digital Multi function flush mounted type with LCD Display
Three Phase electronic Meter to read and display parameters
such as voltage, current ,frequency, power factor etc with
inbuilt selector switches and set of suitable current
transformers of 15VA burden and accuracy Class-1 for
metering etc as required -1 No

f) Auto / manual selector switch -1 No.


g) On-Off Push Buttons along with indication Lamp (LED
type)-9 Sets (for each Capacitor Bank)
h) Advanced micro-processor based self diagnostic features
with all the state of art functions and controls, totally tamper
proof control relay, maximum site reliability and pre-set
programmer integrity, freely programmable for switching of
capacitors, self diagnostic function with digital power factor
meter and direct KVAR sensing , A,V, PF, W, VAR, VA, THD and
VAF Meter control operations for 12-stages - 1 Set.

i) Current transformer of 400/5A ratio having 15 VA burden


class 1 accuracy -1 No. (To be provided at load panel for
sensing)
j) Heavy Duty, Metalised polypropylene film single unit
cylindrical /box type construction with Resin filled, low watt
dry type explosion proof compact and light weight self
healing type (Total Watt loss not more than 0.5 W/KVAR) air
cooled delta connected capacitor suitable for 3 phase, 440V,
AC supply of the following rating.

i) 30 KVAR - 7 Nos.
ii) 40 KVAR - 1 No.
iii) 50 KVAR - 1 No.(as base capacitor and continuously ON )

k) Danger plate and lettering of the Panel for display of


incoming and outgoing switchgear etc., as required. 1 Job

Total of Sub Head II


Sub Head : III ( HT/ LT Cabling & Bus trunking )
Supplying of 3 X 240 Sq.mm HT XLPE cable, 11 KV(E) with
Stranded Compact Circular Aluminium Conductor, Conductor
Screen With Extruded Semi Conducting Compound, XLPE
Insulated, Insulation Screening with extruded Semi
Conducting Compound in combination with Copper Tape
1 (0.3kA for 1 sec), cores laid up, inner sheath of PVC tape, 180 Metre
galvanised flat steel strip armoured and overall PVC Sheathed
Cable conforming to IS 7098 / (PART-II) 1985 with latest
amendments.

Laying of one number PVC insulated and PVC sheathed /


XLPE power cable of 11 KV grade of following size direct in
ground including excavation, sand cushioning, protective
2 covering and refilling the trench etc. as required.

2.1 Above 120 sq. mm and upto 400 sq. mm 20 Metre


Laying of one number PVC insulated and PVC sheathed /
3 XLPE power cable of 11 KV grade of following size in the
existing RCC/ HUME/ METAL pipe as required.
3.1 Above 120 sq. mm and upto 400 sq. mm 100 Metre
Laying of one number PVC insulated and PVC sheathed /
4 XLPE power cable of 11 KV grade of following size in the
existing masonry open duct as required.
4.1 Above 120 sq. mm and upto 400 sq. mm 40 Metre
Supplying and making indoor cable end termination with
heat shrinkable jointing kit complete with all accessories
including lugs suitable for following size of 3core, XLPE
5 aluminium conductor cable of 11KV grade as required.

5.1 240 sq. mm 6 Each


Supplying, installing suspension on ceiling, testing and
commissioning of following capacity Air insulated Compact
Type Bus Trunking for use on 3phase 4wire 415volts, 50Hz
A.C. Supply with metal clad enclosure made of 1.6mm thick
steel duly powder coated in convenient sections complete
with 4Nos aluminium bus bars, necessary joints, elbow joints
& expansion joints, fire barrier at each floor, provision of
tapping at every metre, continues earthing with 2Nos
6 aluminium strip of suitable sixe (one on each side) including,
G.I.clamping brackets, suspenders, angle iron bracket, steel
fasteners, connecting to earthing system etc. as required.

1250 amps 50KA SC for 1 sec ( from Transfomers to NE


6.1 panel ) 25 Metre
1000 amps 50KA SC for 1 sec ( from NE panel to Essential
6.2 panel ) 10 Metre
Supplying and installing following size of perforated pre-
painted M.S. cable trays with perforation not more than
17.5%, in convenient sections, joined with connectors,
7 suspended from the ceiling with M.S. suspenders including
bolts & nuts, painting suspenders etc, complete as required.

7.1 300 mm width X 50 mm depth X 1.6 mm thickness 10 Metre


7.2 150 mm width X 50 mm depth X 1.6 mm thickness 10 Metre
Supplying and installing following size of perforated pre-
painted M.S. cable trays bends with perforation not more
than 17.5%, in convenient sections, joined with connectors,
8 suspended from the ceiling with M.S. suspenders including
bolts & nuts, painting suspenders etc, complete as required.

8.1 300 mm width X 50 mm depth X 1.6 mm thickness 10 Each


8.2 150 mm width X 50 mm depth X 1.6 mm thickness 10 Each
Supply of following size XLPE insulated, aluminium
conductor, armoured (galvanised steel strip), extruded PVC
Type ST2 sheathed, UG cable of 1.1 KV grade, conforming to
9 IS 7098 (Part-1) 1988, duly ISI marked complete as required.

9.1 3 ½ X 400 sq.mm ( from NE panel to Capacitor panel ) 20 Metre


Laying of one number PVC insulated and PVC sheathed/ XLPE
10 power cable of 1.1KV grade of following size on cable tray as
required.
10.1 Above 185 sq. mm and upto 400 sq.mm 10 Metre
Laying of one number PVC insulated and PVC sheathed/ XLPE
11 power cable of 11KV grade of following size in the existing
masonry open duct as required.
11.1 Above 120 sq.mm and upto 400 sq.mm 10 Metre
Supplying and making end termination with brass
compression gland and aluminium lugs for following size of
12 PVC insulated and PVC sheathed/XLPE aluminium conductor
cable of 1.1KV grade as required.

12.1 3 ½ X 400 sq.mm (82mm) 2 Each


Providing, laying and fixing following dia RCC pipe NP 2 class
(light duty) in ground complete with RCC collars, jointing
with cement mortar 1:2 (1 cement : 2 fine sand) including
13 trenching (130 cm deep) and refilling etc. as required.

13.1 250 mm dia 90 Metre


Total of Sub Head III
Sub Head - IV (Earthing)
Earthing with copper earth plate 600mm X 600mm X 3mm
thick including accessories, and providing masonry enclosure
with cover plate having locking arrangement and watering
1 pipe of 2.7 metre long etc. with charcoal/coke and salt as 4 Set
required.
Earthing with G.I. earth plate 600mm X 600mm X 6mm thick
including accessories, and providing masonry enclosure with
cover plate having locking arrangement and watering pipe of
2 2.7 metre long etc. with charcoal/coke and salt as required. 2 Set

Providing and fixing 25 mm X 5 mm copper strip in 40 mm


dia G.I. pipe FRLS earth electrode including connection with
3 brass nut, bolt, spring, washer excavation and re-filling etc. as 20 Metre
required.

Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia


G.I. pipe FRLS earth electrode including connection with G.I.
4 nut, bolt, spring, washer excavation and re-filling etc. as 30 Metre
required.

Providing and fixing 25mm X 5mm copper strip on surface or


5 in recess for connections etc. as required. 30 Metre
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in
6 recess for connections etc. as required. 80 Metre

Total of Sub Head IV


Sub Head - V (Safety Equipment)
Providing and fixing H.T. danger notice plate of 250 mm X
200 mm, made of mild steel, at least 2 mm thick, and vitreous
enameled white on both sides, and with inscription in single
1 red colour on front side as required. 6 Each

Providing and fixing M.V. danger notice plate of 200 mm X


150 mm, made of mild steel, at least 2 mm thick, and vitreous
enameled white on both sides, and with inscription in single
2 red colour on front side as required. 6 Each

Providing and fixing carbon dioxide (CO2) type fire


3 extinguishers confirming to IS 2878 - 1976 and cylinders
fully charged of following capacity.
a) 4.5 Kg. 6 Each
Supply and fixing of foam fire extinguishers, Portable type 9
4 lit capacity hanged on wall with bracket complete as 2 Each
required.
Supply and fixing safety instruction chart in word duly
5 framed with 5mm thick glass as required (approx. Front area 2 Each
1.20 sq.mt.)
Providing of set of 4 nos. 9.5 litre capacity GI bucket painted
in post office red colour with prior coat of red-oxide paint
and written with white paint 'FIRE' and mounted on MS angle
6 iron frame with bracket of appropriate size & capacity I/c 4 Set
filling sand etc.

First Aid Box as approved by St. John Ambulance Brigade /


7 Indian Red Cross conforming to IS 2217-1963. 1 Each
Supply and fixing shock treat chart duly mounted on a
8 wooden frame with 5mm thick glass as reqd. (approximate 2 Each
front area 1.20 sq.m).
Supply of Insulating rubber mat, 2.5mm±10% thick having 1
m. standard width and capable of withstanding working
voltages upto 11 KV A.C ( rms) and having dielectric strength
9 of 45KV A.C ( rms ) with anti-skid aberration marks on the 10 Metre
upper surface of the mat as per IS 15625-2006 as required.

