You are on page 1of 36

20

CHAPTER 2

CONVENTIONAL STATCOM

2.1 COMPENSATION PRINCIPLE OF STATCOM

STATCOM is a converter type FACTS device, which generally


provides superior performance characteristics when compared with
conventional compensation methods employing TSCs and TCRs.
STATCOM based on VSC topology utilize either GTO or IGBT devices. A
functional model of a STATCOM is shown in Figure 2.1. In its simplest
form, the STATCOM is made up of a coupling transformer, a VSC, and a
DC energy storage device. The energy storage device is a relatively small
DC capacitor, and hence the STATCOM is capable of only reactive power
exchange with the transmission system.

Figure 2.1 Functional model of a STATCOM


21

If a DC storage battery or other DC voltage source were used to


replace the DC capacitor, the controller can exchange real and reactive
power with the transmission system, extending its region of operation from
two to four quadrants.

Inorder to understand the compensation principle of


STATCOM, two sources V1 with a phase angle of and V2 with a phase
angle of 0° connected together by means of an inductive link of impedance
(R +j X) ohms as shown in Figure 2.2 are considered. In the STATCOM
principle, the source V1 is the power system voltage at the bus where the
STATCOM is connected, V2 is the AC voltage generated by the
STATCOM inverter, X is the reactance in the line, R is the total loss
resistance in the link comprising of the winding losses in the link inductor,
interface magnetic, the inverter switches and snubber etc. Assuming is
small and R << X, if V2 represents the STATCOM condition and if the
active power flowing into the source V2 is constrained to be zero, the power
delivered by the source V1 and the reactive power delivered to the link by
the source V2 will be given by the following equations .

Figure 2.2 Single line diagram

Active power delivered by V1 is

V12 2
P W (2.1)
R
22

Reactive power delivered by V2 is

V1 V2
Q var (2.2)
R

Also,

V2 (V2 V1 )
Q var (2.3)
X

where the powers P, Q and voltages V1, V2 have phase values.


These relations can be used upto about 20° for . Active power drawn from
the source V1 is independent of sign of phase angle (V1 supply losses only
in R and not at V2) whereas the reactive power delivered by V2 is directly
proportional to the phase angle. The phase angle of V1 with respect to V2 is

R V2 V1
var (2.4)
X V1

Thus Q is proportional to or equivalently to (V2-V1). In the


STATCOM, the required AC voltage source V2 is generated by inverting
the DC capacitor voltage. By making the output voltages of the converter
lag the AC system voltages by a small angle, the converter absorbs a small
amount of active power from the AC system to balance the losses in the
converter. But if the active power which goes into the inverter from the
source is kept zero, the initially charged capacitor will soon discharge
down to zero due to supply of active power losses in the inverter. The DC
side voltage will remain constant if the power drawn from source is just
enough to supply all the losses which take place everywhere due to the
flow of demanded reactive current.
23

The DC side capacitor voltage is,

V1 X
Vdc 1 (2.5)
k R

where V1 is the rms phase voltage of AC mains, k is a constant,


which also absorbs the modulation index of PWM process in the inverter.
Through appropriate switching sequence, VSC transforms DC voltage at its
DC terminals into an AC voltage of controllable frequency, magnitude and
phase angle at its terminals. The output voltage could be fixed or variable,
at a fixed or variable frequency. For FACTS application purposes, it is
always assumed that the output voltage waveform has a fixed frequency
equal to the fundamental frequency of a power system to which the
converter is connected, as high voltage and power harmonics could create
many problems.

2.1.1 Power Exchange in STATCOM Application

The amount and type of power exchange between the


STATCOM and the PCC can be adjusted by controlling the magnitude of
STATCOM output voltage with respect to the system voltage as shown in
Figure 2.3. The STATCOM is connected at the PCC where Vo is the
magnitude of STATCOM output voltage, Vpcc is the magnitude of the

system voltage at PCC and Xs is the equivalent reactance between


STATCOM and the system. The reactive power supplied by the
STATCOM is given by:

Vo Vpcc
Q Vpcc (2.6)
Xs
24

STATCOM supplies or absorbs reactive power based on the Q


value either positive or negative as shown in Figure 2.3, A STATCOM can
provide full capacitive output current at any system voltage, practically
down to zero (Sidhu et al. 2005).

