You are on page 1of 13

GLAXOSMITHKLINE OTC (PVT.) LTD.

, JAMSHORO
PETARO ROAD, SANDOZ NAGAR-JAMSHORO SINDH.
UPGARDATION OF GLATT GRANULATION SUITE
AIR-CONDITIONING & MECHANICAL DRAWINGS
(AUGUST, 2017)

CLIENT: MEP CONSULTANTS


A+Engineers
MEP Consultants
Anum Blessings, 2nd Floor, Suite No. 206, ZCC K.U.C.H.S
GlaxoSmithKline OTC (PVT.) Ltd., Jamshoro Block 7/8, Near Ex-Duty Free Shop, Shahrah-E-Faisal,
Karachi-75400
Petaro Road, Sandoz Nagar-Jamshoro Sindh. Phone: 021-34325466
Email: info@aplusengineers.com
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 aplusengineers@gmail.com
URL: www.aplusengineers.com

DRG.NO.
A+209-M-01
GENERAL NOTES:- LEGEND LEGEND
ABBREVIATION
1. ALL DIMENSIONS ON DRAWINGS ARE IN FEET & INCHES UNLESS OTHERWISE NOTED.
S.NO. DESCRIPTION SYMBOL S.NO. DESCRIPTION SYMBOL
2. MAKING ALL OPENINGS IN PRE-ENGINEERED BUILDING, MASONRY AND CONCRETE SHALL BE THE
CDP CONDENSATE DRAIN PIPE
RESPONSIBILITY OF THE CONTRACTOR. 1 SUPPLY AIR DUCT SA 36 SUPPLY AIR DIFFUSER
3. ALL AIR TERMINALS ARE TO BE INSTALLED IN COORDINATION WITH REFLECTED CEILING PLAN. 2 RETURN AIR DUCT RA
37 RETURN AIR DIFFUSER CFM CUBIC FEET PER MINUTE
3 EXHAUST AIR DUCT EA
4. MISCELLANEOUS DETAILS GIVEN IN TENDER DRAWINGS SHALL BE STRICTLY FOLLOWED FOR RELEVANT
4 DRAIN PIPE D EXHAUST AIR FAN INLINE
APPLICATION. INDICATION OF DETAIL DRAWING REFERENCE NUMBER ON OTHER DRAWINGS IS 38
CENTRIFUGAL TYPE
5 FRESH AIR INTAKE LOUVERS F.A.I.L. DB DRY BULB
NOT ESSENTIAL.
6 EXHAUST AIR LOUVERS E.A.L. 39 PANEL FILTER
5. PROVIDE ACCESS DOORS ON DUCTS ON ALL SPLITTER / FIRE DAMPERS WHERE APPLICABLE.
7 VENTILATION AIR FAN V.A. FAN DL DOOR LOUVER
6. ALL FRESH AIR AND EXHAUST AIR DUCTS TO BE PROVIDED WITH FLANGED JOINTS. E.A. FAN 40 BAG FILTER
8 EXHAUST AIR FAN
7. DATA OF ELECTRICAL RATING EQUIPMENT IS INDICATIVE ONLY AND ALL ELECTRICAL WORK, VARIABLE 9 AIRHANDLING UNIT AHU DR DRAIN
41 CHILLED WATER COOLING COIL
FREQUENCY DRIVES AND MCC's SHALL MEET THE REQUIREMENTS OF FINALLY SELECTED EQUIPMENT AS 10 CONDENSING UNIT CU
PER SPECIFICATIONS. 11 US REFRIGERATION TONS USRT
11/ EA EXHAUST AIR
42 H-11/13 FILTER 13
8. ALL BLACK STEEL PIPING OF DIAMETER LESS THAN 2 INCH SHALL BE THREADED. 12 KILO WATTS kW

9. A/C DRAIN PIPES SHALL NOT TERMINATE DIRECTLY INTO THE DRAINAGE SYSTEM. IT MUST HAVE A 13 GATE VALVE 43 F-9 FILTER 9 EAD EXHAUST AIR DIFFUSER
FLOOR GULLY IN BETWEEN. 14 BALL VALVE
44 F-6 FILTER 6
EF EXHAUST FAN
15 BATTERY LIMIT
45 (CV BOX.) FLOW CONTOLLER
EXT EXTERNAL
12. ALL STEEL SUPPORTS SHALL BE HOT DIPPED GALVANIZED AFTER FABRICATION AND CUTTING. 16 DIFFUSER/REGISTER WITH DAMPER
46 TEMPERATURE INDICATOR T
13. ALL DRAINAGE PIPING IN BUILDING SHALL BE WITH MINIMUM 1% SLOPE, UNLESS OTHER WISE INDICATED. 17 AIR FLOW STATION
A.F.S. F/A-F/B FROM ABOVE / FROM BELOW
14. ALL DRAINAGE CLEAN-OUTS TO BE AT LEAST 18" INCHES AWAY FROM ANY RIGID OBSTRUCTION. 47 HUMIDITY SENSOR H
18 SUPPLY AIR CHANGES / HR --A/C
15. FOR ALL PIPING PROVIDE AUTOMATIC AIR VENTS AT THE HIGHEST POINT AND/WHERE REQUIRED. SU SPLIT UNIT
19 SPACE NUMBER / ROOM NUMBER -- 48 SMOKE DETECTOR SD
16. ALL DRAINAGE & VENT PIPING TO BE SUPPORTED BY HILTI MPN CLAMP OF STANDARD DUTY,
OR APPROVED EQUIVALENT D
20 DOOR CUT 49 DIFFERENTIAL PRESSURE SENSOR P WB WET BULB
C
17. ALL SUPPORTS FOR DUCTING & PIPING SHALL BE FULLY HOT DIPPED GALVANISED. USING FULLY D
21 DOOR LOUVERS 50 COOLING COIL
THREADED GALVANIZED RODS. L T/A TO ABOVE

