DSE8660 ENVIRONMENTAL TESTING STANDARDS

AUTO TRANSFER SWITCH & MAINS ELECTRO MAGNETIC COMPATIBILITY


BS EN 61000-6-2

CONTROL MODULE EMC Generic Immunity Standard for the


Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
FEATURES Industrial Environment

ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment
The DSE8660 is an easy-to-use Comprehensive communications With all communication ports
capable of being active at the same TEMPERATURE
single or multi-mains controller with are also available via RS232, BS EN 60068-2-1
automatic transfer switch capability. RS485 & Ethernet for remote PC time, the DSE8xxx Series is ideal Ab/Ae Cold Test -30oC
Designed to synchronise single or control and monitoring, and for a wide variety of demanding BS EN 60068-2-2
load share applications. Bb/Be Dry Heat +70oC
multiple DSE8610s and DSE8680s integration into building
with single or multiple mains (utility) management systems. VIBRATION
KEY LOAD SHARE FEATURES BS EN 60068-2-6
supplies, the DSE8660 will The comprehensive event log will (WITH DSE8x10) : Ten sweeps in each of three major axes
automatically control the change record up to 250 events to facilitate • Peak lopping/shaving 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
over from mains (utility) to generator maintenance. • Sequential set start HUMIDITY
supply or run generators in • Manual voltage/frequency BS EN 60068-2-30
synchronisation with the mains An extensive number of fixed and Db Damp Heat Cyclic 20/55oC @ 95% RH 48
adjustment Hours
(utility) to provide no-break, peak flexible monitoring and protection • R.O.C.O.F. and vector shift BS EN 60068-2-78
lopping and peak shaving power features are included. Easy protection Cab Damp Heat Static 40oC @ 93% RH 48
solutions. alteration of the sequences, timers • Generator load demand Hours
and alarms can be made using the • Automatic hours run balancing SHOCK
The module can indicate DSE PC Configuration Suite • Mains (Utility) de-coupling BS EN 60068-2-27
Three shocks in each of three major axes
operational status and fault Software. Selected configuration is • Mains (Utility) de-coupling 15gn in 11mS
conditions on the LCD screen also available via the module’s front test mode
(multiple languages available), by panel. DEGREES OF PROTECTION
• Bus failure detection PROVIDED BY ENCLOSURES
illuminated LED, audible sounder • Volts and frequency matching. BS EN 60529
and SMS messaging. IP65 - Front of module when installed into the
• kW & kV Ar load sharing control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE


VARIETY OF LOAD SHARE APPLICATIONS
DSE2130
MODEM MODBUS PC
DSE2131
DSE2133
DSE2152 11 6
DSE2157
DSE2548 232 485

DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS DC POWER
EXPANSION RS485 PORT HOST INPUTS SUPPLY 8-35V
+
ETHERNET

DSE8660 MSC

7
5510 ­7510 ­8xxx
OTHER

MAINS (UTILITY) SENSING N/C VOLT FREE N/O VOLT BUS


OUTPUTS FREE OUTPUT SENSING
CURRENT VOLTS

1ph 1ph 1 1 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N N

ISSUE 2
®

DSEGenset

DSE8660 SPECIFICATION

DC SUPPLY
AUTO TRANSFER SWITCH & MAINS CONTINUOUS VOLTAGE RATING
8 V to 35 V Continuous
CONTROL MODULE CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout
FEATURES and supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.

MAXIMUM OPERATING CURRENT


340 mA at 12 V, 160 mA at 24 V

MAXIMUM STANDBY CURRENT


160 mA at 12 V, 80 mA at 24 V

MAINS (UTILITY)
VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

BUS
VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

OUTPUTS
KEY FEATURES • Five key menu navigation • Can be integrated into building OUTPUTS C & D
• Mains (utility) failure detection • Front panel editing with PIN management systems (BMS) and 8 A at 250 V AC (Volt free)
• Mains (utility) power monitoring protection programmable logic control AUXILIARY OUTPUTS E,F,G,H, I & J
(kW, kV Ar, kV A and pf) • Customisable status screens (PLC) 2 A DC at supply voltage
• Comprehensive synchronising • Configurable inputs (11) • Increased input and output
DIMENSIONS
and loadsharing capabilities • Configurable outputs (8) expansion capability via DSENet® OVERALL
• Base load (kW export) • Configurable timers and alarms • Licence-free PC software 240 mm x 181 mm x 42 mm
functionality • Multiple entry scheduler • IP65 rating (with supplied gasket) 9.4” x 7.1” x 1.6”
• Positive & negative kVAr export • Configurable event log (250) offers increased resistance to water PANEL CUT-OUT
control • Easy access diagnostic pages ingress 220 mm x 160 mm
• Peak lopping & shaving • LED and LCD alarm indication • Advanced Internal PLC editor 8.7” x 6.3”
functionality • USB connectivity allows user configurable functions MAXIMUM PANEL THICKNESS
• Mains (utility) kW export • Backed up real time clock to meet specific application 8 mm
protection • Fully configurable via DSE requirements. 0.3”
• Mains (utility) de-coupling Configuration Suite PC OPERATING TEMPERATURE RANGE
protection Software EXPANSION DEVICES -30°C to +70°C
• Advanced integral PLC editor • DSE124 CAN/MSC Extender
STORAGE TEMPERATURE RANGE
• User configurable RS232, KEY BENEFITS • DSE2130 Input Expansion Module
-40°C to +85°C
RS485 & Ethernet • A single flexible solution for • DSE2131 Ratiometric Input
communications multiple applications Expansion Module
• MODBUS RTU & TCP support • Compatible with DSE5510, • DSE2133 RTD & Thermocouple
• User configurable MODBUS DSE7510 & DSE8x10 series of Expansion Module
pages modules • DSE2152 Analogue Output
• Advanced SMS control and • 132 x 64 pixel ratio display for Expansion Module
fault messaging (additional clarity • DSE2157 Output Expansion
GSM modem required) • Real-time clock provides Module
• DSENet expansion compatible accurate event logging • DSE2548 LED Expansion Module
• Data logging and trending • Ethernet communication
• 4-Line back-lit LCD text display provides built in advanced
• Multiple display languages remote monitoring.

RELATED MATERIALS
TITLE PART NO’S
DSE8660 Installation Instructions 053-070
DSE8660 Operator Manual 057-120
DSE8600 PC Configuration Suite Manual 057-119
DSE8610 Data Sheet 055-083
DSE8680 Data Sheet 055-091
DSE8700 Data Sheet 055-090
DSE8810 Data Sheet 055-116
DSE8860 Data Sheet 055-139

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-086/04/11 (5)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457