Figure 2.3 Operating modes of STATCOM

The maximum capacitive or inductive reactance generated by


STATCOM decreases linearly with voltage with constant current.
Therefore, the capacitor does not change its voltage and this shows that the
capacitor does not play any role in the reactive power generation
(Blaabjerg et al. 2004).

Figure 2.4 (a) shows the STATCOM output current and voltage
diagram where phasors IQ and IP represent the AC current Iac components
that are in quadrature and in phase with the AC system voltage Vac,
respectively. The DC current Idc and voltage Vdc are shown in
Figure 2.4 (b). If the losses in the STATCOM circuit are neglected and it is
assumed that real power exchange with the AC system is zero, then the
25

active current component IP and DC current Idc are equal to zero and the
AC current Iac is equal to the reactive component IQ (Gyugyi 1994).
Assuming that the AC current flows from the STATCOM to the AC
system the AC current magnitude can be calculated as:

Vout Vac
I ac (2.7)
X

where Vout and Vac are the magnitudes of the STATCOM output
voltage and AC system voltage respectively, while X represents the
coupling transformer leakage reactance.

(a) at AC terminals

(b) at DC terminals

Figure 2.4 STATCOM phasor diagrams (Gyugyi 1994)


26

In Figure 2.4 (a), if both real and reactive power flows are
positive, then the power is absorbed by the STATCOM while negative
means that the power is injected by the STATCOM. The corresponding
reactive power exchanged can be expressed as follows:

2
Vout Vout Vac cos
Q (2.8)
X

where the angle is the angle between the AC system bus


voltage Vac and the STATCOM output voltage Vout. Figure 2.5 (a) shows
the case when the angle is equal to zero and there is no real power
transfer between the STATCOM and AC system. The STATCOM absorbs
real power from the AC system, if the STATCOM output voltage is made
to lag the AC system voltage, as shown in Figure 2.5 (b). The amount of
exchanged real power is very small in steady state; hence, the angle is
also small which is approximately equal to 2°. The real power exchange
between the VSC and the AC system can be calculated using:

Vac V out sin


P (2.9)
X

The energy going into the converter at its AC terminals has to


be equal to the energy lost due to switching, plus the energy stored in DC
capacitor and vice versa, i.e.,

Pac Plosses Pdc (2.10)


27

(a) steady-state operation (b) charging of DC capacitor

(c) discharging of DC capacitor

Figure 2.5 STATCOM phasor diagrams

The converter draws a rippled current from the DC capacitor


because the converter output voltage waveform is not perfectly sinusoidal;
the amount of harmonics depends on the modulation strategy used to
obtain the output waveforms. Since the voltage waveform is not perfectly
sinusoidal, the instantaneous power going in/out of converter contains
ripples, resulting in a rippled DC current. While the average value of the
DC current is zero in steady state, during transients this current follows the
changes in the output waveforms to maintain the desired mean DC voltage.

2.2 STATCOM CONTROL STRATEGY

To take effect of the bidirectional flow of reactive power, the


STATCOM output voltage should be varied according to requirement of
the reactive power compensation, and this can be accomplished in two
28

ways: by changing the switching angles of the power electronic devices


(i.e. varying the modulation index) while maintaining constant DC
capacitor voltage (direct control) or keeping the switching angles fixed and
varying the DC capacitors voltages (indirect control) (Schauder and Mehta
1993, Tin and Wang 1997). The variation of DC capacitors voltages is
simply achieved by varying the active power transfer between STATCOM
and power system and by adjusting phase angle difference between the
inverter and the line. All these control schemes have their own merits and
demerits. An important condition for an active operation is a constant DC
link voltage, Vdc.