Supply of Insulating rubber mat, 2.0mm ±10% thick, having 1


m. standard width and capable of withstanding working
voltages upto 3.3 KV A.C ( rms), having dielectric strength of
10 30KV A.C ( rms ) with anti-skid aberration marks on the 20 Metre
upper surface of the mat as per IS 15625-2006 as required.

Total of Sub Head V


Total : C6 SUB STATION EQUIPMENT
C-7 : D.G. SETS
S.No. Description Quantity Unit

SUB-HEAD-I(SITC OF D.G.SET)
Supplying, installing, testing and commissioning of silent
type Diesel Generating set having prime power rating of 500
KVA, 415 Volts at 1500 RPM, 0.8 lagging power factor at 415
1 V suitable for 50 Hz, 3 phase system and for 0.85 load factor
and consisting of the followings:

a) Diesel Engine:
Diesel engine, 4 stroke, turbo charged, after cooled, electric
start of suitable BHP at 1500 RPM suitable for above output
of alternator at 40°C, 50% R.H and at 1000 MSL and
conforming to BS 5514 capable of taking 10% over loading
for one hour after 12 hours of continuous operation. The
engine will be fitted complete with all the required.

Engine mounted Instrument panel shall be fitted with and


shall have digital display for following.
(i) Start - stop switch with key/Push button
(ii) Water temperature indication
(iii) Lubrication oil pressure indicator
(iv) Battery charging indication
(v) RPM indication
(vi) Over speed indication
(vii) Low lub. Oil Pressure trip indication
(viii) Engine Hours indication
b) Alternator
Synchronous alternator rated at 500 KVA, 415 Volts at 1500
RPM, 3 Phase 50 Hz, AC supply with 0.8 lagging power factor
at 40°C, 50% R.H and at 1000 MSL. The alternator shall be
having SPDP enclosure, brushless, continuous duty, self-
excited and self-regulated through AVR, conforming to IS:
4722/ BS 2613, suitable for tropical conditions and with class
- H insulation as required.

c) Base Frame & Foundation


Both the engine and alternator shall be mounted on suitable
base frame made of MS channel with necessary
reinforcement which shall be installed on 1:2:4 ( 1 Cement : 2
coarse sand :4 graded stone aggregate 20 mm nominal size)
cement concrete foundation( as per the drawing duly
approved by the Engineer-in-charge & as per
recommendations of the manufacturer) i/c excavation ,
centering, shuttering, finishing with plastering pdg. vibration
isolation arrangement as required.

d) Fuel Tank
Daily service fuel tank of 700 ltrs. capacity, fabricated out of 3
mm thick M.S. sheet complete with all standard accessories
and fuel piping between fuel tank and diesel engine with MS
class 'C' pipes of suitable dia. complete with valves, level
indications & accessories as required as per specifications.
Fuel tank should consist of Float switch / Fuel level sensor
(four levels, Low level, Low Level, High Level & High Level).
Low level & High level announciation required. Fuel Level in
each tank data to be transferred to BMS System.

e) Exhaust System
Dry exhaust manifold with residential exhaust silencer.
f) Starting System
12 V /24V DC starting system comprising of starter motor:
voltage regulator and arrangement for initial excitation
complete with suitable numbers of batteries (25 plates, 180
AH capacity maintenance free lead acid type) as required as
per specifications.

Acoustic and weather proof enclosure with arrangement for


fresh air intake for cooling of the engine & alternator,
g) extraction, discharging hot air into the atmosphere as per
specifications.

h) Building Management System (BMS) Connectivity.


Above Equipments shall be connected to BMS, the following
parameters to be made available in Desk Computer.
Controllers should be compatible to deliver the data or
Modlone converter is to be considered along with necessary
hardware and software to be provided by tenderer. In the
event of emergency or for testing of DG Sets frequently, On /
Off provision required through computer. Distance from DG
Set to Control room (location of Desktop) shall be 60metres
(approx.) Tenderer has to consider necessary control cables
accordingly with RS 232 / 485 interface cable and modem
communication support.

a). Lubricating Oil Pressure


b). Water Temperature.
c). Engine Speed.
d). Reason for DG fail to start.
e). Voltage, Frequency, Current.
f). KWH readings.
g). Fuel Tank Levels. 2 Set

2 AMF Panel
Fabricating, Installing, Testing and Commissioning of automatic
a) 800 Amps, Four pole, ACB ( EDO type) with 50KA breaking
capacity (Ics=100% Icu), micro processor based releases for
O/L, S/C & E/F protection with communication compatibity
port, Modbus Module, power supply module etc., for BMS, - 2
Nos.

b) Auto/Manual/Test/Off Selector switch


c) 2 Nos. Over voltage relay, 2Nos. Reverse power relay and 2Nos. Under voltage relay- 1 set
d) TPN Aluminium Bus Bars - 800A -1set
e) 3 sets of current transformers, CL-1 15VA accuracy for
protection and 15 VA class-I for metering
f) Energy analyser unit to indicate current, voltage, frequency, power factor and KWH
g) Indicating lamps for load on mains and load on set
h) Fuse for Instruments
i) battery charger, complete with transformer/ rectifier, D.C.
Voltmeter and ammeter, selector switch for trickle, off and
boost and current adjustment
j) Mains supply failure monitor
k) Supply failure timer
l) Restoration timer
m) Control unit with three impulse automatic engine start/
stop and failure to start/ lockout
n) Impulse counter with locking and reset facility
o) ON/OFF/Control circuit switch with indicator
p) Audio/ Video annunciation for
(i) High Water temperature
(ii) Low lubricating oil pressure
(iii) Engine over speed
(iv) Engine fails to start
(v) Full load/ Maximum load warning
q) By pass panel shall have 2Nos. 800 Amps, Four pole,
onload change over switches with intercnnections etc. 2 Each
Supplying and fixing exhaust gas piping of suitable dia.
Welded black M.S. 'B' class pipe confirming to IS:3589 cut to
required lengths and installed with necessary bends,
supports and clamps, anti-vibration mountings, insulation of
3 exhaust system with mineral wool/Rockwool,50 mm thick 66 Metre
wiremesh & aluminium cladding etc., as required as per
specifications.

Supply of following size, XLPE insulated PVC outer sheathed


aluminium conductor armoured UG Cable of 1.1 KV grade,
4 confirming to IS: 7098(Part-I) 1988 as amended upto date as
required

a) 3 1/2 x 400 sq.mm 200 Metre


Laying of one number PVC insulated & PVC sheathed / XLPE
5 Power cable of 1.1 KV grade of following size in the existing
RCC/HUME/METAL Pipe as required.
a) Above 185 sq. mm and upto 400 sq. mm 100 Metre
Laying of one number PVC insulated & PVC sheathed / XLPE
6 Power cable of 1.1 KV grade of of following size in the
existing masonry open duct as required.
a) Above 185 sq. mm and upto 400 sq. mm 60 Metre
Supplying and making end termination with brass
compression gland and aluminium lugs for following size of
PVC insulated & PVC sheathed / XLPE Aluminium conductor
7 cable of 1.1 KV grade as required.

a) 3 1/2 x 400 sq.mm 16 Each


Providing, laying and fixing following dia RCC pipe NP 2 class
(light duty) in ground complete with RCC collars, jointing
with cement mortar 1:2 (1 cement : 2 fine sand) including
8 trenching (75 cm deep) and refilling etc. as required. a) 300 50 Metre
mm dia

Earthing with copper earth plate 600 mm X 600 mm X 3 mm


thick including accessories, and providing masonry enclosure
with cover plate having locking arrangement and watering
9 pipe of 2.7metre long etc. with charcoal/ coke and salt as 4 Set
required. ( For nuetral earthing )

Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm


thick including accessories, and providing masonry enclosure
with cover plate having locking arrangement and watering
10 pipe of 2.7 metre long etc. with charcoal/ coke and salt as 2 Set
required. ( For body earthing )
Providing and fixing 25 mm X 5 mm copper. strip in 40 mm
dia G.I. pipe from earth electrode including connections with
11 G.I.nut, bolt, spring, washer, excavation and refilling etc. as 12 Metre
required.

Providing and fixing 25 mm X 5 mm copper strip on surface


12 or in recess for connections etc as required. 10 Metre
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia
G.I. pipe from earth electrode including connections with
13 G.I.nut, bolt, spring,washer, excavation and refilling etc. as 12 Metre
required.

Providing and fixing 25 mm X 5 mm G.I. strip on surface or in


14 recess for connections etc as required. 10 Metre
Providing and fixing 6 SWG dia G.I. wire on surface or in
15 recess for loop earthing along with existing surface/ recessed 400 Metre
conduit/ submain wiring/ cable as required.