22 LEAKAGE L
18. CONTRACTOR WILL BE RESPONSIBLE TO MAKE SHOP DRAWINGS PRIOR TO EXECUTION OF WORK 51 REHEAT COIL
INCLUDING PLANS, DETAILS & SECTIONS FROM THE INFORMATION GIVEN ON THESE DRAWINGS. TR TONS OF REFRIGERATION
23 FIRE DAMPER
52
19- S.A.D. SUPPLY AIR DIFFUSER INSTALLED IN FALSE CEILING/SLAB SHALL BE T&B TYPE ME.
24 TEMPERATURE GAUGE T/B TO BELOW
20- S.A.R. ALL SUPPLY/FRESH AIR REGISTERS SHALL BE EQUAL TO T & B (TUTTLE & BAILEY) SERIES.
M.G. 53
T 60 DOUBLE DEFLECTION ( STEEL ). 25 MAGNEHALIC GAUGE TBD TO BE DECIDED
21- R.A.R. E.AR. ALL RETURN/EXHAUST AIR REGISTERS SHALL BE EQUAL TO T & B SERIES T
54
26 TEMPERATURE SENSOR
THK THICKNESS
22- ALL FRESH AND EXHAUST AIR LOUVERS SHALL BE FIXED BLADE TYPE AND HAVE BRASS INSECT MESH 20 MESH (FAIL & EAL). 55
27 VOLUME CONTROL DAMPER (VCD)
23- ALL PLANT EQUIPMENT FOUNDATION 1: 2 : 4 RCC OF CONTRACTOR
28 G4 FILTER 56 TYP. TYPICAL
24- E.S.P ELECTRIC SUPPLY POINT TPN WITH TWO EARTHING POINTS
29 LOUVER 57
AND 1 PHASE WITH ONE EARTHING POINT PROVIDED BY EMPLOYER. DIAMETER
30 AIR FLOW DIRECTION
25- ALL DUCTING SHALL BE MEDIUM PRESSURE FLANGED TYPE (FLANGES AND BRACING 58
TO HAVE CHAMFERED CORNERS) AND CONFIRM TO EUROVENT CLASSIFICATION B AND TESTED AT 1000 Pa. 31 ROOM PRESSURE READING (IN PASCAL) -Pa
59 SUPPLY AIR DUCT S.A.D
26- SUPPLY, RETURN & EXHAUST AIR DUCTING SHALL BE INSULATED WITH 40mm 32 VARIABLE FREQUENCY DRIVE VFD
THICK FIBER GLASS DUCT WRAP WITH ALUMINIUM FOIL VAPOUR 60 RETURN AIR DUCT R.A.D
BARRIER AND FINISHED AS SPECIFIED. 33 DRAIN LINE D

27- CHILLED WATER, STEAM & CONDENSATE PIPING TO BE INSULATED AS PER SCHEDULES.
34 PLUG FAN
28- RETURN AIR INSULATED FILTER BOXES SHALL BE INSTALLED AS SHOWN ON LAYOUT
DRAWING AND SHALL BE FACTORY FABRICATED.
35 CENTRIFUGAL FAN FAN

LIST OF DRAWINGS
S. NO. DWG. NO. DRAWING TITLE SCALE

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE

A+ Engineers
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 03/07/2017
UPGRADATION OF NOTES, INDEX & LEGENDS
GlaxoSmithKline OTC (PVT.), Jamshoro MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
GLATT PROJECT NUMBER: 209 DRAWING NO.

Petaro Road, Sandoz Nagar-Jamshoro Sindh. ISSUE DATE: 03-07-2017 A+209-M-02


Shahrah -e-Faisal, Karachi, Pakistan
Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: NTS@A3
TOTAL DWG IN SHEET:
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 aplusengineers@gmail.com DRAWN BY: M. SHOAIB
URL: www.aplusengineers.com CHECKED BY: NA 17
MIXER

WATER BATH
EP
ZONE-2
FLUID BED DRYER
COLLET GRALL BLENDING GRANULATION II
ZONE-1 12'-7" x 22'-10" 13'-1" x 22'-10"
G WORK SHOP 5 PA 5 PA
GRANULATION-I
FREWITT
GS-02 GS-03
26'-4" x 22'-10"
5 PA

FOR RAD
GS-01

SPACE
LEGEND :-
CORRIDOR ZONE-3 S NO. ZONE NO. AREA SERVED AHU NO.
PHARMA ROOM
CLASS
0 PA ZONE CONDITION
15 PA 1. ZONE-1 GRANULATION AREA-I 1 PHARMA 100,000
COB 8'-6" WIDE CORRIDOR ZONE-02 RH NMT 40 %
BLENDING AND PHARMA
20 PA 2. ZONE-2
GRANULATION-II
2
ZONE-02 RH NMT 40 %
100,000
CR GS-04
8'-0" x 8'-6" 3. ZONE-3 3 PHARMA 100,000
CORRIDOR & AIRLOCK ZONE-02 RH NMT 40 %

4. ZONE-4 EXISTING AREA -- -- -- --

GS-01

ROOM AIR LOCK


43'-9"x19'-3" 9'-0" x 19'-3"
30 PA

CORRIDOR

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
AIR CONDITIONING ZONES & AIR FLOW
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 30/06/2017

GlaxoSmithKline OTC (PVT.), Jamshoro A+ Engineers 1 ROOMS ADDED 07/07/2017 UPGRADATION OF PATTERN AT GROUND FLOOR
PROJECT NUMBER: DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh. MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
2 ZONING REVISED AS PER DISCUSSION 26/07/2017
GLATT 209

TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Shahrah -e-Faisal, Karachi, Pakistan 3 REVISE AS PER ARCHITECT LAYOUT 02/08/2017 ISSUE DATE: 30-06-2017 A+209-M-03
Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: 1/8"=1'-0"@A3
TOTAL DWG IN SHEET:
aplusengineers@gmail.com DRAWN BY: ASAD
URL: www.aplusengineers.com CHECKED BY: SHAHZIA ZAHID 17
EA.FAN NO.1

PLENUM
PLENUM
ACCESS

INTAKE
FILTER
F-9
ROOM

WATER BATH
13'-8" x 7'-4"
EP
" x 12'-0"
FLUID BED DRYER
COLLET GRALL MIXER
GRANULATION II
13'-1" x 22'-10"
ENGINEERING WORK SHOP GRANULATION-I
23'-8" x 11'-8" 26'-4" x 22'-10" BLENDING

FREWITT
12'-7" x 22'-10"

FOR RAD
C C

SPACE
C
C

WASHING ROOM
23'-8" x 8'-9"
COB 8'-6" WIDE CORRIDOR
CR
8'-0" x 8'-6"

AIR LOCK
9'-0" x 19'-3"

ROOM
43'-9"x19'-3"

FUTURE
LINE
17'-6" x 55'-11"
VA- 0113

COATING III

CLIENT ARCHITECT. M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
LAYOUT OF AIRCONDITIONING
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 21/06/2017
UPGRADATION OF SYSTEM AT GROUND FLOOR
GlaxoSmithKline Pakistan Ltd., Jamshoro
A+ Engineers
PROJECT NUMBER: 209 DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh.
MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
GLATT ISSUE DATE: 30-06-2017 A+209-M-04
Shahrah -e-Faisal, Karachi, Pakistan
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: 1/8"=1'-0"@A3
TOTAL DWG IN SHEET:
DRAWN BY: ASAD
aplusengineers@gmail.com
URL: www.aplusengineers.com CHECKED BY: SHAZIA ZAHID 17
3'-0"

6'-0"

CLIENT ARCHITECT. M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
LAYOUT OF AIRCONDITIONING
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 21/06/2017
UPGRADATION OF SYSTEM AT ROOF
GlaxoSmithKline Pakistan Ltd., Jamshoro
A+ Engineers
PROJECT NUMBER: 209 DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh.
MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
GLATT ISSUE DATE: 30-06-2017 A+209-M-05
Shahrah -e-Faisal, Karachi, Pakistan
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: 3/32"=1'-0"@A3
TOTAL DWG IN SHEET:
DRAWN BY: ASAD
aplusengineers@gmail.com
URL: www.aplusengineers.com CHECKED BY: SHAZIA ZAHID 17
WATER BATH
EP

FLUID BED DRYER


GRANULATION-I
COLLET GRALL MIXER
GRANULATION II
26'-4" x 22'-10" 13'-1" x 22'-10"
BLENDING
12'-7" x 22'-10"
SHOP
FREWITT

FOR RAD
SPACE

CLIENT ARCHITECT. M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
LAYOUT OF WATER SUPPLY, DRAINAGE
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 02/08/2017
UPGRADATION OF & COMPRESSED AIR AT GROUND FLOOR
GlaxoSmithKline Pakistan Ltd., Jamshoro
A+ Engineers
PROJECT NUMBER: 209 DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh.
MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
GLATT ISSUE DATE: 04-08-2017 A+209-M-06
Shahrah -e-Faisal, Karachi, Pakistan
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: 3/16"=1'-0"@A3
TOTAL DWG IN SHEET:
DRAWN BY: MUHAMMAD SHAKIR
aplusengineers@gmail.com
URL: www.aplusengineers.com CHECKED BY: NA 17
Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.55.01.jpg Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.53.05.jpg Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.55.06.jpg

Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.54.33.jpg

Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.54.38.jpg Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.55.39.jpg Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.53.42.jpg

Y:\209-GSK OTC Jamshoro\I-Old Granulation Suite Upgradation\Incoming\Pics\2017-06-21 14.53.46.jpg

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
DEMOLITION LAYOUT
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 11/02/2016
15/06/2017
AT ROOF
A+ Engineers UPGRADATION OF
GlaxoSmithKline OTC (PVT.), Jamshoro MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings GLATT PROJECT NUMBER: 209 DRAWING NO.

Petaro Road, Sandoz Nagar-Jamshoro Sindh. Shahrah -e-Faisal, Karachi, Pakistan


ISSUE DATE: 30-6-2017
AT ROOF A+209-M-07
Phone: 021-34325466, 021-34325102 GRANUATION SUITE SCALE: NTS@A3
Email: info@aplusengineers.com TOTAL DWG IN SHEET:
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 aplusengineers@gmail.com DRAWN BY: ASAD
URL: www.aplusengineers.com CHECKED BY: NA 17
S. NO. 1 S. NO. 2 S. NO. 3 S. NO. 4 S. NO. 5
NT
VE
AIR
ING IC
AT M AT IL
UL TO CO
OD TER AU AT
M ME GE m RE
HE
AY MO AU 25
m
G/ TYPE T & B
2 W LVE THER R EG TIN
VA U EA ME RAWL RAWL
ESS /H BOLT
PR ING BOLT
OL
CO INSULATION
INSULATION FOR 26g G.I. SHEET SLEEVE
FRICTION TIGHT M.S. CLAMP CHILLED/HOT MIN. 12" LONG 1/8" THICK HOLDING STRAP
WATER PIPING AT SUPPORTS 1- 1/4,"1-1/2" 2"OR WIDE
TEMPRATURE
SENSOR