In general, direct control is preferred where very fast voltage


control is required (absence of capacitor dynamics) makes the response fast
but THD of converter voltage varies with modulation index, thereby
producing more harmonic distortion in the voltage at low modulation
index. On the other hand, indirect control operation is slow as AC output
voltage of STATCOM varies according to variation of DC capacitor
voltages (presence of capacitor dynamics make the response slow) but
harmonic injection in the power system bus voltage can be kept at a very
low level by operating the inverter at a high modulation index where THD
of converter voltage is least.

In the proposed work, a PWM based control technique is


investigated since that real power flow in and out of the STATCOM can be
controlled by controlling the DC bus voltage, while the reactive power
generation/absorption is directly proportional to the magnitude of the
STATCOM output voltage. In this chapter, a new technique based on
interpolation firing control scheme is analyzed and implemented.
29

2.2.1 Conventional PWM Control Technique

The aim of the PWM control scheme is to maintain constant


voltage magnitude at the PCC, under system disturbances. The control
system only measures the rms voltages at the PCC, i.e., no reactive power
measurements are required. With these converters, the AC output voltage
can be controlled by varying the width of the voltage pulses. With PWM
technique, the output of each converter pole is switched several times
during a fundamental cycle between the positive and negative terminals of
the DC source. PWM requires a considerable increase in the number of
switch operations, thereby it generally increases the switching losses of the
converter. However, the always increasing switching frequency of modern
solid-state power switches used in FACTS controllers made possible the
use of PWM in high power applications.

The implementation and the design for the PWM controller are
simpler than for phase control, due to the easy separation of the active and
reactive components of the STATCOM output current without a need for a
d-q decomposition. For a STATCOM with PWM-based controller, the
fundamental component of converter output voltage can be easily
controlled from the maximum value to zero, independently in each phase.
Therefore, it is possible for the PWM converter to control each phase
current independently. This is not possible for phase-control based
STATCOM due to fact that all three phases are directly proportional to the
DC voltage, without possibility to adjust them independently. The basic
structure of a STATCOM with PWM-based voltage controls is depicted in
Figure 2.6 (Schauder et al. 1995).
30

Figure 2.6 Block diagram of a STATCOM with PWM


voltage control

In the block diagram, the Phase Locked Loop (PLL) provides


the basic synchronizing signal which is the phase angle of the bus voltage,
. It is obtained from the zero crossing of the bus voltage. In the case of a
sudden change in the power system, such as cyclic loads, it takes about half
a cycle of voltage for the PLL to be synchronized with the new voltage
phase angle, plus the signal processing delay. During this time the
STATCOM operates at the previous phase angle, while the bus voltage
phase has changed. Depending on the amount of phase angle change and
whether it is increased or decreased an uncontrolled real power, and
therefore reactive power exchange would occur between the STATCOM
and the transmission line during this inherent PLL delay. PWM controls
are becoming a more practical option for transmission system applications
of VSC-based controllers.
31

2.3 INTERPOLATION FIRING CONTROL SCHEME

Power electronic circuits present a special problem for


electromagnetic transient’s simulation (Gole et al. 1997). A power
electronic switch may open and close several times in a cycle. Finite time-
step Electro Magnetic Transient DC (EMTDC) type programs usually
allow such switching to occur on integral multiples of the time-step which
results in slower simulation process. On the other hand, the proposed finite
time-step approach usually results in faster simulation compared to
programs using a variable time step. Interpolation is a means for accurately
modeling the exact switching instant in transient and simulation programs
without using a time step and allows for an exact representation of the
switching event, without having to use smaller time step.

2.3.1 Generation of Interpolation Firing Pulses

Interpolation can be used in the generation of the firing pulses


for power electronic circuits as shown in Figure 2.7.

Figure 2.7 Firing angle measurement with and


without interpolation
32

The firing angle ( ), the time from the zero crossing of the
forward biasing voltage to the time at which the firing pulse is issued, is
generated by the intersection of a timing ramp with the firing angle order
signal. The firing pulse forwarded to the EMTP type algorithm consists of
the pulse itself which can only be synchronous with a time step and the
interpolation correction t2. The additional correction t2 is then passed to
the EMTDC type algorithm so that the above described changes to the
solution process can be made. Similarly, linear interpolation allows for a
much more accurate measurement of by using the additional correction
timestamp t1 as shown in Figure 2.7.