Total of C-7 DG SET :


Sub Head 'D' - Electrical Works
Panels and cabling
Supplying, installation, testing and commissioning of outdoor
floor mounted modular type, sectionalised,
compartmentalized MV panel with bolted construction and
having 31 MVA breaking capacity of suitable size fabricated
from CRCA sheet steel of 2 mm thick for frame work,
enclosure and doors, 3 mm thick for gland plates with
stiffeners wherever required, having vibration free structure
chemically treated with seven tank process before painting
for surface treatment and powder coated, with suitable
electrolytic grade high conductivity copper busbar type,
DMC/SMC busbar supports, suitable for 3 phase 415 V 50 Hz
AC supply including providing and fixing the following
1 switchgear mounted thereon complete with gaskets and 1 Job
interconnections, connections as per specifications complete
as required. (The board shall be dust & vermin proof with IP
54 degree of protection as per IS : 60529, free standing type,
mounted on base channel of MS Section not less than 100
mm X 50 mm X 5 mm)

The feeder pillar shall generally confirm to CPWD General


Specification for Electrical works, Part-I Internal 2013, Part II
External 1994 and Part IV substation equipment 2013 as
amended upto date.

The size of the feeder pillar shall be not less than ACB
section:- 2300 mm (Height)x 1100 mm (Width) x 800 mm
(Depth)+ Switch gear section:- 2300 mm (Height) x 4100 mm
(Width) x 300 mm (Depth)

Note : All metering current transformers shall be Class 0.5, 15


VA.
Incomer
800 Amps, four pole, horizontal electrical draw out type
(EDO), Air Circuit Breaker (ACB) of fault breaking capacity
50kA (Icu = Ics = Icw for 1 sec), with Communication
Compatibility Port for BMS, manually operated, fitted with
interlocked door, automatic safety shutters, mechanical
ON/OFF, LED indicating lamps and service/ test/ isolated
a) position indicators and frame earthing contact, conforming to
IS/IEC 60947-2 & IEC 60947-2 as amended up-to-date
complete with following accessories for ACB. - 1 No.

Independent manual spring closing mechanism - 1 No


Microprocessor release for over current, earth fault & short
circuit protection alongwith inbuilt LCD display for fault
indication, menu setting and trip history information
facilities - 1 set

Communication module ( Modbus Module ) and power


supply module- 1 set.
3 Nos. Phase indication LED lamps with 6Amp back up MCB
breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

Load Manager with suitable ratio CTs with Class-0.5 accuracy


b) and HRC fuse protection - 1 Set
Bus Bar chamber
TPN aluminium bus bars of 800Amps capacity with heat
shrinkable coloured sleeves and i/c DMC/SMC bus bars
supports at required intervals complete suitable for
withstanding fault level of 31 MVA for 1 Sec. - 1 Set

Outgoing
i) 400 Amps. 3 pole, Moulded Case Circuit Breaker (MCCB),
50kA breaking capacity (Ics=100% Icu) with Microprocessor
release, horizontal, mechanical draw out type (MDO),
suitable for Communication Compatibility Port for BMS with
Inbuilt RS485 Port to communicate on MODBUS Protocol for
remote Status & Control of MCCB, having adjustment for
over load, short circuit, protection suitable for operation on
415V, 50Hz, 3 phase, AC supply confirms to IS/IEC : 60947-2
& IEC 60947-2 alongwith spreader links- 4 Nos. (3 chillers -
(2 Working + 1 Standby)+ 1 spare ))
ii) 63 A 3P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -16 Nos. ( 6 Pump sets+
7 AHU +3Spare)

iii) 40 A 3P Moulded Case Circuit Breaker (MCCB), 25kA


breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links - 8 Nos. (3 chilled water
pumps primary+ 3 Nos. Cooling towers (Double Circuit) + 2
Spare)

iv) Star Delta starter and ON/OFF indicating light, ON/OFF


push buttons, control fuses, timers, contractors and control
fuses, wiring, interconnections suitable for following rating
motor.

a. for 20 HP motor –5Sets ( 3 Nos. Condenser pumps+ 2 Nos.


spare )
b. for 15 HP motor –3Sets ( Chiller Water pumps Secondary )

c. Mini motor protection relay comprising protection against


Thermal Overload, Earth Fault, Locked Rotor Single
Phasing,Current Unbalance, Phase Sequence Reversal, Under
Current and control fuses- 8 Nos.

v) DOL Starter with ON/OFF indicating light, ON/OFF push


buttons, control fuses, timers, contractors, wiring,
interconnections suitable for following rating motor.

a. for 7.5 HP motor – 8 Sets (Chilled water pumps Primary


pump- 3 Nos. + 3 Nos. Cooling Tower fan+2 Nos. Spare)

b Mini motor protection relay comprising protection against


Thermal Overload, Earth Fault, Locked Rotor Single
Phasing,Current Unbalance, Phase Sequence Reversal, Under
Current and control fuses- 8 Nos.

vi) R,Y,B LED indication lamps with backup control MCBs – 3


Sets For Chillers
Supplying, installing testing and commissioning of MV Panel
Board of Indoor, cubical type, compartmentlised design
fabricated from 2.00 mm thich CRCA sheet having necessary
cable alleys, powder coated through seven tank process
facility for picking and degreasing, including connections and
inter connections as per specifications complete with
2 following accessories are required. (supply panels in AHU 4 Job
room). The size of the panel shall not be less than 1000 mm
(Height) x 1000 mm (Width) x 300 mm (Depth)

Incomer
63 A 4P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1No.

3 Nos. Phase indication LED lamps with 6Amp back up MCB


breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

1 No.0-500V voltmeter with selector switch


1 set .0-100A ammeter with selector switch and 3 Nos. CTs

2 Nos.Push buttons
2 Nos.On/ Off Indicators
Bus Bar Chamber
TPN aluminium bus bars of 100Amps capacity with heat
shrinkable coloured sleeves and i/c DMC/SMC bus bars
supports at required intervals complete suitable for
withstanding fault level of 31 MVA for 1 Sec. - 1 Set

Outgoing
i) 40 A 3P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1 No.
ii) 32 A 3P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1 No.

iii) Mini motor protection relay comprising protection against


Thermal Overload, Earth Fault, Locked Rotor Single
Phasing,Current Unbalance, Phase Sequence Reversal, Under
Current and control fuses- 1 No.

iv) Fully automatic star delta starter with ON/OFF indicating


light, ON/OFF push buttons, control fuses, timers,
contractors, wiring, interconnections suitable for following
rating motor.

a. for 20 HP motor – 1No. ( AHU fan motor )


R,Y,B LED indication lamps with backup control MCBs – 1 Set

Supplying, installing testing and commissioning of MV Panel


Board of Indoor, cubical type, compartmentlised design
fabricated from 2.00 mm thich CRCA sheet having necessary
cable alleys, powder coated through seven tank process
facility for picking and degreasing, including connections and
inter connections as per specifications complete with
3 following accessories are required. (supply panels in AHU 2 Job
room). The size of the panel shall not be less than 1000 mm
(Height) x 1000 mm (Width) x 300 mm (Depth)

Incomer
63 A 4P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1No.

3 Nos. Phase indication LED lamps with 6Amp back up MCB


breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

1 No.0-500V voltmeter with selector switch


1 set .0-100A ammeter with selector switch and 3 Nos. CTs

2 Nos.Push buttons
2 Nos.On/ Off Indicators
Bus Bar Chamber
TPN aluminium bus bars of 100Amps capacity with heat
shrinkable coloured sleeves and i/c DMC/SMC bus bars
supports at required intervals complete suitable for
withstanding fault level of 31 MVA for 1 Sec. - 1 Set

Outgoing
i) 40 A 3P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1 No.

ii) 32 A 3P Moulded Case Circuit Breaker (MCCB), 25kA


breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1 No.

iii) Mini motor protection relay comprising protection against


Thermal Overload, Earth Fault, Locked Rotor Single
Phasing,Current Unbalance, Phase Sequence Reversal, Under
Current and control fuses- 1 No.

iv) Fully automatic star delta starter with ON/OFF indicating


light, ON/OFF push buttons, control fuses, timers,
contractors, wiring, interconnections suitable for following
rating motor.

a. for 15 HP motor – 1No. ( AHU fan motor )


R,Y,B LED indication lamps with backup control MCBs – 1 Set

Supplying, installing testing and commissioning of MV Panel


Board of Indoor, cubical type, compartmentlised design
fabricated from 2.00 mm thich CRCA sheet having necessary
cable alleys, powder coated through seven tank process
facility for picking and degreasing, including connections and
inter connections as per specifications complete with
4 following accessories are required. (supply panels in AHU 1 Job
room). The size of the panel shall not be less than 1000 mm
(Height) x 1000 mm (Width) x 300 mm (Depth)

Incomer
63 A 4P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1No.

3 Nos. Phase indication LED lamps with 6Amp back up MCB


breaker ON / OFF’ LED indicating lamps with 6Amp back up
MCB, test terminal block set, fuses, circuits as per- standard
practice, as required. - 1 set.

