Professional Documents
Culture Documents
Abstract—When a substation is fed by a combined overhead- number, size, material, and spacing from phase conductors of
cable transmission line, a significant part of the ground fault cur- the ground wire and from towers’ footing resistance.
rent flows through cable sheaths and is discharged into the soil at
When the substation is fed by a combined overhead-cable
the transition station where cables are connected to the overhead
line. Such a phenomenon, known as “fault application transfer,” transmission line, a significant part of the ground fault current
may result in high ground potentials at the transition station which flows through the grounded cable sheaths and discharges into
may cause shocks and equipment damage. The scope of this paper the soil at the transition station (TS), where cables are connected
is to present new analytic formulas which can be used for the di- to the overhead line. This is due to the difference in coupling
rect calculation of the fault current transferred at the transition
station and its ground potential rise as well as the substation earth factors for cable and overhead lines, so that only a small portion
current. The proposed formulas allow evaluating the influence of of the return current carried by cable sheaths continues toward
the main factors to the fault application transfer phenomenon and the remote source through the overhead ground wire; instead, a
can be employed, at the preliminary design stage, to easily assess large portion of such current flows into the soil surrounding the
the most appropriate safety conditions to avoid dangerous effects.
TS ground electrode and continues toward the source through
Index Terms—Fault application transfer, ground fault current the earth. This phenomenon has been presented in literature for
distribution, grounding, safety conditions.
the first time and is called “fault application transfer” by So-
bral et al. [6], referring to an actual transition station and to
I. INTRODUCTION the shocks and equipment damages that have occurred there,
as a consequence of high ground potentials caused by a fault to
HEN a ground fault occurs at a substation, the fault
W current returns back to the supply station, in part, dis-
charging into the soil from the substation grounding system,
ground occurring at the receiving end substation.
The phenomenon of the fault application transfer does not
have any relation to the well-known potential transfer effect and
in part through different metallic return paths either directly it has not been yet extensively dealt with in literature. Reference
or through other auxiliary ground electrodes [1]. The amount [7] reports the results of a measurement campaign of the ground
of the fault current diverted away from the substation ground fault current distribution during a fault at a substation fed by a
grid depends primarily from the conductively and inductively multicombined overhead-cable transmission line. As expected,
coupled parameters of the various possible paths. In practice, measurements have shown that more than 25% of the fault cur-
a significant part of the fault current is diverted away from rent flows between each transition station’s ground electrode
the substation grounding system by overhead ground wires or and the surrounding soil, yielding dangerous voltages which ex-
cable sheaths of feeding transmission lines, mutually coupled ceed allowable safety limits. In [8], the effects of the fault ap-
with the faulted phase conductor; while a smaller quantity is plication transfer have been usefully utilized to design the sub-
carried out by neutrals or other return paths of outgoing lines, station ground grid in a dense urban area, as a suitable technical
which provide only a ground impedance in parallel with the control of the substation ground potential rise (GPR), in order
substation ground grid [2]–[4]. In particular, if the substation to ensure safety conditions, avoiding difficulties in grounding
is fed by a cable transmission line, a very large percentage of measurements. Two additional bare copper bonding wires, tied
the fault current (up to 95% for cable line consisting of three to the cable sheaths, have also been considered in the final de-
single core cables) returns directly to the remote source via the sign to better achieve the fixed objective.
cable sheaths, because of their strong inductive coupling with From the aforementioned, it is clear that the fault applica-
phase conductors [5]. Instead, in case of a substation fed by tion transfer effects must be properly taken into account at the
an overhead line, the return current flowing trough the ground design stage of substations fed by a combined overhead-cable
wire, weakly inductively coupled with phase conductors, varies line, both for a more efficient and economic design of a substa-
from 5–30% of the total fault current in dependence from tion grounding system as well as for safety concerns at the tran-
sition stations. Moreover, it should be considered that problems
Manuscript received November 7, 2006. Paper no. TPWRD-00686-2005. concerning ground fault transfer effects are expected to grow
The author is with the Department of Electrical, Electronic and Telecommu- further in the future for a number of reasons:
nication Engineering, Università degli Studi di Palermo, Palermo 90128, Italy
(e-mail: mangione@unipa.it). • the use of underground transmission cables in modern HV
Digital Object Identifier 10.1109/TPWRD.2007.915895 installations continuously increases due to technical and
0885-8977/$25.00 © 2008 IEEE
1414 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008
(3)
TABLE II
EFFECT OF GROUND WIRE ON THE TS TRANSFERRED CURRENT, I
TABLE III
COMPARISON OF CALCULATION RESULTS OF I , FOR A NONUNIFORM GROUND
WIRE WITH DIFFERENT NUMBERS OF TERMINAL SPANS AND VALUES OF R
Fig. 7. Fault current transferred to the TS against the cable line length.
TABLE IV
COMPARISON OF CALCULATION RESULTS OF I , FOR NONUNIFORM GROUND
WIRE WITH A DIFFERENT NUMBER OF TERMINAL SPANS AND VALUES OF R
Fig. 8. Ground potential rise at the transition station against cable line length.
TABLE I
EFFECT OF GROUND WIRE ON THE SUBSTATION EARTH CURRENT, I
In practice, for the case examined here, in order to obtain similar
effects on the earth current reduction at both the faulted and
the transition stations, it should be sufficient to apply the better
conducting ground wire in a maximum of 15–20 terminal spans
as shown in the next subsection.
C. Method Validation
According to the aforementioned discussion, consider now
is reported, as a function of the cable line length and for dif- the overhead line section with the steel ground wire over its en-
ferent values of . tire length, saved at a certain number of receiving end spans,
where the copper/steel conductor is used. By applying the pro-
B. Effects of Ground Wire Material posed method, based on the compact model of Fig. 5, calcula-
The effect of the type of material used for the overhead tions are made considering only the better conducting ground
ground wire is presented in Tables I and II, where values of wire as it was installed over the entire line length ( ).
and obtained with aluminium/steel and copper/steel ground Tables III and IV compare, for different numbers of terminal
wires, when km, are compared with those obtained spans with copper/steel conductor, the results obtained in such
with the steel conductor. As can be seen, good conducting a manner with those obtained by a computer program which em-
ground wires considerably reduce both the substation earth ploys a more rigorous method [19], based mainly on the over-
current and the TS transferred current; however, the benefits head line complete circuit model and the solution technique pre-
obtained on the latter are much greater. Furthermore, the higher sented in [15]. As can be seen, the maximum error in values of
the TS ground resistance is, the more the decrement of both currents and in all of the studied cases is negligibly small;
currents is. less than 4% in cases of 15 terminal spans with better conducting
Note that the values in Tables I and II are obtained by means ground wires and about 1% in cases of 20 terminal spans.
of (9) and (10), respectively, considering the overhead ground
wire uniform over its entire length. Nevertheless, similar values V. CONCLUSION
should be obtained if the better conducting ground wire is used The compact equivalent model of a combined overhead-cable
only in a limited number of the line’s receiving end spans [10]. line presented in this paper allows deriving relatively simple
1418 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 3, JULY 2008