Although interpolation requires a few additional computations


in the algorithm, it has been shown that this only introduces a small
computation time overhead. Using the proposed interpolation approach it is
possible to get very precise switching times without response to a small
time-step and large processing time. The advantages of interpolation
include

Allows simulation to be run with a larger time step without


affecting accuracy

Results in correct theoretical harmonics generated by switching


devices like FACTS controllers because each switch device fires
at the correct instant

Avoids voltage fluctuations in STATCOM and VSC circuits due


to incorrect back-diode turn on times. Snubber circuits are
required to control these spikes in fixed time step programs
33

Avoids numerical instabilities that can occur due to


arrangements of multiple switching devices in close proximity

Results in more accurate models of non-linear devices like surge


arresters, especially in energy calculations

Models accurately the low frequency damping and harmonics of


switching devices interacting with Sub-Synchronous Resonance
(SSR) effects in machines

2.4 STATCOM MODELING

The control blocks should be modeled in great detail,


representing all necessary firing pulses for each of the valves. The models
should be simplified to reduce computational time and should accurately
capture the controller behavior at the desired fundamental frequency
(Jovcic et al. 1999). The controls should be represented with all functions
that are relevant to the proposed study. Several authors have demonstrated
the importance of realistic modeling of FACTS controllers for steady state
and transient stability studies (Nelson et al. 1995). The STATCOM have
been typically modeled as ideal VSC or Current Source Converter (CSC)
without operating and control limits, i.e. capable of generating or absorbing
unlimited amounts of reactive power. More accurate dynamic and steady
state models, similar to the ones presented in this thesis have been
proposed based on power balance principles between the AC and DC sides
of the VSC. However, these models have been discussed at a theoretical
level and only tested with conventional PWM. The STATCOM proposed
in this chapter are tested in a more realistic power system environment,
which clearly identify the need for representing properly the operating and
control limits.
34

Schauder and Mehta (1993), provide a mathematical modeling


and control approach for a VSC connected to a stiff utility system.
However, in the proposed system, for accurate analysis of the interactions
of the VSC with the utility system, network dynamics and dynamics of the
PLL need to be taken into account and included in the system model.

ia

Va
V sa

idc
ib
V dc V sb
Vb
VSC

ic
C V sc
Vc

Figure 2.8 Equivalent circuit of STATCOM

Figure 2.8 shows the simplified equivalent circuit of the


STATCOM. In this work, the VSC is modelled as a 6-pulse VSC with a
DC link capacitor. It contains a DC link capacitor, a VSC, and series
inductances in the three lines connecting to the system bus.
These inductances account for the leakage inductances of the power
transformer, as well as the inductances used for filtering the STATCOM
AC side currents. The circuit also includes resistance in series with the AC
lines to represent the VSC and transformer conduction losses.

Under balanced conditions, the AC side circuit equations in


Figure 2.8 can be written in a synchronously rotating reference frame using
the d-q transformation (Kundur 1994).
35

did R 1 1
id siq Vd Vsd (2.11)
dt L L L

diq R 1 1
iq i
s d Vq Vsq (2.12)
dt L L L

where R is the equivalent resistance representing the power


losses, is the synchronously rotating angle speed, (id, iq), (vd, vq), and
(vsd, vsq) are the dq components of (ia, ib, ic), (va, vb, vc), and (vsa, vsb, vsc),
respectively. Neglecting the harmonics due to switching and the losses in
the VSC and the transformer, the power balance between the AC and DC
sides of the VSC is given by

3
(Vsd i d Vsq i sq ) Vdc i dc (2.13)
2

With correct alignment of the reference frame, the Vsq term is


zero, and hence, the following equation can be written to relate the DC link
voltage to the d-axis current id and d axis component of the power line
voltage Vsd. Assuming that the DC link voltages are balanced, their
dynamics can be represented using Vdc.

dV dc 3 V sd i d
(2.14)
dt 2 CV dc

where C is the total dc capacitance,Vdc is the equivalent total DC


link voltage.