1 No.0-500V voltmeter with selector switch


1 set .0-100A ammeter with selector switch and 3 Nos. CTs

2 Nos.Push buttons
2 Nos.On/ Off Indicators
Bus Bar Chamber
TPN aluminium bus bars of 100Amps capacity with heat
shrinkable coloured sleeves and i/c DMC/SMC bus bars
supports at required intervals complete suitable for
withstanding fault level of 31 MVA for 1 Sec. - 1 Set

Outgoing
i) 40 A 3P Moulded Case Circuit Breaker (MCCB), 25kA
breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1 No.

ii) 32 A 3P Moulded Case Circuit Breaker (MCCB), 25kA


breaking capacity (Ics=100% Icu) with Thermal magnetic
release, suitable for Communication Compatibility Port for
BMS with Inbuilt RS485 Port to communicate on MODBUS
Protocol for remote Status & Control of MCCB, having
adjustment for over load, short circuit, protection suitable for
operation on 415V, 50Hz, 3 phase, AC supply confirms to
IS/IEC : 60947-2 & IEC 60947-2 alongwith extended rotary
operating handle and spreader links -1 No.

iii) Mini motor protection relay comprising protection against


Thermal Overload, Earth Fault, Locked Rotor Single
Phasing,Current Unbalance, Phase Sequence Reversal, Under
Current and control fuses- 1 No.
iv) DOL starter with ON/OFF indicating light, ON/OFF push
buttons, control fuses, timers, contractors, wiring,
interconnections suitable for following rating motor.

a. for 10 HP motor – 1No. ( AHU fan motor )


R,Y,B LED indication lamps with backup control MCBs – 1 Set

R,Y,B LED indication lamps with backup control MCBs – 1 Set

Supplying of following size copper conductor XLPE


5 insulated and PVC sheathed armoured power cable of 1.1 KV
grade as required.
a) 3 x 95 Sq.mm 100 Metre

b) 3 x 16 Sq.mm 70 Metre

c) 3 x 10 Sq.mm 180 Metre

d) 3 x 6 Sq.mm 50 Metre

Supplying and making end termination with brass


compression gland and copper lugs for following size of PVC
6 insulated and PVC sheathed / XLPE copper conductor cable of
1.1 KV grade as required.

a) 3 x 95 Sq.mm 8 Each

b) 3 x 16 Sq.mm 28 Each

c) 3 x 10 Sq.mm 12 Each

d) 3 x 6 Sq.mm 4 Each

Supplying of following sizes of PVC insulated and PVC


sheathed/ XLPE aluminium conductor UG armoured cable of
1.1 KV grade confirming to IS:7098 (Part-I) 1988 with upto
7 date amendments duly ISI marked complete as required.

a) 3½ x 300 sq.mm 200 Metre

b) 3½ x 70 sq.mm 230 Metre

Laying of one number PVC insulated and PVC sheathed/ XLPE


power cable of 1.1 KV grade of following size in the existing
8 RCC/ HUME/ METAL pipe as required.

a) Above 35 sq. mm and upto 95 sq. mm 80 Metre

b) Above 185 sq. mm and upto 400 sq. mm 20 Metre


Laying and fixing of one number PVC insulated and PVC
9 sheathed / XLPE power cable of 1.1 KV grade of following
size on wall surface as required
Above 35 sq. mm and upto 95 sq. mm (clamped with 25 x
a) 3mm MS flat clamp) 150 Metre

Above 185 sq. mm and upto 400 sq. mm (clamped with


b) 40x3mm MS flat clamp) 180 Metre

Supplying and making end termination with brass


compression gland and aluminium lugs for following size of
10 PVC insulated and PVC sheathed / XLPE aluminium
conductor cable of 1.1 KV grade as required.

a) 3 1/2 x 300 sq.mm (70mm) 4 Each

b) 3 1/2 x 70 sq.mm (38 mm) 14 Each

Earthing
Earthing with copper earth plate 600 mm X 600 mm X 3 mm
thick including accessories, and providing masonry enclosure
with cover plate having locking arrangement and watering
11 pipe of 2.7 metre long etc. with charcoal/ coke and salt as 2 Set
required.

Providing and fixing 25 mm X 5 mm copper strip in 40 mm


dia G.I. pipe from earth electrode including connection with
12 brass nut, bolt, spring, washer excavation and re-filling etc. as 20 Metre
required.

Providing and fixing 25 mm X 5 mm copper strip on surface


13 or in recess for connections etc. as required. 60 Metre

Providing and fixing 25 mm X 5 mm G.I strip on surface or in


14 recess for connections etc. as required. 120 Metre

Providing and fixing 6 SWG dia G.I. wire on surface or in


15 recess for loop earthing as required. 1000 Metre

Total Sub Head D:


Total of Part - A
PART - B (COMPREHENSIVE MAINTENANCE AND OPERATION
OF THE SERVICES)
Operation of the high side and low side of the Air
conditioning plant comprising all the machinery, equipment
installed in the AC plant including cooling towers in three
1 shifts of 8 hours each per day as per maintenance schedule
attached.

a. 1st year (defect liability period) Per


12
Month
b. 2nd year Per
12
Month

c. 3rd year Per


12
Month

d. 4th year Per


12 Month

Comprehensive maintenance of ( routine & preventive ) and


break down maintenance of high side and low side of the Air
conditioning plant comprising all the machinery, equipment
2 installed in the AC plant including cooling towers.

Defect Liability
a. 1st year Period

Per
b. 2nd year 12 Month

Per
c. 3rd year 12 Month

Per
d. 4th year 12 Month

Total PART B:
Total C-8 CENTRAL A.C. PLANT : (A+B)
C9: IBMS
S.No. Description Quantity Unit
PART-A ( SITC OF BMS )
1 CENTRAL CONTROL STATIONS
Supplying, Installing, Testing & Commissioning of the Central
Control Stations consisting of the following
Supply, installation, testing and commissioning of 3rd Gen
Intel Core i3-3220 Processor (Dual Core, 3.30GHz, 3MB, w/
HD2500 Graphics) , minimum of 8 GB RAM, Intel Integrated
Graphics w/DP/DVI, OPTI (320-3778), 8X SlimLine, DVD+/-
RW,& 120GB HDD, optical Mouse, 106 keys keyboard, 10/100
Mbps Ethernet card, USB connection & internal modem,
including providing Central work station client and the
1.1 Workstation shall be preloaded with requisite MS Windos 7 1 Each
or above Licensed software compatible with BMS platform
with Data base, OS & Firewall softwares ( for 1 No. Work
station PC and 2 Nos. web clients )

1.2 132 Column 240 CPS Printer (Alarm & Report) 1 Each
1.3 42 " colour Professional LED monitor 1 Each
2 SOFTWARE
Supplying, Installation, Testing and Commissioning of the
Graphical Building Automation/Management Software
Operating on Windows platform ( All required Software with
original license competent with BMS software, Development
Software, Hardware-Dongle etc. i) Front End GUI /
BMS Software: Web Based Graphical Software meeting the
requirements given in I/O Summary and technical
specifications including configuration and facility to create /
provide the graphic mapping for all I/O Summary points,
animate the Graphics, Navigation between pages, display of 1 Set
logs, changing the time zones, popup alarms, configurable
password protection for Building Automation / Building
Management System as per Specifications.

2.1

ii) Standard Energy management Software to cater to the


requirements of the BMS and
iii) Energy Management Console- Attune Advisory complete
as required.
The Web-Based Server software shall permit use of Standard
Web-Browsers such as Microsoft Internet Explorer, Netscape
Navigator, etc Software should have licensce of 4000 points
(hardwired 1500 points & software 2500 points both).The
OEM shall support the license for minimum of 5 years.

Onboard IP Open Protocol Output Integrators compatible for


BACNET/LON or BACNET/MODBUS output meeting Vendor's
communication platform to Acquire data and Control
2.2 Operation of following Equipment/ Hardwares

a Chiller -3 Nos. to be on BACnet/IP 1 Set


b Fire Alarm System -1 No. to be on BACnet/IP for 500 points 1 Set
c VAV -35 Nos. to be on BACnet/IP 1 Set
d Lifts - 2Nos to be on Modbus RTU With RS 485 Communication 1 Set
e VFD for AHUs/TFAs - 7 Nos. to be on Modbus RTU with RS 48 1 Set
f DG - 2 Nos. to be on Modbus RTU with RS 485 Communication 1 Set
g 2 Nos. UPS to be on Modbus RTU with RS 485 Communication 1 Set
h Energy Meter - 31 Nos. to be on Modbus RTU with RS 485 Com 1 Set
i BTU Meter to be on M-bus/ Modbus RTU with RS 485 Communi 7 Each
3 CONTROLLERS
SITC of BACnet/ LON/ BACnet IP, 32 bit microprocessor
Network DDC controller with inbuilt Gateway and Bacnet
Router function. The controller shall be standalone type and
shall be capable of networked operations to exchange data
with other controllers and workstations. DDC controller must
use Bacnet IP protocol to communicate with IBMS software.
Controller should be capable to function as Gateway for 3rd
party Modbus RTU or Bacnet MSTP devices. Controller
should also be capable to function as Bacnet router for
Bacnet MSTP devices. Controller should also be capable to do
3.1 all the three functions (DDC, Gateway and Rotuer)
simultaneously. Maximum Hard I/O's per Network Controller
including Expansion I/O's not to exceed 256. Maximum
Bacnet MSTP Controller and Modbus devices per Network
DDC controller not to exceed 80.