CFRV 1/8" OR 1/4" PIPE


GAUGE WASHER
COCK
S VIBRATION
AIN ISOLATOR (SHALL
LL DR N
BA LVE PA BE SELECTED
3/4",1" OR VA .75" ACCORDING TO INSULATED PIPE
0 26g G.I. SHEET SPRING
WEIGHT OF PIPES) TYPE PIPE
SLEEVE MIN. 12" 1/8" HOLDING
2" THICK VALVE R VIBRATION
BRACING 4 CE LONG AT STRAP 1 -1/4",1-
RUBBER DU ISOLATOR
NOS. RE SUPPORTS 1/2" OR 2"WIDE MS ROD (SHALL
A/H UNIT IN SHEAR A/H UNIT ANGLE IRON
ON EACH VIBRATION BE SELECTED

~
UNIT ISOLATORS UN ACCORDING TO
1/4" GAP ETR
R WEIGHT OF PIPES)
FINISH PIPE
LL
FLOOR BY BA LVE IL
MIN.6" VA .75" CO IN
LEVEL ING A
MIN.2" C.C. PAD
U SH ALVE SIZE INE
R 0 DR GS FRICTION
FL SS V IPE
STR
A PLU TIGHT
PA AX P ION ANGLE
(M NB) UN M.S.
IRON CLAMP
2" PIPE

~
FLOOR SLAB LL UNINSULATED PIPE
LY BA LVE AIN
WELD RAWL NUT & RAWL

~
PP NUT & 1/8" 14g SADDLE FOR
SU VA DR RAP BOLT BOLT (TYP) BOLT
SIDE VIEW IN T BOLT UNINSULATED PIPES 3"
DRA
TO 6" AND INSULATED
SIZE 2" TO 6" ROLLER
PLAN SECTION A-A
SUPPORT ABOVE 6"

TYPICAL COOLING/HEATING / REHEAT


DETAIL NO.: DETAIL NO.: COIL CONNECTION OF AIRHANDLING UNIT DETAIL NO.: DETAIL OF MULTI PIPE HANGEER FOR DETAIL NO.: DETAIL OF VERTICAL PIPES SUPPORT & DETAIL NO.: DETAIL OF MULTI PIPE HANGER FOR FLOOR
A.H. UNIT FOUNDATION DETAIL
A+H-3 A+H-4 A+H-9 CEILING A+H-10 SECTION A-A A+H-11 / ROOF
(2 - WAY SYSTEM)

S. NO. 6 S. NO. 7 S. NO. 8 S. NO. 9 S. NO. 10

TO NEAREST
DRAIN POINT
3"
2" 2"
MANUAL VENT VALVE
UNLESS AUTOMATIC VENT
VALVE SPECIFIED AT ANY BRANCH
LOCATION POSITION MARKING DUCT
RUBBER BUSH

TO SUIT
BUSH HOUSING
TO NEAREST MAIN DUCT LOCKING DEVICE TAPE
DRAIN POINT 16G. G.I. PLATE

D
16G. G.I SHEET
PIVOT RUBBER GASKIT

AIR FLOW HINGES


AFTER
INSTALLATION G.I. SLEEVE 20g SIZE
FILLED W/WOINSULATION
WITH OF PIPE+1"
FIBERGLASS G.I SHEET METAL DUCT
BRANCH
DUCT
INSULATION

DETAIL NO.: DETAIL NO.: DETAIL NO.: DETAIL NO.: TYPICAL ROUND DUCT BRANCH DETAIL NO.:
DETAIL OF AUTOMATIC AIR VENT DETAIL OF VENT OUTLET AT RISER TOP DETAIL OF PIPE SLEEVE THRU WALL DETAIL OF SPLITTER DAMPER
A+H-18 A+H-20 A+H-21 A+H-30 CONNECTION A+H-32

S. NO. 11 S. NO. 12 S. NO. 13 S. NO. 14 S. NO. 15

1-1/2"x1-1/2"x1/8"
ANGLE IRON

GLASS BLANCKET
PLUG INSULATION WITH
INSULATION
ALUMINUM FOIL
JACKETING
11 4.OZ CORSE CLOTH
/2
/2" " MEDIUM PRESSURE DUCTING SCHEDULE
COVERING ON
11
W1 + 1 1/2" 1" FIBER GLASS DUCT INSULATION
FOR P RAWL TO-18" LARGER DIMENSION 24 GAUGE (ALL FOUR SIDES).
IN WELL CHILLED/HOT BOLT
19- 45" LARGER DIMENSION 22 GAUGE (ALL FOUR SIDE).
DUCT SEALANT GAUGE DUCT WIDTH + INSULATION HOLE 46"-69 LARGER DIMENSION 20 GAUGE (ALL FOUR SIDE). THICK,DENSITY 24 Kg
WATER PIPING
ALAROUND /m 3
ABOVE 69 LARGER DIMENSION 18 GAUGE (ALL FOUR SIDE).
M-7 IN WELL
TO SUIT LOCATION

1 1/2"x1
DAMPER CHILLED/HOT MEDIUM PRESSURE DUCTING JOINT SCHEDULE CONDUCTIVITY.0.036
1/2"x 1/8"
INSULATION WATER PIPING RAWL ANGLE IRON a.LONGITUDINAL
PITTSBURGH LOCK. DOUBLE SEAM . OR GROOVED SEAM.
PACKING BOLT WELDED
DUCT MS ROUND BAR b.CIRCUMFERENTIAL (ALL FOURSIDE)
SEALANT W1 ROUND DUCT LARGER DIMENSION
BAR TO - 18. 25x25x3 mm COMPANION ANGLE FLANGED JOINT.
19"- 48" 32x32x3 mm COMPANION ANGLE FLANGED JOINT.
49"- 60" 40x40x3 mm COMPANION ANGLE FLANGED JOINT.
WASHER

3"
NUT 61"- 84" 50x50x5 mm COMPANION ANGLE FLANGED JOINT.
RAWL
BRACING SCHEDULE BOLT
ANGLE
15mm IRON THE BRACING FOR DUCTING JOINTS AT 4 FT CENTER.