The dynamics of the VSC can be described by a set of first order


Ordinary Differential Equations (ODEs). Since Equation (2.14) is a
nonlinear equation of the DC link voltage, this set of ODEs represents a
36

nonlinear model to be controlled. In terms of the instantaneous variables,


the reactive power balance at the PCC is given by

3
P Vd i d Vq i q (2.15)
2

3
Q Vq i d Vd i q (2.16)
2

Aligning the d-axis of the reference frame along the grid voltage
position, Vq = 0

3
P Vdi d (2.17)
2

3
Q Vdi q (2.18)
2

From the above equations, it can be seen that Q can be


controlled through iq and Vdc can be controlled through id.

2.4.1 STATCOM Transient Stability Model

In transient stability modeling, it is typically assumed that the


converter output voltage is a balanced and harmonic free waveform at
fundamental frequency. The VSC can be accurately represented as a
sinusoidal voltage source operating at fundamental frequency. In order to
develop a fundamental frequency balanced model of the STATCOM, a
power balance technique, similar to the one used in (Schauder et al. 1993)
for developing d-q axis controls of VSC based static compensators is used
here. The proposed model allows the representation of different types of
controls and contains all relevant physical variables required to simulate
37

various PWM control strategies. For the STATCOM, instantaneous power


flowing into the converter from the AC bus, when neglecting transformer
losses, may be represented by :

a Vsh Vac
P 3 sin (2.19)
X

Figure 2.9 Transient stability model of a STATCOM

Assuming balance fundamental frequency voltages, the


controller can be accurately represented in transient stability studies using
the model shown in Figure 2.9. The p.u Differential - Algebraic Equations
(DAE) corresponding to this model can be summarized as follows:

xc
f c X c , , k, Vac , Vdc , Vac,ref , Vdc ,ref (2.20)
k

3a k Vac 1
Vdc sin Vdc (2.21)
CX R CC
38

Vdc2
0 3 Vac I accos( - ) - (2.22)
RC

a k Vdc Vac
P sin
X
0 (2.23)
Vac2 a k Vdc Vac
Q cos
X X

where Xc and fc stand for the internal control variables and


equations respectively and vary depending on which STATCOM internal
structure is used.

2.4.2 STATCOM Steady State Model

The steady state or power flow model can be obtained from the
stability model equations by replacing the corresponding equations with
the steady state equations for the DC voltage and the steady state V-I
characteristics. From Figure 2.9, the steady state equations are

0 Vac - Vac,ref X SL I ac

3 a k Vac 1
0 sin Vdc
CX R CC

3 a k Vac Vdc
0 sin
X RC

a k Vdc Vac
P sin
X
0 (2.24)
Vac2 a k Vdc Vac
Q cos
X X
39

The above equations define the real and reactive power that
STATCOM exchanges with the AC system. During steady state, the
system operation can be described using the phasor diagram shown in
Figure 2.10.

Figure 2.10 Phasor diagram of a PWM converter

The real and reactive power are represented by

Vsin
P 3E S
L
(2.25)
V cos - E S
Q 3E S
L

Equations (2.24) and (2.25) suggest that a VSC can generate a


desired, fixed valued reactive power when the power system network
supplies the variable real power demanded by any load. As shown in
Figure 2.10, this can be done by keeping “V cos ” constant and varying
“V sin ”. Thus by controlling the magnitude and phase voltage V, the
steady state control of active and reactive power is possible. However, the
40

equations fail to explain simultaneous control over real and reactive power,
which is required for a dynamic operation of a STATCOM.

2.4.3 Dynamic d-q Modeling of STATCOM

A variable DC link will introduce undesirable fluctuations in the


magnitude and phase of PWM voltages generated by the converter. It will
cause the active and reactive currents drawn by the converter to vary from
the desired values. This will further introduce additional noise in the DC
link voltage, since these line currents charge and discharge the DC
capacitor. To solve this non-linearity and to achieve fast dynamic response,
an effective dynamic control scheme is needed. The rotating reference
frame d-q theory is first used to obtain a dynamic d-q model of the
converter. General transformation techniques based on the Park’s
transformation are widely used for different types of power system studies.
Assuming that the system has no zero sequence components, all currents
and voltages can be uniquely transformed into the synchronously rotating
d-q reference frame.