a. Chiller and Condenser water pump System ( Minimum of AI - 4, 1 Job


b Air Handling Units - Floor Mounted ( Minimum of AI-10, DI-9, 7 Job
c. Dry type Transformer, Essential panel, Capacitor panel, AC pan 1 Job
d. DG-2Nos Set ( Minimum of AI-2, DI-12, AO-0, DO-2) 1 Job
e. Fire Fighting & Water Pump system ( Minimum of AI-0, DI-25 1 Job
4 SENSORS & FIELD DEVICES
Supply, installation, testing & commissioning of the following Sensors :
a Immersion type temperature sensors for measuring Chilled wat 14 Each
b Duct type temperature sensors for measuring Supply & Return 14 Each
c Single Level Switch For indicating low level status of CT & Wat 12 Each
d Differential Pressure switch across the Air Handling Units & Tr 14 Each
e Differential Pressure switch across the water pumps for indic 9 Each
f Current Relay 25 Each
g Outside Temperature + Rh Sensors 1 Each
h Flame proof level switch for indicating fuel low level status in 2 Each
i CO2 sensor for indicating CO2 level in AHU duct 7 Each
j Water flow switches for Chillers & Cooling Towers 10 Each
BTU Meter with in-built display including the provision for
installing the meter in the chilled water pipe line with with
suitable flanges and fittings with Thermowell temperature
sensors. Meter shall be suitable for single phase AC power
supply. The BTU hour meters shall be insulated in such a
manner so that the display is not covered. The BTU meter
shall have its own integrator and interconnected control
wiring between the BTU meter and integrator. Suitable no of
repeaters shall be provided in the cost of BTU meter only. The
k meter will have low maintenance and high accuracy. Can
operate in cooling as well heating mode shall be suitable for
system integration with M bus module for centralised data
logging. The meter shall be suitable for following pipes sizes:

a. 100 mm dia 2 Each


b. 65 mm dia 3 Each
c. 50 mm dia 1 Each
d. 40 mm dia 1 Each
l Tenant Billing software with M-bus connector and desktop ma 1 Each
5 CABLING
Supplying, laying and fixing of 3x1.5 Sq. mm 500 V grade
flame retardant, steel braided/ copper braided, copper
conductor armoured control cables, stranded, XLPE
Insulated, PVC tape inner sheathed for Multicore Cables,
5.1 650/1100 V grade as per IS 7098 (Part 1) 1988 etc as 500 Mtrs.
required on surface/ existing wireway etc as required.

Supplying, laying and fixing of 4x1.5 Sq. mm 500 V grade


flame retardant, steel braided/ copper braided, copper
conductor armoured control cables, stranded, XLPE
Insulated, PVC tape inner sheathed for Multicore Cables,
5.2 650/1100 V grade as per IS 7098 (Part 1) 1988 etc as 5000 Mtrs.
required on surface/ existing wireway etc as required.

Supplying, laying and fixing of 8x1.5 Sq. mm 500 V grade


flame retardant, steel braided/ copper braided, copper
conductor armoured control cables, stranded, XLPE
Insulated, PVC tape inner sheathed for Multicore Cables,
5.3 650/1100 V grade as per IS 7098 (Part 1) 1988 etc as 2000 Mtrs.
required on surface/ existing wireway etc as required.

Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the


5.4 on surface/ existing wireway etc as required. 1000 Mtrs.

Total of Part - A
PART-'B'
COMPREHENSIVE MAINTENANCE AND OPERATION OF THE
SERVICES
Operation of the BMS system comprising all the machinery,
equipment installed at site in single shift of 8 hours each per
1 day with one number IBMS Engineer as per maintenance
standards of manufacturer.

a. 1st year ( defect liability period ) Per


12
month
b. 2nd year Per
12
month

c. 3rd year Per


12
month

d. 4th year Per


12 month

Comprehensive maintenance of (routine & preventive) and


break down maintenance of BMS components comprising all
equipement controllers, sensors, filed devices, BTU meters
2 software, hardware complete as required.

1st year Defect liability period


a. 2nd year Per
12
month
b. 3rd year Per
12 month
c. 4th year Per
12 month
Total of Part - B
Total C-9 OF IBMS (A+B)
C10: Public Address & Conference System
S.No. Description Quantity Unit
SH.I-PA SYSTEM
Supplying, Installation, testing and commissioning of 6 zone
system Pre-Amplifier with single or dual channel operation,
two inputs for call stations, universal input for
microphone/line with two speech optimized tone control,
three inputs for BGM selection and music optimized tone
control, front panel zone selection for BGM and call station,
1 zone selection for calls, PC and trigger inputs for automated 1 Each
calls, alarm tones etc., Suitable for operation on 230 Volts
AC/115 Volts DC supply complete as required.

Supplying, Installation, testing and commissioning of 480W


Booster Amplifier with Channels / zoning feature as per the
2 specification and requirement of site condition. 1 Each
Supplying, Installation, testing and commissioning of 6 Watt
compact recess mounting type speakers with line matching
3 transformers ( Recessed Mounting type ) as per the 80 Each
specification and requirement of site condition.

Supplying, Installation, testing and commissioning of 24 V,6


zone call station, unidirectional condenser microphone on
flexible system, six zone selection keys, all call key and
4 mementary PTT-key for calls etc., as required. 1 Each

Supplying, installation, testing and commissioning of 12U


5 rack with all connected accessories complete., as required 1 Each

Supplying and drawing 2 core 1 sqmm twin twisted speaker


6 cable in the existing surface / recessed Aluminium / steel / 1000 Mtr
PVC conduit / trunking as required

Total of Sub Head-I


SH.II-Conference System
Supply, installation, Testing and Commissioning of Central
1 Control unit with digital effective as per specifications 1 Each
attached in NIT
Supply, installation, Testing and Commissioning of Chairman
Unit with the following controls and indicators as per
2 specifications attached in NIT (Chairman Unit) 1 Each

Supply, installation, Testing and Commissioning of Delegate


Unit with the following controls and indicators, as per
3 specifications attached in NIT (Delegate units) 19 Each

Supply, installation, Testing and Commissioning of extension


cable 10 meters The extension cable assembly shall consist of
10 m of 6 mm diameter cable terminated at one end with a
4 molded 7-pole male circular connector, and at the other end 2 Each
with a molded 7-pole female circular connector complete as
required.

(For above Units Micro phone)


Supply,installation,Testing and Commissioning of the Cable
Clamp to secure loop through cables to the next unit to
prevent disconnection. Each male/female connector shall
5 consist one cable lock clamp for all deligate units complete 1 job
etc as required.

Supply,installation,Testing and Commissioning of LCD


6 Projector as per specifications attached in NIT 1 Each
Remote Operating Motorised screen with RF remate control
suitable to work on Electric motor of size 1800 mm x 2400
mm(6' x 8') / 3000 mm(120 inch) diagonal and with 16: 9
7 aspect ratio complete as required. complete as required. 1 Each
SITC of wireless DONGLE of Mobility chocolate bar size,easy
8 to carry/compatibility for projectors, fastest projection 1 Each
speed.

Total of Sub Head-II


Total C10: Public Address & Conference System
C11: EPABX
S.No. Description Quantity Unit
SITC of IP Communication EPABX system equipped with 08
Analog Trunk Lines, 02 ISDN BRI lines, 08 Digital Extensions,
52 Analog Extensions ( Expanbable to 68 extensions)
inclusive of IP gate way Card with 08 B channels – 1No. and 1 Each
Auto Attendant License – 01 No complete with following
features as required.

Inbuilt Unified Communication Architecture


Inbuilt LCR Least Cost Routing for multiple operator network

Inbuilt IP Card for IP Networking/IP Phones Connectivity

Inbuilt ISDN architecture on trunks and extensions


1 Inbuilt UCD applications
Dial by name from Digital phone/ PC
External Call forwarding
Support up to ISDN PRI Lines
5 Party Conference
ISDN Video Conference behind EPABX
Multi subscriber numbering behind EPABX on ISDN
MMC in Built
Inbuilt Phone Book with 1000 Numbers
DECT Compatability.
Walk in Class of Service
Project Codes/Account Codes
100% Non-Blocking
Supplying and Fixing OPENSTAGE DIGITAL PHONE with 08
free programmable keys, Full duplex hands free, integrated
USB integrated and colour display bluetooth support
2 including supplying and fixing Openstage 40 BLF with 90 1 Each
Keys complete., as required.