TO - 12 NO BRACING
13 - 24 25x25x3 mm BRACING BETWEEN JOINTS
CEILING OPENING LISTED SIZE + 3" 25 - 36 32x32x3 mm BRACING @ 2FT CENTER.
37 - 48 40x40x3 mm BRACING @ 2FT CENTER.
VALVE FULL SIZE UPTO 40mm PIPE VALVE 40mm FOR 50 49 - 60 50x50x3 mm BRACING @ 2FT CENTER.
61 - 84 75x75x5 mm BRACING @ 2FT CENTER.
TO 200mm PIPE VALVE 50mm FOR 250mm & ABOVE PIPE

DU . I.
CT
G
DUCTING FABRICATION SCHEDULE

DETAIL NO.: DETAIL OF FIXING SUPPLY AIR DIFFUSER IN DETAIL NO.: DETAIL OF DIRT POCKET & DRAIN VALVE DETAIL NO.: DETAIL OF DUCT HANGERS CEILING DETAIL NO.:
DETAIL OF VERTICAL DUCT HANGER
DETAIL NO.: DETAIL OF THERMAL INSULATION FOR
A+H-33 FALSE CEILING A+H-36 AT ALL RISER BOTTOM A+H-41 SUSPENDED A+H-43 A+H-45 INSIDE DUCTING

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 11/02/2016
15/06/2017 MISCELLANEOUS DETAILS-I
A+ Engineers UPGRADATION OF
GlaxoSmithKline OTC (PVT.), Jamshoro MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
GLATT PROJECT NUMBER: 209 DRAWING NO.

Petaro Road, Sandoz Nagar-Jamshoro Sindh. Shahrah -e-Faisal, Karachi, Pakistan


ISSUE DATE: 04-08-2017 A+209-M-08
Phone: 021-34325466, 021-34325102 GRANUATION SUITE SCALE: NTS@A3
Email: info@aplusengineers.com TOTAL DWG IN SHEET:
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 aplusengineers@gmail.com DRAWN BY: ASAD
URL: www.aplusengineers.com CHECKED BY: NA 17
S .NO. 16 S. NO. 17 S. NO. 18 S. NO. 19 S. NO. 20

S
NT
OI
NJ
E DI
IFI 2'
P EC
ES
D UL
HE
SC
AS
2'
LIQUID SEALANT RG
IN THE JOINTS BU
I TTS
ZSG-1191/OR APPROVED P CK
EQUAL LO

DETAIL NO.: DETAIL NO.: DETAIL OF THERMAL INSULATION FOR DETAIL NO.: DETAIL NO DETAIL NO.: U-BOLT SELECTION CHART FOR
DETAIL OF DUCT BRACING & JOINTS DUCT ACCESS DOOR DETAIL DUCT TRANSITION DETAIL
A+H-47 A+H-49 WEATHER EXPOSED DUCTING A+H-64 A+H-66 A+H-77 UN-INSULATED STEEL PIPES

S. NO. 21 S. NO. 22 S. NO. 23 S. NO.24 S. NO. 25

DETAIL NO.: RECTANGULAR DUCT BRANCH TAKE-OFF DETAIL NO.: LONGITUDINAL SEAMS FOR RECTANGULAR DETAIL NO.: FIRE DAMPER (LEAF TYPE)INSTALLATION DETAIL NO.: DETAIL NO.: ARRANGEMENT FOR PRESSURE TESTING
LOW LEVEL RETURN AIR DUCT DETAIL
A+H-78 DETAILS A+H-79 DUCTS A+H-84 DETAIL A+H-85 A+H-86 OF DUCT

S. NO. 26 S. NO. 27 S. NO. 28 S. NO. 29 S. NO. 30

SPACING AS REQUIRED SPACING AS REQUIRED

ESCUTHEON GLUED
WITH SILICONE
SEALANT AS PER
APPROVED SAMPLE &
SILF AND SITE.
300 H

PLASTIC LABEL WHITE ON


BLACK UTILITY DESIGNATION
AS PER APPROVED SAMPLE &
NOMENCLATURE

2mm THICK. SS 316


COVER PLATE

AS REQUIRED BY NUMBER OF PIPES

DETAIL NO.: DETAIL NO.: DETAIL NO.: PIPE AND FITTINGS INSULATION & DETAIL NO.: DETAIL NO.: SCHEME FOR THE IDENTIFICATION OF
DETAIL OF SS VALVE COVER PLATE TYPE-2 PIPING SLEEVE IN PHARMA AREA COLOR CODE FOR PIPING
A+H-87 A+H-89 A+H-91 CLADDING DETAIL A+H-92 A+H-93 PIPING SYSTEMS AS PER ANSI A13.1

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 11/02/2016
15/06/2017 MISCELLANEOUS DETAILS-II
A+ Engineers UPGRADATION OF
GlaxoSmithKline OTC (PVT.), Jamshoro MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings GLATT PROJECT NUMBER: 209 DRAWING NO.