Instantaneous voltages and currents on the three phase


coordinates can be transformed into the quadrature , coordinates by
Clarke transformation (Paul C. Krause 1986) as shown in Figure 2.11.
Since in a three-phase three-wire system neutral current is zero, the zero
sequence current does not exist. Hence using Clarke’s transformation, the
voltages and currents in the reference frame can be expressed as

v vR
v T1 v Y (2.26)
v vB
41

where T1 is the transformation matrix .With this three phase to


two phase transformation the instantaneous powers in both coordinate
systems must remain the same i.e.

Pdq = PRYB (2.27)

Figure 2.11 Three phase to two phase transformation

To obtain this condition the transformation matrix T1 is


2
multiplied by .
3

1 1
1 -
2 2
2 3 3 (2.28)
T1 0
3 2 2
1 1 1
2 2 2

The above system model is still complex and response is slow.


Paul C. Krause (1986) proposed a transformation from stationary to a
fictitious rotary reference frame with a speed of rotation r. Rotating
reference frame is used because it offers higher accuracy than stationary
frame-based techniques (Molina and Mercado 2006). Hence the voltages in
42

reference frame can further be transformed into rotating d-q reference


frame as in Figure 2.12 where r is the angular velocity of the d-q
reference frame.

With this transformation

Vd cos r - sin r
V
(2.29)
Vq sin r cos r
V

cos r - sin r
where T2 (2.30)
sin r cos r

The above equations represent the dynamic d-q model of the


VSC in a reference frame rotating at a speed of r. The current components
in the d-q reference frame can be similarly obtained using the to d-q
transformation matrix. The STATCOM uses the voltage (Vabc) and the
current (Iabc) measurements to check the stability of the system. These two
variables have been transformed into a synchronously rotating reference
frame by using Clarke (V and I ) and Park (Vdq and Idq) transformations.

Figure 2.12 to d-q transformation


43

To transfer the abc variables to a dqo frame a transformation


matrix is with d and q currents and voltages components of STATCOM
proportional to its real and reactive power components respectively.
Thus the control of each current component regulates the corresponding
power component.

2 ia
i 2 1 cos cos 4
3 3
ib (2.31)
i 3 0 sin 2 sin 4
3 3 ic

id cos sin i
(2.32)
iq - sin cos i

0 -1 -1 i as
i qs 2 2 2
i bs (2.33)
i ds 3 0 - 3 3
2 2 i cs

The measured variables are compared with the reference


variables ( Vdq, ref), ( Idq , ref) and the variations are supplied to the system.
By comparing the measured voltage with the reference value, the necessary
reactive current ( i q , ref) is supplied to the system to recover the system

voltage drop. The reactive current injected is controlled by a control


scheme to obtain the specified voltage at the grid side. The DC link voltage
Vdc is compared with its reference value and the variation is used to supply
the necessary active current ( i d , ref) to the system to compensate for the

STATCOM losses.
44

2.5 MITIGATION TECHNIQUE REALIZATION IN PSCAD/


EMTDC

To validate the performance of the STATCOM under PWM


control, a test system, introduced has been implemented in the EMTP.
In this chapter, PSCAD (Power System Computer Aided Design)/EMTDC
software is used to simulate and analyze the mitigation technique.
The basic electronic block of the proposed system shown in Figure 2.13 is
a VSC that converts a DC voltage at its input terminals into a three-phase
set of AC voltages at fundamental frequency with controllable magnitude
and phase angle using interpolation firing scheme.

Figure 2.13 Functional model of the proposed system

The three-phase 2-level six pulse converter is connected by an


appropriate magnetic circuit into a power system with inductive loads to
meet practical harmonic, current and voltage rating requirements.
45

2.5.1 STATCOM Control in Simulation Program

The construction of the control blocks for the control circuit of


voltage control loop in PSCAD is shown in Figure 2.14.

