PLANNING
5.1.1 CONSULTATION
1
a) water damage to an inadequately shielded fire alarm control
panel in a sprinkler protected area with consequent possible
failure of the fire alarm system.
b) Operation or failure of smoke detectors in zones adjacent to
one in which water discharge is taken place because of the
water spray mist travelling to adjacent zones.
The sprinkler system shall provide protection to all parts not specified as
exceptions (in rule 5.2.2) in one of the following:
Sprinklers should not be fitted over salt baths, metal melt pans or frying
ranges, or in positions where water may discharge into them or indirectly
drain into them nor should water pipes be fitted in these positions.
2
by walls (225mm brick or 100mm R.C.C) as per Building
regulations. Fire doors not less than 1hr in fire resistance, shall
be provided in the openings of such walls.
c) Rooms or compartments containing electric power
distribution apparatus, such as switchgear and
transformers, and used for no other purpose(s). Any part
not provided with sprinkler protection shall be separated by
walls (225mm brick or 100mm R.C.C) as per Building
regulations. Fire doors not less than 1hr in fire resistance, shall
be provided in the openings of such walls.
d) in papermaking machines, the undersides of screens or of
shields erected over the wet and (where there is no other fire
hazard);
3
shall be protected by fire doors of not less than 2h fire
resistance.