Petaro Road, Sandoz Nagar-Jamshoro Sindh. Shahrah -e-Faisal, Karachi, Pakistan


ISSUE DATE: 04-08-2017 A+209-M-09
Phone: 021-34325466, 021-34325102 GRANUATION SUITE SCALE: NTS@A3
Email: info@aplusengineers.com TOTAL DWG IN SHEET:
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 aplusengineers@gmail.com DRAWN BY: SHOAIB
URL: www.aplusengineers.com CHECKED BY: NA 17
1 DESIGN CONDITIONS 5 SCHEDULE OF AIR FILTERS FOR
AIRHANDLING UNITS (BANK APPLICATION)
AMBIENT PANEL / BAG NO. OFF. NO. OFF.
AIR
SEASON ROOM ELECTRIC SUPPLY FILTER SIZES G-4 F-6 F-6 H-13
S. NO. UNIT REFRENCE QUANTITY
o o Wmm X Hmm X Dmm 90% EFF. 65% EFF. 95% EFF. 99.95% EFF.
F DB F WB CFM PRE FILTER FILTER FILTER FILTER
1 2 3 4 5 1 2 3 4 5 6 7 8

ROOM CONDITIONS AS 610 x 610 x 610 6 6 6 6


SUMMER 115 81
1. AHU-1 8840
SPECIFIED IN DRAWINGS AS SPECIFIED
-- -- -- -- --
MONSOON - - NO. A+209-M-11,12,13
610 x 610 x 610 4 4 4 4
2. AHU-2 7370
305 x 610 x 610 2 2 2 2

610 x 610 x 610 2 2 2 2


3. AHU-3 1870
-- -- -- -- --

4. CC-1 1960 610 x 610 x 50 2 - - -


2 INSULATION
610 x 610 x 50 1
5. CC-2 1850 - - -
VAPOUR 305 x 305 x 50 1
S. NO. SERVICE THICKNESS MATERIAL CONDUCTIVITY EXTERNAL COVERING
BARRIOUR
6. CC-3 1280 610 x 610 x 610 1 - - -
1 2 3 4 5 6 7
ALL SUPPLY, RETURN AND EXHAUST AIR 2 PLY KRAFT PAPER & ALUMINUM FOIL WITHIN BUILDING JACKET OF, 4 oz
DUCTS IN AHUs ROOMS, CONDITIONED 1.5" (40 mm) FIBREGLASS WITH INTERNAL FIBER GLASS YERN
1 BLANKET DENSITY 24 kg / m3 CANVES CLOTH ABOVE FALSE CEILLING NOTE:
AND NON-CONDITIONED SPACE. REINFORCEMENT AT MAX. 1" CENTRES
FIBREGLASS WEATHER EXPOSED JACKET OF 8 oz 1- G-4 FILTER THICKNESS SHALL BE 50MM WHEREAS H-13FILTERSHALLBE 292MM.
AIR DUCTS EXPOSED TO WEATHER 2" (50 mm) RIGID BOARD 96 / Kg / m3 // CANVES AND 26g G.I. SHEET COVERING.
CHILLED / HOT WATER PIPES
2 UP TO 1" NB 1" (25 mm)
1.5" (40 mm)
FIBREGLASS
PREMOLDED
ASJ 6 DUST COLLECTOR
UP TO 2.5" NB DENSITY 96 kg / m3
3" AND ABOVE 2" (50 mm)
STEAM & STEAM CONDENSATE PIPES
3 1" NB AND ABOVE 1.5" (40 mm) FIBREGLASS // AIR QUANTITY PRESSURE DROP TYPE
BELOW 1" NB 1" (25 mm) PREMOLDED DENSITY 96 kg / m3 S. NO. AREA SERVED
CFM INCH WG

4 CONDENSATE DRAIN PIPES 3/8" (10 mm) AERO FLEX PVC TAPE 1 2 3 4 5
DENSITY 80 kg / m3 26g G.I.SHEET JACKET
0.046 W/mk, 80kg/m3 DENSITY 1 BLENDING GRANULATION-I & II 1500 7 CENTRIFUGAL
ROCK WOOL -
5 FLUE DUCT 2" (50 mm) STITCHED WITH G.I. WIRE AND
BLANKET
WIRE MESH ON BOTH SIDES.
NOTE:

THE CONTRACTOR WILL BE RESPONSIBLE FOR SUPPLY, INSTALLATION AND COMMISSIONING OF THE ABOVE.

3 AIRHANDLING UNITS
FAN
TOTAL
COOLING COIL CONDITIONS REHEAT COIL
CONDITIONS
7 CHEMICAL DEHUMIDIFIERS (ES)
TYPES EXTERNAL FRESH ENTERING AIR LEAVING AIR
A.H.U. AIR
S.NO. SERVICE UNIT TYPE UNIT LOCATION AREA SERVED OF STATIC AIR CAPACITY FLOW CAPACITY FLOW
NO. FLOW DB
6 FILTERS PRESSURE WB DB WB PROCESS AIR INLET REACTIVATION AIR
inch WG CFM CFM MBH GPM MBH MBH
S.NO. MOISTURE CONTENT HEATING SYSTEM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 INLET
SUPPLY/ HORIZONTAL G-4, F-6 , F-9 NO. OFF CFM INLET TEMP. INLET OUTLET OUTLET
1. 1 ROOF GRANULATION 5.8 7840 1960 89.1 62 54 47.8 297 50 - -
RETURN BLOW THRU H-13 DEHUMIDIFIER GR/LB GR/LB GR/LB
SUPPLY/ HORIZONTAL BLENDING, G-4, F-6 , F-9 1 2
2. 2 ROOF 5.8 7610 1850 89.2 62 54 47.8 297 48 - - 3 4 5 6 7 8 9
RETURN BLOW THRU GRANULATION-II H-13 DEHUMIDIFIER
1. 1 1960 58 65.1 16.8 90 115 85
SUPPLY/ HORIZONTAL CORRIDOR, G-4, F-6 , F-9 EXISTING
3. 3 ROOF 5.8 2370 1280 93 60.3 54 43.8 99 17 - -
RETURN BLOW THRU AIR LOCK H-13 DEHUMIDIFIER
2. 2 1850 58 65.1 17.5 90 115 85
FAN LESS
C.C-1 FRESH FRESH AIR TO NEW
4. FRONT ROOF G-4 - 1960 1960 111 83 54 53 331 55 - -
EXISTING AIR DISCHARGE AHU-1
3. 3 1280 58 65.1 17.5 90 115 85
FAN LESS
C.C-2 FRESH FRESH AIR TO NEW
5. FRONT ROOF G-4 - 1850 1850 111 83 54 53 238 40 - -
EXISTING AIR DISCHARGE AHU-2
FAN LESS NOTE:-
C.C-3 FRESH FRESH AIR TO
6. FRONT ROOF G-4 - 1280 1280 111 83 54 53 140 23.3 - -
NEW AIR DISCHARGE AHU-3 1. THE CONTRACTOR MUST SUBMIT A SCHEMATIC AIR FLOW DIAGRAM FOR BOTH PROCESS AND REACTIVATION AIR CIRCUITS, AND
AUTOMATIC CONTROL ARRANGEMENT WITH VARYING CONDITIONS OF OPERATION WITH HIS TENDER.
2 THE CHEMICAL DEHUMIDIFIER SHALL BE OF MUNTERS.
3 (ES) EMPLOYER SUPPLIED