Supplying and Fixing OPENSTAGE DIGITAL PHONE with 08


3 free programmable keys facility ,Full duplex hands free and 6 Each
etc., as required.
Supplying and Fixing Analog Speaker phone with storing
4 facility of 10 phone No's, programmable speed dailing keys 46 Each
etc., as required.
Supplying and drawing following pair, 0.5 mm dia FR PVC
insulated copper conductor, jelly Filled armoured telephone
5 cable in the existing surface / recessed Aluminium / steel /
PVC conduit / trunking as required
a) 10 pair 100 Mtr

b) 20 pair 100 Mtr

c) 50 Pair 200 Mtr


Supply, Installation, Testing and Commissioning of following
pair MDF Box with modules and termination including
6 providing and fixing identification ferrules and console etc. as
required.

a) 10 pair 12 EACH

b) 20 pair 6 EACH

c) 50 Pair 1 EACH
Total C-11 EPABX
220.00 #NAME? 880.00

370.00 #NAME? 37,000.00

760.00 #NAME? 57,000.00

600.00 #NAME? 2,400.00

725.00 #NAME? 72,500.00

1,700.00 #NAME? 13,600.00

9,000.00 #NAME? 72,000.00

18,500.00 #NAME? 111,000.00

6,000.00 #NAME? 6,000.00

7,500.00 #NAME? 7,500.00

#NAME? 379,880.00
1,800.00 #NAME? 2,138,400.00

5,400.00 #NAME? 3,580,200.00

50,000.00 #NAME? 100,000.00

27,000.00 #NAME? 162,000.00

750.00 #NAME? 68,250.00

#NAME? 6,048,850.00

400.00 #NAME? 960,000.00

410.00 #NAME? 246,000.00

3,600.00 #NAME? 1,566,000.00

5,000.00 #NAME? 195,000.00


100.00 #NAME? 27,000.00

#NAME? 2,994,000.00

500.00 #NAME? 162,500.00

500.00 #NAME? 140,000.00

1,050.00 #NAME? 672,000.00

#NAME? 974,500.00

Rate in
Rate in Figure Amount(Rs.)
words

1,490.00 #NAME? 1,376,760.00

145.00 #NAME? 145,000.00


260.00 #NAME? 182,000.00

85.00 #NAME? 59,500.00


215.00 #NAME? 64,500.00
390.00 #NAME? 195,000.00

90.00 #NAME? 36,000.00


135.00 #NAME? 87,750.00
105.00 #NAME? 4,200.00
210.00 #NAME? 6,300.00
315.00 #NAME? 63,000.00

40.00 #NAME? 28,000.00


50.00 #NAME? 100,000.00
60.00 #NAME? 12,000.00

350.00 #NAME? 35,000.00

755.00 #NAME? 120,800.00

1,065.00 #NAME? 79,875.00


525.00 #NAME? 15,750.00

270.00 #NAME? 810.00

4,000.00 #NAME? 48,000.00

300.00 #NAME? 4,500.00

65.00 #NAME? 7,475.00


105.00 #NAME? 12,075.00

400.00 #NAME? 16,400.00

290.00 #NAME? 49,590.00

25.00 #NAME? 15,000.00

30.00 #NAME? 51,000.00

80.00 #NAME? 3,440.00


280.00 #NAME? 36,120.00
1,000.00 #NAME? 7,000.00
#NAME? 2,862,845.00

6,300.00 #NAME? 1,650,600.00

2,030.00 #NAME? 109,620.00

2,170.00 #NAME? 62,930.00


2,660.00 #NAME? 273,980.00

3,780.00 #NAME? 328,860.00

5,795.00 #NAME? 452,010.00

2,780.00 #NAME? 19,460.00


39,000.00 #NAME? 312,000.00

1,700.00 #NAME? 69,700.00

3,000.00 #NAME? 84,000.00


2,650.00 #NAME? 18,550.00
#NAME? 3,381,710.00
130,000.00 #NAME? 910,000.00
136,000.00 #NAME? 952,000.00

5,000.00 #NAME? 75,000.00

5,500.00 #NAME? 33,000.00

7,600.00 #NAME? 395,200.00


9,000.00 #NAME? 234,000.00

9,300.00 #NAME? 130,200.00


9,300.00 #NAME? 65,100.00
22,500.00 #NAME? 45,000.00
35,000.00 #NAME? 35,000.00

100.00 #NAME? 34,200.00


730.00 #NAME? 4,380.00

1,250.00 #NAME? 18,750.00

2,000.00 #NAME? 30,000.00


1,750.00 #NAME? 10,500.00
#NAME? 2,972,330.00

225.00 #NAME? 18,000.00


600.00 #NAME? 66,000.00
885.00 #NAME? 44,250.00

50.00 #NAME? 4,000.00


65.00 #NAME? 10,400.00

400.00 #NAME? 1,600.00


600.00 #NAME? 2,400.00
900.00 #NAME? 1,800.00
#NAME? 148,450.00

75.00 #NAME? 22,500.00

75.00 #NAME? 9,000.00

50.00 #NAME? 1,250.00

100.00 #NAME? 500.00

225.00 #NAME? 5,625.00

2,000.00 #NAME? 2,000.00

#NAME? 40,875.00

12,500.00 #NAME? 37,500.00

175.00 #NAME? 17,500.00

25.00 #NAME? 6,250.00

#NAME? 61,250.00

9,000.00 #NAME? 108,000.00


7,000.00 #NAME? 84,000.00

1,250.00 #NAME? 15,000.00

900.00 #NAME? 10,800.00

3,000.00 #NAME? 66,000.00

4,480.00 #NAME? 53,760.00

14,490.00 #NAME? 144,900.00

5,040.00 #NAME? 75,600.00


45.00 #NAME? 3,150.00

300.00 #NAME? 7,500.00

130.00 #NAME? 59,800.00

30.00 #NAME? 12,000.00

300.00 #NAME? 105,000.00

290.00 #NAME? 34,800.00

150.00 #NAME? 19,500.00

#NAME? 799,810.00

50,000.00 #NAME? 100,000.00

#NAME? 0.00

650.00 #NAME? 7,800.00


3,500.00 #NAME? 3,500.00
3,000.00 #NAME? 6,000.00

46,200.00 #NAME? 46,200.00

225.00 #NAME? 6,750.00

#NAME? 170,250.00
Rate in
Rate in Figure Amount
words
2,800,000.00 #NAME? 2,800,000.00
2,900,000.00 #NAME? 2,900,000.00

#NAME? 5,700,000.00

90,000.00 #NAME? 90,000.00


90,000.00 #NAME? 90,000.00
90,000.00 #NAME? 90,000.00
90,000.00 #NAME? 90,000.00
90,000.00 #NAME? 90,000.00

90,000.00 #NAME? 90,000.00


90,000.00 #NAME? 90,000.00
90,000.00 #NAME? 90,000.00
90,000.00 #NAME? 90,000.00
90,000.00 #NAME? 90,000.00
#NAME? 900,000.00
#NAME? 6,600,000.00

Rate in
Rate in Figure Amount
words
400,000.00 #NAME? 800,000.00
690,000.00 #NAME? 690,000.00
96,000.00 #NAME? 192,000.00

50,000.00 #NAME? 50,000.00


290,000.00 #NAME? 290,000.00
13,500.00 #NAME? 13,500.00

600.00 #NAME? 36,000.00


400.00 #NAME? 12,000.00
185.00 #NAME? 5,550.00

275.00 #NAME? 8,250.00


275.00 #NAME? 8,250.00

600.00 #NAME? 1,200.00


500.00 #NAME? 2,000.00
350.00 #NAME? 700.00

600.00 #NAME? 18,000.00


300.00 #NAME? 3,000.00
200.00 #NAME? 2,000.00
#NAME? 2,132,450.00
22,950.00 #NAME? 160,650.00

8,300.00 #NAME? 91,300.00

5,740.00 #NAME? 206,640.00

8,710.00 #NAME? 60,970.00

9,450.00 #NAME? 151,200.00


6,885.00 #NAME? 20,655.00

103,180.00

9,380.00 #NAME?
6,480.00 #NAME? 77,760.00
5,670.00 #NAME? 5,670.00

14,175.00 #NAME? 14,175.00

8,775.00 #NAME? 17,550.00

8,100.00 #NAME? 24,300.00

8,775.00 #NAME? 96,525.00

31,725.00 #NAME? 63,450.00


40,500.00 #NAME? 40,500.00

2,630.00 #NAME? 65,750.00

2,800.00 #NAME? 840,000.00

2,550.00 #NAME? 63,750.00

2,360.00 #NAME? 59,000.00


1,690.00 #NAME? 135,200.00

4,000.00 #NAME? 60,000.00

400.00 #NAME? 456,800.00


56,025.00 #NAME? 56,025.00

1,690.00 #NAME? 202,800.00


1,280.00 #NAME? 384,000.00
1,110.00 #NAME? 277,500.00
930.00 #NAME? 186,000.00
715.00 #NAME? 71,500.00
610.00 #NAME? 30,500.00
510.00 #NAME? 76,500.00

6,480.00 #NAME? 12,960.00

6,480.00 #NAME? 45,360.00


5,265.00 #NAME? 10,530.00
4,590.00 #NAME? 13,770.00

3,645.00 #NAME? 25,515.00

7,560.00 #NAME? 52,920.00

2,900.00 #NAME? 11,600.00

#NAME? 4,272,505.00
12,500.00 #NAME? 50,000.00

360.00 #NAME? 14,400.00

160.00 #NAME? 4,800.00


#NAME? 69,200.00
#NAME? 6,474,155.00

Rate in
Rate in Figure Amount
words

369,872.00 #NAME? 369,872.00

3,100.00 #NAME? 616,900.00


3,100.00 #NAME? 616,900.00

2,980.00 #NAME? 14,900.00


3,310.00 #NAME? 46,340.00

1,600.00 #NAME? 22,400.00

3,310.00 #NAME? 23,170.00

6,756.00 #NAME? 94,584.00

100.00 #NAME? 19,900.00

134,000.00 #NAME? 134,000.00

38,000.00 #NAME? 76,000.00

115.00 #NAME? 402,500.00

55.00 #NAME? 220,000.00


76.00 #NAME? 38,000.00
#NAME? 2,695,466.00

Rate in
Rate in Figure Amount
words
400,000.00 #NAME? 400,000.00
1,080,000.00 #NAME? 1,080,000.00

