A generating station has five section bus-bar connected with a tie-bar through 7.

5% reactors rated at
3000 kva .Each generator is of 3000 kva with 10% reactance and is connected to one section of the
bus-bar.Find the total steady input to a dead short circuit between the lines on one of the section of
the bus bar (i) with and (ii)without reactors

Sebuah stasiun pembangkit telah lima bagian bus-bar yang terhubung dengan tie-bar melalui 7,5% reaktor
dinilai pada 3000 kva .Setiap generator 3000 kva dengan 10% reaktansi dan terhubung ke salah satu bagian dari
bus-bar.Find total stabil input ke sirkuit pendek mati antara garis-garis pada salah satu bagian dari bar bus (i)
dengan dan (ii) tanpa reaktor

A generator sattion has four bus-bar section.Each section is connected to tie-bar though 20%
reactotrs rated at 200 MVA. Generating of total capacity 100 MVA and 20% reactance are connected
to each bus-bar section.Calculate the MVA fed to a fault under short-circuit condition ono one of the
bus-bar

Sebuah sattion Generator memiliki empat bus-bar bagian section.Each terhubung untuk mengikat-bar meskipun
20% reactotrs dinilai pada 200 MVA. Membangkitkan dari total kapasitas 100 MVA dan 20% reaktansi saling
terhubung satu sama bus-bar section.Calculate MVA diumpankan ke suatu kesalahan di bawah sirkuit pendek
kondisi ono salah satu bus-bar

The 33 kV bus-bar of a station are in two section A and B separated by a reactor.Section A is fed from
four 10 MVA generators each having 20% reactance and section B is fed from the grid through 50
MVA transformer of 10% reactance.The circuit breakers have rupturing capacity of 500 MVA.Find
the reactance of the reactor to prevent the circuit breakers being overloaded if a symmetrical short
circuit occurs on an outgoing feeder connected to it

33 kV bus-bar dari stasiun berada di dua bagian A dan B dipisahkan oleh reactor.Section A
disuplai dari empat 10 generator MVA masing-masing memiliki 20% reaktansi dan bagian B
diberi makan dari grid melalui 50 MVA trafo dari 10% reactance.The pemutus sirkuit telah
pecah kapasitas 500 MVA.Find reaktansi reaktor untuk mencegah pemutus sirkuit kelebihan
beban jika hubungan pendek simetris terjadi pada pengumpan keluar terhubung

A 3 phase transmission line operating at 33 kV and having a resistance of 5 ohm and reactance of 20
ohm is connected to the generating station through 15000 KVA step-up transformer.Connected to
the bus bar are two altenators,one of 10000 KVA with 10% reactance and another of 5000 KVA with
7.5% reactance.Calculate the short circuit KVA fed to the symmetrical fault between phases if it
occurs

(i) At the load end of transmission line


(ii) At the high voltage terminals of the transformer
Sebuah saluran transmisi 3 phase beroperasi pada 33 kV dan memiliki
ketahanan dari 5 ohm dan reaktansi dari 20 ohm terhubung ke stasiun
pembangkit melalui 15.000 KVA langkah-up transformer.Connected ke bar bus
dua altenators, salah satu dari 10.000 KVA dengan 10 % reaktansi dan lain 5000
KVA dengan 7,5% reactance.Calculate sirkuit pendek KVA diumpankan ke
kesalahan simetris antara fase jika terjadi (I) Pada beban akhir saluran transmisi
(Ii) Pada terminal tegangan tinggi dari transformator