4 EXHAUST AIR FAN


FILTERS
CFM INCH W. G.
S.NO. FAN NO. LOCATION AREA SERVED ROOM NO. TYPE
AIR FLOW ESP FILTER SIZES
G-4 F-9
Wmm X Hmm X Dmm

1 2 3 4 5 6 7 8 9 10 11

1. GRANULATION-I, II CENTRIFUGAL 610 x 610 x 610


1 TECHNICAL AREA - 3000 3.1 2 2
BLENDING CABINET

2. CENTRIFUGAL 305 x 305 x 50


1 ROOF CHANGE ROOM - 620 1.3 1 -
CABINET

NOTE:
1- ALL FANS SHALL BE DOUBLE SKIN TYPE WITH NO THERMAL BRIDGE BETWEEN INNER AND OUTER SURFACE.
2- FAN EXTERNAL PRESSURE DROP SPECIFIED ABOVE INCLUDES PRESSURE LOSS IN AIR DUCTS, AIR FILTERS
& AIR DEVICES. THE MANUFACTURER TO ADD UNIT CABINET FAN INLET AND OUT LET LOSSES TO DETERMINE TOTAL STATIC PRESSURE.
3- FACTORY FABRICATED SECTION FOR G - 4 AIR FILTER & ACCESS PLENUM ETC. FOR ALL FANS.
4- G-4 TYPE AIR FILTER THICKNESS IS 50mm.

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE

A+ Engineers
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 03/08/2017
UPGRADATION OF EQUIPMENT SCHEDULE
GlaxoSmithKline OTC (PVT.), Jamshoro MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
GLATT PROJECT NUMBER: 209 DRAWING NO.

Petaro Road, Sandoz Nagar-Jamshoro Sindh. ISSUE DATE: 03-08-2017 A+209-M-10


Shahrah -e-Faisal, Karachi, Pakistan
Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: NTS@A3
TOTAL DWG IN SHEET:
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 aplusengineers@gmail.com DRAWN BY: SHOAIB
URL: www.aplusengineers.com CHECKED BY: NA 17
AIR HANDLING UNIT NO. 1
REACT AIR
P T
T
FAN

ACCESS PLENUM
G-4 PRE FILTER

COOLING COIL
F.A. PLENUM

DISCHAERGE
WET AIR
1960

PLENUM
T
1960 F.A.I.L. T
CFM
CFM
F.A FILTER
DEHUMIDIFIER NO. 1

ACC. PLENUM
C.C-1 (EXISTING DH NO.2)

G-4 FILTER
F-9 FILTER
FAN VCD 3000

PLENUM
1410 CFM;

INTAKE
EXISTING
TO ATMOSP. CFM FOR CONTINUATION
REFER DRAWING. NO.
A+209-M-12
AIR DIFFUSER
COOLING COIL V.C.D.
EA.FAN NO.1
P
900 CFM; TEMP.
FOR CONTINUATION GAUGE

ACCESS PLENUM

ACCESS PLENUM

G-4 PRE FILTER


TO REFER DRAWING. NO. 7840

S.A. PLENUM
SD

MIXING BOX
FD VFD
A+209-M-12

SECTION
ATMOSPHERE
CFM H-13 F-9 F-6

1500
CFM PLUG FAN
EXISTING TEMP.
DUST EA
GAUGE
COLLECTOR
5880 H FD
P P P
CFM

AIR HANDLING UNIT NO.1 (EXISTING AHU NO.1)

FROM CORRIDOR
ROOM CLASSIFICATION : 100,000 (PHARMA ZONE-2)
GRANULATION-I

D
C

1590 230 7840


CFM CFM CFM

600
CFM
55A/C
5880
G-4

CFM MACHINE
GRANULATION-I

7'-10" WIDE CORRIDOR

ZONE-1
CORRIDOR
GRANULATION-I
26'-4" x 22'-10"
15 PA 5 PA
GS-01

2'-6"

5'-0"

30 PA
GS-05
8'-6" WIDE CORRIDOR
AIR LOCK

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
SCHEMATIC AIR DIAGRAM FOR
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 21/06/2017
UPGRADATION OF AIR HANDLING UNIT NO.1
GlaxoSmithKline Pakistan Ltd., Jamshoro
A+ Engineers 1 DRG. NO. REVISED AND ROOM DELETED 11/07/2017
PROJECT NUMBER: DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh.
MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
2 REVISED AS PER AIR CHANGE 02/08/2017
GLATT ISSUE DATE: 30-06-2017
209