1,650,000.00 #NAME? 3,300,000.00

#NAME? 4,780,000.00
1,900,000.00 #NAME? 1,900,000.00
840,000.00 #NAME? 840,000.00
600,000.00 #NAME? 600,000.00
#NAME? 3,340,000.00
1,850.00 #NAME? 333,000.00

50.00 #NAME? 1,000.00

75.00 #NAME? 7,500.00

75.00 #NAME? 3,000.00

12,500.00 #NAME? 75,000.00

24,750.00 #NAME? 618,750.00

19,500.00 #NAME? 195,000.00


600.00 #NAME? 6,000.00
300.00 #NAME? 3,000.00

600.00 #NAME? 6,000.00


300.00 #NAME? 3,000.00

1,725.00 #NAME? 34,500.00

50.00 #NAME? 500.00

50.00 #NAME? 500.00

1,800.00 #NAME? 3,600.00

800.00 #NAME? 72,000.00


#NAME? 1,362,350.00

27,500.00 #NAME? 110,000.00


12,500.00 #NAME? 25,000.00

1,450.00 #NAME? 29,000.00

375.00 #NAME? 11,250.00

1,250.00 #NAME? 37,500.00

175.00 #NAME? 14,000.00


#NAME? 226,750.00

100.00 #NAME? 600.00

100.00 #NAME? 600.00

5,600.00 #NAME? 33,600.00

11,000.00 #NAME? 22,000.00

1,200.00 #NAME? 2,400.00

1,500.00 #NAME? 6,000.00

2,000.00 #NAME? 2,000.00


1,200.00 #NAME? 2,400.00

3,000.00 #NAME? 30,000.00

2,750.00 #NAME? 55,000.00

#NAME? 154,600.00
#NAME? 9,863,700.00

Rate in
Rate in Figure Amount
words
3,300,000.00 #NAME? 6,600,000.00

voltage relay- 1 set

ctor and KWH


680,000.00 #NAME? 1,360,000.00

4,800.00 #NAME? 316,800.00

1,725.00 #NAME? 345,000.00

50.00 #NAME? 5,000.00

50.00 #NAME? 3,000.00

1,800.00 #NAME? 28,800.00

1,200.00 #NAME? 60,000.00

27,500.00 #NAME? 110,000.00

12,500.00 #NAME? 25,000.00


1,250.00 #NAME? 15,000.00

1,250.00 #NAME? 12,500.00

375.00 #NAME? 4,500.00

375.00 #NAME? 3,750.00

25.00 #NAME? 10,000.00

#NAME? 8,899,350.00

735,000.00 #NAME? 735,000.00


38,000.00 #NAME? 152,000.00
35,000.00 #NAME? 70,000.00
33,000.00 #NAME? 33,000.00
900.00 #NAME? 90,000.00

550.00 #NAME? 38,500.00

450.00 #NAME? 81,000.00

300.00 #NAME? 15,000.00

900.00 #NAME? 7,200.00

650.00 #NAME? 18,200.00

500.00 #NAME? 6,000.00

350.00 #NAME? 1,400.00

1,700.00 #NAME? 340,000.00

580.00 #NAME? 133,400.00

140.00 #NAME? 11,200.00

250.00 #NAME? 5,000.00


90.00 #NAME? 13,500.00

150.00 #NAME? 27,000.00

1,500.00 #NAME? 6,000.00

650.00 #NAME? 9,100.00

15,600.00 #NAME? 31,200.00

2,200.00 #NAME? 44,000.00

2,100.00 #NAME? 126,000.00

220.00 #NAME? 26,400.00

24.00 #NAME? 24,000.00


#NAME? 2,044,100.00
#NAME? 10,943,450.00

30,000.00 #NAME? 360,000.00


33,000.00 #NAME? 396,000.00

36,000.00 #NAME? 432,000.00

40,000.00 #NAME? 480,000.00

40,000.00 #NAME? 480,000.00

44,000.00 #NAME? 528,000.00

48,000.00 #NAME? 576,000.00

#NAME? 3,252,000
#NAME? 14,195,450

Rate in
Rate in Figure Amount
words

40,000.00 #NAME? 40,000.00

20,000.00 #NAME? 20,000.00


40,000.00 #NAME? 40,000.00
225,000.00 #NAME? 225,000.00

#NAME? 0.00

#NAME? 0.00

#NAME? 0.00

150,000.00 #NAME? 150,000.00


150,000.00 #NAME? 150,000.00
10,000.00 #NAME? 10,000.00
10,000.00 #NAME? 10,000.00
10,000.00 #NAME? 10,000.00
10,000.00 #NAME? 10,000.00
10,000.00 #NAME? 10,000.00
10,000.00 #NAME? 10,000.00
3,500.00 #NAME? 24,500.00
114,000.00 #NAME? 114,000.00
86,900.00 #NAME? 608,300.00
152,000.00 #NAME? 152,000.00
76,000.00 #NAME? 76,000.00
152,000.00 #NAME? 152,000.00

3,750.00 #NAME? 52,500.00


1,200.00 #NAME? 16,800.00
6,300.00 #NAME? 75,600.00
3,400.00 #NAME? 47,600.00
25,000.00 #NAME? 225,000.00
2,000.00 #NAME? 50,000.00
19,500.00 #NAME? 19,500.00
12,000.00 #NAME? 24,000.00
35,000.00 #NAME? 245,000.00
2,300.00 #NAME? 23,000.00
80,000.00 #NAME? 160,000.00
65,000.00 #NAME? 195,000.00
55,000.00 #NAME? 55,000.00
50,000.00 #NAME? 50,000.00
50,000.00 #NAME? 50,000.00

120.00 #NAME? 60,000.00

135.00 #NAME? 675,000.00

205.00 #NAME? 410,000.00

30.00 #NAME? 30,000.00


#NAME? 4275800
12,000.00 #NAME? 144,000.00

12,000.00 #NAME? 144,000.00

10,000.00 #NAME? 120,000.00

10,000.00 #NAME? 120,000.00

Defect liability period

10,000.00 #NAME? 120,000.00

10,000.00 #NAME? 120,000.00

10,000.00 #NAME? 120,000.00


#NAME? 888,000.00
#NAME? 5,163,800.00

Rate in
Rate in Figure Amount
words

39,300.00 #NAME? 39,300.00

32,460.00 #NAME? 32,460.00


1,000.00 #NAME? 80,000.00

19,200.00 #NAME? 19,200.00

18,000.00 #NAME? 18,000.00

50.00 #NAME? 50,000.00

#NAME? 61,200.00
300,160

168,600.00 #NAME? 168,600.00

36,150.00 #NAME? 36,150.00

29,385.00 #NAME? 558,315.00

4,710.00 #NAME? 9,420.00

1,100.00 #NAME? 1,100.00

80,000.00 #NAME? 80,000.00

55,000.00 #NAME? 55,000.00


28,000.00 #NAME? 28,000.00

#NAME? 936,585.00
#NAME? 997,785.00
1,873,170.00
Rate in
Rate in Figure Amount
words

345,825.00 #NAME? 345,825.00

#NAME?

#NAME?

#NAME?

#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?
#NAME?

26,460.00 #NAME? 26,460.00

2,640.00 #NAME? 15,840.00

1,430.00 #NAME? 65,780.00


90.00 #NAME? 9,000.00

135.00 #NAME? 13,500.00

268.00 #NAME? 53,600.00

2,400.00 #NAME? 28,800.00

3,300.00 #NAME? 19,800.00

4,900.00 #NAME? 4,900.00


#NAME? 583,505.00
C8: Central AC plant.
S.No. Description Quantity Unit Rate in Figure
PART - A (SITC OF AC PLANT)
SUB HEAD 'A' - MACHINERY
Supplying, Installing, testing & commissioning of BMS
compatible Screw type water chilling machine having a
capacity of 140 TR (423636 K.Cal. / hr.) at chilled
water inlet/ outlet temperature of 12.0 deg.C / 7.0
deg.C with chilled water circulation rate of 1300 LPM
(nominal) and condenser water inlet/ outlet
temperature of 32 °C / 36 °C with circulation rate of
1860 lpm (nominal) suitable for stepless continuous
capacity from 100% to 25% and operation on
1 refrigerant R-134a for screw type machine each 2 Each 2,100,000.00
comprising of the following complete as per
specifications and as reqd. The item includes testing of
one of the chillers at AHRI test beds at four points.