Figure 2.14 Control scheme implemented in PSCAD / EMTDC

In the operation of the control circuit, the error amplifier used is


a PI controller, and the gain of this PI controller is adjusted by the slider
error ramp. In this scheme the measured reactive power and the rated
reactive power values are given to the divider component along with the
measured p.u voltage. The voltage output signal is given a droop of 3% to
pass through the filter circuit. At the beginning of simulation the reference
voltage is ramped and compared with the filtered voltage through a
summing junction. The comparator output signal is fed to the PI controller
and whose output is the angle order which represents the required shift
46

between system voltage and the voltage generated by STATCOM.


The shift also determines the direction and amount of real power flow.

Figure 2.15 (a) Generation of triangular pulses

Figure 2.15 (b) Generation of sine wave pulses


47

PWM control is shown in two parts in which the part 1 is;


Generation of triangular waveforms synchronized with system ac voltage
and the part 2 is; Generation of reference waveforms synchronized with
system ac voltage and shifted by the angle order. The modulating angle is
applied to the PWM generators in phase A. The angles for phases B and C
are shifted by 240 and 120 degrees respectively. The generation of
triangular wave forms synchronized with system AC voltage is obtained
using PWM control scheme. The PSCAD/EMTDC circuit model
developed for this PWM technique is shown in Figure 2.15 (a) and
Figure 2.15 (b).

In this scheme of control the parameters of PI controller is given


to the PLL block which generates a ramp signal that varies between 0 and
360°, synchronized or locked in phase, to the input voltage. The gains of
the PLL are controlled using sliders named GpPLL and GiPLL in the
control panel with user interface. The carrier wave is generated by using
PLL block.

The value is multiplied by the carrier frequency along with a


modular factor. Using straight line approximation by a non-linear transfer
characteristic component the triangular waveform signals TrgOn and
TrgOff are generated which are to be synchronized with system AC
voltage.

The triggering pulses for the GTOs used in the VSC are
generated by the Sinusoidal Pulse Width Modulation (SPWM) technique.
The output of the control circuit is added with the output of another PLL
block and the resultant is applied to a sine block which operates on
6-dimensional arrays to get the sinusoidal reference wave signals
RSgnOn and RSgnOff. Both these triangular signals and reference signals
48

are compared to generate the triggering pulses for the power electronic
devices used in the power circuit with interpolation. Two sets of reference
and triangular signals are needed, one set for turning on and the second
one for turning off as shown in Figure 2.15 (a) and Figure 2.15 (b).
Two signals are being sent to each switch, the first signal turns on or off,
the second signal determines an exact moment of switching and is used by
interpolation procedure which allows for switching between time steps.

2.5.2 Interpolation Firing Circuit

EMTDC uses an interpolation algorithm to find the exact instant


of the event if it occurs between time steps. The logic and control blocks
used for construction of the interpolation firing circuit is shown in
Figure 2.16. The process of incorporating interpolation into logic
components is obtained as shown in Figure 2.17.

Figure 2.16 Logic and control blocks in interpolation


49

Firstly the pulse itself which by necessity must be synchronous


with a time step and secondly the time stamp t. The implementation of
logic gates should propagate properly.

Figure 2.17 Interpolation firing component

The interpolation firing component returns the firing pulse and


the interpolation time required for an interpolated turn-ON (or turn-OFF)
of devices, in the form of a two-element array. The first output element is
a 0 or 1 and represents the actual gate control pulse. The second is
information regarding the interpolated switching time. The output is based
on a comparison of High (H) and Low (L) input signals. The L input is
normally a firing angle order and the H input is from a Phase-Locked
Oscillator (PLO). An input signal comparison is provided to the electronic
device for the OFF signal as well.
50

2.6 IMPLEMENTATION OF VSC BASED STATCOM


IN PSCAD

To demonstrate the effect of the power system on the


STATCOM stability, a circuit model for STATCOM is developed using
PSCAD simulation software and the corresponding results are presented.
In simulations such as VSCs or other FACTS devices, care must be taken
in ensuring that the observed losses are realistic. The interpolation
algorithm is automatically invoked during all naturally commutated turns
ON and turns OFF events in order to calculate the exact instant of
switching. However the device turns ON or OFF using a gate signal is not
interpolated unless specifically selected in the input parameters. The user is
provided a choice to interpolate the incoming gate signal. The capacitance
value remains fixed throughout the simulation.