A+209-M-11
Shahrah -e-Faisal, Karachi, Pakistan
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: N.T.S @A3
TOTAL DWG IN SHEET:
aplusengineers@gmail.com DRAWN BY: M. SHOAIB
URL: www.aplusengineers.com CHECKED BY: SHAZIA ZAHID 17
AIR HANDLING UNIT NO. 2
REACT AIR
P T
T

ACCESS PLENUM

COOLING COIL
G-4 PRE FILTER
FAN

F.A. PLENUM

DISCHAERGE
WET AIR
1850

PLENUM
T
1850 F.A.I.L.
T
CFM
CFM
F.A FILTER

DEHUMIDIFIER NO.2
C.C-2 (NEW)
EXISTING

AIR DIFFUSER
COOLING COIL V.C.D.
1410 CFM TO EA FAN NO.1
FOR CONTINUATION P
REFER DRAWING. NO A+209-M-11
TEMP.
GAUGE

ACCESS PLENUM

ACCESS PLENUM

G-4 PRE FILTER


7370

S.A. PLENUM

MIXING BOX
SD FD VFD

SECTION
CFM
H-13 F-9 F-6

TEMP. PLUG FAN


GAUGE
5520 H FD
P P P
CFM

AIR HANDLING UNIT NO.2 (EXISTING AHU NO.2)

FROM CORRIDOR

FROM CORRIDOR
ROOM CLASSIFICATION : 100,000 (PHARMA ZONE-2)
GRANULATION-II
FOR CONTINUATION
REFER DRAWING. NO A+209-M-11

D D
C C

800 230 2535 610 230 4835


CFM CFM CFM CFM CFM CFM

300 600
CFM CFM
40 69
1665 A/C 3855 A/C

G-4

G-4
CFM MACHINE CFM MACHINE
BLENDING GRANULATION-II

7'-10" WIDE CORRIDOR

BLENDING GRANULATION II
12'-7" x 22'-10" 13'-1" x 22'-10"
5 PA 5 PA
GS-02 GS-03

8'-6" WIDE CORRIDOR


GS-04

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
SCHEMATIC AIR DIAGRAM FOR
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 21/06/2017
UPGRADATION OF AIR HANDLING UNIT NO. 2
GlaxoSmithKline Pakistan Ltd., Jamshoro
A+ Engineers 1 REVISED AS PER AIR CHANGE 02/08/2017
PROJECT NUMBER: DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh.
MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
Shahrah -e-Faisal, Karachi, Pakistan
GLATT ISSUE DATE:
209
30-06-2017 A+209-M-12
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com GRANUATION SUITE SCALE:
DRAWN BY:
N.T.S @A3
M. SHOAIB
TOTAL DWG IN SHEET:
aplusengineers@gmail.com
URL: www.aplusengineers.com CHECKED BY: SHAZIA ZAHID 17
AIR HANDLING UNIT NO. 3
REACT AIR
P T
T
FAN

ACCESS PLENUM
G-4 PRE FILTER

COOLING COIL
F.A. PLENUM

DISCHAERGE
WET AIR
1280

PLENUM
T
1280 F.A.I.L. T
CFM
CFM
F.A FILTER
DEHUMIDIFIER NO.3
(NEW)
COOLING COIL UNIT NO.1
(NEW)

AIR DIFFUSER
COOLING COIL V.C.D.

P
TEMP.
GAUGE

ACCESS PLENUM

ACCESS PLENUM

G-4 PRE FILTER


1870

S.A. PLENUM

MIXING BOX
SD FD VFD

SECTION
CFM
H-13 F-9 F-6

G-4 FILTER
FAN VCD 620

PLENUM
INTAKE
TO ATMOSP. CFM PLUG FAN
TEMP.
GAUGE
590 H FD
P P P
CFM
EA.FAN NO.2
AIR HANDLING UNIT NO.3 (EXISTING AHU NO.6)

TO GRANULATION-II

TO GRANULATION-I
2 2 1 1

FROM CORRIDOR
ROOM CLASSIFICATION : 100,000 (PHARMA ZONE-2)

TO CORRIDOR

TO BLENDING
CORRIDOR AND AIRLOCK

D
D D D D D D C D D
C C C C C C C C

200 200 400 590 230 230 230 230 200 1250 620 200 200 220
CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM CFM

13 17 17
A/C A/C A/C

AIR LOCK CORRIDOR CHANGE ROOM

ZONE-3
COB 8'-6" WIDE CORRIDOR
20 PA
CR GS-04
8'-0" x 8'-6"

ROOM AIR LOCK


43'-9"x19'-3" 9'-0" x 19'-3"

CLIENT NORTH DIRECTION M&P CONSULTANT PROJECT DRAWING TITLE


REV. DESCRIPTION DATE
SCHEMATIC AIR DIAGRAM FOR
0 ISSUED FOR REVIEW, COMMENTS & APPROVAL 21/06/2017
UPGRADATION OF AIR HANDLING UNIT NO. 3
GlaxoSmithKline Pakistan Ltd., Jamshoro
A+ Engineers 1 FILLING ROOM DELETED 26/07/2017
PROJECT NUMBER: DRAWING NO.
Petaro Road, Sandoz Nagar-Jamshoro Sindh.
MEP Consultants
Suite # 206, 2nd Floor,Anum Blessings
2 CHANGE ROOM ADDED 02/08/2017
GLATT ISSUE DATE:
209
30-06-2017 A+209-M-13
Shahrah -e-Faisal, Karachi, Pakistan
TEL: (92) 22 3877690 - 96 FAX: (92) 22 3877615 Phone: 021-34325466, 021-34325102
Email: info@aplusengineers.com
GRANUATION SUITE SCALE: N.T.S @A3
TOTAL DWG IN SHEET:
aplusengineers@gmail.com DRAWN BY: M. SHOAIB
URL: www.aplusengineers.com CHECKED BY: SHAZIA ZAHID 17