Note:- The AC plant is to be installted on the terrace


floor of the building, which is of Ground+ 6 upper
floors.
1 No. Single/ multiple screw type compressor semi-
hermatic complete with automatic capacity control,
safety switches, speed increasing gears, forced feed
a) lubrication system etc as per specifications.

1 No.- Suitable capacity squirrel cage induction motor


with class 'B' insulation suitable for operation on
b) 415±10% volts, 3-phase, 50Hz A.C. supply.

1 No.- Close transition type automatic Soft / StarDelta


starter suitable for compressor motor complete with
ammeter with CTs, over load protection, under voltage
protection, protection against phase reversal,
independent single phase preventors, timer control &
c) trip circuit with sensing elements for HP/LP/Anti-
Freeze etc. complete as required.

d) Necessary drive arrangement


1 Set- Lubrication device consisting of automatic
electric oil pump, oil cooler, head tank, oil strainer,
automatic pressure regulating valve, oil heater, oil
e) heater thermal switch etc. as per specifications.

1 No.- Matching shell and tube water cooled condenser


f) of M.S. shell and integrally finned copper tubes
1 No.- Matching shell and tube DX / flooded type
g) chiller for screw type units of MS shell and copper
tubes.
1 Lot- Refrigerant piping fittings, valves and
h) accessories to inter connect compressor, condenser,
chiller and expansion valve.
1 Set- Microprocessor based control panel with alpha-
numeric display in English for all operating parameters
such as supply voltage, frequency, load current, chilled
water inlet, chilled water outlet, condenser inlet and
outlet temperature parameters, operating pressures
i) and compatible to BMS operation and with Bacnet/
Modbus / J Bus communication card etc. complete with
accessories as per specifications

Lot- Refrigerant line accessories comprising of safety


j) valves, angle valve, liquid line indications, liquid level
control etc.
Lot- Water flow switches at inlet and outlet of
k) condenser & chiller, water drain & air purge valves
wherever required.
Lot- Suction line and chiller insulation with minimum
19mm thick polvinyl nitrile rubber insulation finished
l) with 0.63mm thick G.S.S. cladding complete as
required.

Lot- Frame work (including victaulic couplings at the


inlet & outlet of cooler & condenser; & painting of all
components) for mounting the above condenser,
m) chiller compressor and motor with base plate
complete with antivibration pads/ springs.

Lot- Initial / first charge of refrigerant gas &


n) compressor oil
Refrigerant piping shall be factory assembled as per
o) the specifications.
Additional Safety Devices shall include Internal
Thermostat for Compressor Motor, Fusible Plug,
p) Discharge Gas Thermostat, Operation Hour-Meter etc.

q) Lot - RCC/ Cement concrete foundation

SITC of Chiller Plant manager for the above chillers,


primary and condenser water pumps along with
common header temperature sensors for sequential
2 operation, equal run hours etc as per the specifications 1 Job 200,000.00
including control cabling.
Supplying, erection, testing and commisioning of End
suction Primary chilled water pump set capable of
delivering 1300 LPM of water against a head of 15 mtr.
3 Each pump shall comprise of the following and 2 Each 200,000.00
complete as per specifications and as required.

1 No. - End Suction type centrifugal pump with bronze


a) impeller.
1No.- Suitable HP, TEFC squirrel cage induction motor
with class 'F' insulation, 1500 RPM, operating on
b) 415±10%volts, 3phase, 50HZ A.C supply.

Lot- Expanded polystrene (P Quality) insulation of not


less than 50mm thick duly cladded between
aluminium sheets of 0.5mm thickness and properly
c) clamped to pump in two semicircular sections as per
specifications.

Lot- Mounting frame work with anti vibration pads.


d)
e) Lot - RCC/ Cement concrete foundation
All the pumps mentioned above shall also be complete
with mechanical seals, rubber flexible connections
f) with M.S. flanges etc. and drain connections.

Supply, erection, testing and commissioning of End


suction type Condenser water pump set capable of
delivering 1860 LPM of water against 25 mtrs head.
4 Each pump shall comprise of the following and 2 Each 276,000.00
complete as per specifications and as required.

1 No. - End Suction type centrifugal pump with bronze


a) impeller.
1No.- Suitable HP, TEFC squirrel cage induction motor
with class 'F' insulation, 1500 RPM, operating on
b) 415±10%volts, 3phase, 50HZ A.C supply.

c) Lot- Mounting frame with Antivibration pads.


All the pumps mentioned above shall also be complete
d) with mechanical seals, and drain connections.

e) Lot - RCC/ Cement concrete foundation


All the pumps mentioned above shall also be complete
with mechanical seals, rubber flexible connections
f) with M.S. flanges etc. and drain connections.
Supplying, erection, testing and commisioning of End
suction Secondary chilled water pump set capable of
delivering 1300 LPM of water against a head of 30
5 mtrs. Each pump shall comprise of the following and 2 Each 340,000.00
complete as per specifications and as required.

1 No. - End Suction type centrifugal pump with bronze


a) impeller.
1 No.- Suitable HP, TEFC squirrel cage induction motor
with BHP rating 15% higher than the peak capacity
suitable with class 'H' insulation, 1500 rpm
b) synchronous speed, operating on 415±10% volts, 3
phase, 50 Hz A.C. supply.

Lot- Expanded polystrene (P Quality) insulation of not


less than 50mm thick duly cladded between
aluminium sheets of 0.5mm thickness and properly
c) clamped to pump in two semicircular sections as per
specifications.

Lot- Mounting frame work with anti vibration pads.


d)
e) Lot - RCC/ Cement concrete foundation.
All the pumps mentioned above shall also be complete
with mechanical seals, rubber flexible connections
f) with M.S. flanges etc. and drain connections.

Supply, installation, testing & commissioning of


Variable Speed Pumping system consisting of 3 Nos.
adjustable frequency drive (AFD) suitably interfaced
with other system components,hand/auto macro
designed for pumping application, 01 no.dedicated
microprocessor based pump logic controller,parallel
pumping software duly downloaded, 01 sets of
Differential Pressure Sensor/ Transmitters, interfacing
g) amongst all components & compatibility of I/O signals
etc complete with other accessories suitably rated for
motors in Item 4(A) above as required.
Supplying, installing, testing and commissioning of
Induced draft FRP cooling tower of 170 TR (514080
K.Cal / hr.) heat rejection capacity with eliminators
complete with hot water basin either fitted with spray
nozzles or having self rotating sprinklers, statically and
dynamically balanced axial flow type fan-direct driven
or driven through reduction gear box with TEFC
induction motor, suction screen make up quick fill
6 arrangement, overflow and drain connections with 2 Each 400,000.00
necessary valves and suitable aluminum inspection
ladder, access arrangement for cooling tower interior,
anti vibration mountings etc. complete as per
specification and as reqd.

Inlet water temperature 36°C, Outlet water


a) temperature 32°C.
Type of fan : Aerodynamic Propeller type of motor,
b) 1000 RPM, Weather proof.
Lot- RCC/ Cement concrete foundation alongwith MS
c) structure.

Supply, installation, testing & commissioning of factory


fabricated Double Skinned Chilled Water Air Handling
Unit, floor mounted horizontal type fabricated out of
extruded aluminium section with 0.8mm
preplasticized/pre-coated Galvanised steel sheet
outside & 0.8 mm plain Galvanised steel sheet inside
with blower, blower section & Blower shall be DIDW
Forward Curved blade from & blower motor TEFC type
suitable for operation on 415volts±10%,50Hz±5% AC
supply, suitable cooling coil made of Aluminium finned
Copper tube (thickness 0.5mm) with coil section, pre-
filter section with non woven synthetic media of 10
micron particle size with an efficiency of 90%,
polished stainless steel drain pan made out of 18G
7 sheet duly insulated complete with motor & belt drive
package etc. without face & bypass dampers.The AHU
panels shall be insulated with 40mm thick & 38 Kg/m³
density PU foam. The motor & blower assembly shall
be mounted on Aluminium extruded section only. The
complete AHU shall conform to standard specifications
and of following capacities.

Floor Mounted AHU - Capacity :18000 CFM ( for 2nd ,


a) 3rd, 4th and 5th floors ) 4 Each 345,000.00

Floor Mounted AHU - Capacity :16000 CFM ( for 1 st


b) floor ) 1 Each 305,000.00
Floor Mounted AHU - Capacity :11000 CFM ( for 6 th
c) floor ) 1 Each 210,000.00

Floor Mounted AHU - Capacity :9000 CFM ( for Ground


d) floor Entrance lobby area) 1 Each 170,000.00

Supply, Installation, Testing and Commissioning of VFD


8 starter panel for AHUs alongwith differential pressure 1 Lot 450,000.00
sensors.

Total Sub Head A: #NAME?


Rate in Amount
words

#NAME? 4200000.00
#NAME? 200,000.00
#NAME? 400,000.00

#NAME? 552,000.00
#NAME? 680,000.00
#NAME? 800,000.00

#NAME? 1,380,000.00

#NAME? 305,000.00
#NAME? 210,000.00

#NAME? 170,000.00

#NAME? 450,000.00

? 9,347,000.00