The simulation circuit component is a compact representation of


a DC converter, which includes a built in 6-pulse converter, an internal
PLO, firing and valve blocking controls and firing angle measurement.
It also includes built in RC snubber circuits for each thyristor.
The transformer component is the equivalent of three, 1-phase, 2-winding
transformer connected in a 3-phase bank, where the user can select the
winding interconnections to be Y or on either side. Modeling of
STATOM power circuit and control circuit is done in PSCAD simulation
package in order to verify the simulation results. An improved solution
method of PSCAD is obtained by incorporating instantaneous switching
into the interpolated switching algorithm. The test system is simulated with
and without STATCOM in PSCAD / EMTDC simulation environment and
the performance waveforms are compared as shown from Figure 2.18 to
Figure 2.25.
51

Voltage (kV)

(a) Time(s)

Figure 2.18 Load voltage wave form without STATCOM


Voltage (kV)

(b)Time(s)
Figure 2.19 Load voltage wave form with STATCOM
Real Power (MW)

Time(s)
Figure 2.20 Real power consumption without STATCOM
52

Real Power (MW)

Time(s)

Figure 2.21 Real power consumption with STATCOM


Reactive Power (Mvar)

Time(s)

Figure 2.22 Reactive power consumption with STATCOM


Reactive Power (Mvar)

Time(s)

Figure 2.23 Reactive power consumption without STATCOM


53

Vdc (kV)

Time(s)

Figure 2.24 Capacitor voltage wave form


Reactive Power (Mvar)

Time(s)
Figure 2.25 Reactive power injected by STATCOM

2.7 DISCUSSION ON RESULTS

The conventional STATCOM is analyzed and the circuit model


for the system is developed using the blocks available in PSCAD.
The VSC STATCOM is simulated with RL loads and the results are
presented. The dynamic performance of the shunt VSC connected to the
system proves that the voltage profile is transiently increased causing a
change of the VSC operating point from reactive power absorption to
generation.
54

The transient response is fast and the voltage returns to its rated
value after about 0.1 sec, when load voltage is very close to the
reference value i.e. 80% of its rated value (1 p.u)

The STATCOM absorbs reactive power in order to get the


voltage back to reference value

The regulated rms voltage shows a reasonably smooth profile


where the magnitude of the transient overshoots is kept with in
10% with respect to the reference voltage. These transients last
for two to three cycles

In general the voltage sources take a few seconds to stabilize the


line voltage and after that it reaches the steady value

The reactive power supplied by STATCOM goes from leading


to lagging resulting in a limiting of the over voltage

From the waveforms of power flow in the line it can be


observed that the power transfer capability of the line is also
improved

When VSTAT > Vac, STATCOM injects reactive power, so the


current flows from STATCOM to line

When VSTAT < Vac , STATCOM absorbs reactive power ,current


flows from STATCOM to line

When VSTAT= Vac, STATCOM does not work


55

2.8 CONCLUSION

In this chapter a complete transient stability and steady state


model for the conventional VSC based STATCOM has been implemented
and the simulation results are verified and found to be satisfactory.
A six-pulse STATCOM, using a conventional 2-level VSC is successfully
modeled in the EMTP, including a detailed representation of the control
blocks. Also, the PWM based STATCOM is modeled in the EMTP using
one VSC. The presented time-domain simulations in EMTP verify the
adequate operation of the designed controller, demonstrating successful
application of the PWM controller with interpolation firing scheme. Also it
has been observed that the power transfer capability in the line and the
voltage profile are improved by incorporation of STATCOM in the line.
This system suffers from the drawback of the usage of bulky transformers,
requirement of filter connections, low EMI susceptibility and output
harmonics due to conventional STATCOM and PWM modulation
technique. To solve these problems a modular CMC controller topology is
proposed and analyzed in detail in the next chapter.

You might also like